Time-Current Curves Explained in Details
Time-Current Curves Explained in Details
electrical-engineering-portal.com/time-current-curves
To determine how long a breaker will take to trip at a given current, find the level of
current on the bottom of the graph. Draw a vertical line to the point where it intersects the
curve. Then draw a horizontal line to the left side of the graph and find the time to trip. For
example, in this illustration a circuit breaker will trip when current remains at 6 amps for
0.6 seconds.
It can be seen that the higher the current, the shorter the time the circuit breaker will
remain closed. It can be seen from the time-current curve on the following page that
actual time-current curves are drawn on log-log paper, and the horizontal line is in
multiples of the breaker’s continuous current rating.
From the information box in the upper right hand corner, note that the time-current curve
illustrated on the following page defines the operation of a CFD6 circuit breaker.
1/4
Overload protection component of the time-current curve
The top part of the time-current curve shows the performance of the overload trip
component of the circuit breaker. Time-current curves are shown as bands, and the actual
performance of any one breaker can fall anywhere within the band. Using the example
CFD6 breaker and 200 ampere trip unit, the time the breaker will trip for any given
overload can easily be determined using the same procedure as previously discussed.
2/4
For example, the breaker will trip between 25 seconds and 175 seconds at 600 amps with
a 40°C ambient temperature, which is 3 times the the trip unit rating.
The bottom part of the time-current curve shows the performance of the instantaneous
trip component (short circuit) of the circuit breaker. The maximum clearing time (time it
takes for breakers to completely open) decreases as current increases. This is because
of the blow-apart contact design which utilizes the magnetic field built-up around the
contacts.
As current increases the magnetic field strength increases, which aids in opening the
contacts. This circuit breaker has an adjustable instantaneous trip point from 900 A to
2000 A, which is 4.5 to 10 times the 200 A trip unit rating. If the trip point adjustment is set
to minimum (900 A), and a fault current of 900 amps or greater occurs, the breaker will
trip within 1 cycle (16.8 ms). If the trip point setting is set to maximum (2000 A), and a
fault current of 900 amps occurs, the breaker will trip between approximately 12 and 55
seconds.
3/4
SOURCE: Siemens