NOTES
1. THE ELECTRICAL INSTALLATION SHALL MEET THE MINIMUM REQUIREMENTS OF THE
2017 NATIONAL ELECTRIC CODE AS ADOPTED BY THE STATE OF IDAHO AND LOCAL
BUILDING CODES.

2. ALL ELECTRICAL EQUIPMENT SHALL BE LISTED AND APPROVED AND SUITABLE FOR
THE INSTALLATION. A
3. DRAWINGS ARE DIAGRAMMATIC ONLY AND SHOW THE GENERAL INTENT OF
ELECTRICAL SYMBOLS LEGEND ONE-LINE SYMBOLS LEGEND ELECTRICAL ABBREVIATIONS LIST LOCATIONS AND INSTALLATION REQUIREMENTS OF EQUIPMENT. EXACT LOCATIONS
AND INSTALLATION MATERIALS REQUIRED SHALL BE VERIFIED IN FIELD WITH ACTUAL
INSTALLED EQUIPMENT.

4. ALL EXISTING CONDITIONS SHALL BE VERIFIED AT THE JOB SITE PRIOR TO BID
SURFACE MOUNTED PANELBOARD LOW VOLTAGE FIXED CIRCUIT BREAKER 1P 1 POLE (2P, 3P, 4P, ETC.) DC DIRECT CURRENT HT HEIGHT N.C. NORMALLY CLOSED SWBD SWITCHBOARD SUBMITTALS.
DCP DOMESTIC WATER HTG HEATING NEC NATIONAL ELECTRICAL CODE SYM SYMMETRICAL
A AMPERE CIRCULATING PUMP HTR HEATER NEMA NATIONAL ELECTRICAL SYS SYSTEM 5. ALL WALL AND CEILING PENETRATIONS SHALL BE SEALED WITH MATERIALS
DELTA-Y CONNECTION AC ABOVE COUNTER OR AIR DEPT DEPARTMENT HV HIGH VOLTAGE MANUFACTURER'S ASSOCIATION TEL TELEPHONE APPROVED TO MAINTAIN FIRE RATINGS.
CONDITIONER DET DETAIL HVAC HEATING, VENTILATING AND NFDS NON-FUSED SAFETY TEL/DATA TELEPHONE/DATA
DISCONNECT SWITCH ACLG ABOVE CEILING DIA DIAMETER AIR CONDITIONING DISCONNECT SWITCH TERM TERMINAL 6. EQUIPMENT GROUNDING CONDUCTORS SHALL BE INSTALLED IN CONDUIT, UNLESS
CONNECTION DOT ADO AUTOMATIC DOOR OPENER DISC DISCONNECT HWP HYDRONIC WATER PUMP NIC NOT IN CONTRACT TL TWIST LOCK NOTED OTHERWISE.
AF AMP FRAME DIST DISTRIBUTION NL NIGHT LIGHT TR TAMPER RESISTANT
AFF ABOVE FINISHED FLOOR DN DOWN IC INTERRUPTING CAPACITY N.O. NORMALLY OPEN T-STAT THERMOSTAT
7. MULTIWIRED BRANCH CIRCUITS (SHARED NEUTRALS) SHALL NOT BE USED.
ABOVE GRADE EXPOSED CONDUIT LOW VOLTAGE FUSED SWITCH AFG ABOVE FINISHED GRADE DPR DAMPER IG ISOLATED GROUND NPF NORMAL POWER FACTOR TTC TELEPHONE TERMINAL CABINET
AFCI ARC FAULT CIRCUIT DS SAFETY DISCONNECT SWITCH IMC INTERMEDIATE METAL CONDUIT NTS NOT TO SCALE TV TELEVISION
8. PROVIDE PVC40 CONDUIT WITH PVC80 FITTINGS FOR ALL UNDERGROUND CONDUIT.
INTERRUPTER DT DOUBLE THROW INCAND INCANDESCENT TVTC TELEVISION TERMINAL CABINET
AHU AIR HANDLING UNIT DWG DRAWING IR INFRARED OH OVERHEAD TWPR TWISTED PAIR
DISCONNECT SWITCH 9. PROVIDE EMT CONDUIT FOR ALL INDOOR AND OUTDOOR ABOVEGROUND CONDUIT
UNDEGROUND CONDUIT AL ALUMINUM I/W INTERLOCK WITH OL OVERLOADS TYP TYPICAL
PAINTED TO MATCH THE EXISTING CONDITIONS.
ALT ALTERNATE EC ELECTRICAL CONTRACTOR UC UNDER COUNTER
AMP AMPERE ELEC ELECTRIC, ELECTRICAL J-BOX JUNCTION BOX PA PUBLIC ADDRESS UE UNDERGROUND ELECTRICAL
GROUND CONNECTION EQUIPMENT GROUNDING CONDUCTOR 10. PROVIDE THWN/THHN COPPER CONDUCTORS FOR ALL POWER CONDUCTORS. ALL
AMPL AMPLIFIER EGC KCMIL ONE THOUSAND CIRCULAR MILS PB PULL BOX OR PUSHBUTTON UG UNDERGROUND
CONDUITS IN/OUT OF EQUIPMENT ANNUN ANNUNCIATOR EM EMERGENCY KV KILOVOLT PE PNEUMATIC ELECTRIC UH UNIT HEATER CONDUCTORS #10 AND SMALLER SHALL BE SOLID; CONDUCTORS #8 AND LARGER
GROUNDED Y CONNECTION APPROX APPROXIMATELY EMS ENERGY MANAGEMENT SYSTEM KVA KILOVOLT-AMPERE PED PEDESTAL UT UNDERGROUND TELEPHONE SHALL BE STRANDED. TYPE NM CABLE IS NOT PERMITTED.
AQ-STAT AQUASTAT EMT ELECTRICAL METALLIC TUBING KVAR KILOVOLT-AMPERE REACTIVE PF POWER FACTOR UTIL UTILITY
ARCH ARCHITECT, ARCHITECTURAL EP ELECTRIC PNEUMATIC KW KILOWATT PH PHASE UV UNIT VENTILATOR OR 11. ALL CABLE TERMINATIONS AND FITTINGS SHALL BE RATED FOR A MINIMUM OF 75C.
DC1-1 CABLE/CIRCUIT TAG B
ARMS ARCHFLASH REDUCTION EQUIP EQUIPMENT KWH KILOWATT HOUR PIV POST INDICATING VALVE ULTRAVIOLET
MAINTENANCE SYSTEM ERMS ENERGY REDUCTION PM POWER METER 12. PROVIDE BARE COPPER CONDUCTORS FOR BONDING. EQUIPMENT GROUNDING
POWER TRANSFORMER AS AMP SWITCH MAINTENANCE SWITCH LOC LOCATE OR LOCATION PNL PANEL V VOLT CONDUCTORS SHALL BE COPPER WITH GREEN INSULATION.
AT AMP TRIP EWC ELECTRIC WATER COOLER LSI LONG TIME + SHORT TIME + PP POWER POLE VA VOLT-AMPERES
ATS AUTOMATIC TRANSFER SWITCH EX EXISTING INSTANTANEOUS PROTECTION PR PAIR VDT VIDEO DISPLAY TERMINAL 13. ALL OUTDOOR EQUIPMENT SHALL BE NEMA TYPE-3R.
AUTO AUTOMATIC EXH EXHAUST LSIG LONG TIME + SHORT TIME + PRI PRIMARY VERT VERTICAL
AUX AUXILIARY EXP EXPLOSION PROOF INSTANTANEOUS + GROUND PROJ PROJECTION VFD VARIABLE FREQUENCY DRIVE 14. PROVIDE CURRENT LIMITING FUSES FOR ALL FUSES IN ACCORDANCE WITH UL-4248.
AV AUDIO VISUAL FAULT PROTECTION PRV POWER ROOF VENTILATOR VOL VOLUME
EXISTING EQUIPMENT AWG AMERICAN WIRE GAUGE FA FIRE ALARM LT LIGHT PT POTENTIAL TRANSFORMER 15. ELECTRICAL SWITCHBOARDS SHALL HAVE A NEMA TYPE-1 RATINGS WITH COPPER
FABP FIRE ALARM BOOSTER POWER LTG LIGHTING PVC POLYVINYL CHLORIDE W WATT BUSSING. THE CIRCUIT BREAKERS SHALL BE THE BOLT-ON TYPE.
BATT BATTERY SUPPLY PANEL LTNG LIGHTNING (CONDUIT) W/ WITH
BD BOARD FACP FIRE ALARM CONTROL PANEL LV LOW VOLTAGE PWR POWER WG WIRE GUARD 16. GROUND RODS SHALL BE CONE POINTED COPPER, 10' IN LENGTH, WITH A 3/4"
NEW EQUIPMENT BLDG BUILDING FCU FAN COIL UNIT WH WATER HEATER DIAMETER; SECTIONAL RODS ARE PERMITTED.
BMS BUILDING MANAGEMENT FIXT FIXTURE MAX MAXIMUM QUAN QUANTITY W/O WITHOUT
SYSTEM FLR FLOOR MAG.S MAGNETIC STARTER WP WEATHERPROOF 17. PROVIDE A TRANSFORMER PAD AS REQUIRED BY IDAHO POWER.
FLUOR FLUORESCENT M/C MOMENTARY CONTACT RCPT RECEPTACLE
DC1-1 CABLE/CIRCUIT TAG CND CONDUIT FO FIBER OPTIC MC MECHANICAL CONTRACTOR REQD REQUIRED XFMR TRANSFORMER 18. LOCATE EXISTING UNDERGROUND UTILITIES IN THE THE PROPOSED AREA FOR THE
CAB CABINET FU FUSE MCB MAIN CIRCUIT BREAKER RM ROOM XFR TRANSFER NEW SECONDARY CONDUITS FOR UNDERGROUND UTILITIES PRIOR TO DIGGING.
CAT CATALOG FUDS FUSED SAFETY DISCONNECT MCCB MOLDED CASE CIRCUIT RSC RIGID STEEL CONDUIT
CATV CABLE TELEVISION SWITCH BREAKER RTU ROOF TOP UNIT 19. THIS FACILITY IS IN SEISMIC ZONE 2B, CONTRACTOR SHALL ADHERE TO THE LOCAL
CB CIRCUIT BREAKER MCC MOTOR CONTROL CENTER SC SURFACE CONDUIT CODES WHEN INSTALLING AND MOUNTING EQUIPMENT AND RACEWAYS.
CCTV CLOSED CIRCUIT TELEVISION GA GAUGE MCP MOTOR CIRCUIT PROTECTOR SCH SCHEDULE
CKT CIRCUIT GAL GALLON MDC MAIN DISTRIBUTION CENTER SEC SECONDARY
CLG CEILING GALV GALVANIZED MDP MAIN DISTRIBUTION PANEL SHT SHEET
COMB COMBINATION GC GENERAL CONTRACTOR MFR MANUFACTURER SIM SIMILAR ANGLE
CMPR COMPRESSOR GEC GROUNDING ELECTRODE CONDUCTOR MFS MAIN FUSED DISCONNECT S/N SOLID NEUTRAL @ AT
CONN CONNECTION GFCI GROUND FAULT CIRCUIT SWITCH SPEC SPECIFICATION DELTA
CONST CONSTRUCTION INTERRUPTER SPKR SPEAKER ' FEET
MH MANHOLE C
CONT CONTINUATION OR GFP GROUND FAULT PROTECTOR SP SPARE " INCHES
MIC MICROPHONE
CONTINUOUS GND GROUND MIN MINIMUM SPD SURGE PROTECTION DEVICE # NUMBER
CONTR CONTRACTOR GRS GALVANIZED RIGID STEEL MISC MISCELLANEOUS SR SURFACE RACEWAY Ø PHASE
CONV CONVECTOR (CONDUIT) MLO MAIN LUGS ONLY SS STAINLESS STEEL CL CENTER LINE
CP CIRCULATING PUMP GYP BD GYPSUM BOARD MMS MANUAL MOTOR STARTER SSW SELECTOR SWITCH PL PLATE
CRT CATHODE-RAY TUBE MOA MULTIOUTLET ASSEMBLY S/S STOP/START PUSHBUTTONS
CT CURRENT TRANSFORMER HH HANDHOLE MSP MOTOR STARTER PANELBOARD STA STATION
CTR CENTER HORIZ HORIZONTAL MSBD MAIN SWITCHBOARD STD STANDARD
CU COPPER HP HORSEPOWER MT MOUNT SURF SURFACE MOUNTED
HPF HIGH POWER FACTOR MT.C EMPTY CONDUIT SUSE SUITABLE FOR USE AS
MTS MANUAL TRANSFER SWITCH SERVICE EQUIPMENT
MTR MOTOR, MOTORIZED SW SWITCH

THIS DRAWING WAS PREPARED BY POWER DSGN BLP 09/14/20 JOB NUMBER REV
MOUNTAIN RIDES
E0-1-BEL.DWG

ENGINEERS, INC. FOR A SPECIFIC PROJECT,


TAKING INTO CONSIDERATION THE SPECIFIC DRN JK 09/14/20
AND UNIQUE REQUIREMENTS OF THE ELECTRIC BUS CHARGING 165994 B
PROJECT. REUSE OF THIS DRAWING OR ANY CKD ZPB 11/13/20
INFORMATION CONTAINED IN THIS DRAWING
FOR ANY PURPOSE IS PROHIBITED UNLESS B RE-ISSUED FOR BID 11/13/20 JK BLP ZPB JM SCALE: N/A DRAWING NUMBER
WRITTEN PERMISSION FROM BOTH POWER
A ISSUED FOR BID 10/13/20 JK BLP ZPB JM BELLEVUE FACILITY
AND POWER'S CLIENT IS GRANTED.
REV REVISIONS DATE DRN DSGN CKD APPD REFERENCE DRAWINGS FOR 24x36 DWG ONLY
COVER SHEET & LEGEND E0-1
1 2 3 4 5 6 7 8

1 NOTES
1. THE PROPOSED ABB EV BUS CHARGER HAVE A POWER FACTOR OF 0.95.

2. CABLE AMPACITY CALCULATIONS ARE BASED ON A 105F MAXIMUM AMBIENT


TEMPERATURE.

3. PROVIDE PLACARD SHOWING THE UTILITY DISCONNECTS AT EACH SERVICE A


DISCONNECTING MEANS.

KEYED NOTES
1 UTILITY TO PROVIDE NEW UTILITY TRANSFORMER, CT, AND METER. UTILITY TO
PROVIDE PRIMARY POWER CABLES AND ASSOCIATED RACEWAY.

2 CONTRACTOR TO TERMINATE CUSTOMER SUPPLIED CABLES DIRECTLY TO THE


UTILITY TRANSFORMER TERMINALS.

3 BOND NEW GROUNDING ELECTRODE TO EXISTING GROUNDING ELECTRODE


SYSTEM PER NEC 250.

4 PROVIDE SPARE BREAKER FOR FUTURE EV BUS CHARGERS.

5 PROVIDE 6" x 3" RED PLACARD WTIH 1/2" TALL WHITE LETTERING "THIS DEVICE
IS POWERED BY TWO SEPARATE SOURCES; ENSURE ALL POWER IS B
DISCONNECTED PRIOR TO SERVICING.

6 PROVIDE 208Y/120V PANELBOARD WITH INTERGRAL 15KVA TRANSFORMER &


ASSOCIATED CIRCUIT BREAKERS. TRANSFORMER PERCENT IMPEDANCE
ASSUMED AT 2%. REFER TO PANEL SCHEDULE DRAWING FOR CIRCUIT
BREAKER SIZES.

7 ONE OF THE GROUND CONDUCTORS FROM DC CHARGER WILL PASS THROUGH


DC CHARGER DISPENSER A AND CONTINUE TO DISPENSER B.

N G
C

4 4

P-0

DC1-1 DC2-1
3 6

DC1-2 DC2-2
D

B DC1-3 B DC2-3

7 7

5 5 5 5

DC1-5 DC2-5

P-4
E
P-3

P-2
DC1-4 DC2-4
P-1

THIS DRAWING WAS PREPARED BY POWER DSGN BLP 09/10/20 JOB NUMBER REV
MOUNTAIN RIDES
E1-1-BEL.DWG

ENGINEERS, INC. FOR A SPECIFIC PROJECT,


TAKING INTO CONSIDERATION THE SPECIFIC DRN JK 09/10/20
AND UNIQUE REQUIREMENTS OF THE ELECTRIC BUS CHARGING 165994 B
PROJECT. REUSE OF THIS DRAWING OR ANY CKD ZPB 11/13/20
INFORMATION CONTAINED IN THIS DRAWING
FOR ANY PURPOSE IS PROHIBITED UNLESS B RE-ISSUED FOR BID 11/13/20 JK BLP ZPB JM SCALE: NONE DRAWING NUMBER
WRITTEN PERMISSION FROM BOTH POWER
A ISSUED FOR BID 10/13/20 JK BLP ZPB JM BELLEVUE FACILITY
AND POWER'S CLIENT IS GRANTED.
REV REVISIONS DATE DRN DSGN CKD APPD REFERENCE DRAWINGS FOR 24x36 DWG ONLY
ONE LINE DIAGRAM E1-1
1 2 3 4 5 6 7 8

NOTES
1. TWO 400A SPARE BREAKERS ON 480V SWITCHBOARD #1 IS FOR A FUTURE DC
CHARGER.

KEYED NOTES
1 BREAKER SHALL COME EQUIPPED WITH A 30mA GFCI.

1
1
1
1

THIS DRAWING WAS PREPARED BY POWER DSGN BLP 09/14/20 JOB NUMBER REV
MOUNTAIN RIDES
E3-1-BEL.DWG

ENGINEERS, INC. FOR A SPECIFIC PROJECT,


TAKING INTO CONSIDERATION THE SPECIFIC DRN JK 09/14/20
AND UNIQUE REQUIREMENTS OF THE ELECTRIC BUS CHARGING 165994 B
PROJECT. REUSE OF THIS DRAWING OR ANY CKD ZPB 11/13/20
INFORMATION CONTAINED IN THIS DRAWING
FOR ANY PURPOSE IS PROHIBITED UNLESS B RE-ISSUED FOR BID 11/13/20 JK BLP ZPB JM SCALE: NONE DRAWING NUMBER
WRITTEN PERMISSION FROM BOTH POWER
A ISSUED FOR BID 10/13/20 JK BLP ZPB JM BELLEVUE FACILITY
AND POWER'S CLIENT IS GRANTED.
REV REVISIONS DATE DRN DSGN CKD APPD REFERENCE DRAWINGS FOR 24x36 DWG ONLY
ELECTRICAL PANEL SCHEDULES E3-1
1 2 3 4 5 6 7 8

A
SAWCUT AND REPAIR CONCRETE AS
REQUIRED FOR NEW CONDUIT

TYP (E) CMU WALL


FINISHED GRADE

1'-11 2"
NOTE 1

C6X10.5

1'-6"
TYP 3

3'-0" MIN
1/8 SIDES

4'-115 8"
C6X10.5

C6X10.5
C6X10.5

C6X10.5
3'-1018"
RED PLASTIC ELECTRICAL
WARNING TAPE WITH MAGNETIC C6 SEE PLAN
L3X3X1/4
LINING THAT READS "CAUTION -
ELECTRICAL LINE BURIED BELOW"

1"
B
BOLT CHARGERS TO
4" SCH 40 OR SCH 80 PVC CHANNEL FRAME DIA. GRADE

6"
(TYP.) AS NECESSARY TYP 4'-10" (2) 1/2" A325 BOLT TYP
COMPACTED APPROVED BACKFILL 1/8 FLANGES 1'-10" 1'-10"
3" TYP
C6X10.5

1"
5/8" DIA HOLE TYP FOR 112"
1/2" DIA THREADED ROD
2'-3" 2'-3" W/HILTI HIT-HY270 EPOXY, MIN 5"
EMBEDMENT FULLY GROUT CMU
2'-5" 2'-5" 2 1/2" DIA CONDUIT OPENING 2 1/2" DIA CONDUIT OPENING CELLS BEFORE INSTALLATION
4'-10"
5'-218"

CHARGER SUPPORT FRAME MEMBER CONDUIT OPENINGS 4 CHANNEL TO MASONRY WALL CONNECTION
1 TYPICAL DUCT SECTION 2 3
E7-1 SCALE 3" = 1'-0"
E7-1 SCALE 1" = 1'-0" E7-1 SCALE 1" = 1'-0"
E7-1 SCALE 1" = 1'-0"

NOTES:

1. 19-W4 GALVANIZED STEEL BAR GRATING 1-1/2"


HEIGHT, 1/8" THICK C
2. FRAME IS TO SIT ON THE CONCRETE SLAB.
LEVEL WITH GROUT AS NECESSARY.
3. ALL STEEL MEMBERS TO BE PAINTED CARBON
STEEL.

5'-218"

11 2" 3" 3" 11 2"

1 1/2" DIA CONDUIT OPENING 1 1/2" DIA CONDUIT OPENING


2 1/2" DIA CONDUIT OPENING
2 1/2" DIA CONDUIT OPENING

5 MEMBER CONDUIT OPENINGS


E7-1 SCALE 1" = 1'-0" D

THIS DRAWING WAS PREPARED BY POWER DSGN BLP 09/18/20 JOB NUMBER REV
MOUNTAIN RIDES
E6-1-BEL.DWG

ENGINEERS, INC. FOR A SPECIFIC PROJECT,


TAKING INTO CONSIDERATION THE SPECIFIC DRN JK 09/18/20
AND UNIQUE REQUIREMENTS OF THE ELECTRIC BUS CHARGING 165994 B
PROJECT. REUSE OF THIS DRAWING OR ANY CKD ZPB 11/13/20
INFORMATION CONTAINED IN THIS DRAWING
FOR ANY PURPOSE IS PROHIBITED UNLESS B RE-ISSUED FOR BID 11/13/20 JK BLP ZPB JM SCALE: AS INDICATED DRAWING NUMBER
WRITTEN PERMISSION FROM BOTH POWER
A ISSUED FOR BID 10/13/20 JK BLP ZPB JM BELLEVUE FACILITY
AND POWER'S CLIENT IS GRANTED.
REV REVISIONS DATE DRN DSGN CKD APPD REFERENCE DRAWINGS FOR 24x36 DWG ONLY
CONDUIT SECTIONS & DETAILS E6-1
1 2 3 4 5 6 7 8

NORTH

NOTES
1. REFER TO ONE-LINE DIAGRAM DRAWING E1-1 FOR CONDUIT & CABLE
REQUIREMENTS.

2. CONTRACTOR TO PROVIDE EQUIPMENT, CONDUITS, & TERMINATE POWER &


COMMUNICATION CABLES. REFER TO ONE LINE DIAGRAM FOR CABLE SIZING.
A
3. PROVIDE PLACARD SHOWING THE UTILITY DISCONNECTS AT EACH SERVICE
DISCONNECTING MEANS.

4. CONDUIT ROUTING IS SHOWN FOR REFERENCE ONLY. CONTRACTOR TO DETERMINE


THE BEST CONDUIT ROUTE IN THE FIELD.
3
DC CHARGER
DISPENSER 1B

DC1-4 KEYED NOTES


P-3 P-2
DC1-5 1 UTILITY TO PROVIDE NEW UTILITY TRANSFORMER, TRANSFORMER PAD,
1 PRIMARY CABLES & RACEWAYS.
E6-1
P-0 2 CONTRACTOR SCOPE INCLUDES TERMINATION TO THE LOAD SIDE OF THE
480V
3 UTILITY TRANSFORMER.
SWITCHBOARD
DC CHARGER #1
3 PROVIDE 6" x 3" RED PLACARD WTIH 1/2" TALL WHITE LETTERING "THIS DEVICE
DISPENSER 2A DC2-2 5 AC PANEL #1 IS POWERED BY TWO SEPARATE SOURCES; ENSURE ALL POWER IS
& INTEGRAL DISCONNECTED PRIOR TO SERVICING."
DC2-3 XFMR
4 PROVIDE CUSTOM FABRICATED STEEL SUPPORT STAND WITH A 6" C-CHANNEL
DC2-4 DC2-1 UTILITY BASE FOR ABOVEGROUND CONDUIT ENTRY TO THE BOTTOM OF THE EV
6 4
2 XFMR CHARGER. B
DC2-5 DC CHARGER #2
DC1-2 DC1-1 1 5 PROVIDE 10" x 10" WIREWAY ON TOP OF 480V SWITCHBOARD #1 TO BE USED AS
6 4 A PULLBOX AND ENTRY POINT FOR CABLE INTO THE PANEL.
DC1-3
DC CHARGER #1
6 PROVIDE CONDUIT SUPPORT FOR VERTICAL CONDUITS CONTAINING DC1-1,
DC1-2, DC2-1, DC2-2 EXITING THE DC CHARGERS.

P-4

P-1

3
DC CHARGER DC CHARGER
DISPENSER 2B DISPENSER 1A
3

FIRST FLOOR POWER PLAN


1 SCALE: 1/8" = 1'-0"
0 5 10 20 FEET

1/8" = 1'-0"

THIS DRAWING WAS PREPARED BY POWER DSGN BLP 09/14/20 JOB NUMBER REV
MOUNTAIN RIDES
E7-1-BEL.DWG

ENGINEERS, INC. FOR A SPECIFIC PROJECT,


TAKING INTO CONSIDERATION THE SPECIFIC DRN JK 09/14/20
AND UNIQUE REQUIREMENTS OF THE ELECTRIC BUS CHARGING 165994 B
PROJECT. REUSE OF THIS DRAWING OR ANY CKD ZPB 11/13/20
INFORMATION CONTAINED IN THIS DRAWING
FOR ANY PURPOSE IS PROHIBITED UNLESS B RE-ISSUED FOR BID 11/13/20 JK BLP ZPB JM SCALE: 1/8" = 1'-0" DRAWING NUMBER
WRITTEN PERMISSION FROM BOTH POWER
A ISSUED FOR BID 10/13/20 JK BLP ZPB JM BELLEVUE FACILITY
AND POWER'S CLIENT IS GRANTED.
REV REVISIONS DATE DRN DSGN CKD APPD REFERENCE DRAWINGS FOR 24x36 DWG ONLY
FIRST FLOOR POWER PLAN E7-1
1 2 3 4 5 6 7 8

NOTES
1. THE ELECTRICAL INSTALLATION SHALL MEET THE MINIMUM REQUIREMENTS OF THE
2017 NATIONAL ELECTRIC CODE AS ADOPTED BY THE STATE OF IDAHO AND LOCAL
BUILDING CODES.

2. ALL ELECTRICAL EQUIPMENT SHALL BE LISTED AND APPROVED AND SUITABLE FOR
THE INSTALLATION. A
3. DRAWINGS ARE DIAGRAMMATIC ONLY AND SHOW THE GENERAL INTENT OF
ELECTRICAL SYMBOLS LEGEND ONE-LINE SYMBOLS LEGEND ELECTRICAL ABBREVIATIONS LIST LOCATIONS AND INSTALLATION REQUIREMENTS OF EQUIPMENT. EXACT LOCATIONS
AND INSTALLATION MATERIALS REQUIRED SHALL BE VERIFIED IN FIELD WITH ACTUAL
INSTALLED EQUIPMENT.

4. ALL EXISTING CONDITIONS SHALL BE VERIFIED AT THE JOB SITE PRIOR TO BID
SURFACE MOUNTED PANELBOARD LOW VOLTAGE FIXED CIRCUIT BREAKER 1P 1 POLE (2P, 3P, 4P, ETC.) DC DIRECT CURRENT HT HEIGHT N.C. NORMALLY CLOSED SWBD SWITCHBOARD SUBMITTALS.
DCP DOMESTIC WATER HTG HEATING NEC NATIONAL ELECTRICAL CODE SYM SYMMETRICAL
A AMPERE CIRCULATING PUMP HTR HEATER NEMA NATIONAL ELECTRICAL SYS SYSTEM 5. ALL WALL AND CEILING PENETRATIONS SHALL BE SEALED WITH MATERIALS
DELTA-Y CONNECTION AC ABOVE COUNTER OR AIR DEPT DEPARTMENT HV HIGH VOLTAGE MANUFACTURER'S ASSOCIATION TEL TELEPHONE APPROVED TO MAINTAIN FIRE RATINGS.
CONDITIONER DET DETAIL HVAC HEATING, VENTILATING AND NFDS NON-FUSED SAFETY TEL/DATA TELEPHONE/DATA
DISCONNECT SWITCH ACLG ABOVE CEILING DIA DIAMETER AIR CONDITIONING DISCONNECT SWITCH TERM TERMINAL 6. EQUIPMENT GROUNDING CONDUCTORS SHALL BE INSTALLED IN CONDUIT, UNLESS
CONNECTION DOT ADO AUTOMATIC DOOR OPENER DISC DISCONNECT HWP HYDRONIC WATER PUMP NIC NOT IN CONTRACT TL TWIST LOCK NOTED OTHERWISE.
AF AMP FRAME DIST DISTRIBUTION NL NIGHT LIGHT TR TAMPER RESISTANT
AFF ABOVE FINISHED FLOOR DN DOWN IC INTERRUPTING CAPACITY N.O. NORMALLY OPEN T-STAT THERMOSTAT
7. MULTIWIRED BRANCH CIRCUITS (SHARED NEUTRALS) SHALL NOT BE USED.
ABOVE GRADE EXPOSED CONDUIT LOW VOLTAGE FUSED SWITCH AFG ABOVE FINISHED GRADE DPR DAMPER IG ISOLATED GROUND NPF NORMAL POWER FACTOR TTC TELEPHONE TERMINAL CABINET
AFCI ARC FAULT CIRCUIT DS SAFETY DISCONNECT SWITCH IMC INTERMEDIATE METAL CONDUIT NTS NOT TO SCALE TV TELEVISION
8. PROVIDE PVC40 CONDUIT WITH PVC80 FITTINGS FOR ALL UNDERGROUND CONDUIT.
INTERRUPTER DT DOUBLE THROW INCAND INCANDESCENT TVTC TELEVISION TERMINAL CABINET
AHU AIR HANDLING UNIT DWG DRAWING IR INFRARED OH OVERHEAD TWPR TWISTED PAIR
DISCONNECT SWITCH 9. PROVIDE EMT CONDUIT FOR ALL INDOOR AND OUTDOOR ABOVEGROUND CONDUIT
UNDEGROUND CONDUIT AL ALUMINUM I/W INTERLOCK WITH OL OVERLOADS TYP TYPICAL
PAINTED TO MATCH THE EXISTING CONDITIONS.
ALT ALTERNATE EC ELECTRICAL CONTRACTOR UC UNDER COUNTER
AMP AMPERE ELEC ELECTRIC, ELECTRICAL J-BOX JUNCTION BOX PA PUBLIC ADDRESS UE UNDERGROUND ELECTRICAL
GROUND CONNECTION EQUIPMENT GROUNDING CONDUCTOR 10. PROVIDE THWN/THHN COPPER CONDUCTORS FOR ALL POWER CONDUCTORS. ALL
AMPL AMPLIFIER EGC KCMIL ONE THOUSAND CIRCULAR MILS PB PULL BOX OR PUSHBUTTON UG UNDERGROUND
CONDUITS IN/OUT OF EQUIPMENT ANNUN ANNUNCIATOR EM EMERGENCY KV KILOVOLT PE PNEUMATIC ELECTRIC UH UNIT HEATER CONDUCTORS #10 AND SMALLER SHALL BE SOLID; CONDUCTORS #8 AND LARGER
GROUNDED Y CONNECTION APPROX APPROXIMATELY EMS ENERGY MANAGEMENT SYSTEM KVA KILOVOLT-AMPERE PED PEDESTAL UT UNDERGROUND TELEPHONE SHALL BE STRANDED. TYPE NM CABLE IS NOT PERMITTED.
AQ-STAT AQUASTAT EMT ELECTRICAL METALLIC TUBING KVAR KILOVOLT-AMPERE REACTIVE PF POWER FACTOR UTIL UTILITY
ARCH ARCHITECT, ARCHITECTURAL EP ELECTRIC PNEUMATIC KW KILOWATT PH PHASE UV UNIT VENTILATOR OR 11. ALL CABLE TERMINATIONS AND FITTINGS SHALL BE RATED FOR A MINIMUM OF 75C.
DC1-1 CABLE/CIRCUIT TAG B
ARMS ARCHFLASH REDUCTION EQUIP EQUIPMENT KWH KILOWATT HOUR PIV POST INDICATING VALVE ULTRAVIOLET
MAINTENANCE SYSTEM ERMS ENERGY REDUCTION PM POWER METER 12. PROVIDE BARE COPPER CONDUCTORS FOR BONDING. EQUIPMENT GROUNDING
POWER TRANSFORMER AS AMP SWITCH MAINTENANCE SWITCH LOC LOCATE OR LOCATION PNL PANEL V VOLT CONDUCTORS SHALL BE COPPER WITH GREEN INSULATION.
AT AMP TRIP EWC ELECTRIC WATER COOLER LSI LONG TIME + SHORT TIME + PP POWER POLE VA VOLT-AMPERES
ATS AUTOMATIC TRANSFER SWITCH EX EXISTING INSTANTANEOUS PROTECTION PR PAIR VDT VIDEO DISPLAY TERMINAL 13. ALL OUTDOOR EQUIPMENT SHALL BE NEMA TYPE-3R.
AUTO AUTOMATIC EXH EXHAUST LSIG LONG TIME + SHORT TIME + PRI PRIMARY VERT VERTICAL
AUX AUXILIARY EXP EXPLOSION PROOF INSTANTANEOUS + GROUND PROJ PROJECTION VFD VARIABLE FREQUENCY DRIVE 14. PROVIDE CURRENT LIMITING FUSES FOR ALL FUSES IN ACCORDANCE WITH UL-4248.
AV AUDIO VISUAL FAULT PROTECTION PRV POWER ROOF VENTILATOR VOL VOLUME
EXISTING EQUIPMENT AWG AMERICAN WIRE GAUGE FA FIRE ALARM LT LIGHT PT POTENTIAL TRANSFORMER 15. ELECTRICAL SWITCHBOARDS SHALL HAVE A NEMA TYPE-1 RATINGS WITH COPPER
FABP FIRE ALARM BOOSTER POWER LTG LIGHTING PVC POLYVINYL CHLORIDE W WATT BUSSING. THE CIRCUIT BREAKERS SHALL BE THE BOLT-ON TYPE.
BATT BATTERY SUPPLY PANEL LTNG LIGHTNING (CONDUIT) W/ WITH
BD BOARD FACP FIRE ALARM CONTROL PANEL LV LOW VOLTAGE PWR POWER WG WIRE GUARD 16. GROUND RODS SHALL BE CONE POINTED COPPER, 10' IN LENGTH, WITH A 3/4"
NEW EQUIPMENT BLDG BUILDING FCU FAN COIL UNIT WH WATER HEATER DIAMETER; SECTIONAL RODS ARE PERMITTED.
BMS BUILDING MANAGEMENT FIXT FIXTURE MAX MAXIMUM QUAN QUANTITY W/O WITHOUT
SYSTEM FLR FLOOR MAG.S MAGNETIC STARTER WP WEATHERPROOF 17. PROVIDE A TRANSFORMER PAD AS REQUIRED BY IDAHO POWER.
FLUOR FLUORESCENT M/C MOMENTARY CONTACT RCPT RECEPTACLE
DC1-1 CABLE/CIRCUIT TAG CND CONDUIT FO FIBER OPTIC MC MECHANICAL CONTRACTOR REQD REQUIRED XFMR TRANSFORMER 18. LOCATE EXISTING UNDERGROUND UTILITIES IN THE THE PROPOSED AREA FOR THE
CAB CABINET FU FUSE MCB MAIN CIRCUIT BREAKER RM ROOM XFR TRANSFER NEW SECONDARY CONDUITS FOR UNDERGROUND UTILITIES PRIOR TO DIGGING.
CAT CATALOG FUDS FUSED SAFETY DISCONNECT MCCB MOLDED CASE CIRCUIT RSC RIGID STEEL CONDUIT
CATV CABLE TELEVISION SWITCH BREAKER RTU ROOF TOP UNIT 19. THIS FACILITY IS IN SEISMIC ZONE 2B, CONTRACTOR SHALL ADHERE TO THE LOCAL
CB CIRCUIT BREAKER MCC MOTOR CONTROL CENTER SC SURFACE CONDUIT CODES WHEN INSTALLING AND MOUNTING EQUIPMENT AND RACEWAYS.
CCTV CLOSED CIRCUIT TELEVISION GA GAUGE MCP MOTOR CIRCUIT PROTECTOR SCH SCHEDULE
CKT CIRCUIT GAL GALLON MDC MAIN DISTRIBUTION CENTER SEC SECONDARY
CLG CEILING GALV GALVANIZED MDP MAIN DISTRIBUTION PANEL SHT SHEET
COMB COMBINATION GC GENERAL CONTRACTOR MFR MANUFACTURER SIM SIMILAR ANGLE
CMPR COMPRESSOR GEC GROUNDING ELECTRODE CONDUCTOR MFS MAIN FUSED DISCONNECT S/N SOLID NEUTRAL @ AT
CONN CONNECTION GFCI GROUND FAULT CIRCUIT SWITCH SPEC SPECIFICATION DELTA
CONST CONSTRUCTION INTERRUPTER SPKR SPEAKER ' FEET
MH MANHOLE C
CONT CONTINUATION OR GFP GROUND FAULT PROTECTOR SP SPARE " INCHES
MIC MICROPHONE
CONTINUOUS GND GROUND MIN MINIMUM SPD SURGE PROTECTION DEVICE # NUMBER
CONTR CONTRACTOR GRS GALVANIZED RIGID STEEL MISC MISCELLANEOUS SR SURFACE RACEWAY Ø PHASE
CONV CONVECTOR (CONDUIT) MLO MAIN LUGS ONLY SS STAINLESS STEEL CL CENTER LINE
CP CIRCULATING PUMP GYP BD GYPSUM BOARD MMS MANUAL MOTOR STARTER SSW SELECTOR SWITCH PL PLATE
CRT CATHODE-RAY TUBE MOA MULTIOUTLET ASSEMBLY S/S STOP/START PUSHBUTTONS
CT CURRENT TRANSFORMER HH HANDHOLE MSP MOTOR STARTER PANELBOARD STA STATION
CTR CENTER HORIZ HORIZONTAL MSBD MAIN SWITCHBOARD STD STANDARD
CU COPPER HP HORSEPOWER MT MOUNT SURF SURFACE MOUNTED
HPF HIGH POWER FACTOR MT.C EMPTY CONDUIT SUSE SUITABLE FOR USE AS
MTS MANUAL TRANSFER SWITCH SERVICE EQUIPMENT
MTR MOTOR, MOTORIZED SW SWITCH

THIS DRAWING WAS PREPARED BY POWER DSGN BLP 09/14/20 JOB NUMBER REV
MOUNTAIN RIDES
E0-1-KET.DWG

ENGINEERS, INC. FOR A SPECIFIC PROJECT,


TAKING INTO CONSIDERATION THE SPECIFIC DRN JK 09/14/20
AND UNIQUE REQUIREMENTS OF THE ELECTRIC BUS CHARGING 165994 B
PROJECT. REUSE OF THIS DRAWING OR ANY CKD ZPB 11/13/20
INFORMATION CONTAINED IN THIS DRAWING
FOR ANY PURPOSE IS PROHIBITED UNLESS B RE-ISSUED FOR BID 11/13/20 JK BLP ZPB JM SCALE: N/A DRAWING NUMBER
WRITTEN PERMISSION FROM BOTH POWER
A ISSUED FOR BID 10/13/20 JK BLP ZPB JM KETCHUM FACILITY
AND POWER'S CLIENT IS GRANTED.
REV REVISIONS DATE DRN DSGN CKD APPD REFERENCE DRAWINGS FOR 24x36 DWG ONLY
COVER SHEET & LEGEND E0-1
1 2 3 4 5 6 7 8

1 NOTES
1. THE PROPOSED ABB EV BUS CHARGER HAVE A POWER FACTOR OF 0.95.

2. CABLE AMPACITY CALCULATIONS ARE BASED ON A 105F MAXIMUM AMBIENT


TEMPERATURE.

3. PROVIDE PLACARD SHOWING THE UTILITY DISCONNECTS AT EACH SERVICE A


DISCONNECTING MEANS.

KEYED NOTES
1 UTILITY TO PROVIDE NEW UTILITY TRANSFORMER, CT, AND METER. UTILITY TO
PROVIDE PRIMARY POWER CABLES AND ASSOCIATED RACEWAY.

2 CONTRACTOR TO TERMINATE CUSTOMER SUPPLIED CABLES DIRECTLY TO THE


UTILITY TRANSFORMER TERMINALS.

3 BOND NEW GROUNDING ELECTRODE TO EXISTING GROUNDING ELECTRODE


SYSTEM PER NEC 250.

4 PROVIDE SPARE BREAKER FOR FUTURE EV BUS CHARGERS.

5 PROVIDE 6" x 3" RED PLACARD WTIH 1/2" TALL WHITE LETTERING "THIS DEVICE
IS POWERED BY TWO SEPARATE SOURCES; ENSURE ALL POWER IS B
DISCONNECTED PRIOR TO SERVICING.

6 PROVIDE 208Y/120V PANELBOARD WITH INTERGRAL 15KVA TRANSFORMER &


ASSOCIATED CIRCUIT BREAKERS. TRANSFORMER PERCENT IMPEDANCE
ASSUMED AT 2%. REFER TO PANEL SCHEDULE DRAWING FOR CIRCUIT
BREAKER SIZES.

7 ONE OF THE GROUND CONDUCTORS FROM DC CHARGER WILL PASS THROUGH


DC CHARGER DISPENSER A AND CONTINUE TO DISPENSER B.

N G
C

4 4 4 4

P-0
3
DC1-1 DC2-1
6

DC1-2 DC2-2
D

B DC1-3 B DC2-3

7 7

5 5 5 5

DC1-5 DC2-5

P-4
E
P-3

P-2
DC1-4 DC2-4
P-1

THIS DRAWING WAS PREPARED BY POWER DSGN BLP 09/10/20 JOB NUMBER REV
MOUNTAIN RIDES
E1-1-KET.DWG

ENGINEERS, INC. FOR A SPECIFIC PROJECT,


TAKING INTO CONSIDERATION THE SPECIFIC DRN JK 09/10/20
AND UNIQUE REQUIREMENTS OF THE ELECTRIC BUS CHARGING 165994 B
PROJECT. REUSE OF THIS DRAWING OR ANY CKD ZPB 11/13/20
INFORMATION CONTAINED IN THIS DRAWING
FOR ANY PURPOSE IS PROHIBITED UNLESS B RE-ISSUED FOR BID 11/13/20 JK BLP ZPB JM SCALE: NONE DRAWING NUMBER
WRITTEN PERMISSION FROM BOTH POWER
A ISSUED FOR BID 10/13/20 JK BLP ZPB JM KETCHUM FACILITY
AND POWER'S CLIENT IS GRANTED.
REV REVISIONS DATE DRN DSGN CKD APPD REFERENCE DRAWINGS FOR 24x36 DWG ONLY
ONE LINE DIAGRAM E1-1
1 2 3 4 5 6 7 8

NOTES
1. TWO 400A & 150A SPARE BREAKERS ON 480V SWITCHBOARD #1 ARE FOR FUTURE DC
CHARGERS.

KEYED NOTES
1 BREAKER SHALL COME EQUIPPED WITH A 30mA GFCI.

1
1
1
1

THIS DRAWING WAS PREPARED BY POWER DSGN BLP 09/14/20 JOB NUMBER REV
MOUNTAIN RIDES
E3-1-KET.DWG

ENGINEERS, INC. FOR A SPECIFIC PROJECT,


TAKING INTO CONSIDERATION THE SPECIFIC DRN JK 09/14/20
AND UNIQUE REQUIREMENTS OF THE ELECTRIC BUS CHARGING 165994 B
PROJECT. REUSE OF THIS DRAWING OR ANY CKD ZPB 11/13/20
INFORMATION CONTAINED IN THIS DRAWING
FOR ANY PURPOSE IS PROHIBITED UNLESS B RE-ISSUED FOR BID 11/13/20 JK BLP ZPB JM SCALE: NONE DRAWING NUMBER
WRITTEN PERMISSION FROM BOTH POWER
A ISSUED FOR BID 10/13/20 JK BLP ZPB JM KETCHUM FACILITY
AND POWER'S CLIENT IS GRANTED.
REV REVISIONS DATE DRN DSGN CKD APPD REFERENCE DRAWINGS FOR 24x36 DWG ONLY
ELECTRICAL PANEL SCHEDULES E3-1
1 2 3 4 5 6 7 8

KEYED NOTES
1 CONDUITS MUST PENETRATE EXTERIOR WALL 24" MINIMUM ABOVE TOP OF UTILITY XFMR
PAD AND HAVE A WATERPROOF SEAL BETWEEN LB CONDULETS AND WALL PENETRATION.
1 WATER PROOF SEAL TO BE FOAM APPROVED FOR CABLE INSULATION AND DUCT SEAL
WALL PENETRATION MINIMUM COMPOUND.
OF 24" ABOVE TOP OF A
SAWCUT AND REPAIR CONCRETE AS TRANSFORMER PAD WATERPROOF SEAL AT
REQUIRED FOR NEW CONDUIT WALL PENETRATION

FINISHED GRADE
UTILITY
LB XFMR

24"
CONDULET
4" RGC CONDUIT

1'-6"
(TYP. ABOVE
GROUND)

3'-0" MIN
UTILITY XFMR PAD
FINISHED GRADE

RED PLASTIC ELECTRICAL


WARNING TAPE WITH MAGNETIC
LINING THAT READS "CAUTION -
ELECTRICAL LINE BURIED BELOW" 480V SWITCHBOARD #1

4" SCH 40 OR SCH 80 PVC


(TYP. UNDERGROUND) SHOP FLOOR
EXTERIOR
3" TYP WALL

COMPACTED APPROVED BACKFILL

WALL PENETRATION DETAIL


1 TYPICAL DUCT SECTION 2 TYPICAL DUCT SECTION
E7-1 SCALE 1" = 1'-0" E7-1 NTS

2'-6"
2'-17 8"
C
1"
2"

C6X10.5
TYP 3
1/8 SIDES

2'-17 8"
C6X10.5

C6X10.5
3'-1018"

41 4" 412" 27 8"

BOLT CHARGERS TO
CHANNEL FRAME AS
NECESSARY
2 1/2" DIA CONDUIT OPENING 1 1/2" DIA CONDUIT OPENING
2 1/2" DIA CONDUIT OPENING
C6X10.5

5/8" DIA HOLE (BOTTOM FLANGE ONLY)


FOR 1/2" DIA KWIK BOLT TZ-CS MIN 3"
EMBEDMENT TYPICAL (1) EACH CORNER
USE BEVELED WASHER.

3 CHARGER SUPPORT FRAMES 4 MEMBER CONDUIT OPENINGS


E7-1 SCALE 1"=1'-0"
E7-1 SCALE 1"=1'-0"

NOTES:
ALL MATERIAL TO BE PAINTED CARBON STEEL.

CHARGER SUPPORT FRAME IS TO SIT ON THE


CONCRETE SLAB. GROUT UNDERNEATH AS NECESSARY
TO LEVEL THE FRAME.

THIS DRAWING WAS PREPARED BY POWER DSGN BLP 09/18/20 JOB NUMBER REV
MOUNTAIN RIDES
E6-1-KET.DWG

ENGINEERS, INC. FOR A SPECIFIC PROJECT,


TAKING INTO CONSIDERATION THE SPECIFIC DRN JK 09/18/20
AND UNIQUE REQUIREMENTS OF THE ELECTRIC BUS CHARGING 165994 B
PROJECT. REUSE OF THIS DRAWING OR ANY CKD ZPB 11/13/20
INFORMATION CONTAINED IN THIS DRAWING
FOR ANY PURPOSE IS PROHIBITED UNLESS B RE-ISSUED FOR BID 11/13/20 JK BLP ZPB JM SCALE: AS INDICATED DRAWING NUMBER
WRITTEN PERMISSION FROM BOTH POWER
A ISSUED FOR BID 10/13/20 JK BLP ZPB JM KETCHUM FACILITY
AND POWER'S CLIENT IS GRANTED.
REV REVISIONS DATE DRN DSGN CKD APPD REFERENCE DRAWINGS FOR 24x36 DWG ONLY
CONDUIT SECTIONS & DETAILS E6-1
1 2 3 4 5 6 7 8

PLAN
TRUE
NORTH
NORTH
NOTES
1. REFER TO ONE-LINE DIAGRAM DRAWING E1-1 FOR CONDUIT & CABLE
REQUIREMENTS.

2. CONTRACTOR TO PROVIDE EQUIPMENT, CONDUITS, & TERMINATE POWER &


COMMUNICATION CABLES. REFER TO ONE LINE DIAGRAM FOR CABLE SIZING.
A
3. PROVIDE PLACARD SHOWING THE UTILITY DISCONNECTS AT EACH SERVICE
DISCONNECTING MEANS.

4. CONDUIT ROUTING IS SHOWN FOR REFERENCE ONLY. CONTRACTOR TO DETERMINE


THE BEST CONDUIT ROUTE IN THE FIELD.

KEYED NOTES
1 UTILITY TO PROVIDE NEW UTILITY TRANSFORMER, TRANSFORMER PAD,
PRIMARY CABLES & RACEWAYS.

2 CONTRACTOR SCOPE INCLUDES TERMINATION TO THE LOAD SIDE OF THE


UTILITY TRANSFORMER.

3 PROVIDE 6" x 3" RED PLACARD WTIH 1/2" TALL WHITE LETTERING "THIS DEVICE
IS POWERED BY TWO SEPARATE SOURCES; ENSURE ALL POWER IS
DISCONNECTED PRIOR TO SERVICING."

4 PROVIDE CUSTOM FABRICATED STEEL SUPPORT STAND WITH A 6" C-CHANNEL


BASE FOR ABOVEGROUND CONDUIT ENTRY TO THE BOTTOM OF THE EV
CHARGER. B
5 CONDUITS MUST PENETRATE WALL 24" MINIMUM ABOVE TOP OF THE UTILITY
TRANSFORMER PAD AND HAVE WATER PROOF SEAL AT WALL PENETRATION.
REFER TO SHEET E6-1 FOR DETAIL.

4
DC1-1
DC CHARGER #1
3
DC1-2 DC CHARGER
DC1-3 DISPENSER 1B EXISTING PANEL

EXISTING PANEL

3 DC CHARGER EXISTING STARTER

DISPENSER 1A DC1-4 480V SWITCHBOARD #1

DC CHARGER DC2-2 DC1-5 UTILITY


DC2-1 1 2
DISPENSER 2A DC2-3 XFMR
P-1
P-2 P-0 1
3
E6-1

P-3 B
AC PANEL #1 2 C
DC CHARGER #2
& INTEGRAL E6-1
4 5
XFMR

P-4

DC2-4
DC2-5

3
DC CHARGER
DISPENSER 2B

FIRST FLOOR POWER PLAN


1 SCALE: 3/32" = 1'-0"
0 5 10 20 FEET

3/32" = 1'-0"

THIS DRAWING WAS PREPARED BY POWER DSGN BLP 09/14/20 JOB NUMBER REV
MOUNTAIN RIDES
E7-1-KET.DWG

ENGINEERS, INC. FOR A SPECIFIC PROJECT,


TAKING INTO CONSIDERATION THE SPECIFIC DRN JK 09/14/20
AND UNIQUE REQUIREMENTS OF THE ELECTRIC BUS CHARGING 165994 B
PROJECT. REUSE OF THIS DRAWING OR ANY CKD ZPB 11/13/20
INFORMATION CONTAINED IN THIS DRAWING
FOR ANY PURPOSE IS PROHIBITED UNLESS B RE-ISSUED FOR BID 11/13/20 JK BLP ZPB JM SCALE: 3/32"=1'-0" DRAWING NUMBER
WRITTEN PERMISSION FROM BOTH POWER
A ISSUED FOR BID 10/13/20 JK BLP ZPB JM KETCHUM FACILITY
AND POWER'S CLIENT IS GRANTED.
REV REVISIONS DATE DRN DSGN CKD APPD REFERENCE DRAWINGS FOR 24x36 DWG ONLY
FIRST FLOOR POWER PLAN E7-1