Maxitrol 220
Maxitrol 220
210 Series
1 2
A
A
B
B
C C
D
D E
E
DIMENSIONS
Model Standard*
Brown Orange Green Cd Plt Pink Violet Blue Red Yellow Black
Number Plated
210D 3 to 6 1 to 3.5 4 to 8 5 to 15 2 to 5 3 to 8 4 to 12 5 to 12 10 to 22 15 to 30 20 to 42
210E 3 to 6 1 to 3.5 4 to 8 5 to 15 2 to 5 3 to 8 4 to 12 5 to 12 10 to 22 15 to 30 20 to 42
210G 3 to 6 1 to 3.5 4 to 8 5 to 15 2 to 5 3 to 8 4 to 12 5 to 12 10 to 22 15 to 30 20 to 42
210J 3 to 6 — — — 2 to 5 3 to 8 4 to 12 5 to 12 10 to 22 15 to 30 20 to 42
*Factory set at 4.0 w.c.
© 2007 Maxitrol Company, All Rights Reserved. 2
210 series spring loaded models
The 210 series has been designed for maximum control recommends that the regulator is within one size of the mani-
functions in an easy-to-use package. For gas-fired boilers, fold pipe size. Maxitrol also recommends 10 pipe diameters of
steam generators, industrial furnaces, ovens and similar straight pipe at the inlet & outlet of the regulator. Remote sens-
high demand equipment. ing is available.
Balanced valve design eliminates the inlet pressure effect For “zero governor” applications, a counterspring is
acting on the valve. Regulating stability is improved and mounted beneath the valve. A maximum inlet pressure
hunting tendencies reduced by the use of dampening mecha- of 5 psi is recommended. Outlet pressure may be
nisms in both the breather outlet and sensing tube. You get adjusted from -1.0” w.c. to +1.5” w.c. The Maxitrol
precise regulation over a broad range of pressures and flow 210 is designed to operate as a zero governor in the
rates with a Maxitrol 210, including “zero governor” applica- normal upright position.
tion.
SENSING TAPS AVAILABLE
Housings of the 210D, E & G models are of high-strength
aluminum alloy. The housings are reinforced with webs for Tap locations are available for downstream sensing, cross con-
maximum strength. The 210J models are of cast aluminum nections , and differential control. Four convenient
and steel construction with 125 pound flange connections. . locations can be tapped and plugged for measuring
. . . Internal parts are cast or machined from corrosion resis- pressure. Remote sensing also available on most models.
tant metals or are electroplated. Diaphragms are of the
finest quality synthetic coated fabrics. 210J regulators are Vertical vent tapped - 3/8” NPT on 210D, 1/2” NPT on 210E,
painted providing a protective coating if used out-of-doors 3/4” NPT on 210G & J.
(optional on D, E, G).
210 series industrial regulators are intended for use with all
fuel gases. Ambient temperature limits are -400F to 2000F.
Maximum emergency exposure pressure is 25 psi. At this
pressure, the regulator will suffer no internal damage but it
may not provide accurate regulation. A. Internal sensing D. Outlet pres-
#7 — furnished sure
The regulator should be mounted in an upright position in a as standard. tape #2. #1 on
horizontal pipe run. Gas flow must be oriented to arrow on B. Remote sensing side opposite.
bottom casting. When selecting a regulator, Maxitrol tap #5. E. Inlet pressure tap
C. Remote sensing #4. #3 on side
tap #6. opposite.
The 220 series, utilizing a servo-operated design rather 220 series industrial regulators are intended for use with all
than the more conventional spring-loaded design, delivers fuel gases.
higher outlet pressure than the spring loaded models.
The regulator will perform most accurately when mounted in
The main diaphragm on the Maxitrol 220 is loaded with gas an upright postion in a horizontal pipe run. Gas flow must
pressure rather than with a spring. This gas pressure is be oriented to arrow on regulator. When selecting for pipe
precisely controlled by a small pilot regulator in the upper size, make sure regulator is not more than one size larger
housing. When the regulated outlet pressure of the pilot or smaller than manifold pipe size.
regulator is changed, by spring adjustment, the outlet
pressure of the main regulator will change proportionately. Single vent, equipped with model 12A06 vent limiting orifice,
is located in upper housing.
Outlet pressure adjustments are readily made by first
removing the hood of the Maxitrol 220. Then remove the Ambient temperature limits are -400F to 2000F. Maximum
cap atop the pilot regulator, which exposes the adjusting emergency exposure pressure is 25 psi. At this pressure
screw, and adjust to desired pressure. the regulator will suffer no internal damage but it may not
provide accurate regulation.
Three positions can be tapped and plugged for making inlet
or outlet pressure readings. The fourth position is used to Two outlet pressure adjustment springs are available.
supply inlet pressure to the pilot regulator. Remote sensing
is also available. R325C10-1022 (K spring) . . . . . . . . . . . . . . . 1 psi to 3 psi
R325C10-1530 (L spring) . . . . . . . . . . . . . . . 2 psi to 5 psi
DIMENSIONS
Model A B C
B
220D 10-3/16” 7” 6”
B A
220E 11-1/4” 9-1/8” 7-5/8” A
220G 14-3/4” 13-1/2” 10-3/8”
220J 20-1/2” 18” 13-7/8” C