2 - IEEE STD 1547 - 2018-2003 - Redline
2 - IEEE STD 1547 - 2018-2003 - Redline
Sponsored by the
IEEE Standards Coordinating Committee 21 on Fuel Cells, Photovoltaics, Dispersed
Generation, and Energy Storage
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
IEEE Std 1547™-2018
(Revision of IEEE Std 1547-2003)
Sponsor
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
This is a Redline Document produced by Techstreet, a business of
Clarivate Analytics
This document is intended to provide users with an indication of changes from one edition
to the next. It includes a full-text version of the new document, plus an indication of
changes from the previous version.
Redlines are designed to save time and improve efficiencies by using the latest software
technology to find and highlight document changes. More professionals are using valuable
new technologies like redlines, to help improve outcomes in a fastpaced global business
world.
445 Hoes Lane, Piscataway, NJ 08854 USA | http://standards.ieee.org | Tel. +1 732-981-0060 Fax +1 732-562-1571
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
Redline Processing Notes:
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
Abstract: The technical specifications for, and testing of, the interconnection and
interoperability between utility electric power systems (EPSs) and distributed energy resources
(DERs) are the focus of this standard. It provides requirements relevant to the performance,
operation, testing, safety considerations, and maintenance of the interconnection. It
also includes general requirements, response to abnormal conditions, power quality,
islanding, and test specifications and requirements for design, production, installation
evaluation, commissioning, and periodic tests. The stated requirements are universally
needed for interconnection of DER, including synchronous machines, induction machines, or
power inverters/converters and will be sufficient for most installations. The criteria and
requirements are applicable to all DER technologies interconnected to EPSs at typical
primary and/or secondary distribution voltages. Installation of DER on radial primary and
secondary distribution systems is the main emphasis of this document, although
installation of DERs on primary and secondary network distribution systems is considered. This
standard is written considering that the DER is a 60 Hz source.
IEEE and IEEE 2030 are registered trademarks in the U.S. Patent & Trademark Office, owned by The Institute of Electrical and Electronics
Engineers, Incorporated.
National Electrical Safety Code and NESC are registered trademarks and service marks in the U.S. Patent & Trademark Office, owned by
the Institute of Electrical and Electronics Engineers, Incorporated.
National Electrical Code, NEC, and NFPA 70 are registered trademarks in the U.S. Patent & Trademark Office, owned by the National Fire
Protection Association.
2
Copyright © 2018 IEEE. All rights reserved.
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
Important Notices and Disclaimers Concerning IEEE Standards Documents
IEEE documents are made available for use subject to important notices and legal disclaimers. These notices
and disclaimers, or a reference to this page, appear in all standards and may be found under the heading “Important
Notices and Disclaimers Concerning IEEE Standards Documents.” They can also be obtained on request from IEEE
or viewed at http://standards.ieee.org/IPR/disclaimers.html.
Translations
The IEEE consensus development process involves the review of documents in English only. In the event that an IEEE
standard is translated, only the English version published by IEEE should be considered the approved IEEE standard.
3
Copyright © 2018 IEEE. All rights reserved.
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
Official statements
A statement, written or oral, that is not processed in accordance with the IEEE-SA Standards Board Operations
Manual shall not be considered or inferred to be the official position of IEEE or any of its committees and
shall not be considered to be, or be relied upon as, a formal position of IEEE. At lectures, symposia, seminars,
or educational courses, an individual presenting information on IEEE standards shall make it clear that his or her
views should be considered the personal views of that individual rather than the formal position of IEEE.
Comments on standards
Comments for revision of IEEE Standards documents are welcome from any interested party, regardless of
membership affiliation with IEEE. However, IEEE does not provide consulting information or advice pertaining to
IEEE Standards documents. Suggestions for changes in documents should be in the form of a proposed change of
text, together with appropriate supporting comments. Since IEEE standards represent a consensus of concerned
interests, it is important that any responses to comments and questions also receive the concurrence of a balance of
interests. For this reason, IEEE and the members of its societies and Standards Coordinating Committees are not
able to provide an instant response to comments or questions except in those cases where the matter has previously
been addressed. For the same reason, IEEE does not respond to interpretation requests. Any person who would like
to participate in revisions to an IEEE standard is welcome to join the relevant IEEE working group.
Users of IEEE Standards documents should consult all applicable laws and regulations. Compliance with the provisions
of any IEEE Standards document does not imply compliance to any applicable regulatory requirements. Implementers
of the standard are responsible for observing or referring to the applicable regulatory requirements. IEEE does not, by
the publication of its standards, intend to urge action that is not in compliance with applicable laws, and these
documents may not be construed as doing so.
Copyrights
IEEE draft and approved standards are copyrighted by IEEE under U.S. and international copyright laws. They are
made available by IEEE and are adopted for a wide variety of both public and private uses. These include both use, by
reference, in laws and regulations, and use in private self-regulation, standardization, and the promotion of engineering
practices and methods. By making these documents available for use and adoption by public authorities and private
users, IEEE does not waive any rights in copyright to the documents.
Photocopies
Subject to payment of the appropriate fee, IEEE will grant users a limited, non-exclusive license to photocopy portions
of any individual standard for company or organizational internal use or individual, non-commercial use only. To
arrange for payment of licensing fees, please contact Copyright Clearance Center, Customer Service, 222 Rosewood
Drive, Danvers, MA 01923 USA; +1 978 750 8400. Permission to photocopy portions of any individual standard for
educational classroom use can also be obtained through the Copyright Clearance Center.
4
Copyright © 2018 IEEE. All rights reserved.
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
Updating of IEEE Standards documents
Users of IEEE Standards documents should be aware that these documents may be superseded at any time by
the issuance of new editions or may be amended from time to time through the issuance of amendments,
corrigenda, or errata. An official IEEE document at any point in time consists of the current edition of the document
together with any amendments, corrigenda, or errata then in effect.
Every IEEE standard is subjected to review at least every ten years. When a document is more than ten years old
and has not undergone a revision process, it is reasonable to conclude that its contents, although still of some value,
do not wholly reflect the present state of the art. Users are cautioned to check to determine that they have the latest
edition of any IEEE standard.
In order to determine whether a given document is the current edition and whether it has been amended through
the issuance of amendments, corrigenda, or errata, visit the IEEE-SA Website at https://ieeexplore.ieee.org/ or
contact IEEE at the address listed previously. For more information about the IEEE-SA or IEEE’s standards
development process, visit the IEEE-SA Website at http://standards.ieee.org.
Errata
Errata, if any, for all IEEE standards can be accessed on the IEEE-SA Website at the following
URL: http://standards.ieee.org/findstds/errata/index.html. Users are encouraged to check this URL for errata
periodically.
Patents
Attention is called to the possibility that implementation of this standard may require use of subject matter covered
by patent rights. By publication of this standard, no position is taken by the IEEE with respect to the existence or
validity of any patent rights in connection therewith. If a patent holder or patent applicant has filed a statement of
assurance via an Accepted Letter of Assurance, then the statement is listed on the IEEE-SA
Website at http://standards.ieee.org/about/sasb/patcom/patents.html. Letters of Assurance may indicate whether
the Submitter is willing or unwilling to grant licenses under patent rights without compensation or under
reasonable rates, with reasonable terms and conditions that are demonstrably free of any unfair discrimination to
applicants desiring to obtain such licenses.
Essential Patent Claims may exist for which a Letter of Assurance has not been received. The IEEE is not
responsible for identifying Essential Patent Claims for which a license may be required, for conducting inquiries
into the legal validity or scope of Patents Claims, or determining whether any licensing terms or conditions
provided in connection with submission of a Letter of Assurance, if any, or in any licensing agreements are
reasonable or non-discriminatory. Users of this standard are expressly advised that determination of the validity of
any patent rights, and the risk of infringement of such rights, is entirely their own responsibility. Further
information may be obtained from the IEEE Standards Association.
5
Authorized licensed use limited to: China University of Copyright
Petroleum. © 2018 IEEE.
Downloaded on All rights reserved.
November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
IEEE Std 1547-2018
IEEE Standard for Interconnection and Interoperability of Distributed Energy Resources with Associated Electric Power
Systems Interfaces
Acknowledgements
During the writing of this standard, one of our Working Group members, Keith Harley, passed away. Keith
had an enthusiasm and passion for his career and for his family. He made a positive impact on those he
worked with and made the travel more interesting and fun with his adventurous personality and stories
about travel. Keith had a unique ability to articulate very complex technical issues into language that is
clear and meaningful. On several occasions, his leadership contributed to establishing some major
milestones in this standard and for other IEEE standards development for North America. We are
saddened by his loss. His contributions to the industry have been important and will be long-lasting.
Participants
At the time this standard was completed, the Standards Coordinating Committee 21 on Fuel Cells,
Photovoltaics, Dispersed Generation, and Energy Storage had the following membership:
At the time this standard was completed, the Interconnection and Interoperability of Distributed Energy
Resources with Associated Electric Power Systems Interfaces Working Group (P1547 WG) of the Standard
Coordinating Committee 21 (SCC21) on Fuel Cells, Photovoltaics, Dispersed Generation, and Energy
Storage had the following membership:
Facilitators
Richard Bravo, Leo Casey, Frances Cleveland, Michael (Mike) Coddington, Dan Mungovan,
Mohammad (Aminul) Huque, Marty Page, Jeannie M. Piekarz-Amber, Michael (Mike) Ropp,
Chris Rowe, Brian Seal, Wayne Stec, Reigh Walling
6
Copyright © 2018 IEEE. All rights reserved.
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
IEEE Std 1547-2018
IEEE Standard for Interconnection and Interoperability of Distributed Energy Resources with Associated Electric Power
Systems Interfaces
The following working group members participated in finalizing the development of the standard with
working group inputs, and in facilitating the development of those inputs development process:
The following members of the individual balloting committee voted on this standard. Balloters may have
voted for approval, disapproval, or abstention.
7
Copyright © 2018 IEEE. All rights reserved.
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
IEEE Std 1547-2018
IEEE Standard for Interconnection and Interoperability of Distributed Energy Resources with Associated Electric Power
Systems Interfaces
8
Copyright © 2018 IEEE. All rights reserved.
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
IEEE Std 1547-2018
IEEE Standard for Interconnection and Interoperability of Distributed Energy Resources with Associated Electric Power
Systems Interfaces
When the IEEE-SA Standards Board approved this standard on 15 February 2018, it had the following
membership:
*Member Emeritus
9
Copyright © 2018 IEEE. All rights reserved.
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
Introduction
This introduction is not part of IEEE Std 1547™-2018, IEEE Standard for Interconnection and Interoperability of
Distributed Energy Resources with Associated Electric Power Systems Interfaces.
IEEE Std 1547 was the first of a series of standards developed by Standards Coordinating Committee 21 on
Fuel Cells, Photovoltaics, Dispersed Generation, and Energy Storage (SCC21) concerning distributed
resources interconnection. IEEE Std 1547 was amended in 2014 (IEEE Std 1547a™-2014) in response to a
widely expressed need to make changes to subclauses related to voltage regulation, voltage response to
Area EPS abnormal conditions, and frequency response to Area EPS abnormal conditions in
IEEE Std 1547-2003. The additional documents in that series are as follows:
IEEE Std 1547.1™ [B17] provides conformance test procedures for equipment interconnecting
distributed energy resources (DER) with electric power systems (EPS). 1
IEEE Std 1547.2™ [B18] is an application guide for IEEE Std 1547.
IEEE Std 1547.3™ [B19] provides guidance for monitoring, information exchange, and control of
DER interconnected with EPS.
IEEE Std 1547.4™ [B20] provides guidance for design, operation, and integration of distributed
resource island systems with EPS.
IEEE Std 1547.6™ [B21] is a recommended practice for interconnecting DER with electric
distribution secondary networks.
IEEE Std 1547.7™ [B22] provides guidance for conducting distribution impact studies for DER
interconnection.
The first publication of IEEE Std 1547 was an outgrowth of the changes in the environment for production
and delivery of electricity and built on prior IEEE recommended practices and guidelines developed by
SCC21 (which included IEEE Std 929™-2000 [B14] and IEEE Std 1001™-1988 [B15]).
Traditionally, utility EPSs were not designed to accommodate active generation and storage at the
distribution level. The technologies and operational concepts to effectively integrate DERs into existing
EPSs continue to be further developed to realize additional benefits and to avoid negative impacts on
system reliability and safety.
There is a critical need to have a single document of consensus standard technical requirements for DER
interconnection rather than having to conform to numerous local practices and guidelines. This standard
addresses that critical need by providing uniform criteria and requirements relevant to the performance,
operation, testing, safety considerations, and maintenance of the interconnection.
The intent of this standard is to define the technical requirements in a manner that can be universally
adopted. The universality relates not only to the technical aspects, but also to the adoption of this standard
as being pertinent across a number of industries and institutions, e.g., hardware manufacturers, utilities,
energy service companies, codes and standards organizations, regulators and legislators, and other
interested entities.
This standard focuses on the technical specifications for, and testing of, the interconnection itself, and not
on the types of the DER technologies. This standard aims to be technology-neutral, although acknowledges
that the technical attributes of DER and the types and characteristics of EPSs do have a bearing on the
interconnection requirements. The addition of a DER to an EPS will change the system and its response in
some manner. Although this standard establishes criteria and requirements for interconnection, this
1
The numbers in brackets correspond to the numbers of the bibliography in Annex A.
10
Copyright © 2018 IEEE. All rights reserved.
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
standard is not a design handbook nor is it an application guideline. This standard provides the
minimum functional technical requirements that are universally needed to help assure a
technically sound interconnection. Any additional local requirements should not be implemented to
the detriment of the functional technical objectives of this standard.
This standard recognizes that distributed energy resources need to be integrated into the Area EPS
in coordination with the Area EPS operator. The functions specified in this standard may need to
be supplemented in coordination with the Area EPS operator for specific situations.
It is beyond the scope of this standard to address the methods used for performing EPS impact
studies, mitigating limitations of the Area EPS, or addressing the business or tariff issues
associated with interconnection.
11
Copyright © 2018 IEEE. All rights reserved.
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
Contents
1. Overview .................................................................................................................................................. 15
1.1 General .............................................................................................................................................. 15
1.2 Scope ................................................................................................................................................. 15
1.3 Purpose .............................................................................................................................................. 16
1.4 General remarks and limitations ........................................................................................................ 16
1.5 Conventions for word usage and notes to text, tables and figures ..................................................... 20
2. Normative references................................................................................................................................ 20
8. Islanding ................................................................................................................................................... 65
8.1 Unintentional islanding ...................................................................................................................... 65
8.2 Intentional islanding .......................................................................................................................... 65
12
Copyright © 2018 IEEE. All rights reserved.
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
9. DER on distribution secondary grid/area/street (grid) networks and spot networks ................................ 67
9.1 Network protectors and automatic transfer scheme requirements ..................................................... 67
9.2 Distribution secondary grid networks ................................................................................................ 68
9.3 Distribution secondary spot networks................................................................................................ 68
Annex C (informative) DER intentional and microgrid island system configurations ................................107
C.1 Introduction ......................................................................................................................................107
C.2 Connecting DER not designed for intentional island or microgrid operation ..................................108
Annex D (informative) DER communication and information concepts and guidelines ............................109
D.1 Introduction .....................................................................................................................................109
D.2 General principles ............................................................................................................................109
D.3 Communication protocols ................................................................................................................111
D.4 Cyber security ..................................................................................................................................111
D.5 Related standards .............................................................................................................................113
Annex F (informative) Discussion of testing and verification requirements at PCC or PoC ......................121
13
Copyright © 2018 IEEE. All rights reserved.
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
G.5 Limitation of overvoltage ................................................................................................................128
G.6 Related standards .............................................................................................................................128
14
Copyright © 2018 IEEE. All rights reserved.
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
IEEE Standard for Interconnecting Interconnection and Interoperability
of Distributed Energy Resources with Associated Electric Power Systems
Interfaces
1. Overview
1.1 General
requirements, and test specifications and requirements for distributed energy resources (DERs).
Additionally, there is a bibliography several annexes are included as Annex A that lists citations
referred to in this standard that provide additional material for informative purposes, but that are
1.2 Scope
This standard establishes criteria and requirements for interconnection of distributed energy
resources (DR) with electric power systems (EPSs) and associated interfaces. The stated technical
specifications and requirements, both technical and testing, are universally needed for
or power inverters/converters, distributed energy resources (DERs) 2 and will be sufficient for most
installations. 1 3 The specified performance requirements apply at the time of interconnection and as
1 3 Additional technical requirements and/or tests may be necessary for some limited higher DER penetration situations.
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
1.3 Purpose
This standard document provides a uniform standard for the interconnection and interoperability of
distributed energy resources with electric power systems. It provides requirements relevant to the
The requirements shall be met at the point of common coupling (PCC), although the devices used to
meet these requirements can be located elsewhere. This standard applies to interconnection based on
the aggregate rating of all the DR units that are within the Local EPS. The functions of the
interconnection system hardware and software that affect the Area EPS are required to meet this
The criteria and requirements in this document are applicable to all distributed energy resource
technologies, with aggregate capacity of 10 MVA or less at the PCC, interconnected to EPSs at
typical primary and/or secondary distribution voltages voltage levels. Installation of DR DER on
radial primary and secondary distribution systems is the main emphasis of this standard, although
installation of DR DER on primary and secondary network distribution systems is considered. This
standard is has been written considering that the DR is assuming a 60 Hz source nominal system
frequency. 4
Figure 1 illustrates the scope of this standard. The criteria and requirements in this document may
influence the design and capabilities of the power interface, the local DER communication interface and
all those parts of a DER that are related to meeting the requirements of this standard. In Clause 4 to
Clause 11, the term ‚DER‛ refers to all those parts of a DER that are related to meeting the
4 If the standard is used with other nominal frequency values, all frequency values in the standard should be adjusted appropriately.
This may require proportional adjustment of the frequency values in coo rdination with the regional reliability coordinator.
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
(New)
The following list describes what remains outside the scope of this standard:
― This standard as a whole is not intended for, and is in part inappropriate for, application to
― This standard does not define the maximum DR DER capacity for a particular installation
given feeder.
clauses, this standard does not prescribe DR DER self-protection or all any DER operating
requirements for DR units, as long as these do not preclude the DER from meeting the
5 Investigations of events that inadvertently tripped bulk power system connected resources in North America suggest that one root
c ause may have been misapplication of previous versions of this standard; refer to NERC [B28] for more details.
6 The performance of energy resources connected to transmission or networked sub-transmission systems may be specified by the
7 Requirements specified in 6.4.2 and 6.5.2 do provide constraints that must be respected in the application of DER self-protec tion.
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
― This standard does not address planning, designing, operating, or maintaining the Area
― This standard does not apply to automatic transfer schemes in which load is transferred
between the DR DER and the EPS in a momentary make-before-break operation provided
the duration of paralleling the sources is less than 100 ms, except as noted in 4.1.4 Clause 9.
― As defined in 4.13, 5.3.1, 6.4.2.1, 6.5.2.1, and 10.1, emergency and standby DER8 are exempt
― This standard does not give any guidance regarding how the Area EPS operator may
specify functional parameter settings other than the default setting within the specified
ranges of allowable settings, e.g., to coordinate with the existing Area EPS protection and
control devices.
― This standard does not determine the communication network specifics nor the utilization
of the DER provisions for a local DER interface capable of communicating (local DER
standard.
― The lower and upper values of the ranges of allowable settings for voltage and frequency trip
settings specified in this standard for DER are not intended to limit the capabilities and
― For DER interconnections that include individual synchronous generato r units rated 10
MVA and greater, and where the requirements of this standard conflict with the
requirements of IEEE Std C50.12 or IEEE Std C50.13, the requirements of IEEE Std C50.12
or IEEE Std C50.13, as relevant to the type of synchronous generator used, shall prevail.
9 Refer to footnotes 80 and 99 on recommendations for utility practices to use trip settings on Area EPS equipment that conflic t with
this standard to occasionally and selectively accommodate worker safety practices or to safeguard distribution infrastructure while
in an abnormal configuration.
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
This standard applies to interconnection based on the aggregate nameplate rating of all the DER
units that are within the Local EPS. Supplemental DER devices other than DER units may be used to
achieve compliance with the requirements of this standard at the applicable reference point per
Clause 4. These devices are not required to be co-located with the DER units, but shall be within the
Local EPS. The requirements of this standard shall be met regardless of the location of the DER and
supplemental DER devices within the Local EPS. These relationships are shown in Figure 2.
(New)
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
(Deleted)
NOTE 1—The example of Local EPS 1 includes only load. An y requirements for this Local EPS are
NOTE 2—The example of Local EPS 2 includes only DER. Depending on the DER rating,
requirements of this standard apply either at the PCC or the PoC. The DER unit in this example is
able to meet requirements at its terminals without any supplemental DER device; the PoC coincides
with‖the‖DER‖unit’s‖terminals.
NOTE 3—The example of Local EPS 3 includes both DER units and load. Depending on the
apply either at the PCC or the PoC. The two (or more) DER units are able to meet requirements at its
terminals‖without‖any‖supplemental‖DER‖device;‖the‖PoC‖coincides‖with‖the‖DER‖units’‖terminals;‖
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
NOTE 4—The example of Local EPS 4 includes a DER unit, a supplemental DER device, and load.
standard apply either at the PCC or the PoC. The DER unit is not able to meet requirements at its
terminals without any supplemental DER device; the PoC is the point where the requirements of this
standard are met by the DER unit in conjunction with the supplemental DER device exclusive of any
NOTE 5—The example of Local EPS 5 includes two (or more) DER units and a supplemental DER
device‖ but‖ no‖ load.‖ Depending‖ on‖ the‖ aggregate‖ DER‖ units’‖rating,‖requirements‖of‖this‖standard‖
apply either at the PCC or the PoC. As indicated by the curved line, the PCC and PoC may be
located well apart from each other. The two (or more) DER units are not able to meet requirements
at their terminals without any supplemental DER device; the PoC is the point wher e the
requirements of this standard are met by two (or more) DER units in conjunction with the
supplemental DER device exclusive of any load, if present, in the respective part of the Local EPS.
The stated technical specifications and requirements are universally needed for interconnection and
interoperability of DER10 and will be sufficient for most installations. 11 The applicability of certain
specifications and requirements are dependent on application considerations. For these, the
(AGIR) to determine applicability. The rationale used as the basis for the performance categories is
as follows:
For categories related to reactive power capability and voltage regulation performance requirements
(Clause 5):
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
— Category A covers minimum performance capabilities needed for Area EPS voltage
regulation and are reasonably attainable by all DER technologies as of the publication of
this standard. This level of performance is deemed adequate for applications where the
DER penetration in the distribution system is lower, 12 and where the overall DER power
capabilities needed to adequately integrate DERs in local Area EPSs where the aggregated
DER penetration is higher or where the overall DER power output is subject to frequent
large variations.
For categories related to response to Area EPS abnormal conditions (Clause 6):
— Abnormal operating performance Category I is based on essential bulk power system (BPS)
stability/reliability needs and reasonably attainable by all DER techn ologies that are in
— Abnormal operating performance Category II covers all BPS stability/reliability needs and is
coordinated with existing reliability standards 13 to avoid tripping for a wider range of
12 This c lause intentionally uses qualitative DER penetration levels qualifiers. The impact of DER on frequency and voltage
performanc e of the interconnections and the regional power systems differs significantly and it remains in the responsibility of an
AGIR to quantify impactful DER penetration levels. Refer to Annex B for more rationale on category assignments.
13 In North America, the limitations for transmission-connected resources as specified in NERC PRC-024-2 [B27] may be used for
referenc e.
14 Inc ludes 1LG stuck breaker transmission faults as well as normally and delayed cleared faults at the lower-level transmission and
sub-transmission levels where fault durations can be longer (primarily due to the use of zone impedance relaying), e.g ., sub-
transmission 3LG with normal fault clearing or simultaneous 1LG faults on different phases of two sub-transmission circuits on the
same struc ture with normal fault clearing. (NERC [B26], [B28], [B29], [B30].)
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
— Abnormal operating performance Category III is based on both BPS stability/reliability and
All performance categories specify minimum equipment capability requirements and may also
specify designated limiting requirements for ranges of allowable settings of control or trip parameter
values. For categories related to reactive power capability and voltage regulation performance
requirements (Clause 5), Category B is inherently capable of meeting the requirements for Category
A. For categories related to response to Area EPS abnormal conditions (Clause 6), categories with
higher number values are inherently capable of meeting the voltage and frequency ride-through
requirements of lower number value categories; however, this may not hold for voltage and
frequency trip requirements because their ranges of allowable settings may be mutually exclusive. If a
DER listed for a higher level abnormal operating performance category was used in a lower-level
category application, the correct range of allowable settings for magnitude and duration values of trip
settings shall be ensured, for example by the use of software profiles designated for each abnormal
Additional guidelines on criteria for assignment of DER performance categories are given in Annex
B. 16
Where applicable, the stated technical specifications and requirements are given in generator sign
convention, which is opposite to load sign convention. In generator sign convention, a DER current
lagging voltage provides/injects reactive power to the system (over-excited operation of DER,
positive reactive power), and this tends to increase the applicable voltage under normal syst em
conditions; a DER current leading voltage consumes/absorbs reactive power from the system
(under-excited operation of DER, negative reactive power), and this tends to decrease of the
16 As proposed in the IEEE P1547 response to FERC NOPR RM16-8 submitted by the IEEE S tandards Association in May 2016 [B6],
the c riteria for assignment of DER performance categories outlined in the informative Annex B may be used as a reference point to
partly‖spec ify‖‚Good‖Utility‖Practice‛‖for‖specific‖ride‖through‖requirements‖as‖required‖from‖small‖generating‖facilities‖pe r FERC
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
1.5 Conventions for word usage and notes to text, tables and figures
In this document, the word shall is used to indicate a mandatory requirement. The word should is
used to indicate a recommendation. The word may is used to indicate a permissible action. The word
Notes to text, tables, and figures are for information only and do not contain requirements needed to
2. Normative references
The following referenced documents are indispensable for the application of this document (i.e.,
they shall be understood and used, so each referenced document is cited in text and its relationship
to this document is explained). For dated references, only the edition cited applies. For undated
references, the latest edition of the referenced document (including any amendments or corrigenda)
applies.
The following standards shall be used in conjunction with this standard. When the stated version of
the following standards is superseded by an approved revision, then that revision shall apply.
The applicability of the following standards is determined by the specific requirements stated in this
ANSI C84.1-1995, Electric Power Systems and Equipment—Voltage Ratings (60 Hz). 2 17
limits for the connection of fluctuating installations to MV, HV and EHV power systems. 18
2 17 ANS I publications are available from the S ales Department, American National S tandards Institute, 25 West 43rd S treet, 4th
18 IEC public ations are available from the International Electrotechnical Commission (http://www.iec.ch) and the Americ an
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
IEC 61000-4-3, Electromagnetic compatibility (EMC)—Part 4-3: Testing and measurement
[B5] IEEE Std 519-1992™, IEEE Recommended Practices and Requirements for Harmonic Control in
IEEE Std 1453™, IEEE Recommended Practice for the Analysis of Fluctuating Installations on Power
Systems.
IEEE Std 1815™, IEEE Standard for Electric Power Systems Communications-Distributed Network
Protocol (DNP3).
IEEE‖Std‖2030.5™,‖IEEE‖Adoption‖of‖Smart‖Energy‖Profile‖2.0‖Application‖Protocol‖Standar d.
IEEE Std C37.90.1™-2002, IEEE Standard Surge Withstand Capability (SWC) Tests for Relays and
IEEE Std C37.90.2™-1995, IEEE Standard Withstand Capability of Relay Systems to Radiated
IEEE Std C50.12™, IEEE Standard for Salient-Pole 50 Hz and 60 Hz Synchronous Generators and
3 19 The IEEE standards or products referred to in Clause 2 are trademarks owned by The Institute of Electrical and Elec tronic s
4 20 IEEE publications are available fro m The Institute of Electrical and Electronics Engineers, 445 Hoes Lane, P.O. Box 1331,
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C62.41.2™-2002, IEEE Recommended Practice on Characterization of Surges in Low
IEEE Std C62.45™-2002, IEEE Recommended Practice on Surge Testing for Equipment Connected to
IEEE‖ Std‖ C62.92.1™,‖ IEEE‖ Guide‖ for‖ the‖ Application of Neutral Grounding in Electric Utility
For the purposes of this standard document, the following terms and definitions apply. IEEE 100TM,
The Authoritative Dictionary of IEEE Standards Terms, Seventh Edition [B4], 6 Dictionary Online should
3.1 Definitions
abnormal operating performance category: The grouping for a set of requirements that specify
technical capabilities and settings for a DER under abnormal operating conditions, i.e., outside the
continuous operation region.
applicable voltage: Electrical quantities that determine the performance of a Local EPS or DER
specified with regard to the reference point of applicability, individual phase-to-neutral, phase-to-
22 Notes in text, tables, and figures of a standard are given for information only and do not contain requirements needed to
5 NEMA public ations are available from Global Engineering Documents, 15 Inverness Way East, Englewood, Colorado 80112, US A
(http://global.ihs.com/).
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
NOTE—Applicable voltages are used as a synonym for applicable frequency, which can be derived from
3.1.3 design test: Test of one or more devices made to a certain design to show that the design meets
certain specifications.
3.1.4 distributed generation (DG): Electric generation facilities connected to an Area EPS through a
3.1.6.1 area electric power system, area (Area EPS): An EPS that serves Local EPSs.
NOTE—Typically, an Area EPS has primary access to public rights-of-way, priority crossing of
3.1.1 area electric power system operator (Area EPS operator): The entity responsible for designing,
authority governing interconnection requirements (AGIR): A cognizant and responsible entity that
defines, codifies, communicates, administers, and enforces the policies and procedures for allowing
electrical interconnection of DER to the Area EPS. This may be a regulatory agency, public utility
commission, municipality, cooperative board of directors, etc. The degree of AGIR involvement will
vary in scope of application and level of enforcement across jurisdictional boundaries. This authority
may be delegated by the cognizant and responsible entity to the Area EPS operator or bulk power
system operator.
various stakeholder interests, including but not limited to Load Customers, Area EPS operators, DER
authority having jurisdiction: Authority having the rights to inspection and approval of the design
available active power: Active power that a DER can deliver to the Area EPS subject to the
availability‖of‖the‖DER’s‖primary‖source‖of‖energy.
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
NOTE—Examples are solar irradiance in the case of a photovoltaic DER and wind speed in case of a
bulk power system (BPS): Any electric generation resources, transmission lines, interconnections
3.1.2 cease to energize: Cessation of energy outflow capability active power delivery under steady-
NOTE 2—This does not necessarily imply, nor exclude disconnection, isolation, or a trip.
NOTE 3—Limited reactive power exchange may continue as specified, e.g., th rough filter banks.
NOTE 4—Energy storage systems are allowed to continue charging but are allowed to cease from
actively charging when the maximum state of charge (maximum stored energy) has been achieved.
clearing time: The time between the start of an abnormal condition and the DER ceasing to energize
the Area EPS. It is the sum of the detection time, any adjustable time delay, the operating time plus
arcing time for any interposing devices (if used), and the operating time plus arcing time for the
interrupting device (used to interconnect the DER with the Area EPS).
continuous operation: Exchange of current between the DER and an EPS within prescribed behavior
while connected to the Area EPS and while the applicable voltage and the system frequency is within
specified parameters.
operation.
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
3.1.5 distributed resources energy resource (DR DER): Sources A source of electric power that are is
not directly connected to a bulk power transmission system. DR DER includes both generators and
energy storage technologies capable of exporting active power to an EPS. An interconnection system
or a supplemental DER device that is necessary for compliance with this standard is part of a DER. 23
NOTE 1—Controllable loads used for demand response are not included in the definition of DER.
distributed energy resource operator (DER operator): The entity responsible for operating and
distributed energy resource (DER) unit: An individual DER device inside a group of DER that
distributed energy resource managing entity (DER Managing Entity): An entity that monitors and
manages the DER through the local DER communication interface. The DER managing entity could be
disturbance period: The range of time during which the applicable voltage or the system frequency is
3.1.6 electric power system (EPS): Facilities that deliver electric power to a load.
energize: Active power outflow of the DER to an EPS under any conditions (e.g., steady state and
transient).
enter service: Begin operation of the DER with an energized Area EPS.
NOTE—Above a certain threshold, flicker becomes annoying. The annoyance grows very rapidly
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
with the amplitude of the fluctuation. At certain repetition rates even very small amplitudes can be
3.1.11.1 island, intentional island: A planned electrical island that is capable of being energized by
one or more Local EPSs. These (1) have DER(s) and load, (2) have the ability to disconnect from and
to parallel with the Area EPS, (3) include one or more Local EPS(s), and (4) are intentionally
planned.
NOTE—An intentional island may be an intentional Area EPS island or an intentional Local EPS island
(also:‖‚facility‖island‛).
intentional Area EPS island: An intentional island that includes portions of the Area EPS.
intentional Local EPS island: An intentional island that is totally within the bounds of a Local EPS.
3.1.7 interconnection: The result of the process of adding a DR unit DER to an Area EPS, whether
NOTE—See Figure 2.
(Deleted)
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
3.1.9 interconnection system: The collection of all interconnection and interoperability equipment
and functions, taken as a group, used to interconnect a DR unit(s) DER to an Area EPS. 24
NOTE—See Figure 2.
interface: An electrical or logical connection from one entity to another that su pports one or more
energy or data flows implemented with one or more power or data links.
components to externally exchange and readily use information securely an d effectively. (IEEE Std
2030® [B23])
3.1.10 inverter: A machine, device, or system that changes direct-current power to alternating-
current power.
3.1.11 island: A condition in which a portion of an Area EPS is energized solely by one or more
Local EPSs through the associated PCCs while that portion of the Area EPS is electrically separated
from the rest of the Area EPS on all phases to which the DER is connected. When an island exists, the
DER‖energizing‖the‖island‖may‖be‖said‖to‖be‖‚islanding‛.
load: Devices and processes in a local EPS that use electrical energy for utilization, exclusive of
devices or processes that store energy but can return some or all of the energy to the local EPS or
local DER communication interface: A local interface capable of communicating to support the
information exchange requirements specified in this standard for all applicable functions that are
24 This term was frequently used in IEEE S td 1547-2003. Given the scope of the present standard, which may have implications to
the‖design‖of‖the‖entirety‖of‖the‖DER,‖this‖standard‖uses‖the‖term‖‚DER‛‖in‖most‖places.
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
3.1.6.2 local electric power system, local (Local EPS): An EPS contained entirely within a single
NOTE—See Figure 1 2.
mandatory operation: Required continuance of active current and reactive current exchange of DER
with Area EPS as prescribed, notwithstanding disturbances of the Area EPS voltage or frequency
operation.
medium voltage: A class of nominal system voltages equal to or greater than 1 kV and less than or
equal to 35 kV.
NOTE—IEEE‖standards‖are‖not‖unanimous‖in‖establishing‖the‖range‖for‖‚medium‖voltage‛.
momentary cessation: Temporarily cease to energize an EPS, while connected to the Area EPS, in
response to a disturbance of the applicable voltages or the system frequency, with the capability of
immediate Restore Output of operation when the applicable voltages and the system frequency return
momentary cessation.
nameplate ratings: Nominal voltage (V), current (A), maximum active power (kW), apparent power
(kVA), and reactive power (kvar) at which a DER is capable of sustained operation.
NOTE—For Local EPS with multiple DER units, the aggregate DER nameplate rating is equal to the
sum of all DERs nameplate rating in the Local EPS, not including aggregate capacity limiting
mechanisms such as coincidence factors, plant controller limits, etc., that may be applicable for
specific cases.
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
normal operating performance category: The grouping for a set of requirements that specify
technical capabilities and settings for DER under normal operating conditions, i.e., inside the
open loop response time: The duration from a step change in control signal input (reference value
or system quantity) until the output changes by 90% of its final change, before any overshoot.
NOTE 1—The control loop considered in this definition refers to the DER control system in
time when the DER is interconnected with a stiff grid (ideal voltage source).
NOTE 2—The open loop response time is equal to 2.3 times the time constant of a first -order (i.e.,
operating mode: Mode of DER operation that determines the performance during normal or
abnormal conditions.
performance operating region: A region bounded by point pairs consisting of magnitude (voltage
or frequency) and cumulative time duration which are used to define the operational performance
permissive operation: Operating mode where the DER performs ride-through either in mandatory
operation or in momentary cessation, in response to a disturbance of the applicable voltages or the system
frequency.
operation.
permit service: A setting that indicates whether a DER is allowed to enter or remain in service.
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
per unit (p.u.) / percent of (%): Quantity expressed as a fraction of a defined base unit quantity. For
active power (active current), the base quantity is the rated active power (rated active current). For
apparent power (current), the base quantity is the rated apparent power (rated current). For system
frequency, the base quantity is the nominal frequency (i.e., 60.0 Hz in North America). Quantities
expressed in per unit can be converted to quantities expressed in percent of a base quantity by
3.1.13 point of common coupling (PCC): The point where a Local EPS is connected to an of
NOTE 2—Equivalent,‖in‖most‖cases,‖to‖‚service‖point‛‖as‖specified‖in‖the‖National‖Electrical‖Code ®
(NEC®) [B31] and the National Electrical Safety Code® (NESC®) [B1].
3.1.14 point of distributed energy resources connection (point of DR DER connection–PoC): The
point where a DR DER unit is electrically connected in an a Local EPS and meets the requirements of
this standard exclusive of any load present in the respective part of the Local EPS.
NOTE 2—For (a) DER unit(s) that are not self-sufficient to meet the requirements without (a)
supplemental DER device(s), the point of DER connection is the point where the requirements of this
standard are met by DER (a) device(s) in conjunction with (a) supplemental DER device(s) exclusive
post-disturbance period: The period starting upon the return of all applicable voltages or the system
frequency to the respective ranges of the mandatory operation region or continuous operation region.
protective function(s): The behavior whose purpose is to maintain safe operations and/or maintain
safe conditions.
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
range of allowable settings: The range within which settings may be adjusted to values other than
reference point of applicability (RPA): The location where the interconnection and interoperability
regional reliability coordinator: The functional entity that maintains the real-time operating
restore output: Return operation of the DER to the state prior to the abnormal excursion of voltage
ride-through: Ability to withstand voltage or frequency disturbances inside defined limits and to
3.1.15 simulated utility: An assembly of variable frequency and variable voltage test equipment
step response: The output as a function of time t when the input is a step.
supplemental DER device: Any equipment that is used to obtain compliance with some or all of the
NOTE—Examples include capacitor banks, STATCOMs, harmonic filters that are not part of a DER
3.1.16 total demand distortion (TDD): The total root-sum-square harmonic current distortion, in
3.1.17 total rated-current distortion (TRD): The total root-sum-square of the current distortion
components (including harmonics and inter-harmonics) created by the DR DER unit operating into
expressed as a linear balanced load divided by the greater percentage of the test load current
demand (IL ) or the DER rated current capacity of the DR unit (Irated).
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
trip: Inhibition of immediate return to service, which may involve disconnection.
type test: A test of one or more devices manufactured to a certain design to demonstrate, or provide
information that can be used to verify, that the design meets the requirements specified in this
standard.
zero-sequence continuity: Circuit topology providing continuity between two defined points in the
NOTE—A transformer that has a delta or ungrounded-wye winding in the topological path between
3.2 Acronyms
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
DG distributed generation
DR distributed resources
I current
IL load current
NP network protector
PV photovoltaic
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
4. General interconnection technical specifications and performance
requirements
4.1 Introduction
The reference point of applicability (RPA) is the location where the interconnection and
interoperability performance requirements specified in this standard shall be met. The electr ical
quantities referred to in this standard are those at the RPA, unless stated otherwise in this standard.
The requirements in this clause shall be met at the PCC, although the devices used to meet these
requirements can be located elsewhere. The performance requirements of this standard apply to
interconnection of either a single DR DER unit based on that unit’s rating or multiple DR DER units
within a single Local EPS (‚DER system‛), based on the aggregate rating of all the DR DER units
that are within the Local EPS. The capabilities and functions of the interconnection system DER
hardware and software that affect the Area EPS are required to meet this standard regardless of their
location on the EPS. The performance requirements in this clause standard are functional and do not
The technical specifications and performance requirements specified here are universally needed for
interconnection and interoperability of DER25 and will be sufficient for most installations. 26 The
For these, the requirements are provided in terms of a limited number of technology-neutral
performance categories, for which it is the responsibility of the authority governing interconnection
25 For example, The stated technical specifications and requirements are universally needed for interconnection of DR, inc luding
sync hronous machines, induction machines, or static power inverters/converters , and will be sufficient for most installations.7
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
DER shall be designed and installed such that it meets the performance and test and verification
requirements described in Clause 4 to Clause 11 of this standard. Unless specified otherwise, the
term‖‚DER‛‖means‖‚DER‖system‛.‖In‖specific‖cases,‖‚DER‖unit‛‖is‖explicitly‖stated.
The characteristics of the Local EPS and DER shall determine the reference point of applicability (RPA).
Except as otherwise stated in this standard, the RPA for all performance requirements of this
standard shall be the point of common coupling (PCC).
Alternatively, for Local EPSs where zero sequence continuity 27 between the PCC and PoC is
maintained and either of the following conditions apply, the RPA for performance requirements of
this standard may be the point of DER connection (PoC), or by mutual agreement between the Area
EPS operator and the DER operator, at any point between, or including, the PoC and PCC:
b) Annual average load demand28 of greater than 10% of the aggregate DER nameplate
rating, and where the Local EPS is not capable of, or is prevented from, exporting more
27 When the zero sequence continuity is broken, for example by a delta-wye transformer between the PCC and the PoC, the
voltages at the PoC may not be representative of the voltages at the PCC under abnormal voltage conditions. Examples of issue s
―‖ Diffic ulty‖ of‖ ‘sensing’‖ single-phase-to-ground faults or failure to detect ground-fault overvoltages. Note that 7.4.1 spec ifies
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
For all other Local EPSs meeting either of the conditions a) or b) above but not meeting the
requirement for zero sequence continuity, the RPA for performance requirements other than the
response to Area EPS abnormal conditions specified in 6.2 and 6.4 shall be the PoC, or by mutual
agreement between the Area EPS operator and the DER operator, at any point between, or including,
the PoC and PCC. The RPA for performance requirements of 6.2 and 6.4 shall be a point between, or
including, the PoC and PCC that is appropriate to detect the abnormal voltage conditions. 29, 30
Where the RPA is not at the PCC, any equipment or devices in the Local EPS between the RPA and
the PCC shall not preclude the DER from meeting the disturbance ride-through requirements
For Local EPS where aggregate DER nameplate rating is greater than 500 kVA, and annual average
load demand28 is greater than 10% of the aggregate DER nameplate rating, and the Local EPS is
capable of, and is not prevented from, exporting more than 500 kVA for longer than 30 s, the RPA
shall be the PCC and performance requirements specified in 5.2 for reactive power capability and in
Clause 7 for power quality may be evaluated excluding the influence of the Local EPS load.
Figure H.1 illustrates a decision tree to determine the RPA for Local EPS where zero sequence
continuity is maintained. Figure H.2 illustrates a decision tree to determine the RPA for Local EPS
29 The intent of meeting the response to Area EPS abnormal voltage conditions requirements of 6.4 at the PCC is to appro priately
30 For DER that are permitted to use the PoC as the RPA, the location selected as the RPA may be different for each of the vario us
31 Examples are undervoltage and overcurrent relays within the local EPS between the RPA and PCC that are set such that they
may trip the DER during the voltage disturbance ride -through operation for short-circuit faults other than ones on the Area EPS
c irc uit sec tion to which the DER is connected. This does not preclude selectively tripping DER for faults on the Area EPS as
spec ified in 6.2.1.
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
4.3 Applicable voltages
The applicable voltages 32 determine the performance of a Local EPS or DER and are the electrical
quantities specified with regard to the reference point of applicability, individual phase-to-neutral,
For DER with a PCC located at the medium-voltage level, the applicable voltages shall be determined
by the configuration and nominal voltage of the Area EPS at the PCC. For DER with a PCC located
at the low-voltage33 level, the applicable voltages shall be determined by the configuration of the low-
voltage winding of the Area EPS transformer(s) between the medium-voltage system and the low-
voltage system. The applicable voltages that shall be detected are shown in Table 1 and Table 2. For
multi-phase systems, the requirements for applicable voltages shall apply to all phases.
(New)
(New)
aA three-phase transformer or a bank of single-phase transformers may be used for three-phase
systems.
32 Applica ble voltages are used in synonym for applicable frequency, which can be derived from the applicable voltages.
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
bFor 120/208 V two-phase services, line-to-line voltages shall be sufficient.
senses the line-to-line and is therefore compliant with this requirement. Sensing line-to-ground may
also be used; however, the ground connection should only be used for voltage sensing purposes.
The applicable frequency is the fundamental-frequency component. The applicable voltages shall be
quantified as the effective (RMS) values over the preceding fundamental frequency period, unless
For voltage-reactive power 34 (volt-var) mode requirements in 5.3.3 and voltage-active (real)
power 35 mode requirements in 5.4.2 where DER do not respond to individual phase voltages, the
applicable voltages are quantified as the average of the three-phase effective (RMS) values or
alternatively positive sequence component of voltages over one fundamental frequency period.
For voltage trip and ride-through requirements in 6.4, the following shall apply:
― For low-voltage ride-through and undervoltage trip, the relevant voltage at any given time
shall be the least magnitude of the individual applicable voltages relative to the
― For high-voltage ride-through and overvoltage trip, the relevant voltage at any given time
shall be the greatest magnitude of the applicable voltages relative to the corresponding
nominal voltage.
For rate of change of frequency (ROCOF) ride-through requirements in 6.5.2.5, the ROCOF shall be
the average rate of change of frequency over an averaging window of at least 0.1 s.
34 Voltage-reactive‖power‖mode‖may‖also‖be‖commonly‖referred‖to‖as‖‚volt-var‛‖mode.
35 Voltage-ac tive‖power‖mode‖may‖also‖be‖commonly‖referred‖to‖as‖‚volt-watt‛‖mode.
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
4.4 Measurement accuracy
The DER36 shall meet the minimum steady-state37 and transient 38 measurement and calculation 39
accuracy requirements for voltage, frequency, active power, reactive power, and time as specified in
Table 3. Actual measurement and calculation accuracy of a DER shall be stated for each of the values
above.
for manufacturersa
(New)
aMeasurement accuracy requirements specified in this table are applicable for voltage THD < 2.5%
36 The DER includes any equipment required to meet the interconnection performance and interoperability requirements of the
37 S teady-state measurements may be used for providing monitoring information through a local DER communication interface at the
38 Transient measurements can be used by protective relays for achieving the mandatory voltage and frequency -tripping
39 Only the fundamental parameters can actually be measured, e.g., time, voltage, and current. Other quantities are calc ulated
based on the fundamental parameters measured, e.g., frequency, active power, and reactive power.
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
bAccuracy requirements for frequency are applicable only when the fundamental voltage is greater
In the cease to energize state, the DER shall not deliver active power during steady-state or transient
conditions. The requirements for cease to energize shall apply to the point of DER connection (PoC).
For Local EPS with aggregate DER rating less than 500 kVA, the reactive power exch ange in the cease
to energize state shall be less than 10% of nameplate DER rating and shall exclusively result from
passive devices. For Local EPS with aggregate DER rating 500 kVA and greater, the reactive power
exchange in the cease to energize state shall be less than 3% of nameplate DER rating and shall
If requested by the Area EPS operator, the DER operator shall provide the reactive susceptance that
Import of active power and reactive power exchange in the cease to energize state is permitted only
Alternatively, the requirements for cease to energize may be met by disconnecting 41 the local EPS, or
the portion of the local EPS to which the DER is connected from the Area EPS. The DER may
continue to deliver power to the portion of the Local EPS that is disconnected from the Area EPS. 42
40 In c ases where the Area EPS is isolated, the passive reactive power devices of the DER will rapidly discharge by Area EPS loads
and transformer magnetization and cease to exchange reactive power with the isolated Area EPS .
42 This may allow DER units to continue to energize the isolated Local EPS and supply local loads when disconnected from the
Area EPS .
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
4.6 Control capability requirements
The DER shall be capable of responding to external inputs 43 as specified in this subclause.
The DER shall be capable of disabling the permit service setting and shall cease to energize the Area
The DER shall be capable of limiting active power as a percentage of the nameplate active power
rating. The DER shall limit its active power output to not greater than the active power limit set
point in no more than 30 s or in the time it takes for the primary energy source to reduce its active
power output to achieve the requirements of the active power limit set point, whichever is greater. 45
In cases where the DER is supplying loads in the Local EPS, the active power limit set point may be
implemented as a maximum active power export to the Area EPS. Under mutual agreement
between the Area EPS operator and the DER operator, the DER may be required to reduce active
Transition between modes shall commence in no more than 30 s after the mode setting change is
received at the local DER communication interface. Changes of control functional modes shall be
executed such that the DER output is transitioned smoothly over a time period between 5 s and 300
s.
43 The external input may come through a manual DER control panel or through the local DER communication interface spec ified in
Clause 10.
44 This func tion is not intended to necessarily meet all requirements for protection, such as direct transfer trip. The objective of this
45 Linear ramping and step-wise ramping with small step sizes may be desirable.
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
Ramping of DER output is not required for control parameter setting changes. For all control and
protective function parameter settings, the time following the input to the local DER communication
interface and preceding the point in time when the invoked action begins shall be no greater than 30
s.
a) The response to disabling permit service setting specified in 4.6.1 shall take precedence
b) DER tripping requirements specified in 6.2, 6.4.1, and 6.5.1 shall take precedence over any
1) Where the prescribed trip duration settings for the respective voltage or frequency
magnitude are set at least 160 ms or 1% of the prescribed tripping time, whichever is
greater, beyond the prescribed ride-through duration, the DER shall comply with the
2) In all other cases, the ride-through requirements shall apply until 160 ms or 1% of the
prescribed tripping time, whichever is greater, prior to the prescribed tripping time.
c) DER ride-through requirements specified in 6.4.2 and 6.5.2 shall take precedence over all
other requirements within Clause 5 and Clause 6, with the exception of tripping
that does not actually exist shall not justify non-compliance with ride-through
inhibit the islanding detection performance specified in 8.1 where a valid unintentional
46 Based on the actual settings of the control modes, a mode with lower priority may still take effect prior to a mode with higher
priority.
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
d) The voltage-active power mode requirements specified in 5.4.2 and frequency-droop
(frequency-power) response requirements specified in 6.5.2.7 shall take precedence over all
other requirements within Clause 5 and Clause 6, with the exception of tripping and ride-
through requirements listed in item b) and item c) above. If both voltage-active power and
frequency-droop modes are active, the lesser of the power value shall take precedence.
e) The response to active power limit signal specified in 4.6.2 shall take precedence over all
other requirements within Clause 5 and Clause 6, with the exception of tripping and ride-
through requirements listed in item b) and item c) above, and voltage-active power mode
f) The voltage regulation functions specified in 5.3 shall take precedence over any remaining
The DR shall not actively regulate the voltage at the PCC. The DR shall not cause the Area EPS
service voltage at other Local EPSs to go outside the requirements of ANSI C84.1-1995, Range A.
Each DR unit of 250 kVA or more or DR aggregate of 250 kVA or more at a single PCC shall have
provisions for monitoring its connection status, real power output, reactive power output, and
When required by the Area EPS operating practices, a readily accessible, lockable, visible-break
isolation device shall be located between the Area EPS and the DR unit DER. 47
47 The isolation device should be clearly marked to include signage per The National Electrical Code ® [B31], as applicable.
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
4.9 Inadvertent energization of the Area EPS
The DR DER shall not energize the Area EPS when the Area EPS is de-energized. Exceptions may be
given for intentional Area EPS islands per 8.2 at the discretion of the Area EPS operator.
4.10.1 Introduction
The enter service criteria for DER of Category I, Category II, and Category III are specified in Table
4. 48
The active power performance during entering service is specified in 4.10.3. The requirements of 4.10
When entering service, the DER shall not energize the Area EPS until the applicable voltage and
system frequency are within the ranges specified in Table 4 and the permit service setting is set to
‚Enabled‛. 49
Table 4—Enter service criteria for DER of Category I, Category II, and
Category III
(New)
aThis corresponds to the Range B of ANSI C84.1, Table 1, column for service‖voltage‖of‖120−600‖V.
49 The enter service criteria in Table 4 specify the conditions for which a DER is permitted to enter service; these criteria do not
mandate any DER to enter service or stay in operation for the specified voltage and frequency conditions.
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
4.10.3 Performance during entering service
b) DER shall be capable of delaying enter service by an intentional adjustable minimum delay
when the Area EPS steady-state voltage and frequency are within the ranges specified in
Table 4. The adjustable range of the minimum intentional delay shall be 0 s to 600 s with a
c) DER shall increase output of active power, 50 or exchange of active power for energy-
storage-DER, during enter service as specified. Active power shall increase linearly, or in a
stepwise linear ramp, with an average rate-of-change not exceeding the DER nameplate
active power rating divided by the enter service period. The duration of the enter service
period shall be adjustable over a range of 1 s to 1000 s with a default time of 300 s. 51 The
maximum active power increase of any single step during the enter service period shall be
less than or equal to 20% of the DER nameplate active power rating. Where a stepwise
ramp is used, the rate of change over the period between any two consecutive steps shall
not exceed the average rate-of-change over the full enter service period. This requirement is
a maximum ramp rate requirement and the DER may increase output slower than
specified.
Exception 1: For Local EPS that have an aggregate DER rating of less than 500 kVA, individual
DER units may increase output of active power with no limitation of the rate-of-change, following
an additional randomized time delay with a default maximum time random interval of 300 s, and
with an adjustable range for the maximum time random interval of 1 s to 1000 s.
50 For Restore Output of active power after Return to S ervice, direction of active power may be negative (charging) for Energy
S torage DER, e.g., return to frequency reduction via charging through droop or dispatch control, if operating for that purpose prior
to trip. This requirement does not exclude use of alternate means to meet this requirement.
51 Base values for quantities expressed in per unit and percent of are specified in 3.1.
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
Exception 2: Increase of output of active power by Local EPS having an aggregate DER rating of
equal to or greater than 500 kVA and increasing output with active power steps greater than 20%
of nameplate active power rating shall require approval of the Area EPS operator in coordination
4.10.4 Synchronization
The DR unit DER shall parallel with the Area EPS without causing a step changes in the RMS
voltage fluctuation at the PCC greater than ±5 exceeding 3% of nominal when the prevailing PCC is
at medium voltage level, or exceeding 5% of nominal when the Area EPS at the PCC, and meet the
DER that produce fundamental voltage before connecting to the Area EPS 52 shall not be
synchronized outside of the tolerances specified in Table 5. 53, 54 The synchronization limits stated
in Table 5 may be waived by the Area EPS operator if paralleling does not exceed the limitation of
(New)
52 Examples may include synchronous generators, self-excited (grid-forming) inverters, or self-excited induction generators.
53 These parameters are maximum synchronization tolerances and by no means require that DER equipment be designed to sustain
these toleranc es. If the equipment requires tighter tolerances and the synchronization is performed consistent with the equipment
requirements, then the synchronization will be compliant with this subclause.
54 For example, round rotor synchronous generators with ratings 10 MVA and larger and salient pole synchronous generators with
ratings 5 MVA and larger may use the synchronization criteria described in IEEE S td 67, which are tighter than the ones spec ified
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
(Deleted)
The interconnection system DER shall have the capability to withstand electromagnetic interference
(EMI) environments in accordance be compliant with IEEE Std C37.90.2-1995, IEC 61000-4-3, or other
applicable industry standards with a minimum electric field strength of 30 V/m. 55 The influence of
EMI, having an electric field less than or equal to the value specified in this subclause, shall not
result in a change in state or misoperation of the interconnection system DER that affects
The interconnection system shall have the capability to withstand voltage and current surges in
accordance with the interconnection system ratings and environments defined in IEEE Std C62.41.2-
2002 or , IEEE Std C37.90.1-2002, IEEE Std C62.45, or IEC 61000-4-5, as applicable.
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
4.11.3 Paralleling device
Where used for isolation of a DER unit that continues to produce voltage after isolation from the
interconnection system Area EPS, the DER paralleling-device shall be capable of withstanding 220%
of the interconnection system DER rated voltage across the paralleling device for an indefinite
duration. 56
Unless specified otherwise by the Area EPS operator, the grounding scheme of the DR DER
interconnection shall not cause overvoltages that exceed the rating of the equipment connected to
the Area EPS and shall not disrupt the coordination of be coordinated with the ground fault
DER systems designated by authority having jurisdiction as emergency, legally required, or critical
operations power systems providing backup power to hospitals, fire stations or other emergency
facilities as defined by applicable industry code, 58 shall be exempt from the following:
56 The paralleling device must be rated for 220% of nominal voltage to accommodate Area EPS and DER voltages that are out of
57 S ubc lause 7.4 limits overvoltages produced by DER, including overvoltages caused by ground faults.
58 In the United S tates, examples of applicable industry code are NFPA 110 [B32], NFPA 70 [B31], or the NES C [B1].
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
c) Interoperability, information exchange, information models, and protocols specified in
Clause 10
and may cease to energize the Area EPS or may separate from the Area EPS without limitations.
— For testing purposes only and tests are not performed more frequently than 30 times per
year; or
— During load transfer in a period of less than 300 s to or from the Area EPS,
Clause 10
and may cease to energize the Area EPS or may separate from the Area EPS without limitations.
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
5. Reactive power capability and voltage/power control requirements
5.1 Introduction
Different characteristics and capabilities for response to voltage variations within the normal
operating range are specified in certain parts of this subclause for normal operating performance
Category A and Category B DER. 59 Table 6 specifies the attributes of voltage and reactive power
control requirements specified in 5.3 and the voltage and active power control requirements
specified in 5.4 to performance Category A and Category B DER. Under mutual agreement between
Area EPS operator and DER operator, requirements other than those specified below are also
permitted.
The Area EPS operator shall specify the DER performance category that is required. Guidance
The requirements of this subclause apply to the continuous operation region when the voltage is
between 0.88 and 1.1 times the nominal voltage (VN). Continued operation of functions defined in
Clause 5 outside of the continuous operation region may be acceptable to support functions covered in
6.4. During abnormal voltage conditions, this reactive power range shall be provided subject to the
limitations of the DER. The DER shall return to its pre-disturbance operating mode after the system
The DER shall not cause the Area EPS primary circuit voltage at any location to go outside the
In addition, the DER shall not cause the Area EPS service voltage at any Local EPS to be outside of
dedicated service transformer or dedicated feeder/circuit as determined by the Area EPS operator.
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
Table 6—Voltage and reactive/active power control function
requirements for DER normal operating performance categories
(New)
aVoltage-reactive‖ power‖mode‖may‖also‖be‖commonly‖referred‖to‖as‖‚volt-var‛‖mode.
The DER shall be capable of injecting reactive power (over-excited) and absorbing reactive power
(under-excited) for active power output levels greater than or equal to the minimum steady-state
active power capability (P min ), or 5% of rated active power, P rated (kW) of the DER, whichever is
greater.
When operating at active power output greater than 5% and less than 20% of rated active power, the
DER shall be capable of exchanging reactive power up to the minimum reactive power value given
in Table 7 multiplied by the active power output divided by 20% of rated active power.
Operation at any active power output above 20% of rated active power shall not constrain the
required by the active control function at the time, as defined in 5.3. Curtailment of active power to
meet apparent power constraints is permissible. These reactive power requirements are illustrated in
60 This‖is‖c ommonly‖known‖as‖‚reactive‖power‖priority‛‖mode.
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
Table 7—Minimum reactive power injection and absorption capability
(New)
The DER may produce active power up to the kVA rating provided that the DER remains capable at
all times to absorb or inject reactive power, to the full extent of the reactive power capability ranges
defined above, as demanded by the reactive power control mode and corresponding settings
5.3.1 General
The DER shall provide voltage regulation capability by changes of reactive power. The approval of
the Area EPS operator shall be required for the DER to actively participate in voltage regulation.
The voltage and reactive power control functions do not create a requirement for the DER to operate
The DER shall, as specified in Table 6, provide the capabilities of the following mutually exclusive
61 The DER Prated may be less than or equal to Srated. The DER may need to reduce active power in order to meet the demanded
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
― Constant reactive power mode
The DER shall be capable of activating each of these modes one at a time.
Constant power factor mode with unity power factor setting62 shall be the default mode of the
The DER operator shall be responsible for implementing setting modifications and mode selections,
as specified by the Area EPS operator within a time acceptable to the Area EPS operator. Under
mutual agreement between the Area EPS operator and DER operator, reactive power control modes
and implementations other than the ones listed above and described below shall be permitted.
Emergency or standby DERs63 as specified in 4.13 shall only be required to operate in constant
When in this mode, the DER shall operate at a constant power factor. The target power factor shall
be specified by the Area EPS operator and shall not require reactive power exceeding the reactive
capability requirements specified in 5.2. The power factor settings are allowed to be adjusted locally
and/or remotely as specified by the Area EPS operator. The maximum DER response time to
62 DER may operate at any power factor, e.g., for the purpose of compensating for the reactive power demand of the Local EPS , as
long as the power factor requirements specified by the Area EPS are met at the RPA.
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
5.3.3 Voltage-reactive power mode 64
When in this mode, the DER shall actively control its reactive power output as a function of voltage
power characteristic is shown in Figure H.4. The voltage-reactive power characteristic shall be
configured in accordance with the default parameter values specified in Table 8 if not specified by
the Area EPS operator. If specified by the Area EPS operator, the voltage-reactive power
characteristic shall be configured using values in the optional adjustable range. The voltage-reactive
power characteristics shall be adjustable locally and/or remotely as specified by the Area EPS
operator.
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
Table 8—Voltage-reactive power settings for normal operating
performance Category A and Category B DER
(New)
bIf needed DER may reduce active power output to meet this requirement.
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
The DER shall be capable of autonomously adjusting reference voltage (VRef) with VRef being equal
to the low pass filtered measured voltage. The time constant shall be adjustable at least over the
range of 300 s to 5000 s. The voltage-reactive power Volt-Var curve characteristic shall be adjusted
autonomously as VRef changes. The approval of the Area EPS operator shall be required for the DER
to autonomously adjust the reference voltage. Implementation of the autonomous VRef adjustability
and the associated time constant shall be specified by the Area EPS operator.
When in this mode, the DER shall actively control the reactive power output as a function of the
active power output following a target piecewise linear active power-reactive power characteristic,
without intentional time delay. In no case, shall the response time be greater than 10 s. Example
active power-reactive power characteristic is shown in Figure H.5. The target characteristic shall be
configured in accordance with the default parameter values shown in Table 9. The characteristics
shall be allowed to be configured as specified by the Area EPS operator using the values specified in
The left-hand side of Figure H.5 and corresponding requirements specified in Table 9 shall only
The active power-reactive power characteristics are allowed to be adjusted locally and/or remotely
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
Table 9—Active power-reactive power settings for normal operating
performance Category A and Category B DER
(New)
When in this mode, the DER shall maintain a constant reactive power. The target reactive power
level and mode (injection or absorption) shall be specified by the Area EPS operator and shall be
within the range specified in 5.2. The reactive power settings are allowed to be adjusted locally
and/or remotely as specified by the Area EPS operator. The maximum DER response time to
5.4.1 General
Category B DER shall, as specified in Table 6, provide a voltage regulation capability by changes of
active power. Enabling/disabling this function is at the discretion of the Area EPS operator. The
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
5.4.2 Voltage-active power mode
When in this mode, the DER shall actively limit the DER maximum active power as a function of the
voltage following a voltage-active power piecewise linear characteristic. Two examples of these
characteristics are shown in Figure H.6. The characteristic shall be configured in accordance with the
default parameter values specified in Table 10 for the given DER normal operating performance
category. The characteristic may be configured as specified by the Area EPS operator using the values
If enabled, the voltage-active power mode shall remain active while any of the voltage-reactive
power modes described in 5.3 are enabled. For DER that do not absorb active power, P 2, which is
the minimum set point for active power generation due to overvoltage, is subject to the equipment
capability. If P 2 is outside the continuous operation region of the DER, the active power generation is
allowed to be reduced to the minimum DER capability instead of P 2 or DER shutting down.
DER that can inject and absorb active power, P'2, which is the maximum set point for active power
absorption change due to system overvoltage, is subject to the equipment capability. If P'2 is outside
the continuous operation region of the DER, the active power absorption is allowed to be reduced to
The voltage-active power characteristics curves are allowed to be adjusted locally and/or remotely as
65 As permitted by 4.6.2, for cases where the DER is supplying loads in the Local EPS, the DER active power may be implemented
as a maximum active power export limit set point. The DER shall not be required to reduce active power below the level needed to
support loc al loads.
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
Table 10 —Voltage-active power settings for Category A and Category B
DER
(New)
aP min is the minimum active power output in p.u. of the DER rating (i.e., 1.0 p.u.).
bP'rated is the maximum amount of active power that can be absorbed by the DER. ESS operating in
the negative real power half plane, through charging, shall follow this curve as long as available
cAny settings for the open loop response time of less than 3 s shall be approved by the Area EPS
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
6. Response to Area EPS abnormal conditions10
6.1 Introduction
Abnormal conditions can arise on the Area EPS that require a response from the connected DR to
which the DER shall appropriately respond. This response contributes to the stability of the Area
EPS, safety of utility maintenance personnel and the general public, as well as the avoidance of
damage to connected equipment, including the DR DER. DER response should consider the
performance requirements of the Area EPS and the bulk power system (BPS) to which the Area EPS is
connected. 66 All voltage and frequency parameters performance requirements specified in these
subclauses shall be met at the PCC, reference point of applicability specified in 4.2 and shall refer to the
Different characteristics and capabilities for response to abnormal Area EPS conditions are specified
in certain parts of this subclause for abnormal operating performance Category I, Category II, and
66 Distributed Energy Resources—Connection, Modeling, and Reliability Considerations, North American Electric Reliability
67 S ubc lause 4.3 states: For low-voltage ride-through and undervoltage trip, the relevant voltage at any given time shall be the least
magnitude of the individual applicable voltages relative to the corresponding nominal voltage. For high-voltage ride-through and
overvoltage trip, the relevant voltage at any given time shall be the greatest magnitude of the applicable voltages relative to the
10 The isolation of a portion of the Area EPS , presenting the potential for an unintended DR island, is a special concern and is
addressed in 4.4.1.
S etting adjustments may only be made as approved by the authority who has jurisdiction over the DR interconnection.
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
The Area EPS operator, as guided by the AGIR who determined applicability of the performance
categories as outlined in 4.3, 68 shall specify which of abnormal operating performance Category I,
Category II, or Category III performance is required. 69 Guidance regarding the assignment of
With regard to ride-through as specified in 6.4.2 and 6.5.2 and methods utilized to meet the
― While the DER is connected to an Area EPS that is connected to a bulk power system, any
requirements for ride-through as specified in 6.4.2 and 6.5.2 shall not be falsely inhibited
by any methods or design features utilized to meet the unin tentional islanding detection as
specified in 8.1 when an actual unintentional island condition does not exist.
― Conversely, the unintentional islanding detection requirements specified in 8.1 shall not be
islanding conditions. 70
― While the DER is connected to an Area EPS that is not connected to a bulk power system (i.e.,
an intentional Area EPS island), requirements for ride-through as specified in 6.4.2 and 6.5.2
68 Refer to Annex B for further guidelines for DER performance category assignment.
69 This may be subject to regulatory requirements that are outside the scope of this standard and may consider DER type,
applic ation purpose, future regional DER penetration, and the Area EPS characteristics.
71 S ubc lause 8.2 specifies requirements and criteria for intentional Area EPS islands and DER operating within an intentional Area EPS
isla nd.
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
All requirements related to the delivery of active power shall be subject to the availability of the
DER’s‖ primary‖ source‖ of‖ energy‖ (available active power). 72 Abnormal voltage and frequency
otherwise, this shall be deemed a failure to comply with ride-through of abnormal voltage and
All DER shall be field adjustable for the adjustable parameters specified in this clause. 74 The
adjustability may be required via communication, if specified by the Area EPS operator as defined
The actual applied trip settings shall be specified by the Area EPS operator. If the Area EPS operator
does not specify any settings, the default settings shall be used.
The DR unit shall cease to energize the Area EPS For short-circuit faults on the Area EPS circuit
section to which it the DER is connected, the DER shall cease to energize and trip unless specified
otherwise by the Area EPS operator. 75 This requirement shall not be applicable to faults that cannot
72 Decrease of solar irradiance in the case of a photovoltaic DER, or decrease of wind speed for a wind turbine generator, occ urring
during a voltage disturbance, are examples where DER power output decrease is compliant with this requirement.
73 Examples of non-compliant decrease of active power availability are loss of control power to the power conversion devic e or
75 The Area EPS Operator may elect to use sequential tripping for the smaller DER with relatively low impact and allow the DER to
cea se to energize after the protective device on the Area EPS opened.
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
NOTE 1—DER can desensitize detection of faults that can be detected by the Area EPS protection
systems prior to the interconnection of the DER. Adjustments to the settings of the Area EPS
protection systems or changes to the DER interconnection parameters, which can compensate for
DER’s‖ fault‖ current‖ contribution,‖ may‖ be‖ needed‖ to maintain proper fault detection time and
NOTE 2—The presence of a ground source within the Local EPS can pose a back-feed risk to the
The DER shall detect and cease to energize and trip all phases to which the DER is connected for any
open phase condition occurring directly at the reference point of applicability per 4.2 and the
applicable voltages per 4.3. The DER shall cease to energize and trip within 2.0 s of the open phase
condition.
Appropriate means shall be implemented to help ensure that Area EPS automatic reclosing onto a
circuit remaining energized by the DER does not expose the Area EPS to unacceptable stresses or
disturbances due to differences in instantaneous voltage, phase angle, or frequency between the
Operation in momentary cessation operating mode meets this cease to energize requirement. Restore
76 Appropriate means may include, for example, Area EPS measures to block reclosing if the circuit remains energized, or existence
of low DER penetration and DER technology -types such that energization would not be maintained for as long as the time of
rec losing, or means to cease energization by DER when the Area EPS is isolated (e.g., transfer trip, or reliance on islanding detec tion
requirements as specified in 8.1).
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
In addition to these requirements, the requirements from 4.10 shall be considered. Voltage ride-
The DR shall cease to energize the Area EPS circuit to which it is connected prior to reclosure by the
Area EPS.
6.4 Voltage
When any applicable voltage is less than an undervoltage threshold, or greater than an overvoltage
threshold, as defined in this subclause, the DER shall cease to energize the Area EPS and trip within
the respective clearing time as indicated. 77 Under and overvoltage tripping thresholds and clearing
times shall be adjustable over the ranges of allowable settings specified in Table 11 for abnormal
operating performance Category I, Table 12 for Category II, or Table 13 for Category III. Unless
specified otherwise by the Area EPS operator, default settings shall be used.
The voltage and time set points shall be field adjustable and may be remotely adjustable per the
The ranges of allowable settings do not mandate a requirement for the DER to ride through this
magnitude and duration of abnormal voltage condition. The Area EPS operator may specify the
voltage thresholds and maximum clearing times within the ranges of allowable settings; settings outside
of these ranges shall only be allowed as necessary for DER equipment protection and shall not
conflict with the voltage disturbance ride through requirements specified in 6.4.2.
77 When clea ring times are less than 0.16 seconds greater than the specified clearing time, the provisions of 4.7 item b)1) are
applic able.
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
Two overvoltage trip functions, OV1 and OV2, and two undervoltage trip functions, UV1 and UV2
apply simultaneously to DER of Category I, Category II, and Category III. For the overvoltage (OV)
and undervoltage (UV) trip functions clearing time ranges and for the OV trip functions voltage
ranges, the lower value is a limiting requirement (the setting shall not be set to lower values) and the
upper value is a minimum requirement (the setting may be set above this value). For the UV trip
functions voltage ranges, the upper value is a limiting requirement (the setting shall not be set to
greater values) and the lower value is a minimum requirement (the setting may be set to lower
values). 78 Area EPS operators may specify values within the specified range subject to the
limitations on voltage trip settings specified by the regional reliability coordinator. 79, 80
78 The following are recommendations for hardware design of equipment used to implement the trip functions by use of fixed
func tions voltage ranges, the lower value should be a limiting design requirement (the range of adjustability should not extend to
lower values) and the upper value should be a minimum design requirement (the range of adjustability may be extended above this
value). For the UV trip functions voltage ranges, the upper value should be a limiting design requirement (the range of adjus tability
should not extend to greater values) and the lower value should be a minimum design requirement (the range of adjustability may
be extended to lower values).
79 In North America, the limitations for transmission-connected resources as specified in NERC PRC-024-2 [B27] may be used for
referenc e.
80 The lower and upper values of the ranges of allowable settings for voltage and frequency trip settings specified in this standard for
DER are not intended to limit the capabilities and settings of other equipment on the Area EPS . It is recommended that settings
applied on Area EPS equipment conform to the voltage and frequency ride -through objectives of this standard whenever the Area
EPS is in normal configuration. However, it is recognized that in certain cases Area EPS operators may need to occasionally and
selec tively use trip settings outside the ranges of allowable settings to accommodate worker safety practices or to safeguard
distribution infrastructure while in an abnormal configuration, e.g., during automatic reconfiguration of a circuit sec tion or
temporary loss of direct transfer trip of mid- and large-scale DER. Area EPS operators should limit trip settings on Area EPS
equipment that conflict with this standard to only affect those selective DER and A rea EPS equipment and only for a limited period
nec essary to meet these worker safety and equipment protection goals. Area EPS operators should coordinate these practic es with
the regiona l reliability coordinator who may consider bulk power system impacts of affected aggregate DER capacity.
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
Table 11 —DER response (shall trip) to abnormal voltages for DER of
abnormal operating performance Category I (see Figure H.7)
(New)
aThe Area EPS operator may specify other voltage and clearing time trip settings within the range of
bNominal system voltages stated in ANSI C84.1, Table 1 or as otherwise defined by the Area EPS
operator. The ranges of allowable settings do not mandate a requirement for the DER to ride through
this magnitude and duration of abnormal voltage condition. The Area EPS operator may specify the
voltage thresholds and maximum clearing times within the ranges of allowable settings; settings outside
of these ranges shall only be allowed as necessary for DER equipment protection and shall not
conflict with the voltage disturbance ride through requirements specified in 6.4.2. For the
overvoltage (OV) and undervoltage (UV) trip functions clearing time ranges and for the OV trip
functions voltage ranges, the lower value is a limiting requirement (the setting shall not be set to
lower values) and the upper value is a minimum requirement (the setting may be set above this
value). For the UV trip functions voltage ranges, the upper value is a limiting requirement (the
setting shall not be set to greater values) and the lower value is a minimum requirement (the setting
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
Table 12 —DER response (shall trip) to abnormal voltages for DER of
abnormal operating performance Category II (see Figure H.8)
(New)
aThe Area EPS operator may specify other voltage and clearing time trip settings within the range of
bNominal system voltages stated in ANSI C84.1, Table 1 or as otherwise defined by the Area EPS
operator. The ranges of allowable settings do not mandate a requirement for the DER to ride through
this magnitude and duration of abnormal voltage condition. The Area EPS operator may specify the
voltage thresholds and maximum clearing times within the ranges of allowable settings; settings outside
of these ranges shall only be allowed as necessary for DER equipment protection and shall not
conflict with the voltage disturbance ride through requirements specified in 6.4.2. For the
overvoltage (OV) and undervoltage (UV) trip functions clearing time ranges and for the OV trip
functions voltage ranges, the lower value is a limiting requirement (the setting shall not be set to
lower values) and the upper value is a minimum requirement (the setting may be set above this
value). For the UV trip functions voltage ranges, the upper value is a limiting requirement (the
setting shall not be set to greater values) and the lower value is a minimum requirement (t he setting
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
Table 13 —DER response (shall trip) to abnormal voltages for DER of
abnormal operating performance Category III (see Figure H.9)
(New)
aThe Area EPS operator may specify other voltage and clearing time trip settings within the range of
bNominal system voltages stated in ANSI C84.1, Table 1 or as otherwise defined by the Area EPS
operator. The ranges of allowable settings do not mandate a requirement for the DER to ride through
this magnitude and duration of abnormal voltage condition. The Area EPS operator may specify the
voltage thresholds and maximum clearing times within the ranges of allowable settings; settings outside
of these ranges shall only be allowed as necessary for DER equipment protection and shall not
conflict with the voltage disturbance ride-through requirements specified in 6.4.2. For the
overvoltage (OV) and undervoltage (UV) trip functions clearing time ranges and for the OV trip
functions voltage ranges, the lower value is a limiting requirement (the setting shall not be set to
lower values) and the upper value is a minimum requirement (the setting may be set above this
value). For the UV trip functions voltage ranges, the upper value is a limiting requirement (the
setting shall not be set to greater values) and the lower value is a minimum requirement (the setting
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
6.4.2 Voltage disturbance ride-through requirements
The performance required of DER during voltage disturbances is specified in this clause. DER shall
meet either the abnormal operating performance Category I, Category II, or Category III requirements
of this clause, as specified by the Area EPS operator. The voltage disturbance ride-through
requirements specified in this clause do not apply when frequency is outside of the ride-through
DER shall be designed to provide the voltage disturbance ride-through capability specified in this
clause without exceeding DER capabilities. Any tripping of the DER, or other failure to provide the
specified ride-through capability, due to DER self-protection as a direct or indirect result of a voltage
disturbance within a ride-through region, shall constitute non-compliance with this standard.
The DER shall specify its abnormal operating performance category within the nameplate information.
The voltage disturbance ride-through specified in the remainder of 6.4.2 shall not apply and DER
may cease to energize the Area EPS and trip without limitations if any of the following applies:
a) The net active power exported across the point of common coupling into the Area EPS is
continuously maintained at a value less than 10% of the aggregate rating of DER connected
to the Local EPS prior to any voltage disturbance, and the Local EPS disconnects from the
Area EPS, along with Local EPS load to intentionally form a Local EPS island, or
b) An active power demand of the Local EPS load equal or greater than 90% of the pre-
disturbance aggregate DER active power output is shed within 0.1 s of when the DER
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
For voltage disturbances where the applicable voltage is outside the ride-through operating region
parameters (voltage range and corresponding cumulative duration, minimum time) specified in
Table 14 for abnormal operating performance Category I, Table 15 for Category II, or Table 16 for
Category III, requirements for continued operation (ride-through), or restore output subsequent to the
(New)
aCessation of current exchange of DER with Area EPS in not more than the maximum specified time
and with no intentional delay. This does not necessarily imply disconnection, isolation, or a trip of
81 Overvoltage and undervoltage events usually occur independently from each other, but may also be initiated by the same event
(e.g., after c learing a fault, there may be an overvoltage event due to electromagnetic transients or system dynamic response). Thus,
the high-voltage ride-through and the low-voltage ride-through requirements are based on cumulative durations and have to be
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
Table 15 —Voltage ride-through requirements for DER of abnormal
operating performance Category II (see Figure H.8)
(New)
aCessation of current exchange of DER with Area EPS in not more than the maximum specified time
and with no intentional delay. This does not necessarily imply disconnection, isolation, or a trip of
(New)
aCessation of current exchange of DER with Area EPS in not more than the maximum specified time
and with no intentional delay. This does not necessarily imply disconnection, isolation, or a trip of
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
bTemporarily cease to energize an EPS, while connected to the Area EPS, in response to a
disturbance of the applicable voltages or the system frequency, with the capability of immediate
restore output of operation when the applicable voltages and the system frequency return to within
defined ranges.
cThe voltage threshold between mandatory operation and momentary operation may be changed by
mutual agreement between the Area EPS operator and DER operator, for example to allow the DER
Voltage disturbances of any duration, for which the applicable voltage as specified in 4.3 remains
within Range B as defined by ANSI C84.1, shall not cause the DER to cease to energize and trip from
the Area EPS. The DER shall remain in operation during any such disturbance, and shall continue to
deliver available active power of magnitude at least as great as its pre-disturbance level of active
power, prorated by the per-unit voltage level of the least phase voltage if that voltage is less than the
nominal voltage. 82 Temporary deviations of active power having durations not exceeding 0.5 s shall
be allowed.
Exception: Three-phase DER may cease to energize and trip if the negative sequence component of the
applicable voltage is greater than 5% of the nominal voltage for greater than 60 s or greater than 3% of the
nominal voltage for greater than 300 s, provided that the voltage imbalance is neither caused nor aggravated
82 Changes of active power are permitted in response to control commands in accordance with 4.6 or in response to o ther c ontrol
settings.
83 It should be noted that the equipment design requirements for continuous and short-time negative sequence current capabilities
spec ified in IEEE S td C50.12 and IEEE S td C50.13 may not be sufficient for round rotor synchronous gene rators with ratings 10
MVA and larger or salient pole synchronous generators with ratings 5 MVA and larger to operate reliably in unbalanced applica ble
volta ge c onditions that may regularly occur in Area EPS governed by this standard. Note in 1.4 that this standard as a whole is not
intended for, and is in part inappropriate for, application to energy resources connected to transmission or networked sub -
transmission systems and that for DER interconnections that include individual synchronous generator units rated 10 MVA and
greater, and where the requirements of this standard conflict with the requirements of IEEE S td C50.12 or IEEE S td C50.13, the
requirements of IEEE S td C50.12 or IEEE S td C50.13, as relevant to the type of synchronous generator used, shall prevail.
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
6.4.2.3 Low-voltage ride-through
6.4.2.3.1 General
For low-voltage ride-through, the relevant voltage at any given time shall be the least magnitude of
During temporary voltage disturbances, for which the applicable voltage on the phase that has the
least voltage magnitude is less than the minimum of the continuous operation region, and within the
corresponding voltage ranges and cumulative duration (minimum time) specified in Table 14 for
Category I, Table 15 for Category II, and Table 16 for Category III, the DER shall be capable to ride-
through and
During low-voltage ride-through, the DER shall operate in the following operating modes as
specified in Table 14 for Category I, Table 15 for Category II, and Table 16 for Category III with the
following requirements:
84 For all DER: maintain functioning of auxiliary equipment. For synchronous generation-based DER: maintain transient stability.
For inverter-based‖ DER:‖ maintain‖ ‚Current‖ Angle‖ S tability.‛‖ ‚Current‖ Angle‖ S tability‛‖ is‖ the‖ ability‖ of‖ a‖ DER,‖ which‖ is‖ grid-
interfac ed via a voltage source converter (VS C) and operated in parallel to the grid to inject current (magnitude, angle) for
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
During temporary voltage disturbances, for which the applicable voltage on the phase that has the
least voltage magnitude is within the mandatory operation region, the DER
DER of Category II and Category III shall, by default, not reduce its total apparent current during
the disturbance period in mandatory operation mode below 80% of the pre-disturbance value or of the
corresponding active current level subject to the available active power, whichever is less, subject to
the following:
― Active and reactive current oscillations that are positively damped are permitted during
― Transient apparent current magnitude changes having duration less than 30 ms, and
dynamic current magnitude oscillations for which the mean value is greater than o r equal
By mutual agreement between the Area EPS operator and DER operator, other current
During temporary voltage disturbances, for which the applicable voltage on the phase that has the
least voltage magnitude is within the permissive operation region, the DER
― Shall maintain synchronism with the Area EPS or shall not trip.
― May continue to exchange current with the Area EPS or may cease to energize.
85 For example, dynamic voltage support as specified in 6.4.2.6 may be used within the mandatory operating region.
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
For Category III DER, during temporary voltage disturbances, for which the applicable voltage on the
phase that has the least voltage magnitude is within the momentary cessation operation region, the DER
6.4.2.4.1 General
For high-voltage ride-through, the relevant voltage at any given time shall be the greatest magnitude
During temporary voltage disturbances, for which the applicable voltage on the phase having the
greatest voltage magnitude is greater than the maximum of the continuous operation region, and
within the corresponding voltage ranges and cumulative duration (minimum time) specified in
Table 14 for abnormal operating performance Category I, Table 15 for Category II, or Table 16 for
86 For sync hronous generation-based DER, maintain transient stability. For inverter-based DER, maintain control stability or
‚c urrent‖angle‖stability.‛‖For‖all‖DER,‖maintain‖functioning‖of‖auxiliary‖equipment.
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
6.4.2.4.3 High-voltage ride-through performance
During high-voltage ride-through, the DER shall operate in the following operating modes as
specified in Table 14 for abnormal operating performance Category I, Table 15 for Category II, and
During temporary voltage disturbances, for which the applicable voltage on the phase having the
greatest voltage magnitude is within the permissive operating region, the DER
― Shall maintain synchronism with the Area EPS or shall not trip.
― May continue to exchange current with the Area EPS or may cease to energize.
For Category III DER, during temporary voltage disturbances, for which the applicable voltage on the
phase having the greatest voltage magnitude is within the momentary cessation operation region, the
DER
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
6.4.2.5 Ride-through of consecutive voltage disturbances 87
The requirements for continued operation (ride-through), or restore output shall apply to multiple
consecutive voltage disturbances within a ride-through operating region, for which the voltage range
and corresponding cumulative durations are specified in Table 14 for abnormal operating performance
Category I, Table 15 for Category II, and Table 16 for Category III. These requirements are subject to
the following provisions that specify conditions in Table 17 for which a DER may trip: 88
a) For a set of consecutive disturbances in which voltages fall within a ride-through operating
region multiple times, each interspersed by a period of voltage within the continuous
operation region that has a duration no greater than specified in Table 17 Column 3 for the
respective performance category, the cumulative duration of voltage within the respective
ride-through operating region for all such disturbances shall be compared with the maximum
required duration for the respective voltage disturbance severity. If this cumulative
b) If voltages remain entirely within the continuous operation region for a time period greater
than specified in Table 17, Column 3 for the respective performance category, any further
87 The primary intent of voltage ride-through requirements for consecutive voltage disturbances is for DER to ride through a
reasonable tripping and reclosing sequence associated with a short-circuit fault on a different portion of the Area EPS than that to
whic h it is c onnected, but which causes these voltage disturbances at the DER. Other causes for consecutive disturbanc es are
separate faults that might occur in a severe storm, or dynamic voltage swings that cyclically transition in and out of the continuous
88 None of these provisions specifies that a DER shall trip for consecutive voltage disturbances. These provisions only spec ify
c onditions for which a DER may trip and is relieved of the mandatory requirement to ride through voltage disturbances. The ride-
through of a DER for more than the specified number of disturbance sets (Column 2), for disturbance sets that are separate d by less
than the spec ified minimum time (Column 3), and disturbance sets occurring more frequently than the specified time window for
new c ount (Column 4) does not pose a risk to the Area EPS , and DER should ride through as many disturbance sets as they are
c apable.
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
c) The DER shall not be required to ride through any more ride-through disturbance sets
than the maximum number given in Table 17, Column 2 within the time period specified
in Table 17, Column 4. Once a period-of-time as given in Table 17, Column 4 has passed
since the last disturbance, the DER shall be required to ride through any new sets of
Exception: DER shall be allowed to trip if the timing of multiple consecutive voltage disturbances during a
specific event stimulate electromechanical oscillations to the degree where DER synchronism is lost or
(New)
89 It should be noted that IEEE S td C50.13 provides assessment criteria for a site -specific study of torsional stress for synchronous
generators with ratings 10 MVA and larger. Per 1.4, this standard as a whole is not intended for, and is in part inappropriate for,
applic ation to energy resources connected to transmission or networked sub-transmission systems and for DER interconnec tions
that inc lude individual synchronous generator units rated 10 MVA and greater, and where the requirements of this standard
c onflic t with the requirements of IEEE S td C50.12 or IEEE Std C50.13, the requirements of IEEE S td C50.12 or IEEE S td C50.13, as
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
6.4.2.6 Dynamic voltage support
Dynamic voltage support 90 from DER can support the applicable voltage by supplying the Area EPS
Alternate means of DER control and designs can exist to provide dynamic voltage support. Support
of the applicable voltage can provide benefits to the Area EPS and BPS.
Any DER may have the capability of dynamic voltage support during low-voltage ride-through and
high-voltage ride-through.
The dynamic voltage support capability may be utilized during mandatory operation or permissive
operation under a mutual agreement with the Area EPS operator 92 considering both the capability
and the DER-specific implementation of the dynamic voltage support function. The DER shall
maintain synchronism with the Area EPS and may provide dynamic voltage support to the Area EPS
during and following temporary voltage disturbances, for which the applicable voltage on any phase
is as follows:
a) Less than the minimum of the continuous operation region and within either the mandatory
90 Dyna mic voltage support provides rapid reactive power exchanges during voltage excursions. Dynamic voltage support may provide
better voltage stability in the distribution system during transient events extending into voltage ride -through or high-voltage ride-
through regions. Valuable information on the preferable characteristics of current injected to the Area EPS as dynamic voltag e
91 The relative effectiveness active and reactive current of the dynamic voltage support can depend on the X/R ratio of the Area
EPS .
92 The Area EPS operator may consider the impact of a dynamic voltage support from DER on the Area EPS protection.
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
b) Greater than the maximum of the continuous operation region and within the permissive
operation region.
The dynamic voltage support shall not cause the DER to cease to energize in situations where the DER
If the DER rides through a voltage disturbance without trip and the DER does not provide dynamic
voltage support (see 6.4.2.6) while in a mandatory operation or permissive operation region, once the
applicable voltage surpasses the lower value of the mandatory operation region during low-voltage ride-
through or the applicable voltage returns below the upper value of the continuous operation region
― Shall restore output of active current to at least 80% of pre-disturbance active current level
within 0.4 s. Active and reactive current oscillations in the post-disturbance period that are
If the DER rides through a voltage disturbance without trip and the DER provides dynamic voltage
support while in a mandatory operation or permissive operation region, once the applicable voltage enters
93 The implementation (design, testing and conformance, communications, etc.) of the dynamic voltage support is recommended to
have adequate capability to prevent the creation of overvoltage in any phases of the applicable voltages when providing dyna mic
volta ge support for any types of faults (balanced and unbalanced), for which the overvoltage would not occur without the DER.
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
― Shall continue to provide dynamic voltage support up to 5 s after the applicable voltage
surpasses the lower value of the continuous operation region and restore output of active
current to at least 80% of pre-disturbance active current level or to the available active
― Shall discontinue providing dynamic voltage support 5 s after the applicable voltage surpasses
the lower value of the continuous operation region and resume reactive power
functionality for normal conditions as defined in 4.2 for the mode that has been selected.
If the RPA of a Category III DER is the PCC, the requirement for transitioning between momentary
cessation and mandatory operation or momentary cessation and continuous operation, may optionally be
based on the voltage measured at the PoC. When this optionality is excercised, the momentary
cessation threshold shall be adjusted94 for the predicted voltage difference between the PCC and
PoC, such that the performance of the DER approximates the defined performance based on PCC
voltage. This option does not apply to Category I and Category II DER. 95
94 The c apability to adjust the momentary cessation threshold may be mutually agreed upon between the Area EPS Operator in
c oordination with the regional reliability coordinator and the DER Operator and may otherwise be exempt from the interoperability
management information requirements in 10.6.
95 Bec ause Category I and Category II have permissive operating regions at voltages somewhat less than the lower limit of the
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
The protection functions of the interconnection system shall detect the effective (rms) or
fundamental frequency value of each phase-to-phase voltage, except where the transformer
connecting the Local EPS to the Area EPS is a grounded wye-wye configuration, or single-phase
installation, the phase-to-neutral voltage shall be detected. When any voltage is in a range given in
Table 1, the DR shall cease to energize the Area EPS within the clearing time as indicated. Clearing
time is the time between the start of the abnormal condition and the DR ceasing to energize the Area
EPS. For DR less than or equal to 30 kW in peak capacity, the voltage set points and clearing times
shall be either fixed or field adjustable. For DR greater than 30 kW, the voltage set points shall be
field adjustable.
The voltages shall be detected at either the PCC or the point of DR connection when any of the
a) The aggregate capacity of DR systems connected to a single PCC is less than or equal to 30
kW,
b) The interconnection equipment is certified to pass a non -islanding test for the system to
which it is to be connected,
c) The aggregate DR capacity is less than 50% of the total Local EPS minimum annual
integrated electrical demand for a 15 minute time period, and export of real or reactive
(Deleted)
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
aBase voltages are the nominal system voltages stated in ANSI C84.1-1995, Table 1.
bDR‖≤‖30‖kW,‖maximum‖clearing‖times;‖DR‖>‖30kW,‖default‖clearing‖times.
6.5 Frequency
When the system frequency is in a range given in Table 18, and the fundamental-frequency
component of voltage on any phase is greater than 30% of nominal, the DER shall cease to energize the
Area EPS and trip within a clearing time as indicated. 96 Under and overfrequency tripping
thresholds and clearing times shall be adjustable over the ranges of allowable settings specified in Table
18. The underfrequency and overfrequency trip settings shall be specified by the Area EPS operator
in coordination with the requirements of the regional reliability coordinator. If the Area EPS operator
does not specify any settings, the default settings shall be used.
The frequency and time set points shall be field adjustable and may be remotely adjustable per the
The ranges of allowable settings do not mandate a requirement for the DER to ride through this
magnitude and duration of abnormal frequency condition. The Area EPS operator may specify the
frequency thresholds and maximum clearing times within the ranges of allowable settings; settings
outside of these ranges shall only be allowed as necessary for DER equipment protection and shall
not conflict with the frequency disturbance ride-through requirements specified in 6.5.2.
96 When clea ring times are less than 0.16 seconds greater than the specified clearing time, the provisions of 4.7 b)1) are applic able.
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
Two overfrequency trip functions, OF1 and OF2, and two underfrequency trip functions, UF1 and
UF2 apply simultaneously. For the overfrequency (OF) and underfrequency (UF) trip functions
clearing time ranges and for the OF trip functions frequency ranges, the lower value is a limiting
requirement (the setting shall not be set to lower values) and the upper value is a minimum
requirement (the setting may be set above this value). For the UF trip functions frequency ranges,
the upper value is a limiting requirement (the setting shall not be set to greater values) and the lower
value is a minimum requirement (the setting may be set to lower values). 97 Area EPS operators may
specify values within the specified range subject to the limitations on frequency trip settings
97 The following are recommendations for hardware design of equipment used to implement the trip functions by use of fixed
‘ranges‖of adjustability’: For the overfrequency (OF) and underfrequency (UF) trip functions clearing time ranges and for the OF trip
func tions frequency ranges, the lower value should be a limiting design re quirement (the range of adjustability should not extend to
lower values) and the upper value should be a minimum design requirement (the range of adjustability may be extended above this
value). For the UF trip functions frequency ranges, the upper value s hould be a limiting design requirement (the range of
adjustability should not extend to greater values) and the lower value should be a minimum design requirement (the range of
adjustability may be extended to lower values).
98 In North America, the limitations for transmission-connected resources as specified in NERC PRC-024-2 [B27] may be used for
referenc e.
99 The lower and upper values of the ranges of allowable settings for voltage and frequency trip settings specified in this standard for
DER are not intended to limit the capabilities and settings of other equipment on the Area EPS . It is recommended that settings
applied on Area EPS equipment conform to the voltage and frequency ride -through objectives of this standard whenever the Area
EPS is in normal configuration. However, it is recognized that in certain cases Area EPS operators may need to occasionally and
selec tively use trip settings outside the ranges of allowable settings to accommodate worker safety practices or to safeguard
distribution infrastructure while in an abnormal configuration, e.g., during automatic reconfiguration of a circuit sec tion or
temporary loss of direct transfer trip of mid- and large-scale DER. Area EPS operators should limit trip settings on Area EPS
equipment that conflict with this standard to only affect those selective DER and Area EPS equipment and only for a limited period
nec essary to meet these worker safety and equipment protection goals. Area EPS operators should coordinate these practic es with
the regiona l reliability coordinator who may consider bulk power system impacts of affected aggregate DER capacity.
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
Table 18 —DER response (shall trip) to abnormal frequencies for DER of
abnormal operating performance Category I, Category II, and Category
III (see Figure H.10)
(New)
aThe frequency and clearing time set points shall be field adjustable. The actual applied
underfrequency (UF) and overfrequency (OF) trip settings shall be specified by the Area EPS
operator in coordination with the requirements of the regional reliability coordinator. If the Area EPS
operator does not specify any settings, the default settings shall be used.
bThe ranges of allowable settings do not mandate a requirement for the DER to ride through this
magnitude and duration of abnormal frequency condition. The Area EPS operator may specify the
frequency thresholds and maximum clearing times within the ranges of allowable settings; settings
outside of these ranges shall only be allowed as necessary for DER equipment protection and shall
not conflict with the frequency disturbance ride through requirements specified in 6.5.2. For the
overfrequency (OF) and underfrequency (UF) trip functions clearing time ranges and for the OF trip
functions frequency ranges, the lower value is a limiting requirement (the setting shall not be set to
lower values) and the upper value is a minimum requirement (the setting may be set above this
value). For the UF trip functions frequency ranges, the upper value is a limiting requirement (the
setting shall not be set to greater values) and the lower value is a minimum requirement (the setting
cThis time shall be chosen to coordinate with typical regional underfrequency load shedding
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
6.5.2 Frequency disturbance ride-through requirements
The performance required of DER during frequency disturbances is specified in this clause. DER
shall meet one of the abnormal operating performance Category I, Category II, or Category III of this
clause. The frequency disturbance ride-through requirements specified in this clause do not apply
DER shall be designed to provide the frequency disturbance ride-through capability specified in this
clause without exceeding DER capabilities. Any tripping of the DER, or other failure to provide the
frequency disturbance within a ride-through region, shall constitute non -compliance with this
standard.
The DER shall specify its abnormal operating performance category within the nameplate information.
The frequency disturbance ride-through specified in the remainder of 6.5.2 shall not apply and DER
may cease to energize the Area EPS and trip without limitations if any of the following applies:
a) The net active power exported100 across the point of common coupling into the Area EPS is
continuously maintained at a value less than 10% of the aggregate rating of DER connected
to the Local EPS prior to any frequency disturbance, and the Local EPS disconnects from
the Area EPS, along with Local EPS load to intentionally form a Local EPS island, or
b) An active power demand of the Local EPS load equal or greater than 90% of the pre-
disturbance aggregate DER active power output is shed within 0.1 s of when the DER
100 Energy Storage DER operating in a manner that modulates active power, i.e., importing and exporting active power, shall be
evaluated for this exception based solely on the maximum positive power point over the modulated power range.
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
For frequency disturbances outside the ride-through operating region parameters (frequency range
and corresponding cumulative duration, minimum time) specified in Table 19 for Category I,
Category II, and Category III, requirements for continued operation (ride-through), or restore output
(New)
aAny DER shall provide the frequency-droop (frequency-power) operation for high-frequency
bDER of Category I may provide the frequency-droop (frequency-power) operation for low-
frequency conditions specified in 6.5.2.7. DER of Category II or Category III shall provide the
Frequency disturbances of any duration, for which the system frequency remains between 58.8 Hz
and 61.2 Hz and the per-unit ratio of Voltage/frequency is less than or equal to 1.1, sh all not cause
the DER to trip. The DER shall remain in operation during any such disturbance, and shall be able to
continue to exchange active power at least as great as its pre-disturbance level of power.
101 This standard may be adopted by AGIRs with fre quency values defining frequency ride -through performance in the continuous
opera tion region and mandatory operation region other than the ones specified.
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
6.5.2.3 Low-frequency ride-through
During temporary frequency disturbances, for which the system frequency is less than 58.8 Hz and
greater than or equal to 57.0 Hz, and having a cumulative duration below 58.8 Hz of less than 299 s
― Shall not reduce its active power output below the value specified in Table 20, depending
on the DER performance category as described in Clause 4. Reductions of available active
power due to the underfrequency event shall not be allowed when the voltage is within the
continuous operating range. Active power may be reduced in proportion with the grid
voltage when the grid voltage is below the level for continuous operation.
(New)
During low-frequency ride-through, the DER shall operate in the mandatory operation region as
specified in Table 19 for abnormal operating performance Category I, Category II, and Category III with
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
During temporary frequency disturbances, for which the system frequency is within the mandatory
― Shall continue to exchange pre-disturbance current with the Area EPS subject to
limitations specified in Table 20 and shall neither cease to energize nor trip. Active and
specified in Table 22, depending on the DER performance category as described in Clause 4.
Neither provision of energy storage capability, nor operation of DER at power outputs less
than the power available in order to allow reserve for power increase in response to
During temporary frequency disturbances, for which the system frequency is greater than 61.2 Hz
and less than or equal to 61.8 Hz, and having a cumulative duration greater than 61.2 Hz of less than
299 s in any ten-minute period, the DER shall be capable to ride-through and shall maintain
During high-frequency ride-through, the DER shall operate in mandatory operation region as specified
in Table 19 for abnormal operating performance Category I, Category II, and Category III with the
following requirements:
102 Pre-c urtailment or other measures to provide frequency response reserve may be included in contractual agreements and
interc onnection agreements, which are outside the scope of this standard. The intent of the requirement in this standard is for the
DER to only have the control capability in the DER to provide frequency response when the reserve exists, either due to spec i fic
c ontrac tual arrangements, dispatch control, or when curtailment exists for other reasons. Direction of active power can be negative
(c harging) for Energy Storage DER, e.g., return to frequency reduction via charging through droop or dispatch control, if ope rating
for that purpose prior to trip.
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
During temporary frequency disturbances, for which the system frequency is within the mandatory
― Shall continue to exchange current with the Area EPS and shall neither cease to energize nor
trip.
Within the continuous operation region and the low-frequency and high-frequency ride-through
operating regions (frequency range and corresponding cumulative duration, minimum time), the
DER shall ride through and shall not trip for frequency excursions having magnitudes of rates of
change of frequency (ROCOF) that are less than or equal to the values specified in Table 21 per
abnormal operating performance category. 103 As specified in 4.3, the ROCOF shall be the average rate of
(New)
103 The values specified in Table 21 are intended for DER to withstand frequency disturbances that can occur in interconnec ted
bulk power systems. Frequency disturbances during conditions where the bulk power system has split into multiple islands c an
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
6.5.2.6 Voltage phase angle changes ride-through
Multi-phase DER shall ride through for positive-sequence phase angle changes within a sub-cycle-
to-cycle time frame of the applicable voltage of less than or equal to 20 electrical degrees. In addition,
multi-phase DER shall remain in operation for change in the phases angle of individual phases less
than 60 electrical degrees, provided that the positive sequence angle change does not exceed the
forestated criterion. Single-phase DER shall remain in operation for phase angle changes within a
sub-cycle-to-cycle time frame of the applicable voltage of less than or equal to 60 electrical degrees.
Active and reactive current oscillations in the post-disturbance period that are positively damped or
momentary cessation of the DER having a maximum duration of 0.5 s shall be acceptable in response
to phase angle changes.
Depending on the DER abnormal operating performance category as described in Clause 4, the DER
shall have the capability of mandatory operation with frequency-droop (frequency-power) during low-
(New)
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
6.5.2.7.2 Frequency-droop (frequency-power) operation
During temporary frequency disturbances, for which the system frequency is outside the adjustable
deadband db OF and db UF as specified in Table 24, but still between the trip settings in Table 18, the
DER shall adjust its active power output from the pre-disturbance levels, according to the formulas
in Table 23. The active power output shall be as defined by the relevant formula in Table 23, plus
any inertial response to the rate of change of frequency, until frequency returns to within the
deadband.
The DER response shall conform to the prioritization of DER responses specified in 4.7.
Figure H.7 shows three example curves of a frequency-droop function for which the DER is
operating at different pre-disturbance levels of nameplate rating. A DER response during low-
frequency conditions may be subject to available active power and the pre-disturbance dispatch level.
performance categories
(New)
where
p is the active power output, 104 in p.u. of the DER nameplate active power rating
104 Inc ludes positive and negative active power for Energy S torage DER during low- and high-frequency conditions respec tively.
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
ppre is the pre-disturbance active power output, defined by the active power output at the
point of time the frequency exceeds the deadband, in p.u. of the DER rating
pmin is the minimum active power output due to DER prime mover constraints, in p.u. of
the
respectively, in Hz
respectively, in Hz
Adjustments to db OF, db UF, k OF, k UF, and T response (small-signal) shall be permitted in coordination with
the Area EPS operator and the requirements of the regional reliability coordinator.
(New)
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
bFor the single-sided deadband values (db OF, db UF) ranges, both the lower value and the upper value
is a minimum requirement (wider settings shall be allowed). For the frequen cy droop values (k OF,
k UF) ranges, the lower value is a limiting requirement (the setting shall not be set to lower values)
and the upper value is a minimum requirement (the setting may be set to greater values). For the
open-loop response time, T response (small-signal), the upper value is a limiting requirement (the
setting shall not be set to greater values) and the lower value is a minimum requirement (the setting
may be set to lower values). Any settings different from the default settings in Table 24 s hall be
approved by the regional reliability coordinator with due consideration of system dynamic oscillatory
behavior.
The time performance of the frequency-droop (frequency/power) operation for all th ree DER
5% of Rated Active Power): the open-loop response time T response (small-signal) of the
DER shall be adjustable within the ranges specified in Table 24. If the Area EPS operator
does not specify any settings, the default setting shall be 5 s. Any settings different from
the default settings in Table 24 shall be approved by the regional reliability coordinator with
or greater than 5% of Rated Active Power): The DER shall not be required to change its
active power output at a rate greater than 20% of nameplate rating per minute, in order to
meet the minimum response requirement, if the Primary Energy Source is physically
105 The maximum available power ramp rate of the DER shall be as fast as technically feasible, and equal or greater than the
minimum 20% per minute ramping capability requirement. This waiver of the minimum time requirement shall only apply for
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
6.5.2.8 Inertial response
Inertial response, in which the DER active power is varied in proportion to the rate of change of
When the system frequency is in a range given in Table 2, the DR shall cease to energize the Area
EPS within the clearing time as indicated. Clearing time is the time between the start of the
abnormal condition and the DR ceasing to energize the Area EPS. For DR less than or equal to 30 kW
in peak capacity, the frequency set points and clearing times shall be either fixed or field adjustable.
For DR greater than 30 kW, the frequency set points shall be field adjustable.
Adjustable under-frequency trip settings shall be coordinated with Area EPS operations.
(Deleted)
aDR‖≤‖30‖kW,‖maximum‖clearing‖times;‖DR‖>‖30‖kW,‖default‖clearing‖times.
106 If Area EPS Operator and DER Operator mutually agree to use DER inertial response, the performance requirements should be
c oordinated with the regional reliability coordinator with due consideration of system dynamic oscillatory behavior.
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
4.2.6 Reconnection to Area EPS
After an Area EPS disturbance, no DR reconnection shall take place until the Area EPS voltage is
within Range B of ANSI C84.1-1995, Table 1, and frequency range of 59.3 Hz to 60.5 Hz.
The DR interconnection system shall include an adjustable delay (or a fixed delay of five minutes)
that may delay reconnection for up to five minutes after the Area EPS steady-state voltage and
The Return to Service criteria for DER of Category I, Category, II, and Category III are specified in
4.10.
7. Power quality
Refer to the informative Annex G for additional information regarding DER induced power quality
The DR and its interconnection system DER shall not inject dc current greater than 0.5% of the full
7.2.1 General
The DER shall not create unacceptable rapid voltage changes or flicker at the point of common
coupling (PCC).
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
7.2.2 Rapid voltage changes (RVC)
When the PCC is at medium voltage, the DER shall not cause step or ramp changes in the RMS
voltage at the PCC exceeding 3% of nominal and exceeding 3% per second averaged over a period of
one second. When the PCC is at low voltage, the DER shall not cause step or ramp changes in the
RMS voltage exceeding 5% of nominal and exceeding 5% per second averaged over a period of one
second. Any exception to the limits is subject to approval by the Area EPS operator with
These RVC limits shall apply to sudden changes due to frequent energization of transformers,
frequent switching of capacitors or from abrupt output variations caused by DER misoperation.
These RVC limits shall not apply to infrequent events such as switching, unplanned tripping, or
7.2.3 Flicker
The DER contribution (emission values) to the flicker, measured at the PCC, shall not exceed the
greater of the limits listed in Table 25 and the individual emission limits defined by IEC/TR 61000-3-
7. Any exception to the limits shall be approved by the Area EPS oper ator with consideration of
(New)
a95% probability value should not exceed the emission limit based on a one week measurement
period.
107 Subclause 7.2.2 is not inte nde d to addre ss issues associated with slow voltage variations, which can be cause d by
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
Assessment and measurement methods for flicker are defined in IEEE Std 1453 and IEC/TR 61000-3-
― Equipment other than a DER shall be allowed to mitigate the flicker induced by a DER.
― E Pst is the emission limit for the short-term flicker severity, P st If not specified differently,
― E Plt is the emission limit for long-term flicker severity, P lt. If not specified differently, the P lt
evaluation time is 2 h.
(New)
Harmonic current distortion, inter-harmonic current distortion, and total rated-current distortion
(TRD) at the reference point of applicability (RPA) shall not exceed the limits stated in the following
The methodology for measuring harmonic and inter-harmonic values in this requirement is defined
in IEEE Std 519. 108 Note that Table 26 and Table 27 differ from any table in IEEE Std 519. In this
TDD (in Table 26) and the even order current distortion limits above the second order are relaxed for
108 IEEE S td 519 requires that the harmonic h be calculated as the ro ot-sum-square of the spectral component value at the ac tual
integer multiple of the fundamental frequency and spectral components in the adjacent ± 5 Hz bins from the gapless 10/12 c yc l e
(approximately 200 ms) measurement window. All of the other 5 Hz bins spectral components are similarly combined using root-
sum-square into the inter-harmonic value between adjacent harmonics.
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
Any aggregated harmonics current distortion between h ± 5 Hz, where h is the individual harmonic
order, shall be limited to the associated harmonic order h limit in Table 26 and Table 27. Any
the lesser magnitude limit of h and h + 1 harmonic order in Table 26 and Table 27.
The DR shall not create objectionable flicker for other customers on the Area EPS. 11
4.3.3 Harmonics
When the DR is serving balanced linear loads, harmonic These current injection into the Area EPS at
the PCC shall not exceed the distortion limits stated below in Table 3. The harmonic current
injections shall be exclusive of any harmonic currents due to harmonic voltage distortion present in
the Area EPS without the DR DER connected. Upon mutual agreement between the Area EPS
operator and the DER operator the DER may inject current distortion in excess of these tables, such
current (Irated)a
(New)
109 Typical utility instrument transformers may not be able to accurately reproduce high order harmonic content. Adherence to the
higher order harmonics may need to be confirmed in a laboratory setting or, if in the field, using equipment designed for use at the
11 Flic ker is c onsidered objectionable when it either causes a mo dulation of the light level of lamps sufficient to be irritating to
humans, or c auses equipment misoperation. For guidance, refer to IEEE Std 519 TM-1992 [B5], IEEE P1453 TM [B10], IEC/TR3 61000-
3-7 [B1], IEC 61000-4-15 [B2], IEC 61400-21 [B3].
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
(Deleted)
aIrated = the greater of the Local EPS maximum load current integrated demand (15 or 30 minutes)
without the DR unit, or the DR DER unit rated current capacity (transformed to the PCC RPA when
a transformer exists between the DR DER unit and the PCC RPA).
bEven harmonics are limited to 25% of the odd harmonic limits above.
(New)
aIrated = the DER unit rated current capacity (transformed to the RPA when a transformer exists
The total rated current distortion (TRD) in Table 26 , which includes the harmonic distortion and
(New)
where
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
Irated is the DER rated current capacity (transformed to the RPA when a transformer exists
Irms is the root-mean-square of the DER current, inclusive of all frequency components, as
The DER shall not contribute to instantaneous or fundamental frequency overvoltages with the
following limits:
a) The DER shall not cause the fundamental frequency line-to-ground voltage on any portion
of the Area EPS that is designed to operate effectively grounded, as defined by IEEE Std
C62.92.1, to exceed 138% of its nominal line-to-ground fundamental frequency voltage for
b) The DER shall not cause the line-to-line fundamental frequency voltage on any portion of
the Area EPS to exceed 138% of its nominal line-to-line fundamental frequency voltage for
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
7.4.2 Limitation of cumulative instantaneous overvoltage
The DER shall not cause the instantaneous voltage on any portion of the Area EPS to exceed the
magnitudes and cumulative durations shown in Figure 3. The cumulative duration shall on ly
include the sum of durations for which the instantaneous voltage exceeds the respective threshold
(New)
(New)
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
8. Islanding
8.1.1 General
For an unintentional island in which the DR DER energizes a portion of the Area EPS through the
PCC, the DR interconnection system DER shall detect the island and , cease to energize the Area EPS,
and trip within two seconds 2 s of the formation of an island. 12 111 False detection of an
unintentional island that does not actually exist shall not justify non-compliance with ride-through
Upon mutual agreement between the Area EPS operator and the DER operator, the clearing time may
111 Relianc e solely on under/over voltage and frequency trip is not considered sufficient to detect and cease to energize and trip. IEEE
112 To ac hieve coordination between unintentional islanding detection and automatic reclosing, auto-reclose times longer than 2 s
1. The DR aggregate capacity is less than one -third of the minimum load of the Local EPS .
3. The DR installation contains reverse or minimum power flow protection, sensed between the Point of DR Connection and the
PCC, which will disconnect or isolate the DR if power flow from the Area EPS to the Local EPS reverses or falls below a set
threshold.
4. The DR c ontains other non-islanding means, such as a) forced frequency or voltage shifting, b) transfer trip, or c) governor and
exc itation controls that maintain constant power and constant power factor.
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
8.1.3 Area EPS with automatic reclosing
Requirements with regard to Area EPS automatic reclosing coordination are specified in 6.3. 113
8.2.1 General
An intentional island can be an intentional Area EPS island or an intentional Local EPS island. The
An intentional island that includes any portion of the Area EPS is an intentional Area EPS island. An
intentional Area EPS island, while islanded, shall be designed and operated in coordination with the
An intentional island that is totally within the bounds of a Local EPS is an intentional Local EPS
island. 114 DER that support intentional Local EPS islands, while interconnected to an Area EPS that is
not islanded, shall be subject to all requirements for interconnection of DER to Area EPS specified in
There are two means by which an intentional island system can transition to an islanded condition:
113 It is important to bear in mind that islanding detection methods in inverters are generally designed to detect islands with a
generation-load balance. They are not intended or designed to detect faults and should not be relied upon for that purpose.
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
8.2.2 Scheduled intentional islands
Scheduled intentional islands are formed through DER operator or Area EPS operator manual action
or other operating dispatch means (e.g., Energy Management System or Automatic Generator
Control action) that trigger the transition from being in parallel and synchronized with the Area
EPS, to operation as an islanded system. Reasons for forming a scheduled intentional island can
include enhanced reliability, economic dispatch decisions for self-supply or import/export of power
with or through the Area EPS, or pre-emptive Area EPS operator action to island ahead of inclement
weather.
Unscheduled intentional islands are formed autonomously from local detection of abnormal
conditions at the interconnection(s) with the Area EPS, and then automatic relay action that triggers
switching action to isolate the intentional island rapidly from the Area EPS.
An intentional island may disconnect from the Area EPS and transition to intentional island mode for
― Whenever any of the exception conditions described in 6.4.2.1 and 6.5.2.1 are met, or
― If any of the trip conditions described in Clause 6 are met (i.e., where Clause 6 would allow
or mandate tripping, the intentional island may transition to intentional island mode), or
― If the conditions of 8.1 are met (i.e., the DER detects an island and the DER ceases to
energize the Area EPS under 8.1), the intentional island may enter intentional island mode
instead of ceasing to energize the Area EPS, provided that the intentional island does not
energize any part of the Area EPS that is outside the defined intentional island).
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
8.2.5 Transition of an intentional island from the Area EPS
If an intentional island that does not qualify as an exception under 6.4.2.1 or 6.5.2.1 disconnects from
the Area EPS when the voltage and frequency of the Area EPS are within the Continuous Operation
An intentional island that has disconnected from the rest of the Area EPS may reconnect to the rest of
the Area EPS when the conditions listed in 4.10 are met at the intentional island point of common
coupling. When the intentional island reconnects to the Area EPS, the conditions of 4.10.4 shall be
met.
When operating in an intentional Area EPS island, participating DER may have to adjust several
control and protection settings. These alternate settings and ranges of allowable settings, including
those specified in 8.2.7, shall be enabled only when the intentional Area EPS island is isolated from the
Area EPS. In order to meet this requirement, adaptive protection and control settings may be
required.
For DER operating in an intentional Area EPS island, the following requirements apply:
― 5.2 (reactive power capability of the DER) and 5.3 (voltage and reactive power control) for
― 6.4.1 (mandatory voltage tripping) the range of allowable settings in overvoltage trip function
2 (OV2) shall be 0.008 s to 0.16 s for all three categories, in Table 11, Table 12, and Table 13.
― 6.5.1 (mandatory frequency tripping) the range of allowable settings in overfrequency trip
setting 1 (OF1) and underfrequency trip setting 1 (UF1) shall be 11 s to 1000 s for all three
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
― 6.5.2.7 (frequency-droop) for all aggregate DER ratings. For DER complying with Category
III of Table 23, the frequency droop (k OF) shall be adjustable from 0.0055 to 0.05 per-unit.
For participating DER in Category III of Table 24, the lower value of the range of allowable
― Shall be capable of operating in Area EPS-connected mode, in intentional island mode, and
A DER that participates in an intentional Area EPS island shall be categorized in one of the following
ways:
1) Uncategorized: A DER not designed for intentional island operation may be allowed to
participate in the intentional island if certain system criteria are met (for examples of this,
please see Annex C). Otherwise, it shall cease to energize the Area EPS during intentional
2) Intentional island-capable: Applies to DER that can disable or modify its islanding detection
3) Black start-capable: Applies to intentional island-capable DER that can also energize an EPS
These categories shall be stated by the DER operator, but utilization shall be by mutual agreement
between the DER operator and the operator of the intentional Area EPS island. In no case shall a DER
be required to operate outside of the voltage, current, and frequency ratings required to provide
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
9. Distributed resources DER on distribution secondary grid/area/street
(grid) networks and spot networks
Network protectors (NPs) shall not be used to connect, separate, switch, serve as breaker failure
backup, or in any manner isolate a network or network primary feeder to which DR DER is
connected from the remainder of the Area EPS network, unless the protectors are rated and tested
DR Unless specified otherwise by the Area EPS operator, DER installations on a spot network, using
an automatic transfer scheme in which load is transferred between the DR DER and the EPS in a
momentary make-before-break operation, shall meet all the requirements of this clause regardless of
Power flow during this transition shall be positive from the Area EPS to the load and the DER unless
— Monitor instantaneous power flow at the PCC of the DER interconnected to the secondary
grid or spot network for reverse power relaying, minimum import relaying, dynamically
controlled inverter functions and similar applications to prevent reverse power flow
— Maintain a minimum import level at the PCC as determined by the Area EPS operator.
— Control DER operation or disconnect the DER from the Area EPS based on an autonomous
setting at the PCC and/or a signal sent by the Area EPS operator.
115 9 IEEE C37.108 TM-2002 [B8] and IEEE S td C57.12.44™-2000 [B9 B25] provide provides guidance on the capabilities of network
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
DER on grid or spot networks shall not
— Prevent or delay the NP from opening for faults on the Area EPS.
— Energize any portion of an Area EPS when the Area EPS is de-energized.
— Require the NP settings to be adjusted except by consent of the Area EPS operator.
— Any DR installation connected to a spot network shall not cause operation or Prevent
reclosing of any network protectors installed on the spot network. This coordination shall
In addition to the requirements in 9.1, DER on secondary grid networks shall not cause an islanding
In addition to the requirements in 9.1, in the event of an adjacent feeder fault, network protector
master relays shall not be actuated by the presence of DER. The interconnected DER shall be
coordinated with NP relay functions and shall be evaluated by the Area EPS operator to ensure
network reliability.
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
9.3 Distribution secondary spot networks 8
In addition to the requirements in 9.1, connection of the DR DER to the Area EPS is only permitted if
the Area EPS network bus is already energized by more than 50% of the installed network
protectors. 116
The network equipment loading and fault interrupting capacity shall not be exceeded with the
addition of DR.
protocols117
A DER shall have provisions for a local DER interface capable of communicating (local DER
communication interface) to support the information exchange requirements specified in this standard
Under mutual agreement between the Area EPS operator and DER operator additional
The decision to use the local DER communication interface or to deploy a communication system shall
116 S ee IEEE S td 1547.6 [B21] for more explanation for this requirement.
117 This standard mandates these interoperability c apabilities; however, how they are implemented, recorded, and reported is up to
loc al jurisdic tions and should be addressed in those processes and procedures (such as interconnection agreements).
8 When required by the authority who has jurisdiction over the DR interconnection, a study may be conducted to dete rmine that all
of the requirements of this subclause can be met when the aggregate DR installed on a spot network exceeds 5% of the spot
network’s‖maximum‖load.
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
Emergency and standby DER are exempt as specified in 4.13 from the interoperability requirement s
The specific DER functionality required by this standard results in the set of mandatory information
elements identified in 10.3 through 10.6. These information elements shall be supported by the DER
For information interoperability, these communication capabilities shall use a unified information
model, and non-proprietary protocol encodings based on intern ational standards or open industry
specifications as described in 10.7.
ability of the DER to perform functions. This information may be read or written.
― Management information: This information is used to update functional and mode settings
Nameplate information shall be available through a local DER communication interface and include at
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
Table 28 —Nameplate information
(New)
Configuration information shall be available through a local DER communication interface to allow the
Each rating in Table 28 may have an associated configuration setting that represents the as-
configured value. If a configuration setting value is different from the corresponding nameplate
value, the configuration setting value shall be used as the rating within the DER. Changes to the
configuration setting shall be made with mutual agreement between the DER system operator and
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
10.5 Monitoring information
The DER shall be capable of providing monitoring information through a local DER communication
interface at the reference point of applicability and shall include at a minimum the information
contained in Table 29. The information shall be the latest value that has been measured within the
(New)
10.6.1 General
Management information is used to update functional and mode settings for the DER. This
Parameters for constant power factor mode as described in 5.3.2 shall be available for reading and
writing through a local DER communication interface. Power factor value and excitation encoding are
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
Table 30 —Constant power factor mode parameters
(New)
NOTE—The‖terms‖‚over-excited‛‖and‖‚under-excited‛‖are‖illustrated‖in‖the‖informative‖Figure‖H.3‖
in Annex H.
Parameters for voltage-reactive power mode as described in 5.3.3 shall be available for reading and
(New)
Parameters for active power-reactive power mode as described in 5.3.4 shall be available for reading
and writing through a local DER communication interface. See Table 32.
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
Table 32 —Active power-reactive power mode parameters
(New)
Parameters for constant reactive power mode as described in 5.3.5 shall be available for reading and
(New)
Parameters for voltage-active power mode as described in 5.4.2 shall be available for reading and
(New)
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
10.6.7 Voltage trip and momentary cessation parameters
Parameters for voltage trip as described in 6.4.1 shall be available and the momentary cessation
threshold as specified in 6.4.2.1 may be available for information exchange through a local DER
communication interface. Both settings, if applicable, shall be specified as a set of piecewise linear
curves that define the regions associated with the voltage regions described in the functional
(New)
(New)
Parameters for frequency trip as described in 6.5.1 shall be available for reading and writing through
a local DER communication interface. Frequency trip settings shall be specified as a set of piecewise
linear curves that define the regions associated with the frequency regions described in the
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
Table 37 —Frequency parameters
(New)
Parameters for frequency droop as described in 6.5.2.7 shall be available for reading and writing
through a local DER communication interface. See Table 38.
(New)
Parameters for enter service as described in 4.10 shall be available for reading and writing through a
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
Table 39 —Enter service after trip parameters
(New)
A DER can be directed to cease to energize and trip by changing the Permit service setting to
Parameters to limit maximum active power as specified in 4.6.2 shall be available for reading and
writing through a local DER communication interface. See Table 40.
(New)
The protocol requirements set forth in this subclause apply at the local DER communication interface.
As illustrated in Figure 4, the protocols and physical layers utilized within communication networks
and within the DER may differ according to the network architecture and technology, and are out of
118 For example, the Area EPS operator may deploy networks that utilize the IEEE 2030.5 protocol even if it is not the native
protoc ol supported at the local DER communication interface. The standard protocol support requirement does not preclude the use of
additional protocols such as the information model defined by IEC 61850-7-420 [B8] exchanged using IEC 61850-8-1 [B9] or IEC
61850-8-2 [B10], or profiles of the IEC 61850-7-420 information model mapped to IEEE S td 1815 (DNP3) or to S unS pec Modbus.
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
(New)
The DER shall support at least one of the protocols specified in Table 41. The protocol to be utilized
may be specified by the Area EPS operator. Additional protocols, including proprietary protocols,
may be allowed under mutual agreement between Area EPS operator and DER operator. Additional
physical layers may be supported along with those specified in the table.
(New)
Communication performance requirements for the interface to DER are set forth in Table 42. These
requirements do not constrain or define the performance of various communication systems that
may be utilized to integrate DER, but only apply to the DER themselves.
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
Table 42 —Communication performance requirements for DER
interfaces
(New)
It is recognized that cybersecurity is a critically important issue for DER deployments connected to
broader monitoring and control communications networks. Each standardized local DER
communication interface option provides different security capabilities. The interoperability and
communications cyber security requirements of specific DER deployments may be based on mutual
agreement and may also be subject to regulatory requirements that may vary across jurisdictions.
This standard, therefore, does not mandate specific cyber security requirements at the DER interface.
11.1 Introduction
The technical requirements specified in Clause 4 through Clause 10 define the interconnection and
interoperability requirements of this standard. These requirements are tested and verified in
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
The requirements contained in this standard identify the necessary conditions that shall be verified
to improve proper and reliable operation of the DER. These requirements include properties of the
DER, properties that shall be maintained at operational interfaces, and properties that are needed
throughout the life of the installed system. All DER verification requirements contained in this
document shall be met, and then verified in accordance with IEEE Std 1547.1 [B17]. Depending upon
the circumstances and selected verification method, it is possible that additional requirements may
accuracy of recorded data, conditions of unit under test, temporary patches and turnarounds.
This clause provides specifies the test requirements applicable testing and verification methods to
demonstrate verify that the interconnection system a DER meets the requirements of Clause 4. The
applicable tests from this clause are required for all interconnection systems. and interoperability
requirements specified in Clause 4 through Clause 10 at the applicable reference point as specified in
4.2. This clause further specifies at which stage in the interconnection process testing and verification
shall be required. The applicable test and verification methods from this clause are required for all
DERs. 119 The results of these test and verification methods shall be formally documented. 120
119 The stated test specifications and requirements are universally needed for interconnection of DR DER including synchronous
mac hines, induction machines, or static power inverters/conv erters, and will be are sufficient for most installations. 13
120 The responsibilities, procedures, requirements, and criteria for the applicable test and verification methods are specified in IEEE
S td 1547.1 [B17].
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
11.2 Definition of test and verification methods
11.2.1 General
All DER interconnection and interoperability requirements of this standard shall be demonstrated
through either type tests, production tests, DER evaluation, commission ing tests, or periodic tests or
a combination of these tests and verification methods. Requirements and capabilities that are only
partially121 verified through type testing shall be fully verified through DER evaluation and
commissioning tests.
A type test may be performed on one device or combination of devices. In case of a combination of
devices forming a system, this test shows that the devices are able to operate together as a system.
This design test Type tests shall be performed, as applicable, to the specific interconnection DER unit
or DER system technology. The test tests shall be performed on a representative sample DER unit or
DER system, either in the factory, at a testing laboratory, or on equipment in the field. 14 Type test
results from a DER within a product family of the same design, including hardware and software,
shall be allowed as representative of other DERs within the same product family with power ratings
For systems in the field, replacement of DER equipment with substitutive components compliant
and tested with this standard shall be allowed and not invalidate previous type test and production
test results. However, field demonstration of performance shall be as agreed with the EPS operator
121 Partial verification may occur for DER that may have to meet requirements at the PCC per Clause 4 or that require a
14 The design test of 5.1 may be adopted as the testing basis for certification of interconnection systems.
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
This test applies to a packaged interconnection system using embedded components or to an
The design test shall be conducted on the same sample in the sequence of Table 4.
(Deleted)
This test shall demonstrate that the DR ceases to energize the Area EPS when the voltag e or
frequency exceeds the limits as specified in 4.2.3 and 4.2.4. Interconnection systems provided with
field adjustable set points shall also be tested at the minimum, midpoint, and maximum of the
adjustable set point ranges. These tests shall be conducted using either the simulated utility or
5.1.2 Synchronization
with the requirements of 4.1.3. The appropriate conditions to be met for specific interconnection
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
A. Synchronous interconnection to an EPS, or an energized local EPS to
an energized Area EPS
This test shall demonstrate that at the moment of the paralleling-device closure, all three parameters
in Table 5 are within the stated ranges. This test shall also demonstrate that if any of the parameters
are outside of the ranges stated in the table, the paralleling-device shall not close.
B. Induction interconnection
This test shall determine the maximum start-up (in-rush) current drawn by the unit. 15 The results
shall be used, along with Area EPS impedance information for the proposed location, to estimate the
starting voltage drop and verify that the unit shall not exceed the synchronization requirements in
C. Inverter interconnection 16
An inverter-based interconnection system that produces fundamental voltage before the paralleling
device is closed shall be tested according to the procedure for synchronous interconnection as stated
in A of 5.1.2.
All other inverter-based interconnection systems shall be tested to determine the maximum start -up
current. The results shall be used, along with Area EPS impedance for the proposed location, to
estimate the starting voltage magnitude change and verify that the unit shall meet the
16 S ome inverter-based interconnection systems may need to be tested to both requirements of C in 5.1.2.
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
5.1.3 Interconnect integrity test
The interconnection system shall be tested in accordance with IEEE Std C37.90.2-1995 to confirm that
the results are in compliance with 4.1.8.1. The influence of EMI shall not result in a change in state or
The interconnection system shall be tested for the requirement in 4.1.8.2 in all normal operating
modes in accordance with IEEE Std C62.45-2002 for equipment rated less than 1000 V to confirm that
the surge withstand capability is met by using the selected test level(s) from IEE E Std C62.41.2-2002.
Interconnection system equipment rated greater than 1000 V shall be tested in accordance with
equipment signal and control circuits, use IEEE Std C37.90.1-2002. The results of these tests shall
indicate the unit did not fail, did not misoperate, and did not provide misinformation.
A dielectric test across the open-circuited paralleling device shall be conducted to con firm
A test or field verification shall be conducted to confirm that 4.4.1 is met regardless of the selected
Inverter based DR shall be tested to confirm that the DR does not inject dc current greater than
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
5.1.6 Harmonics
The intent of the harmonics interconnection test is to assess that under a controlled set of conditions
The DR shall be operated in parallel with a predominantly inductive voltage source with a short
circuit current capacity I SC of not less than 20 times the DR rated output current at fundamental
frequency. The voltage and frequency output of the voltage source shall correspond to the rated
voltage and frequency of the DR. The unloaded voltage waveform produced by the Area EPS or
simulated utility voltage source shall have a total harmonic distortion (THD) less than 2.5%.
The DR shall be operated at an output test load current, I L , of 33%, 66%, and at a level as close to
100% of rated output current as practical. Use total rated-current distortion (TRD) in place of TDD.
TRD is the total rms value of the sum of the current harmonics created by the DR unit operating into
a linear balanced load divided by the greater of the test load current (I L ) demand or the rated current
capacity of the DR unit (Irated). The individual harmonic distortion and TRD of the DR output
current shall be measured for the first 40 harmonics. The harmonic current injections shall be
exclusive of any harmonic currents due to harmonic voltage distortion present in the Area EPS
without the DR connected. The test results shall not exceed the values in 4.3.3, Table 3. 18
either after installation or while powering a balanced resistive load and isolated fro m any other
sources. The voltage harmonics while powering a resistive load at 100% of the machine kVA rating
shall not exceed the levels in Table 6. Voltage harmonics shall be measured line to line for 3-phase/3
wire systems, and line to neutral for 3-phase/4-wire systems.
18 These values or lower values may be required to meet the TDD of 5% at the PCC.
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
Table 6—Maximum harmonic voltage distortion in percent of rated
voltage for synchronous machines
(Deleted)
Production tests shall be conducted on every unit of DER and interconnect of equipment prior to
Each interconnection system shall be subjected to requirements of 5.1.1 and 5.1.2. Interconnection
systems with adjustable set points shall be tested at a single set of set points as specified by the
manufacturer. This test Production tests shall verify the operability of every unit of DER and
interconnect equipment manufactured for customer use. These tests assume that the equipment has
met the applicable interconnection and interoperability requirements of this standard and may be
conducted as a factory test or may be performed as part of a DER evaluation or commissioning test
(see 5.4). The summary reporting shall provide a list of normal and abnormal performance category
Manufacturers having certified production facilities or proven production processes and quality
control methods certified by a NRTL shall be allowed to use said approved practices and
For systems in the field, replacement of DER equipment with substitutive components compliant
and tested with this standard shall be allowed and not invalidate previous production test results.
However, field demonstration of performance shall be as agreed with the Area EPS operator and
DER operator.
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
11.2.4 DER evaluation
11.2.4.1 General
DER evaluation comprises a design evaluation desk study during the interconnection review
process and an as-built installation evaluation on site at the time of commissioning to verify that the
composite of the individual partially compliant DER(s) and, if applicable, the supplemental DER
device(s) forming a system meet the interconnection and interoperability requirements of this
standard.
The design evaluation (desk study) is an evaluation during the interconnection review process to
verify that the composite of the individual partially compliant DERs forming a system as designed
meets the interconnection and interoperability requirements of this standard. This evaluation is
The as-built installation evaluation (on-site) is an evaluation at the time of commissioning to verify
that the composite of the individual partially compliant DERs forming a system as delivered and
installed meets the interconnection and interoperability requirements of this standard. This
A basic DER evaluation shall be limited to verify that the DER has been designed and installed with
the proper components and connections. A detailed DER evaluation shall include an engineering
verification of the chosen components and may require modeling and simulation of the composite of
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
11.2.5 Commissioning tests and verifications
11.2.5.1 General
Commissioning tests are tests and verifications on one device or combination of devices forming a
system to confirm that the system as designed, delivered, and installed meets the interconnection
All commissioning tests shall be performed based on written test procedures. 19 The following visual
owner and Area EPS operator. Commissioning tests shall include visual inspections and may
— A visual inspection shall be made to ensure that the grounding coordination requirement
— A visual inspection shall be made to confirm the presence of the isolation device if
required by 4.1.7.
Initial commissioning tests shall be performed on the installed DR and interconnection system
equipment prior to the initial parallel operation of the DR. The following tests are required:
— A basic functional commissioning test includes visual inspection and an operability test on the
isolation device. A detailed functional commissioning test shall include a basic functional test and
functional tests to verify interoperability of a combination of devices forming a system to verify that
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
— Any tests of 5.1 that have not been previously performed on a representative sample and
formally documented
A reverse-power or minimum power function, if used to meet the requirements of 4.4.1, shall be
tested using injection techniques or by adjusting the DR output and local loads to verify that the
If tests in 5.4.1.1 and 5.4.1.2 are not applicable to the interconnection system, the interconnection
system shall be tested in accordance with procedures provided by the manufacturer or system
integrator.
Check the cease to energize functionality by operating a load interrupting device and verify the
equipment ceases to energize its output terminals and does not restart/reconnect for the required
time delay. The test shall be performed on each phase individually. This test verifies conformance to
the cease to energize requirement of 4.1.4, 4.2.1, 4.2.2, 4.2.3, 4.2.4, and 4.4.1.
Periodic tests are tests and verifications, according to a scheduled time period or other criteria, that
confirm that one already interconnected device or combination of devices forming a system meets
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
Periodic test requirements and intervals for all interconnection-related protective functions and
associated batteries shall be periodically tested at intervals specified provided by the manufacturer,
interconnection equipment manufacturers or system integrator, or and approved by, the authority
who has jurisdiction over AGIR or the DR interconnection Area EPS operator. Frequency of retesting
shall be determined by Area EPS operator policies for protection system testing, or manufacturer
The Area EPS operator may require a commissioning test be performed outside of the normal
For systems in the field, replacement of DER equipment with substitutive components compliant to
this standard shall be allowed and not invalidate previous type test and production test results. The
Area EPS operator may still require commissioning testing on any equipment replaced.
Information describing facility changes such as; (software, firmware, hardware) shall be available to
the Area EPS operator through the interoperability requirements of Clause 10. Reverification of the
interconnection and interoperability requirements of this standard may be required when any of the
― Functional software or firmware changes have been made on the interconnection system
DER.
― Any hardware component of the interconnection system DER has been modified in the
field, or, has been replaced or repaired with parts different from the tested configuration
Sublauses 5.4.1 and 5.4.2, and the applicable tests of 5.2 shall be repeated if:
― Protection functions have been adjusted after the initial commissioning process.
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
11.3 Full and partial conformance testing and verification
11.3.1 General
Requirements define the capability, design, and performance of a built system. Test and verification
is confirming that the requirements have been satisfactorily met. The test and verification
requirements are specified by use of a test requirements matrix as described in Table 43 and Table
44. These matrices provide a means of traceability between the need to verify a given requirement
and the means of verification. These matrices help ensure that there is consistency throughout the
stages in interconnection process testing and verification for DER that shall meet requirements in
Clause 4 through Clause 10. Test requirement matrices provide minimum testing requirements for
traceability, but the Area EPS operator shall not be limited from requiring supplemental
Note that this document presents two traceability matrices—one for connections at the PCC and one
for requirements to be tested at the PoC. As indicated in 4.2, many applications exist where the
applicable point for meeting performance requirements shall be the PoC. This includes small-scale
DER, applications where DER units are interconnected to Local EPS having substantial load.
According to 4.2, the requirements of this standard apply either at the PCC or the PoC, depending
on the aggregate nameplate DER rating and the average annual load in the Local EPS. 122 Where
requirements apply at the PoC, equipment type testing will be sufficient to verify conformance with
most requirements, in most cases. However, for DER facilities, i.e., Local EPS that are large enough
so that requirements apply at the PCC, equipment testing will have to be supplemented by
additional compliance verification measures such as the DER evaluation and further commissioning
tests defined above. The same holds for any DER that use supplemental DER devices to meet the
requirements of this standard. Annex F provides further information concerning testing and
verification requirements at the PCC or PoC, including the concept of combined type test and DER
evaluation.
122 As per 4.2 some DER units have some requirements that shall be met at the PCC and other requirements that shall be met at the
PoC.
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
NOTE—Subclause 11.3 only maps the required test and verification procedures to the performance
requirements of this standard. The subclause does not specify exactly how these procedures are
implemented. The details of the actual test and verification procedures are specified in IEEE Std
1547.1 [B17].
This subclause outlines a methodology for testing and verification of DER that may be used to
demonstrate conformance at the PCC per Clause 4 through Clause 10 for interconnection and
interoperability requirements of this standard. The Area EPS operator may have additional
For DER that shall meet requirements at the PCC per 4.2, Table 43 specifies the test and verification
requirements. 123
The DER system or DER unit 124 shall be classified as either fully compliant or partially compliant.
Type tests, DER evaluations, and commissioning tests shall be done as indicated in the table for all
123 The c orresponding responsibilities, procedures, requirements, and criteria for the applicable test and verification methods are
124 Individual DER units that are considered fully compliant at the PoC may only be considered fully compliant at the PCC if the
impedanc e between the PoC and the PCC is less than 0.5% on the DER rated apparent power and voltage base.
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
Table 43 —Interconnection test specifications and requirements for DER
that shall meet requirements at the PCC
(New)
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
(New)
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
(New)
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
(New)
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
(New)
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
(New)
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
(New)
cIslanding trip time test data can be used to assist in the DER design evaluation line item for 6.3.
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
5.3 Interconnection installation evaluation
A system design verification shall be made to help ensure that the requirements of 4.16.2 (for Area
EPS faults) have been met. Type tests shall be made to verify the requirements of 6.2 (for individual
open phase conditions) of this standard have been met. The Type test (set-up) and certification
record shall include each of the specific interconnection transformer vector groups with which the
specific DER unit is intended to be interconnected. DER evaluations and/or commissioning tests
may also be made to verify the requirements of 6.2 for the DER (for individual open phase
The test and verification requirements are specified by use of a test requirements matrix (Table 44).
This matrix provides a means of traceability between the need to verify a given requirement and the
means of verification. These matrices ensure that there is consistency throughout the stages in
interconnection process testing and verification for DER that shall meet requirements at the PoC.
This subclause outlines a methodology for testing and verification of DER that may be used to
demonstrate conformance at the PoC per Clause 4 through Clause 10 for interconnection and
interoperability requirements of this standard. The Area EPS operator may have additional
For DER that shall meet requirements at the PoC per 4.2, Table 44 specifies the test and verification
requirements. 125
The DER unit shall be classified as either fully compliant or partially compliant. Type tests, DER
evaluations, and commissioning tests shall be done as indicated in the table for all line items under
125 The c orresponding responsibilities, procedures, requirements, and criteria for the applicable test and verification methods are
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
Table 44 —Interconnection test specifications and requirements for DER
that shall meet requirements at the PoC
(New)
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
(New)
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
(New)
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
(New)
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
(New)
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
(New)
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
(New)
aIslanding trip time test data, from the line item for 8.1 in this table, can be used to assist in the DER
design evaluation.
dIslanding trip time test data can be used to assist in the DER design evaluation line item for 6.3.
A system design verification shall be made to ensure that the requirements of 4.1.7 have been met.
A system design verification shall be made to ensure that the provisions for monitoring are in
A system design verification shall be made to ensure that the requirements of 4.2.1 6.2 (for Area EPS
faults) of this standard have been met. Type tests shall be made to verify the requirements of 6.2 (for
individual open phase conditions) have been met. The Type test (set-up) and certification record
shall include each of the specific interconnection transformer vector groups with which the specific
DER unit is intended to be interconnected. DER evaluations and/or commissioning tests may also be
made to verify the requirements of 6.2 for the DER (for individual open phase conditions) of this
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
11.4 Fault current characterization
11.4.1 General
This subclause defines tests and documentation of parameters that are useful in characterizing DER
This subclause applies to electronically coupled generation with aggregate rated capacity of 500 kVA
or greater. This requirement shall also apply to three-phase systems comprised of three sets of
single-phase systems, if the aggregate facility rating at the PCC is 500 kVA or greater. The objective
is to determine the controller response of the DER under certain fault conditions. The requirements
in this subclause exclude directly connected synchronous and indu ction generators without active
The DER operator shall provide to the Area EPS operator oscillographic voltage and current data for
all three phases measured during type testing. Sequence impedance characteristics of the extern al
source used during DER type tests shall be provided. The DER shall be type tested for maximum
The data requirements for synchronous and induction generator DER are the nameplate kVA rating,
impedance, and subtransient impedances. The requirements in this subclause exclude induction
126 The interc onnection of DER may impact the equipment and operation of the EPS . S ystem impact studies identify potential
problems and allow the Area EPS operator to determine the modifications to the Area EPS facilities that may mitigate potential
problems.
127 A doubly-fed induction machine is considered to have active control of the rotor current.
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
5.3.5 Area EPS reclosing coordination
A system design verification shall be made to verify the interconnection system is coordinated with
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
Annex A
(informative)
Bibliography
Bibliographical references are resources that provide additional or helpful material but do not need
to be understood or used to implement this standard. Reference to these resources is made for
[B1] Accredited Standards Committee C2-2012, National Electrical Safety Code® (NESC®).
[B2] BDEW Bundesverband der Energie-und Wasserwirtschaft e.V. (German Association of Energy
and Water Industries) (2008): Technical Guideline: Generating Plants Connected to the Medium-
Voltage‖ Network.‖ Guideline‖ for‖ generating‖ plants’‖ connection‖ to and parallel operation with the
[B3] Boemer, J. C. (2016): On Stability of Sustainable Power Systems. Network Fault Response of
Transmission Systems with Very High Penetration of Distributed Generation. PhD diss. Delft
University of Technology, Delft, The Netherlands. Intelligent Electrical Power Grids. Available
online at http://doi.org/10.4233/uuid:78bffb19-01ed-48f9-baf6-ffb395be68a0.
[B5] EPRI White Paper, Recommended Settings for Voltage and Frequency Ride-Through of Distributed
http://www.epri.com/abstracts/Pages/ProductAbstract.aspx?ProductId=000000003002006203. 128
128 EPRI publications are available from the Electric Power Research Institute (http://www.epri.com).
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
[B6] FERC Docket RM16-8-000, IEEE P1547 Response to FERC NOPR RM16-8 decision on Proposed
https://elibrary.ferc.gov/idmws/file_list.asp?document_id=14461876.
[B7] FERC Order No. 828. Requirements for Frequency and Voltage Ride-Through Capability of
Small Generating Facilities. Final Rule. Docket No. RM16-8-000. FERC. July 21, 2016. Available
online at http://www.ferc.gov/whats-new/comm-meet/2016/072116/E-11.pdf.
[B8] IEC 61850-7-420, Communication networks and systems for power utility automation —Part 7-
[B9] IEC 61850-8-1, Communication networks and systems for power utility automation—Part 8-1:
Specific communication service mapping (SCSM)—Mappings to MMS (ISO 9506-1 and ISO 9506-2)
[B10] IEC 61850-8-2, Communication networks and systems for power utility automation—Part 8-2.
Protocol (XMPP).
[B11] IEC TR 61850-80-3, Communication networks and systems for power utility automation—Part
[B12] IEC 62351-12, Power Systems Management and Associated Information Exchange—Data and
129 FERC doc kets are available fro m Federal Energy Regulatory Commission (https://elibrary.ferc.gov/idmws/docket_sheet.asp).
130 IEC publications are available from the International Electrotechnical Commission (http://www.iec.ch) and the Americ an
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
*B13+‖IEEE‖Std‖67™,‖IEEE‖Guide‖for‖Operation‖and‖Maintenance‖of‖Turbine‖Generators.‖ 131, 132
The following citations are referred to in this standard for informative purposes and are not required
[B1] IEC TR3 61000-3-7, Assessment of Emission Limits for Fluctuating Loads in MV and HV Power
Systems.
[B3] IEC 61400-21, Wind Turbine Generator Systems—Part 21: Measurement and Assessment of
[B4] IEEE 100, The Authoritative Dictionary of IEEE Standards Terms, Seventh Edition, New York,
[B14] IEEE Std 929™-2000, IEEE Recommended Practice for Utility Interface of Photovoltaic (PV)
Systems.
[B15] IEEE Std1001™-1988, IEEE Guide for Interfacing Dispersed Storage and Generation Facilities
[B8] IEEE Std C37.108-1989 (R2002), IEEE Guide for the Protection of Network Transformers.
[B10] IEEE P1453, Draft Recommended Practice for Measurement and Limits of Voltage Flicker on
AC Power Systems.
[B17] IEEE Std P1547.1™,‖ Draft IEEE Standard For Conformance Test Procedures for Equipment
131 20 The IEEE standards or products referred to in Annex A are trademarks owned by The Institute of Electrical and Elec tronic s
132 IEEE publications are available from The Institute of Electrical and Electronics Engineers (http://standards.ieee.org/).
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
[B18] IEEE Std P1547.2™, Draft IEEE Application Guide for IEEE Std 1547™-2003, IEEE Standard for
[B19] IEEE Std P 1547.3™, Draft IEEE Guide for Monitoring, Information Exchange, and Control of
[B20] IEEE Std 1547.4™,‖IEEE Guide for Design, Operation, and Integration of Distributed Resource
[B21] IEEE Std 1547.6™, IEEE Recommended Practice for Interconnecting Distributed Resources
[B22] IEEE Std 1547.7™, IEEE Guide for Conducting Distribution Impact Studies for Distributed
Resource Interconnection.
[B23] IEEE Std 2030®, IEEE Guide for Smart Grid Interoperability of Energy Technology and
Information Technology Operation with the Electric Power System (EPS), End-Use Applications,
and‖Loads.‖*B24+‖IEEE‖Std‖C37.102™,‖IEEE‖Guide‖for‖AC‖Generator‖Protection.
[B25] IEEE Std C57.12.44-2000™, IEEE Standard Requirements for Secondary Network Protectors.
[B26] NERC Distributed Energy Resources Task Force Report, Distributed Energy Resources:
Connection, Modeling, and Reliability Considerations. North American Electric Reliability Corporation
http://www.nerc.com/comm/Other/essntlrlbltysrvcstskfrcDL/Distributed_Energy_Resources_Report
.pdf.
[B27] NERC PRC-024-2, Standard PRC-024-2 Generator Frequency and Voltage Protective Relay
Settings. 133
133 NERC publications are available from the North American Reliability Corporation (http://www.nerc.com/).
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
[B28] NERC Report, 1,200 MW Fault Induced Solar Photovoltaic Resource Interruption Disturbance
Report. Southern California 8/16/2016 Event. North American Electric Reliability Corporation (NERC),
Photovoltaic-Resource-Interruption-Disturbance-Report.aspx.
[B29] NERC Variable Generation Task Force Report, Performance of Distributed Energy Resources
During and After System Disturbance. Voltage and Frequency Ride-Through Requirements. North
http://www.nerc.com/pa/RAPA/ra/Reliability%20Assessments%20DL/IVGTF17_PC_FinalDraft_Dec
emb er_clean.pdf.
[B30] NERC Special Report, Potential Bulk System Reliability Impacts of Distributed Resources. North
https://www.nerc.com/pa/RAPA/ra/Reliability%20Assessments%20DL/IVGTF_TF-1-8_Reliability-
Impact-Distributed-Resources_Final
Draft_2011%20(2).pdf#search=Reliability%20Impacts%20of%20Distributed%20Resources%2E.
[B32] NFPA 110, Standard for Emergency and Standby Power Systems. [B33] NISTIR 7628,
[B14] UL 1741, Inverters, Converters, and Controllers for Use in Independent Power Systems.
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
Annex B
(informative)
B.1 Introduction
Energy Resources (DER) based on attributes such as technology, application purpose, power
generation variability, and the specific characteristics of the point of common coupling with the Area
EPS.
As proposed in the IEEE P1547 response to FERC NOPR RM16-8 submitted by the IEEE Standards
Association in May 2016 [B6], the criteria for assignment of DER performance categories outlined in
for specific ride through requirements as required from small generating facilities per FERC Order
828 [B7].
B.2 Background
Rapidly increasing penetration of DER in the electric power system has driven the need for a limited
set of specific DER performance characteristics in this standard, particu larly with regard to the
following:
― Participation of the DER in the voltage and reactive power management of the Area EPS
(Clause 5).
power system security and Area EPS power quality (Clause 6 and Clause 7).
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
The inherent abilities of various DER types to achieve these performance attributes differ. In
situations where DER penetration is high, basic levels of performance that can be readily achieved
by all DER technologies have been deemed insufficient to meet existing bulk system reliability
needs, or to address more localized Area EPS power quality issues. 134 On the other hand,
universally requiring high levels of performance that are sufficient to meet BPS reliability and power
quality needs in all reasonable situations would, in practice, exclude certain types of DER from
Often, the DER technologies that would tend to be excluded by uniform minimum performance
standards provide unique societal benefits that cannot be provided by technologies that are more
using synchronous generators. Synchronous generators are inherently limited in their ability to
remain connected to the Area EPS during low-voltage (typically fault) events of extended
duration. 135 While synchronous generators possess this inherent electrical limitation, they provide
additional benefits such as increased system inertia, dispatchable spinning reserve in most typical
synchronous generator applications, and other non -electrical and societal benefits. There are a
number of DER applications having positive environmental, energy efficiency, or public safety
benefits where synchronous generators are the only practical choice. Examples include combined
heat and power applications, conversion of waste methane gas, and backup power to critical
facilities.
134 This annex intentionally uses qualitative DER penetration levels qualifiers. The impact of DER on frequency and voltage
performanc e of the interconnections and the regional power systems differs significantly and it remains in the responsibility of an
AGIR to quantify impactful DER penetration levels.
135 S ynchronous operation depends on a balance of mechanical power from the prime mover and electrical power to the load (or
grid). During a low-voltage event, the electrical power delivered to the Area EPS is inherently reduced, creating a power imbalanc e
that ac c elerates the rotational speed of the generator. If that imbalance is too great, or persists too long, the machine will lose
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
B.3 Normal and abnormal performance category standar d approach
B.3.1 General
through technology-specific standards. This approach has been intentionally avoided in the
technology of DER simply because it can provide the capability, at a cost, while relieving
other technologies of that burden due to the infeasibility to meet the requirement. As a
matter of policy, IEEE standards should remain technology-neutral where possible, and
technologies may evolve. For example, doubly fed generators, commonly used in wind
turbines, behave in some situations like rotating generators and in other situations like
power-electronic inverters.
primary energy source as much as the power conversion device (i.e., generator or inverter).
Tradeoffs between electrical performance limitations and the wider societal benefits offered by a
particular DER technology or application type can be made. However, evaluation of such non-
electrical factors is outside the scope of this IEEE standard. Therefore, this standard defines
performance and capability categories to which DER equipment and systems can be designed and
tested. The discretion of how to apply the categories to specific technologies, application purposes,
and Area EPS point of common coupling characteristics is left to the AGIR.
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
Figure B.1 gives a high-level overview of the performance-based category approach, which is
summarized as follows:
― The AGIR, which could be state regulators, bulk power system operators, or the Area EPS
operator would perform a DER impact assessment based on anticipated DER deployment
for the future. This assessment would consider technical conditions such as fut ure DER
penetration levels, DER power output variability, distribution system characteristics, e.g.,
protection, as well as bulk system characteristics, e.g., power reserves or future system
inertia. It could also consider non-technical issues such as DER use cases and the broader
impacts of DER on the environment, emissions, and sustainability. This analysis could be a
starting point for a stakeholder process, initiated and managed by the AGIR, with the
ultimate goal of assigning DER performance categories to specific DER (technology) types
analyze the costs associated with meeting certain performance categories for their
products. They would also analyze their market segments, based on the category
assignment of AGIRs, and ultimately make decisions on how to design their products.
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
(New)
For the application of the standard, the following sets of performance categories are used:
― Categories A and B for voltage regulation performance and reactive power capability
requirements (Clause 5)
The performance and capability category levels in Clause 5 and Clause 6 are not inherently tied to
each other. Keeping categories for different performance requirements sets de-linked from each
other gives the AGIR flexibility to consider the particular characteristics of the DER interconnection.
For example, the AGIR may require less demanding bulk system issues-related requirements
(Category I for disturbance ride-through) while still requiring more demanding distribution system
issues-related requirements (Category B for voltage regulation) in justified cases. However , for
consistency in the levels of performance and capability, it is strongly recommended to pair Category
I with Category A, and to pair Category II and Category III with Category B.
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
The bases and intended purposes for the performance categories defined in this standard are
B.3.2.1 General
Different characteristics and capabilities for response to voltage variations within the normal
operating range are specified in certain parts of Clause 5 for performance Category A, and Category
B DER. Under mutual agreement between Area EPS operator and DER operator, requirements other
B.3.2.2 Category A
Category A covers minimum performance capabilities needed for Area EPS voltage regulation and
are reasonably attainable by all state-of-the-art DER technologies. This level of performance is
deemed adequate for applications where the DER penetration in the distribution system is lower,
and where the DER power output is not subject to frequent large variations.
B.3.2.3 Category B
Category B covers all requirements within Category A and specifies supplemental capabilities
needed to adequately integrate the DER in local Area EPS where the DER penetration is higher or
B.3.3.1 Category I
Category I is based on minimal bulk power system (BPS) reliability needs and is reasonably attainable
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
The disturbance ride-through requirements for Category I are derived from the German Association
of Energy and Water Industries (BDEW [B2]) standard for medium voltage synchronous generators
and is one of the most widely applied standards in Europe. Many synchronous generator
manufacturers are currently designing products to meet the requirements of this standard.
Category I disturbance ride-through performance, however, is not consistent with the reliability
standards imposed on bulk power system generation resources. High penetrations of DER having only
Category I capabilities could be detrimental to bulk power system reliability, but limited penetration
of this category would not have a material negative impact. It should be noted that penetration, with
regard to bulk power system reliability impacts, should be measured on a regional or bulk system-
wide136 basis, and local distribution system penetration levels are not typically of particular
relevance.
B.3.3.2 Category II
Category II performance covers all BPS reliability needs and coordinates with the existing BPS
reliability standard, NERC PRC-024-2 [B26], developed to avoid adverse tripping of bulk system
generators during system disturbances. Additional voltage ride-through capability is specified for
DERs, beyond mandatory voltage ride-through defined by NERC PRC-024-2 [B26], to account for
the potential for fault-induced delayed voltage recovery on the distribution system, due to
Category III provides the highest disturbance ride-through capabilities, intended to address
integration issues such as power quality and system overloads caused by DER tripping in local A rea
EPS that have very high levels of DER penetration. This category also provides increased bulk power
system security by further reducing the potential loss of DER during bulk system events. These
requirements are based on the California Rule 21 [B4] Smart Inverter requirements.
136 S ync hronous interconnections, such as the Eastern Interconnection, ERCOT, WECC, are examples of bulk systems in this
c ontext.
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
B.4 Performance category assignment
B.4.1 General
Prior to assignment of categories, the needs of th e bulk system on a wide basis and regional basis, as
well as the local Area EPS, possibly down to feeder level, should be considered.
Before performance level categories can be assigned, a systematic categorization of DER types
should be devised. The following list of DER attributes that should be considered is non -exhaustive:
― Primary power source, such as solar, biogas, fossil fuel, hydro, wind, energy storage
device, etc.
― Prime mover or type of primary energy source conversion, such as reciprocating engine,
― DER application purpose, such as combined heat and power (cogeneration), merchant
power generation, backup generation for critical facilities, retail customer self-supply,
― Factors related to the point of common coupling into the Area EPS, such as high-
― Other attributes.
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
The AGIR should identify DER type groupings that consider the previous attributes and any other
attributes that may be deemed appropriate. A full matrix of type groupings that considers separately
each and every one of the attributes above would be unwieldy and impractical to administer.
Therefore, discretion should be applied to combine attributes in a meaningful way to reduce the
number of DER types to a manageable level, while also providing adequate means to discriminately
apply the performance category assignments in a way that balances total societal benefits and
impacts.
To deal with power quality issues caused by increasing DER penetration, especially of variable-
generation DER, the majority of the DER should have Category B performance. However, DER
connected to a PCC that is relatively close to the substation as well as non -variable-generation DER
may have less impact on the distribution system voltage than DER that are connected close to the
end of a feeder or DER with power output that is subject to frequent large variations. In those cases,
When making the assignment of performance categories to DER types, it is recommended that the
― Is the power output of the DER constant and not subject to frequent large variations?
― Is the rating of the DER, relative to the distribution system short-circuit strength at the
point of common coupling, small such that the DER does not have significant impact on
distribution voltage?
― Is the projected penetration of all DER types allowed to interconnect with Category A
capability and performance relatively small compared to the total load level on the
particular feeder?
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
Depending on the answers to these questions, the assignment of performance Category A to the
particular DER type grouping may be appropriate from the standpoint of power quality issues
caused by increasing DER penetration. In certain cases, however, the AGIR might consider imposing
higher levels of voltage regulation performance and reactive power capability requirements, but
Particularly in areas of high DER penetration and where the predominate DER types involve
inherent power output variability (e.g., solar PV), requirements for DER to meet Category B
The categorization of DER types and the assignment of voltage regulation performance and reactive
power capability categories based on criteria that are at least partially subjective, is complex. To
facilitate this process, an example decision tree for the performance category assignment is provided
in Figure B.2. While this figure is an example, it provides a recommended starting point for
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
(New)
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
B.4.3.3 Assignment of abnormal performance categories (Clause 6)
To preserve the security of the bulk power system, the majority of DER should have Category II
disturbance ride-through performance. However, there are notable exceptions when disturbance
ride-through performance Category I and III should be applied instead. When the total societal
benefits are evaluated, it is reasonable to interconnect a limited amount of DER capacity that is
When making the assignment of performance categories to DER types, it is recommended that the
― Is it impractical for the given DER type to be designed to meet Category II or III
performance?
― Is there a societal benefit provided by the DER type that offsets the potential adverse
― Is the projected penetration of all DER types allowed to interconnect with Category I
performance relatively small compared to the total load level in the region?
NOTE—Bulk electrical system reliability impacts are related to the total amount of DER in a
relatively large region, and penetration levels at individual distribution systems or circuits are not of
particular relevance.
If‖ the‖ answer‖ to‖ each‖ of‖ the‖ previous‖ is‖ ‚yes,‛‖ then‖ assignment‖ of‖ performance‖ Category‖ I‖ to‖ the‖
particular DER type grouping is appropriate from the standpoint of bulk power system reliability. In
all other cases, the AGIR should assign performance Category II or might consider imposing even
higher levels of performance requirements such as Category III, but may also consider the overall
In areas of particularly high DER penetration and where nuisance tripping of DER could cause
voltage collapse or system overloads, requirements for DER to meet Category III performance may
be necessary.
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
Even within such high-penetration regions, it may be reasonable to allow a limited amount of DER
with Category I or II performance capabilities that provide unique benefits. An example could be a
bio-gas generator that provides consistent power output in a distribution system that also ha s very
The categorization of DER types and the assignment of disturbance ride-through performance
categories based on criteria that are at least partially subjective, is complex. To facilitate this process,
an example performance category assignment grid is provided in Table B.1. While this table is an
example, it provides a recommended starting point for determining DER attribute groupings and
other‛‖ application‖ purpose‖ (i.e.,‖ column)‖ to‖ accommodate‖ applications‖ not‖ foreseen‖ or‖ otherwise‖
addressed.
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
Table B.1—Example abnormal performance category assignment grid 137
(New)
aMerchant generation in this table is intended to characterize DER facilities installed for the express
purpose of exporting power, and is not intended to imply only FERC-jurisdictional generation or
bOnly applies to critical backup generation interconnected to the Area EPS for the purposes of
periodic testing. If backup generation is also used for merchant generation or other purposes, the
cCategory III should be required where DER penetration on a distribution feeder exceeds [%
137 The purpose of this table is to provide a reco mmended starting point for determining DER attribute groupings and performance
c ategory assignments. The table is not intended to suggest any equipment capability.
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
Annex C
(informative)
C.1 Introduction
Figure C.1, from IEEE Std 1547.4-2011 [B20], shows examples of different kinds of islands
incorporating DER. The intentional island interconnection device (IIID) is used to create the island, as
described in 6.2 of IEEE Std 1547.4-2011 [B20]. For example, CB3 may be opened to create the
‚Circuit‖Island‛‖in‖Figure‖C.1,‖and‖there‖are‖five‖DERs‖within‖the‖‚Circuit‖Island‛.‖Those‖five‖DERs‖
may have five individual PCCs, or less than five through aggregation. None of the five DER
breakers can serve as the IIID in this example. On the other hand, each of those DERs could
participate in more than one of the example islands shown. Furthermore, whenever the substation
feed is available those DERs can also participate in the non -island mode.
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
(New)
This standard is concerned only with the PCC interconnection. The same reasoning applies with
example intentional islands including microgrids; the intentional island or microgrid interface will
Furthermore, this standard is not concerned with intentional island or microgrids that operate only as
a‖ Local‖ EPS.‖ For‖ example,‖ the‖ ‚Facility‖ Island‛‖ in‖ Figure‖ C.1‖ is‖ excluded‖ from‖ the‖ scope‖ of‖ this‖
standard, except when CB1 closes for the local DER to participate in the ‚Circuit Island,‛ the
‚Substation Bus‖Island,‛‖or‖the‖‚Substation‖Island.‛
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
C.2 Connecting DER not designed for intentional island or microgrid
operation
The following examples outline intentional island or microgrid implementations where a DER not
designed for intentional island or microgrid operation may be allowed to participate by the intentional
― A generator is able to provide the maximum steady-state load in the intentional island or
microgrid island (MI), and has the speed of response to buffer the power transients of the
― Energy storage is implemented to buffer the power transients of the DER not designed for
intentional island or microgrid operation.
― A device has been fitted that disconnects the DER, not designed for intentional island or
These examples are provided for guidance only; it is the responsibility of the IIO or MO to ensure
the desired quality of service in the intentional island or microgrid.
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
Annex D
(informative)
D.1 Introduction
This annex provides additional informative information about the interoperability and
D.2.1 General
This subclause outlines the general principles used to guide the interoperability and
communications content.
D.2.2 Scope
The approach taken for interoperability an d communication support in this standard is to specify
only the DER functional requirements for communication at the DER interface. It is considered
beyond the scope of this standard to specify any requirements related to network technologies that
The interoperability and communication content in this standard is based on the functionality in the
standard that specifies settings with a range of allowable settings. The purpose of the local DER
communication interface is to allow all the settings information to be read and written through the
interface providing remote adjustability. Monitoring of some measurement and status information is
also specified.
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
D.2.3 Standardized local DER communication interface
A set of protocols have been identified in the normative text that satisfy the requirement for
communication support. Each option provides different capabilities inherent in the stack. It is
intended that the standardized communication capability of a DER be the basis for a more
comprehensive communication solution based on the requirements of a DER installation and other
appropriate standards.
It is not mandated that the standardized local DER communication interface be used for any DER
installation. Proprietary communication interfaces may be developed and used to interface to a DER
but the standardized local DER communication interface shall always be an available option. The intent
Figure D.1 and Figure D.2 show examples of the use of standardized and custom interfaces. In both
cases, the IEEE 1547 interface option shall be present. The examples also illustrate the interface that
is addressed by this standard and the interfaces that are out of scope.
(New)
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
(New)
In many cases, more than one protocol stack is used to transfer the information between the DER
and the managing entity. It is important that information models in each protocol stack be
harmonized to maintain the correct meaning of the information being transferred. This
harmonization can be facilitated by using industry standard ways of representing certain types of
information. The use of piecewise linear curves is an example of information representation that is
supported across different protocol information models. This consideration has influenced the
D.3.1 General
This subclause provides additional detail about the specific protocols that are identified as a
standardized interface and other relevant protocols that may be additionally supported.
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
D.3.2 IEEE Std 2030.5 (SEP2)
IEEE Std 2030.5 provides support for monitoring and control of DER devices. The standard defines
the mechanisms for exchanging application messages, the exact messages exchanged including error
messages, and the security features used to protect the application messages.
IEEE Std 1815 is used to interface to DER devices, often used by utility supervisory control and data
acquisition (SCADA) systems. Several specific IEEE 1815 application notes have been developed to
The SunSpec Alliance specifies standard Modbus-based information models to support monitoring
IEC 61850-7-420 [B8], specifies the information models to support monitoring and control of DER
devices. IEC 61850-7-420 [B8] provides guidelines on the DER functions. IEC 61850-8-2 [B10] defines
a standardized protocol based on Internet protocols, and IEC TR 61850-80-3 [B11] provides guidance
The security requirements associated with DER entail both local physical access and remote network
access. The level of security required is proportional to the risk associated with a breach of the
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
The risk profile evaluation associated with differen t use cases can involve many factors such as the
This standard does not address the requirements associated with physical security of DER systems.
DER devices often provide front panels to allow interaction by an operator with the DER. This
standard does not address the requirements associated with front panel behavior or security.
The networks used to connect DER to remote managing entities, and the cyber security requirements
of these networks, are out of scope of this standard. DER integration networks will likely be of many
kinds and technologies and will use a variety of cyber security mechanisms that evolve over the life
of the DER. For this reason, a modular approach has been taken in this standard, excluding the DER
network requirements from scope and only specifying the local DER communication interface.
D.4.5.1 General
When a DER is capable of exchanging information through a local DER communication interface,
consideration should be given to protecting access to DER through that interface. A DER is just like
any other system where a malicious or uninformed actor can have an adverse effect on the system.
This standard does not mandate any specific cyber security requirements at the DER interface for at
least the following reasons: scope of this standard, scope and complexity of cyber security
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
An additional set of standards may be required to properly address the cyber -physical security
requirements of system(s) containing DER and possible requirements specific to the local DER
communication interface.
D.4.5.2 Scope
Cyber security is a system-wide issue requiring a system-wide solution. This standard specifies the
base functionality of a DER including the capability of exchanging specific information over a local
DER communication interface. This standard cannot correctly address system level issues and should
There are many different networking and security scenarios in which a DER may be deployed.
The organization responsible for maintaining the reliability and security of the communications path
to the DER must also be able to perform regular maintenance, upgrades, and changes to the network
It is possible to couple a secure networking device with a DER providing an open interface to
provide a secure communications path to the DER. Such secure networking devices are common in
the utility industry for critical infrastructure integration such as voltage regulators, switches, and
capacitors. These networking devices can be designed such that access to the open interface at the
DER does not allow access to other devices connected on the same network.
It is important for low-cost DER to be able to be coupled with different networking technologies that
may change over the life of the DER. Each networking technology may have different security
Non-standardized security features implemented in a DER may make it harder to secure the overall
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
Providing advanced networks for secure DER integration is a science and specialization of its own
and DER manufacturers may or may not have this expertise or desire to enter the networking
business.
A single network may integrate many different DER types, models, and brands and yet the network
DER system software is often a monolithic implementation that does not facilitate tracking and
DER manufacturers may stop support for a model or go out of business making it difficult or
D.4.5.4 Testability
is one of the guiding principles for determining what is in scope for the normative content of this
standard.
It is difficult to specify meaningful test procedures for general non -standardized requirements.
What types of protections can be provided to assist in preventing unauthorized use of a local DER
One option is to have the local DER communication interface disabled by default and to only enable it
through a password-protected front panel interface. This would prohibit access through the local
DER communication interface until a secure network device is attached. The nature of the physical
security and properties of the connection is out of scope for this specification.
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
D.5 Related standards
IEC 62351-12, Power Systems Management and Associated Information Exchange—Data and
IEEE Std 1547.2 [B18] provides technical background and application details to support the
IEEE Std 1547.2 [B18] facilitates the use of IEEE Std 1547 by characterizing the various forms of
distributed resource technologies and the associated interconnection issues. Additionally, the
background and rationale of the technical requirements are discussed in terms of the operation of
the distributed resource interconnection with the electric power system. Presented in the document
are technical descriptions and schematics, applications guidance, and interconnection examples to
IEEE Std 1547.3 [B19] provides guidelines for monitoring, information exchange, and control for
distributed resources (DR) interconnected with electric power systems (EPS). The 2007 version
requires an update to address current security issues and capabilities that affect h igh penetrations of
DER.
138 At the time of the publication of this standard, IEEE S td 1547.2-2008 is the most recent version of IEEE S td 1547.2 [B18]. This
version, however, is inconsistent with the requirements of this version of IEEE S td 1547 and has limited usefulness.
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
This document facilitates the interoperability of one or more distributed resources interconnected
with electric power systems. It describes functionality, parameters, and methodologies for
monitoring, information exchange, and control for the interconnected distributed resources with (or
associated with) electric power systems. Distributed resources include systems in the areas of fuel
cells, photovoltaics, wind turbines, microturbines, other distributed generators, and distributed
IEEE Std 2030 [B23] is an umbrella standard that provides standardized, transparent and systems
level guidelines for interoperability between Power, Communications, and Information Systems.
It was the first standard to be created jointly by the three IEEE Societies: Power and Energy Society,
It‖ defines‖ the‖ SmartGrid‖ Interoperability‖ Reference‖ Model™‖ (SGIRM™),‖ which‖ organizes‖ all‖ the‖
architecture perspectives (IAPs). The three IAPs primarily relate to logical, functional considerations
of power systems, communications interfaces, and IT data flows for smart grid interoperability:
― Power systems IAP (PS-IAP): The emphasis of the power system perspective is the
applications in the context of the Smart Grid. The perspective includes communication
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
― Information technology IAP (IT-IAP): The emphasis of the information technology
perspective is the control of processes and data management flow. The perspective
includes technologies that store, process, manage, and control the secure information
data flow.
NISTIR 7628 [B33], Guidelines for Smart Grid Cybersecurity, provides additional guidelines for
smart grid cyber security that may be applicable to DER deployment. 139
139 NIS T publications are available from the National Institute of S tandards and Technology (https://www.nist.gov/).
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
Annex E
(informative)
E.1 Introduction
This annex is informative. It is intended to help readers understand the requirements in 6.4.2.5 by
Note that this standard allows an unlimited number of multiple consecutive voltage disturbances
that‖ DER‖are‖required‖to‖ride‖through‖within‖a‖single‖disturbance‖‚set,‛‖as‖long‖as‖the‖cumulative‖
duration of all the disturbances in this set does not exceed the maximum required ride-through
duration for the respective voltage disturbance severity (and performance category). The standard
also requires that DER ride through several of these sets occurring consecutively within a certain
time frame. Each voltage disturbance set may correlate to voltage disturbances during a reclosing for
a particular sustained fault, intermittent fault activity, or oscillatory voltage triggered by response
distinct sets may correlate to several unrelated faults occurring within a short time frame or
subsequent reclosing event where the reclosing delay is greater than the time separating sets, as
would be typical for transmission system faults. The specification for the consecutive voltage
disturbance ride-through requirements were derived from typical transmission and primary
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
E.2 Faults, fault protection, and reclosing
The most typical faults on transmission, sub-transmission, and primary distribution power systems
system phase(s) and a neutral or a grounded part. These short -circuits—unintended, low-
impedance, shunt connections— appear in many forms. At the EHV (greater than 300 kV)
transmission level comprising the backbone of the bulk power system, common causes of faults are
insulator contamination, insulator physical failures, switching surges, supporting structure failures,
wildfires, and operational errors (e.g., failure to remove personal protective ground jumpers prior to
re-energization). Lightning is rarely a cause for EHV line faults, but HV transmission lines do
experience lightning-related faults. At the primary distribution and sub-transmission voltage levels
the common causes of faults are direct lightning strikes or lightning-induced flashovers, tree
branches falling across energized conductors, animals bridging the gap between energized
conductors and the grounded parts they are standing on, failures of insulating components or other
equipment failures.
Whatever the form of these short-circuits, they have the following two significant effects:
— They cause a disturbance in the normal voltage levels, because they change the
sources to loads and the normally high-impedance shunt connections of those loads
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
The high-magnitude currents resulting from a short-circuit fault usually are orders of magnitude
above the current-carrying capability of power system equipment, and must be stopped quickly
before significant damage is done. Also, the resulting collapse of voltage due to transmission faults
eliminates or greatly reduces the ability to transmit power, thus threatening the stability of the bulk
power system. The use of current differential or impedance detection relaying represents the vast
majority of protection employed on transmission systems and in substations against damage from
these fault currents. At the EHV transmission level, more sophisticated communication-based
protection schemes are used to provide greater detection speed, reliability, selectivity, and security.
distribution circuits between sources and loads, since these are the paths that the high -magnitude
current takes directly to a fault if one should occur. These types of protection react to abnormal
current or impedance conditions, and the response is usually to cause an opening of the series path
to the fault, interrupting the fault current (e.g., through the tripping of a breaker or the operation of
a fuse). However, depending on the location of the faulted section, this action can also disconnect
the normal flow of power through the power system to the loads beyond the open -circuit that is
created.
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
Utility engineers attempt to apply fault protection devices and relaying to maximize the reliability
and speed of detecting and interrupting faults (dependability) while minimizing the number of
system elements or customers also interrupted (selectivity) and the chances of an unint ended
operation (security). This is usually achieved by applying fault protection at as many locations as
possible, such as at every transmission line terminal or distribution tap, but applying it in such a
way that only the protection for the faulted section operates first. This results in having to
coordinate the operation of many protection devices in series along fault current pathways,
directional discrimination, and by selecting different response time characteristics where protection
zones overlap. The response time characteristics determine the speed at which that protection
responds to faults in different protection zones or at different levels of current. By applying proper
choices of fault protection with coordinated response time characteristics, a reasonable degree of
dependability versus security can be achieved between multiple devices along the fault current
pathway.
All sources connected on a section of the power system that suffers a fault are expected to cease to
energize and trip from the rest of the power system by the operation of whatever fault protection is
applied. This includes DER on the faulted section, either through their own detection and response
to the fault, or through their detection of the resulting unintended island resulting from the
operation of the power system fault protection. The DER response is covered in the mandatory
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
While the path of the high-magnitude current caused by a short-circuit fault is restricted to the series
paths between the sources and the fault, the voltage disturbances (e.g., voltage dips) caused by a
short-circuit fault will be experienced by all devices or equipment connected in close proximity to
the fault, 140 even if not on the faulted section. Examples include wide-area voltage disturbances
caused by faults on transmission systems, and localized voltage disturbances caused by faults on
distribution systems. The extent of the system that can experience these disturbances can range from
just the small nearby portion of a single distribution circuit affected by a fault on an adjacent section
of the circuit, to an entire interstate region affected by a high -voltage transmission fault. In these
cases, if the voltage disturbance is not severe enough or does not last long enough, DER on these
portions‖of‖the‖system‖are‖required‖to‖‚ride-through‛‖these‖disturbances‖and‖remain‖in‖operation‖as‖
described in 6.4.2.
An additional aspect of fault protection on utility power systems is that many short-circuit faults are
temporary. Most typically, temporary fault is caused by a flashover across an insulator or open -air
gap that does no permanent damage, and will cease to exist once the current has been interrupted to
clear the resulting arc. Such flashovers are typically caused by transient overvoltages related to
lightning strikes or (at the EHV transmission level) switching transients. At the distribution level,
temporary faults are also caused by a tree branch or an animal that falls off or is blasted clear after
making initial contact with energized conductors. Because temporary faults often make up a sizeable
share of the types of faults that occur on power systems, attempts are often made to quickly re-
energize the disconnected portion of the power system once the interruption by fault protection has
taken place. This practice is known as automatic reclosing. It is commonly performed by reclosing
relays controlling circuit breakers or, commonly on distribution systems, by reclosers (devices
140 This proximity is in an electrical context relative to the impedance network around the location of the fault, rather than a
geographic al c ontext.
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
Reclosing is the application of a finite number of automatic closures (reclosures) of the breaker or
recloser in a brief window of time to re-energize the faulted section of the system. If the fault was
temporary and no longer exists upon re-energization, then the fault protection has nothing to
respond to and electric service or transmission path is restored with no further action. If the fault is
persistent or re-ignites, the fault protection will cause the breaker or recloser to trip again. This
tripping and reclosing will happen as many times as the number of selected reclosing attempts
applied for that device. If the device continues to trip beyond the number of selected reclosures, it
Faults at the transmission level, followed by unsuccessful reclosing attempts, appear as multiple
consecutive undervoltage events. (In some situations, the system response to fault clearing may also
result in multiple periods of overvoltage as well.) These consecutive voltage disturban ces may affect
There are two significant consequences to DER from the application of automatic reclosing at the
distribution level. First, for situations where the DER trips due to a fault on the section to which they
are connected, that tripping shall occur prior to the first reclosing attempt to re-energize the section.
Second, for situations where DER rides through a voltage disturbance due to a fault on a different
section, the DER shall ride through a series of multiple consecutive voltage disturbances due to the
re-appearance of that fault upon each reclosure in the selected reclosing sequence.
The series of multiple consecutive voltage disturbance experienced by the DER, whether from
voltages during the times that the fault is present, separated by periods of relatively normal voltages
during the times that the fault is disconnected or not active. Examples of what the DER may
experience are illustrated in Figure E.1, Figure E.2, and Figure E.3 for three different scenarios. 141
141 Note that Figure E.1, Figure E.2, and Figure E.3 give only three examples of what can be a whole spectrum of possibilities of
multiple c onsecutive voltage disturbance severities, durations, number of occurrences, and the timing between them.
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
(New)
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
(New)
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
(New)
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
In the examples in Figure E.1, Figure E.2, and Figure E.3, note the differences in the severity and
durations of the abnormal voltages (periods during active fault) and the differences in the number
and duration of periods of relatively normal voltages in between (periods where fault is not active).
The differences in the severity of the abnormal voltages experienced at a particular DER are due to
the impedance of the fault that is occurring, the relative location of the fault, the DER, and other
sources on the electric system, and the impedance matrix of the entire power system network.
Obviously, these conditions are different for each fault that may occur, and for each DER
experiencing the disturbances associated with any of those faults. The differences in the durations of
the abnormal voltages are due to the different operating times of the applied fault protection in
response to the conditions to which it is exposed. For faults on transmission systems and within
substations, the typical current differential, directional comparison, and impedance (distance)
protection schemes have high-speed or short, fixed, incremental response times, usually of less than
one second and rarely longer than two seconds, and largely independent of the fault current
magnitude (but rather the protection zone in which he fault occurs). For simpler time-overcurrent
protection, different fault durations are caused not only by different time-current response selections
at different protection installations, but also because different levels of fault current will exist for
different faults (and thus different response times at the same installation), again due to different
fault impedances and system impedances to different fault locations. Finally, the number and
duration of periods of relatively normal voltages are due to the selected number of reclosing
attempts and the selected reclosing interval times (open times) between each reclosure.
Where automatic reclosing is applied, common selections for a reclosing sequence include 1, 2, or 3
Different reclosing equipment may offer even more possible reclosing attempts, but the selection of
more than three attempts is not as common. A wide range of reclosing interval times (open times) is
usually‖ available‖ for‖ selection,‖ from‖ an‖ ‚instantaneous‛‖ reclosure on the first attempt to mere
reclosing‖ delays‖ are‖ typically‖ 30‖ s‖ or‖ longer‖ except‖ where‖ ‚high‖ speed‛‖ reclosing‖ is‖ used‖ with‖ a‖
delay of approximately 0.5 s. Delays longer than 1 s but less than 30 s are not typically used at the
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
At the distribution level, not all reclosing devices have selectable reclosing interval times,
hydraulically controlled reclosers being a prime example. Where reclosing interval times are
selectable, common selections are approxomately 0.2 s to 30 s, although there is much more variation
here depending on type of power system (e.g., transmission, distribution, in cross-country right-of-
way or along public streets), types of faults typically experienced on that system (e.g., lightning,
Another scenario of power system faults that can occur causing multiple consecutive voltage
disturbances is when several different faults occur at different locations within an area and within a
relatively short window of time. Rather than resulting from multiple reclosures into the same fault,
this scenario of multiple different faults may be triggered by a large weather-related event hitting an
area, such as numerous lightning strikes during a thunderstorm, severe wind events including
A third scenario of power system faults that can occur causing multiple consecutive voltage
disturbances is an intermittent arcing fault. This type of ‚sputtering‛ fault may arc and extinguish
itself multiple times without causing any fault protection to operate, either due to high fault
impedance resulting in low fault currents that go undetected, or due to relatively rapid self-
extinguishing before the fault protection has had enough time to respond. In many cases, this type of
fault can continue in this way for a long time, sometimes burning clear and other times eventually
evolving into a sustained short-circuit fault. This type of fault may occur at the distribution voltage
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
E.5 Voltage oscillations
The disruption of power flow from generation sources to loads caused by transmission faults cause
the synchronous generators in the system to accelerate or decelerate such that their electrical angle
with respect to an ideal fundamental-frequency reference is shifted from its pre-fault steady-state
value. When the fault is cleared, the generator angles swing to the original value, if the system
configuration remains unchanged, or to a new steady-state value if lines, loads, or sources are
removed in the process of clearing the fault. Similar to a pendulum displaced from its resting
position, the angles do not go to the post-fault values and stop, but rather oscillate with a period of a
fraction of a second to several seconds. The resulting system oscillations cause the magnitude of the
voltage throughout the system to be modulated at this low frequency. Modulation of distribution
substation voltage by the dynamic behavior of the transmission system is reflected down to the
voltages experienced by DER connected to the distribution system. As a result, DER PCC voltage
magnitudes will tend to oscillate after the clearing of a transmission fault, and these oscillations may
cause the voltage to repeatedly transition between the normal and abnormal (potentially including
both high- and low-voltage periods) a number of times over a period of a number of seconds. These
oscillations typically will dampen out within ten seconds. From the DER perspective, the transitions
from normal to abnormal voltage might appear as multiple disturbances. This standard addresses
this by specifying ride-through on a cumulative time duration basis. A given dynamic event should
be all within one disturbance set, and the DER must ride through up to the total duration specified
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
Annex F
(informative)
The requirements of this standard apply either at the PCC or the PoC, depending on the aggregate
nameplate DER rating and the average annual load in the Local EPS. Where requirements apply at
the PoC, equipment type testing will be sufficient to verify conformance with most requirements, in
most cases. However, for DER facilities, i.e., Local EPS that are large enough so that requirements
apply at the PCC, equipment testing should be supplemented by additional compliance verification
measures such as the DER evaluation and further commissioning tests defined in Clause 11. The
same holds for any DER that use supplemental DER devices to meet the requirements of this
standard. The concept of combined type test and DER evaluation is summarized in Table F.1.
(New)
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
DERs should meet the general requirements for full and partial conformance testing and verification
a) For DER that meet requirements at the PoC per 4.2 and that are fully compliant with all
requirements of this standard without the use of a supplemental DER device, DER should
be type tested. A DER evaluation and commissioning test should not be required for
test. DER that are type tested with the use of a supplemental device are permitted as well.
b) For DER that meet requirements at the PoC per 4.2 and that are partially compliant with
the requirements of this standard and that comply with all requirements of this standard
in combination with supplemental DER device(s), DER should be type tested and a DER
c) For DER that meet requirements at the PCC per 4.2, for both full and partial compliance,
DER should be type tested and a DER evaluation and commissioning test should be
performed.
d) Combinations of DER unit(s) and supplemental DER device(s) forming a system that are
type tested as a DER system should not require a DER evaluation or commissioning test
e) In all other situations, a detailed DER evaluation and detailed commissioning test should
be required.
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
(New)
DERs should meet the specific requirements for full and partial conformance testing and verification
as specified in 11.3.2 and 11.3.3 by assignment of test and verification methods to the interconnection
and interoperability requirements of this standard in form of a test matrix (an example of this is
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
(New)
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
Annex G
(informative)
G.1 Introduction
This annex provides additional information about power quality (Clause 7). It outlines the general
principles and approach applied to update PQ requirements for DER in IEEE Std 1547. While there
is growing body of experience related to distributed generation, almost all the previous standards
development for power quality have been related to loads and not generators. A key consideration,
and challenge, in setting PQ requirements for DER is performance dependence on the frequency
response and relative capacity at the PCC. This is particularly true for voltage-related limits like
RVC and flicker depending on the relative capacity of the PCC, and for production of harmonic
currents depending on the harmonic impedance at the PCC. Short -term overvoltage related to the
DER often depends on PCC loading and grounding details. There are potential interactions between
the DER and the grid that may not be easy to predict in a study or remove from the certification
process. Most of the discussions in this annex address these interactions relative to setting power
quality limits.
IEC 61000-4-30:2015 defines RVC as a quick transition in rms voltage occurring between two steady-
state conditions, and during which the rms voltage does not exceed sag/swell thresholds (10% above
or below nominal voltage). Alternatively, IEEE Std 1453-2015 defines RVCs as changes in
fundamental frequency rms voltage over several cycles. Both standards recognize RVC as an event
that may not be captured by either steady-state or flickermeter measurements, yet may need to be
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
On the end-user-side, beyond lighting, incompatibilities can manifest in torque transients on motor
loads. On the utility-side, there have been incompatibilities between DER and distribution operating
equipment such as voltage regulators, and involving reclosures and capacitors. In this context, RVC
is included as a DER requirement. Some causes of rapid voltage changes include start -ups, inrush
currents, and switching operation of equipment such as capacitor banks and transformers. An
(New)
The concern with transformer energizations associated with DER is not one-time events like plant
System planning levels for RVCs are provided in Table G.1 adopted from IEEE Std 1453. The levels
important‖ to‖ note‖ that‖ the‖ ‚system‖ design‖ planning‖ levels‛‖ in‖ this‖ table‖are‖intended‖to‖represent‖
aggregate limits of all sources of RVC at a point of evaluation (PCC or PoC). Since IEEE Std 1547
applies to DER, the most-strict limit of 3%, was adopted, applying a rationale to reserve some of the
system capacity for other fluctuating installations, whether those installations are loads or DER. For
purposes of individual DER performance evaluation, IEEE Std 1547 includes the ΔV% and a ramp
rate that specifies a one-second time period. This individual DER limit is intentionally more specific
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
Table G.1—System design planning level for RVCs (IEEE Std 1453)
(New)
In setting planning limits for aggregate RVC, the application of Table G.1 for screening or studies
has some practical limitations. One limitation is that the DER rapid change performance is not likely
known for inputting into prediction calculations. Various DER RVC performances are not expected
to be documented during certification. For larger plants, it may be good practice to document and
record plant energization, including waveforms, during commissioning. This can be useful if there
Also, related to aggregate RVC limits, some planners will assume a step-voltage change at the PCC
as if all DER connected to an Area EPS simultaneously have a 100% change in output power, from
fully off or fully on. While this worse case is sometimes used in planning, its application to
interconnection decisions is excluded in IEEE Std 1547. The rationale for exclusion is that the likely
reason for all DER to trip simultaneously is in response to a grid event that takes voltage or
frequency beyond ride-thru limits. Since the grid is outside normal operating limits in this case, it is
Other‖ tripping‖ or‖ power‖ change‖ scenarios‖ would‖ likely‖ have‖ less‖ ΔV/V because of diversity. The
number of changes per minute is also not predicable with various cases and sources of RVC.
Therefore, specific design and operating environment of the DER should be considered to determine
expected aggregate performance tests. Unexpected individual DER malfunctions may cause field
problems and will also be difficult to predict in screening or studies. If there is a dispute about cause
and effect, DER or grid, then field measurements and application of IEC/TR 61000-3-7 allocation
142 Users c an also refer to IEEE S td 1453.1 [B16] since it is an adoption of the IEC technical report.
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
G.3 Flicker limits
Flicker is the subjective impression of fluctuating luminance caused by voltage changes over a
period of time, even if individual changes are not observed. Assessment methods for flicker, caused
by highly fluctuating loads such as arc furnaces and welding are described in IEEE Std 1453. These
methods are also defined in IEC/TR 61000-3-7. Included within this IEEE recommend practice is a
table of indicative planning levels of flicker for different voltage levels, Table G.2. These levels are
intended to account for the aggregate of fluctuating installations and are typically the basis for
allocating emission limits to individual facilities using summation laws in the IEC document. Also,
methods are provided to address transfer from HV to MV and between different PCCs. The
allocation of emission limits to individual facilities (denoted as E Pst and E Plt ) are set so that
aggregate effects do not cause overall flicker at any PCC to exceed the adopted planning level.
(New)
Techniques normally used for fluctuating loads are applied in this standard to voltage fluctuations
caused by fluctuating power generation. The limits for an individual DER facility are specified in
7.2.3. Based on the IEC method, allocations of emission limits to a DER are determined as a fraction
of the planning level aggregate allocation. This allocation depends on the agreed capacity of the DER
relative to the total available grid capacity at the point of evaluation. Specific calculations for this
allocation at both MV and HV are provided in the IEC document. If the agreed capacity of the DER
is relatively small compared to the grid capacity at the point of evaluation then a minimum
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
A key concept here, similar to RVC limits, is that IEEE Std 1547 addresses individual flicker limits
and not the aggregate system performance, which is addressed by the recommended planning
levels. Also, it is important to recognize that all these flicker limits have been developed based on
basic 60 W incandescent lamps. Lamps of lower wattage may have more noticeable lumination
changes with the same voltage environment. New types of lighting products generally perform
In setting DER flicker requirements, consideration was given to the probability of producing voltage
fluctuations and the likelihood of flicker complaints based on empirical or field experience to date.
With exceptions, most properly functioning DER are not expected to produce pulsating power
outputs that cause flicker complaints. For example, the range of known wind and solar resource
variations (frequency and rate of change of the input power) have not been sufficient to result in
flicker complaints. Also, other properly functioning DER such as gas-fired IC engines, fuel cells, or
micro-turbines should not be naturally fluctuating sources prone to cause flicker. In these cases,
screening for flicker, or attempting to predict it in a study, are not usually warranted.
On the other hand, certain power conversion technologies, such as particular wind tur bine designs,
have been known to cause flicker. Generally, these characteristics will be apparent either from
interconnect. For example, IEC 61400-21 defines flicker coefficients for certain types of wind turbines
and provides methods to predict (screen or study) for potential flicker based on the grid
characteristics at a PCC.
Despite best practices in processing DER applications, screening, studies, physical interconnection,
and commissioning, unexpected field problems can happen. Flicker measurement (defined in IEC
61000-4-15) and analysis has proven useful in differentiating when a site is not functioning properly
if there are unexpected interactions with the grid. The specifics on how to address field problems,
determine responsibility, and allocate grid capacity are covered in IEC/TR 61000-3-7.
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
G.4 Current distortion limits
In this standard only current distortion limits are defined. The methodology for sett ing current
distortion limits and for distortion measurement are adopted from IEEE Std 519. There are a few
intentional, and notable, differences. The first is a change from total harmonic distortion (THD)
limits, used in 2003, to total rated current distortion (TRD). The reason for this change is to capture
inter-harmonics in the total distortion calculation. This method is described in a footnote in the
normative requirements. The second difference from IEEE Std 519 is regarding the limits on even
harmonics. The technical basis for tighter limits (i.e., 25% of odd harmonic limits) for even
harmonics in IEEE Std 519 was researched. The key concern is the DC offset effect of even harmonics
that have the potential to cause mis-operation of electronic switching by impacting zero crossing and
other control logic. Practically, this DC offset effect is mainly caused by the 2nd harmonic and the
effect of higher order harmonics diminishes rapidly. Additionally, the tighter limits for even
harmonics for the higher order harmonics are found to fall outside the specified accuracy of PQ
meters. Therefore, in this document, the limits for the higher order (8th and higher) harmonics have
been relaxed to be the same as those for corresponding odd harmonics and the limits for the 2nd
harmonic have not been relaxed at all. However, a stepped approach was taken for the for the 4th
and the 6th and they have been relaxed to 50% and 75% of the corresponding odd harmonic limits
respectively. It may be noted that limits for overall distortion have not been relaxed at all to act as
Voltage distortion limits are not defined for the DER and the current distortion limits are intended to
be exclusive of harmonic currents due to harmonic voltage distortion present in the Area EPS
without the DER connected. In the 2003 version of IEEE Std 1547, voltage harmonic tests were
specified as an alternative performance measure, specifically for synchronous generator DER. The
rationale for excluding voltage distortion limits in the case of synchronous generator DER in this
A voltage distortion limit may be defined in the test procedure for synchronous generators.
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
The meaning of voltage distortion limits of DER while operating grid-connected is unclear and
could be misapplied. Defined DER current distortion limits would need to be adjusted for the test.
A very stiff grid may allow significant low-order current harmonic levels for a synchronous
There are application concerns in relieving the DER of responsibility for current and sharing
There are several challenges involved with harmonic compliance testing in the field vs in the lab
Inverter based generation often includes pulse width modulated converters that have switch ing
frequencies of several kHz. It is feasible to anticipate measurable 3 kHz (50 th order) harmonics on
the generated output. Documented cases show harmonics above the 50 th present on inverter based
DER outputs. However, many utility-grade voltage and current sensors will not accurately
reproduce frequency content above 2 kHz. These practical constraints need to be considered for any
field verification as well as the requirement for special equipment adhering to accuracy limits to
monitor an inverter-based site. The practice to accept type and production testing results, and then
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
Because of the challenges, it is difficult to confirm adherence to the higher order distortion limits in
the field. Therefore, it is important to consider not only individual limits but also the TRD limit. The
expectation and intention is that if the individual harmonics and inter -harmonics limits that are
tabulated in Table 26 and Table 27 are met, and the TRD value is met, then obviously the current
distortion ought to be acceptable. In contrast, if a higher order individual limit measures outside the
limit in the field, but the TRD is within limit, consideration should be given to whether the sensor
involved is capable of accurately reproducing the frequency in question.
The presence of background voltage distortion is to be expected. As such, the DER current distortion
performance can be affected by voltage distortion that exists before the installation of the DER. The
current distortion requirements are intended to be written in a manner such that DER will not to be
held responsible for current distortion that results from background voltage distortion.
Most DER appear as a harmonic voltage source behind an impedance that is primarily defined by
the case of rotating generators) at higher harmonic orders. At lower harmonic orders, at frequencies
within an order of magnitude of an inverter’s current regulator control bandwidth, the control
characteristics may significantly affect the effective impedance. The flow of harmonic current, into or
out of the DER, is the phasor superposition of the flow due to the external harmonic voltage
distortion‖with‖the‖DER’s‖internal‖source‖shorted,‖and‖the‖flow‖due‖to‖the‖DER’s‖internal‖harmonic‖
voltage‖ source‖ with‖ the‖ grid’s‖ harmonic‖ voltage‖ source‖ shorted‖ (i.e.,‖ an‖ undistorted‖ grid) . Given
these basic characteristics, harmonic current flow may occur even when the DER is not providing a
source at the particular harmonic frequency, or harmonic current flow may be substantially altered
by grid distortion at frequencies where the DER does provide a source.
The characterization of voltage-source inverter and rotating generator DER as harmonic current
sources‖ is‖ a‖ generally‖ inaccurate‖ concept‖ with‖ today’s‖ technology. In the past, line-commutated
converter technology was in common use and influenced industry’s practices for harmonic
distortion limitation (such as the original IEEE Std 519). Despite its limitations, and due to the lack of
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
DER that meet current distortion limits when connected to an undistorted external system, such as
during type testing, may exceed current distortion limits when measured in a field environment
having voltage distortion. In those situations, the Area EPS operator will need to determine the
appropriate resolution. Many times, such current distortion flows in the presence of background
voltage distortion are only slightly beyond limits and therefore, immaterial to the cumulative
voltage distortion of the Area EPS. Such cases are not likely to warrant the additional costs
associated with study designed for differentiating the distortion caused by the Area EPS. However,
it is possible for the DER to be in resonance with a system harmonic impedance, in which case the
measured current distortion would be significantly beyond the acceptable limit and in need of
mitigation.
Overvoltages may occur when DER is islanded with a ground fault present on the islanded system.
The potential for overvoltage depends on the characteristics of the DER, presence of any external
ground sources, and the characteristics of the load remaining connected to the island. Evaluation of
such overvoltages in the case of rotating generator DER is well defined by conventional analysis
practices. For current-regulated sources, such as inverters, conventional fault analysis practices are
inaccurate. The latter situation is described in detail in IEEE Std C62.92.6, with recommendations for
The following standards are related to this annex and provided here for convenience:
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
IEEE Std 1453.1-2012, IEEE Guide—Adoption of IEC 61000-3-7:2008, Electromagnetic compatibility
IEEE Std C62.92.6-2017, IEEE Guide for the Application of Neutral Grounding in Electrical Utility
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
Annex H
(informative)
(New)
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
(New)
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
(New)
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
(New)
(New)
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
(New)
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
(New)
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
(New)
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
(New)
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
(New)
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
(New)
NOTE—A DER response during low-frequency conditions may be subject to available active power
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.
I
EEE
st
andards
.i
eee.
org
Phone:+17329810060 Fax:+17325621571
©IEEE
Authorized licensed use limited to: China University of Petroleum. Downloaded on November 02,2024 at 10:36:47 UTC from IEEE Xplore. Restrictions apply.