MI5090 Rev 05
MI5090 Rev 05
SAS au Capital de 2 158 244 € - 444 871 933 R.C.S. Bourges - APE : 332B
a Delft Instruments company Headquarters : Bât 59, rue Isaac Newton - ZA Port Sec Nord – 18000 Bourges - France
Enraf Marine Systems MI5090
85, avenue de Saint-Cloud Rev05 - 06/06
78000 Versailles - France Page 2/18
T + 33 (0) 1 39 20 38 27 All rights
F + 33 (0) 1 39 02 35 61 reserved
Email [email protected]
PL3700 - INSTALLATION MANUAL
CONTENT
2. STORAGE...........................................................................................................................................................3
9. CODIFICATION ................................................................................................................................................16
9.1. LEVEL TRANSMITTER PL3700 ......................................................................................................................16
9.2. PRESSURE TRANSMITTER PL3700................................................................................................................18
2. STORAGE
The material should be stored in covered area, and protected in the original packing
CAUTION :
If any kind of work are carried out around the transmitter, it is necessary to protect
the diaphragm and transducer against chocks, sandblasting, painting, etc….
3.2. Mounting
Different possibilities of mounting are possible : immersed or side mounting, depending of
type of tanks, liquid and pressure to measure.
● Immersed mounting for Level application :
S.S 316L
Fixation KIT
Vent pipe
T- shape
PL 3700 Connection
Flange mounting
Hull shell
Valve
Flexible option
Top tank fitting
connection
Deck
Fixed pipe
Side tank
Fixations
Welded Flange
PRESSURE APPLICATION
PIPE
LEVEL APPLICATION
Screwed Flange
TANK
Test Flange
1/8 test connection plug
DO NOT:
- Tighten high until crushing of the cable with cable fixation.
- Fix cable alongside pipe with temperature which exceed 80°C.
- Expose cable to chemical or corrosive product.
Cable gland
Tightening torque 2.5 to 3 m/Kg
170 mini
Mini radius
40 mm
Bulkhead
50 mini
IMPORTANT RECOMMENDATIONS :
Remote box in Polyester must be installed:
- Outside the tank.
- In area protected against possible chock which can damage housing.
- In area protected against possible projection of chemical or corrosive
product which can damage housing.
- More high position possible.
- With cable gland positioned downwards.
- In area where room temperature will not exceed +85°C.
PG 13
Cable Ø 6 to Ø 12mm
or PG 16
Cable Ø 10 to Ø 14mm
+ reducer
Transducer Input
Power supply Input
Venting
for pipe connection
1/8” NPT Cable gland
Positioned downward
Pipe for venting
To dry area
IMPORTANT RECOMMENDATIONS :
Remote box in stainless steel must be installed :
- When there is a risk of chock damage.
- On chemical or corrosive area.
- Outside the tank.
- More high position possible.
- With cable gland positioned horizontally.
- In area where room temperature will not exceed +85°C.
Flexible must be mounted and tightened correctly.
Venting
for pipe connection
1/8” NPT
The cable-gland bodies are definitely screwed on remote box housing with a
special compound for tightness, do not try to remove them.
Cables arrive to stainless steel remote box connection terminal through two flexible
pipes delivered with it. This flexible pipe is made, inside, with special rubber and outside,
with stainless steel armoring.
(1) Sealing
(4) Washer washer ( 6) Locking nut Coupling
● PCB connection
G 0V Sg 5V
+_ G
Braid ground
Supply 0V (brown) Power supply
Ground 12 – 30 Vdc
Signal (blue) (28Vdc for I.S.
_
application)
Supply 5V (red)
Output
+ 4 – 20 mA
Vent plastic pipe
The PL3700 transmitter is certified II 1 G/D EEx ia IIC or IIB T6 under certificate n°
LCIE 02 ATEX 6180 X, meaning that it must be associated to an intrinsically safe certified
device, complying with the transmitter's intrinsic safety parameters.
The internal capacitance is ≤ 8 nF; the inductance is 30 ≤ µH.
The result of such association is an intrinsically safe system, which must be certified. The certification
is the responsibility of the provider of the associated device.
As consequence, a suitable Zener barrier must be installed in Safe Area, according to following
diagram :
Current loop
Output
4 - 20mA
Zener barrier
Shield
he PL3700 Atmospheric Pressure model is fitted with a polyester housing for wall mounting.
CAUTION :
The transducer diaphragm must typically point downwards, as well as the cable
gland, never upwards.
Mounting procedure :
- Open the box cover
- Use the four internal holes for wall mounting
The pressure inlet must be in relation with the real atmospheric pressure, to be used
as reference for all gage pressure measurements. So, when the transmitter is
installed inside a room where the ambient pressure is different, a pipe is to be
connected to the inlet with a coupling fixed on the thread fitted for that purpose,
toward that real atmospheric pressure.
The current loop output is to be connected as shown in chapter 4.5 and 4.6.
6.1. Verification
Before powering ON PL3700, check the polarity on all the equipment connected to the
processing line.
- 4 mA if no liquid or no pressure.
- 4 to 20 mA if liquid or pressure.
6.4. Setting
● Calibration of PL3700 is pre-set in factory and no adjustment is required.
● The measuring range is indicated in mbar on transducer and associated remote box.
● The indicated value corresponds to maximum hydrostatic pressure calculated as
follow, for Level application (refer to PTDQ §7 ) :
P = (H-hz) x Sg x 0,981
P = Hydrostatic pressure. (mbar)
H = Total height to gauge. (cm)
Hz = Zero line. (cm)
Sg = Specific gravity of liquid.
L1 Hv
hz
Tank bottom
hz Zero line (4 mA)
8. PERSONAL NOTES
9. CODIFICATION
1 2 3 4 5 6 7 8 9 10 11 12 13
PL3700
Pressure Transmitter PL3700
| | | | | | | | | | | |
2 | | | | | | | | | | | Type of measure
G | | | | | | | | | | | Gauge pressure
A | | | | | | | | | | | Absolute pressure
| | | | | | | | | | |
3 | | | | | | | | | | Range Type
P | | | | | | | | | | -200 to 1000 mbar forbidden if abs pressure (digit 2=A)
Q | | | | | | | | | | 900 to 1300 mbar forbidden if gage pressure (digit 2=G)
R | | | | | | | | | | 800 to 2000 mbar forbidden if gage pressure (digit 2=G)
S | | | | | | | | | | 0 to 20000 mbar forbidden if gage pressure (digit 2=G)
T | | | | | | | | | | 0 to 7000 mbar forbidden if gage pressure (digit 2=G)
| | | | | | | | | |
4 | | | | | | | | | Environment Comment
S | | | | | | | | | Non-Corrosive Product Viton HNBR(for PL3700 ATM )
C | | | | | | | | | Corrosive Product ( chemical ) Kalrez gasket, forbidden if digit 3=Q
| | | | | | | | |
5 | | | | | | | | Flange / process connection Comment
F | | | | | | | | Welded flange PN40 DN25 all except atm pressure (digit 3=Q)
P | | | | | | | | 1/2'' gas female connection only for manifold pressure ( digit 3=S )
0 | | | | | | | | Without flange only for atm pressure ( digit 3=Q )
Y | | | | | | | | Other welded flange On request
| | | | | | | |
6 7 8 | | | | | Cable Material and Lenght Comment
A | | | | | Polyethylen (PET), lenght in meter (min 01/max 50) all types, temp < 85°C
B | | | | | Teflon (FEP), lenght in meter (min 01/max 50) all types, high temp and corrosive atm
| | | | |
9 | | | | Electronic Housing Comment
A | | | | Polyester housing all types, for protected installation
C | | | | 316L stainless steel housing all types, for "on deck" installation
| | | |
10 | | | Flexible options and cable protection Comment
0 | | | No cable protection all types
A | | | Adaptators Kit (for flexible conduits) Only for SST box ( digit 9=C )
B | | | 1 flexible conduit (cell-electronic box) Only for polyester box (digit 9=A,B)
C | | | 2 flexible conduits Only for SST box ( digit 9=C )
D | | | 3 flexible conduits Only for SST box ( digit 9=C )
| | |
11 | | Calibration Comment
0 | | Standard calibration all types
| |
12 | Test flange option Comment
0 | Without test flange all types
|
13 Mechanical installation options Comment
0 Without any option all types
A 316L fixation kit only for atm pressure (digit 3=Q)