Testing Commissioning ARC Flash Detection Paper APPTC 2014 Gupta ENU
Testing Commissioning ARC Flash Detection Paper APPTC 2014 Gupta ENU
Introduction
Arc flash faults inside switchgears are proved to be
Arc Flash Phenomenon
fatal and dangerous not only for personal but also > Arc fault is a short circuit through ionized
for equipments and production processes. Arc gas (normally air) between one live part
faults often leave the equipment damaged to such and ground or between live parts.
extent that it need complete replacement or major > Arc fault can be characterized as an
repair. Many times it is also hazardous for the electrical explosion, because of the
personal working around the switchgear/ speed, power, heat and pressure of the
equipments. The arc flash energy increase phenomenon.
exponentially with the time , so to reduce the
damage by ARC fault is to reduce the isolation
time. The light is the first thing to appear in case of
ARC fault so fastest way of detection of ARC fault
is to detect light and isolate the faulty section by
the fastest way. The ARC flash protection system
provide tripping time of 1 to 8 ms which reduce the
isolation time to 35 to 80 ms depending upon the
breaker operation time. To avoid nuisance tripping
many time over current is also added as additional
logic to ensure correct operation. Today with
advance ARC flash protection systems we can
achieve customized schemes for selected
operations depending upon the fault location. The
Arc protection schemes can not only reduce
damage to equipment & personal but also ensure
faster availability of the system to minimize the
production cycle losses.
Damage to equipment
Direct damage
Often very high indirect costs due to
interruption of processes
o Electricity distribution process
o Industrial processes (steel, paper, oil
refining etc.)
Other possible indirect costs, e.g. legal and
medical expenses
ARC Flash protection system Dedicated arc stages, trip <= 15 ms with
L>&I> and/or L>&Io> criteria
Communicates with VAMP arc protection
Purpose of Arc flash protection systems is to
system (VAMP221 and VAMP 121) via
detect arcs which occur during short-circuits in
BIO interface
LV/MV equipments and to limit damage to
personnel & equipment thru reduction in time of Economical arc protection
operation of Switchgear to isolate the faulty Selective tripping possibilities
section. With following features :
> Selective ARC protection system
ARC Flash Protection – Sensors
> Indication of activation
Point sensor
> Developed in accordance with protection
Fixed in each protected compartment
relay standards
Simple installation
Exact fault spot location
Recommended for MV applications
Fiber optic sensor
Routed through protected areas
Cost effective solution recommended for
low voltage applications
Personal sensor
Utilized temporarily during live work
- Connected to clothes or next to work place
ARC Protection with IED & Arc system ARC flash Protection system
Testing & Commisioning
System Inspection
o Checking that the used settings correspond o Current injection device with ARC flash
to the system plans and further, checking Initiator like OMICRON CMC 356,
any anomalies in the settings, like a CMC 353, CMC 256plus and CMC 256-6
deviation from the planned value, with the o Powerful light source like the ARC 256x
customer. Arc Flash Initiator
o Based on the details of the system, defining o Screwdriver kit
the proper testing procedure.
o Test leads
o Checking device code and location map;
o Extension cord
comparing the device and location codes
with the available system drawings and o Multimeter
documenting the deviations in the test report o Relay tester
o Arc flash resistive clothing including helmet,
protective goggles and gloves
Testing & Commissioning
o For testing Arc Flash simulator initiates an Summary
arc by strong source like a xenon tube,
positioned close to the arc flash sensor
o A connection cable is to external socket of It is described that ARC faults are often result in
the testing kit set . Providing supply damage of equipments and personal hazardous.
voltage & Trigger Signal The Arc flash protection system with optical
sensors and logical schemes can safeguard not
o Protection system is then automatically only Human and equipment but can also ensure
tested thru software, controlling the trigger faster availability of the equipment.
signal & measures operation delay
o The Arc flash simulator Position shall be
secured very close to linear sensor by About the Author
adhesive rubber compound.
Required equipment
o Special tools and protective clothing are
required during the testing.
> Internal Arc 40 kA for 1 sec will only prevent the arc to go in such a direction
that it will not harm the person operating the panel from front side or rear (IAC
AFLR LSC2B) however it does not:
- Prevent any damage to the panel and apparatus inside
- Panel cannot be brought back into service without complete replacement .
> If a internal ARC happens then there would be need for a long downtime for
ARC Flash Testing & Commissioning the complete switchboard resulting in loss of production and increase in
maintenance cost.
OMICRON _ AP.PTC
> Active arc fault protection embedded in IED’s provide the benefit of fast
detection ( during flash phase) using optical sensors and thus with the help of
CB are able to clear and extinguish the fault thus saving the equipment from
damage
14th to 16th Oct. 2014
Vishal Gupta
Energy – VAMP
Photo: J. Vogler
> Animals, dirt, grease, gas, fluid
> Results in an arc short-circuit between one live part and ground or between Heated air
live parts Hazardous voltage
pressure and sound
wave
Confidential Property of Schneider Electric 5 Confidential Property of Schneider Electric 6
> The severity of arc-flash burns depends on the working distance, the voltage, the
current and the arcing time
> The easiest way to limit the arc energy is often limiting the arcing time by high-speed
protection current
pressure
I²t, kA² s
Steel fire
Cable fire
Total breaking time
with arc protection
7 + (35 .. 80)ms
50/51,
50/51N master
Overcurrent setting
87
50/51,
• Light information 1ms 50/51N ARC Flash Protection Scheme
• O/C comparison 1ms
• Initiate trip 5 ms slave
17 18
ARC Protection with IED & Arc system ARC Protection with IED & Arc system
Presentation 13.9
Normal situation:
Normal situation: The main transformer feeds
The Main transformer feeds the busbar. A fault in the CB
the busbar. A fault in the cable compartment.
compartment.
I> &
Arc sensor in CB
An arc
The
Lightmain
sensor
and
fault
current:
transformer
transfers
in the the
feeds
light Light
An
The arc
main
fault
and
fault
current
current:
transformer
in cannot feeds
be
compartment picks the arc
information
the
TRIP!
cable
fault.
compartment
to the relay within TRIP!
measured
the CB
fault.
compartment
in the outgoing
and transfers light info to the
1ms. feeder. Therefore, the light
relay within 1 ms
information is transferred to
the incomer.
&
Only the faulted outgoing
feeder tripped. Busbar and The incomer CB tripped,
other feeders still in service. because the fault in the CB
compartment.
Confidential Property of Schneider Electric 19 Confidential Property of Schneider Electric 20
20
19
ARC Protection with IED & Arc system Three busbar system
Full Selectivity with ZONES & several Tripping outputs
Simplified SLD-Three bus bar system ARC flash detection system Example
Presentation 13.10
I> I>
I>
-12L
-Breaker
-Fault
-Point
-321 has current
opens
occur
sensor
detects
indication
and faulty
detects
the faultthetogetger
feeder
light
current
with
is
and
and light
isolated
send
sends information
the
the
and trip signal
Information
Information is given
forward
forward
12L - Feeder 12L - Feeder 12L - Feeder 12L - Feeder
+
Confidential Property of Schneider Electric 23 Confidential Property of Schneider Electric 24
ARC Flash Protection System - Sensors ARC Flash Protection System - Sensors
Personal Protector –
Optical sensor selection
For Workforce safety
1) Point sensor
- Fixed in each protected
compartment
- Simple installation
Master Master
- Exact fault spot location
Point Sensor – For HV/LV Chambers - Recommended for MV applications
3) Personal sensor
Optical Sensor – For Bus Bar ,
- Utilized temporarily during live work
cable alley etc. - Connected to clothes or next to work place
(8000 LUX Sensitivity )
Confidential Property of Schneider Electric 25 Confidential Property of Schneider Electric 26
System Inspection
Presentation 13.11
> Before the actual testing begins, the station and the system to be tested
should be inspected. The aim is to find out the relevant details of the system
to be able to choose a suitable testing procedure. The inspection consists of
different procedures. .
> Consulting the customer about the details of the system as good communication and
mutual understanding is a prerequisite for successful testing.
> Defining the boundaries of the safe and hazardous working areas and checking that
they are properly marked.
ARC Flash Testing & Commisioning > Inspecting the devices and wiring visually.
> Checking the application; comparing the actual system to the available system
Back up Slides