EngineGen Submittal Form Diesel Drive (3.3 KV)
EngineGen Submittal Form Diesel Drive (3.3 KV)
3 KV
Al Sowwah Island
Engine Generator Set Manufacturer:
Number of Units Proposed: 6 units, each rated
Model Size Designation: 2,600 KVA Continuous power
Total Plant Net Electric Output: 15.6 MVA @ p.f. 0.94 Continuous Electric output characteristics: 3.3 KV / 3 phase -
Duty 3wire - 50 Hz
Engine Rated Speed: 1500 RPM No. of Cylinders /Arrangement:
Bore/Stroke, mm: Displacement liters:
Compression Ratio: Unit net Electric output kW:
Engine Generator Set Performance Indicated is at Field Conditions, Continuous Output Duty
Altitude 100 m; Suction Air Temperature 51°C; Air Pressure 100kPa; Coolant Ambient Air at 43°C
Commercial Grade Diesel Fuel Oil (SSU @ 100°F 32~42)
DERATING RULES
Reference conditions
Reference altitude ASL m 1500
Reference air pressure kPa 85
Reference intake air temperature 40
Reference charge air coolant temp. °C 40
Site Conditions
Altitude ASL m 100
Air pressure kPa 100
Turbocharger intake air temperature °C 51
Ducted from outside the
Turbocharger air intake room.
Maximum Engine Hall room temperature °C 53
Charge air coolant water temperature °C
Maximum Air Intake Restriction Allowed: mmWG
Exhaust gas back pressure allowed max. mmWG
Crankcase Breather, Volume Flow actual lit/sec
Crankcase Suction Vacuum, mmWG
Power adjustment factor for site conditions
Fuel consumption adjustment factor
Engine Loading Rate: (At Site Conditions) 100 90.0 80.0 75.0
Output Power, shaft kWmech
Alternator Output @ p.f.=1.0 kWe
Alternator Output @ p.f.=0.85 kWe
Alternator efficiency @ p.f.=1.0 %
Alternator efficiency @ p.f.=0.85 %
BMEP Continuous Duty kPa
Net heating value, reference fuel kJ/lit
Alternator
Manufacturer: Advise
Model Designation:
Type: A.C. Synchronous Unit
Mounting Configuration: Horizontal Foot Mounted
Enclosure: ODP; IP22
Enclosure: Optional IP55
Cooling: Water cooled
Standard: IEC (or NEMA)
Location: Indoors
Ambient Design Temperatures: Max 53°C / Min -20°C
Elevation, Design: 1000 m ASL
Duty: Continuous
Operation: Continuous
Supply: Non Sinusoidal
Amount non sinusoidal Load: kVA Advise
Rated Voltage: V 3,300 Volt
Rated Apparent Power: kVA Advise
Alternator terminals , efficiency % 96% Min.
Rated Mechanical Power Input: kW Advise
Rated Electrical Power Output: kW Advise
Rated Current: Amp Advise
Rated Power Factor: 0.94
Rated Speed: RPM 1500
Frequency: 50 Hz
Overspeed Capability& Duration min 125% Nom. Speed & min.
Insulation, Vacuum Pressure Impregnated: Class H
Temperature Rise above 50°C, by Resistance °C Class F (155 Deg C)
Designed to be driven directly by: Reciprocating Engine
Sustained Short Circuit Current & Duration Advise
3 Pole Main In-Line Circuit Breaker with Shunt trip A/VAC/I2t Advise
Lubrcation pump size when used: kW/VAC Advise
Space Heater Size: kW/VAC Advise
Insulated non drive end bearing Include
Bearing RTD's: Two each 100 ohm Pt
RTD in Air flow Stream: One 100 ohm Pt
Hi Volt Differential CT's detail: Include
Coupling Type: Min s.f.≥3.0 Detail:
Winding RTD's Six 100 ohm Pt
Synchronization unit, load shedding/sharing unit Detail:
Physical Dimensions:
Overall Size: mm Lng x Wd x Hi
Weight: kgs Advise
Rotor weght: kgs Advise
Heaviest Component weight (Maintenance) kgs Advise
Engine Auxiliaries:
Spring Isolators Include
Heat Exchangers:
Heat Exchangers, type Plate & Frame
Water Supply, Cold side: Cooling Tower Water
Heat Exchangers, Circuit Arrangement Parallel Connection
Cold side Water Temp. In 35°C (95°F)
Exchanger Cold Side Water Temp. Out: °C Advise
Exchanger Cold Side Water Flow Rate: m³/hr Advise
Exchanger Cold Side Water Presuure drop: kPa Advise
Exchanger Hot Side Water Presuure drop: kPa Advise
Dimensions (LgxWdxHi) : mxmxm Advise
Weight: Dry (Operating) kgs Advise
Number of Plates : Advise
Materials: Plates (Gaskets) Advise
Flanged Connections: In (Out) Cold Side inch Advise
Flanged Connections: In (Out) Hot Side inch Advise
Control Center:
Industrial Grade Arranged for Interface with PLC In Central Control Room
Nema 12 Dustproof Enclosure: Provide Required Interface
24 VDC Control Circuit:
Battery charger with indication kW/VAC Advise
Battery Type / Life Cycle Avise
Containing All necessary Safety, Operating,
Monitoring, Metering and Alarming Devices:
As a minimum to include:
Auto Start/Stop control & Emergency stop.
Safety Shut down for:
Low Oil Pressure; High coolant temperature;
Low Coolant level;Overcrank protection
Cylinder Unbalance via RTD's; Overspeed.
Minimum Readouts for:
Engine RPM; Run Time; Oil Pressure;
Coolant Temperature;System VDC; Line Volts;
L-N Volts; 3-phase Amps, Frequency;
El kW; kVA; kVAR; %kW; Power Factor
Programmable Relaing Functions:
Under/Over Volts;Under/Over Frequency;
Reverse power; 3-ph overcurrent;
Earth fault;kW level relay
Spare Alarm/Shutdown Inputs; (min 4)
Spare Indicator Lights
Engine Generator Submittal Data Sheet - 3.3 KV
Al Sowwah Island
Engine service Requirements Specified Proposed Comments
Oil Data
SAE Viscosity grade
Sulfated Ash, % Weight Low Ash content
TBN (ASTM D2896)
Service Contract
On call service and one monthly visit or at
each 1,000 hours service contract
Labor cost AED/year/engine
Inclusive all parts other than those
Parts cost AED/year/Engine mentioned above.
Service contract labor & parts cost AED/year/Engine
Based on site condition guaranteed output
electic capacity and 90% engine load
Service contract cost AED/Kwh 0.015 Max factor.
Top End Overhaul
Other than those included in service
Intervals - Hours 12,000 Min. contract
Parts required for top end overhaul - AED/engine
Labor required for top end overhaul AED/engine
Based on site condition guaranteed output
electic capacity and 90% engine load
Top end Overhaul cost AED/Kwh 0.01 Max factor.
Major Overhaul
Intervals - Hours 24,000 Min.
Parts required for top end overhaul - AED/engine
Labor required for top end overhaul AED/engine
Based on site condition guaranteed output
electic capacity and 90% engine load
Major Overhaul cost AED/Kwh 0.01 Max factor.