Diesel Engine Generator Submittal Data Sheet - 3.

3 KV
Al Sowwah Island
Engine Generator Set Manufacturer:
Number of Units Proposed: 6 units, each rated
Model Size Designation: 2,600 KVA Continuous power
Total Plant Net Electric Output: 15.6 MVA @ p.f. 0.94 Continuous Electric output characteristics: 3.3 KV / 3 phase -
Duty 3wire - 50 Hz
Engine Rated Speed: 1500 RPM No. of Cylinders /Arrangement:
Bore/Stroke, mm: Displacement liters:
Compression Ratio: Unit net Electric output kW:
Engine Generator Set Performance Indicated is at Field Conditions, Continuous Output Duty
Altitude 100 m; Suction Air Temperature 51°C; Air Pressure 100kPa; Coolant Ambient Air at 43°C
Commercial Grade Diesel Fuel Oil (SSU @ 100°F 32~42)

ISO CONDITIONS , SHAFT


Engine loading rate: % 100 90 75 50
ISO Total Shaft Power Output, kWmech
Fuel consumption, shaft lit/hr
Specific Fuel Consumption, mechanical kJ/kWmech.hr
Minimum Allowed Engine Loading: kWmech
ISO conditions, Alternator terminals
Power Output at Alternator Terminals kWe
Alternator Efficiency %
Specific Fuel Consumption, terminals kJ/kwe.hr

DERATING RULES
Reference conditions
Reference altitude ASL m 1500
Reference air pressure kPa 85
Reference intake air temperature 40
Reference charge air coolant temp. °C 40
Site Conditions
Altitude ASL m 100
Air pressure kPa 100
Turbocharger intake air temperature °C 51
Ducted from outside the
Turbocharger air intake room.
Maximum Engine Hall room temperature °C 53
Charge air coolant water temperature °C
Maximum Air Intake Restriction Allowed: mmWG
Exhaust gas back pressure allowed max. mmWG
Crankcase Breather, Volume Flow actual lit/sec
Crankcase Suction Vacuum, mmWG
Power adjustment factor for site conditions
Fuel consumption adjustment factor
Engine Loading Rate: (At Site Conditions) 100 90.0 80.0 75.0
Output Power, shaft kWmech
Alternator Output @ p.f.=1.0 kWe
Alternator Output @ p.f.=0.85 kWe
Alternator efficiency @ p.f.=1.0 %
Alternator efficiency @ p.f.=0.85 %
BMEP Continuous Duty kPa
Net heating value, reference fuel kJ/lit

FUEL CONSUMPTION AT SITE CONDITIONS


Site fuel Lit/hr
Shaft , heat rate kJ/kWmech.hr
Shaft ,efficiency %
Alternator terminals , heat rate kJ/kWe.hr
Alternator terminals , efficiency %
Engine Overload Allowed kW
Overload Operating Time Allowed in a 24 hour day hrs
Minimum Engine Loading allowed continuous duty kW
Diesel Engine Generator Submittal Data Sheet - 3.3 KV
Al Sowwah Island
EngineHEAT
Generator Set Manufacturer:
BALANCE AT SITE CONDITIONS
Engine loading rate: % 100.0 90.0 80.0 75.0
Engine Mechanical Power Output kWmech
Heat Rejection Rate in Jacket Water Circuit kW
Heat Rejection Rate in Lube Oil Cooler Circuit kW
Heat Rejection Rate in After Cooler Water Circuit kW
Heat Rate Loss through Exhaust kW
Radiation Heat Rate Loss kW

Main Lube Oil Pump Driver kW


Coolant Circulator Pump Driver kW
kW
Total kW
Fuel Heat Input kW

Air Intake & Exhaust:


Engine loading rate: % 100.0 90.0 80.0 75.0
Air Intake Flow Rate Nm³/hr
Exhaust Gas Mass Flow Rate kg/hr
Exhaust Gas Temperature °C
Required Filtering Efficiency (coarse dust per StdE?) %
Lube Oil System: (Force feed Full Flow)
Lube Oil Flow Rate m lit/min
Lube Oil Consumption gm/kWmech.hr
Lube Oil Consumption lit/hr
Lube Oil Temperature leaving Oil Cooler °C °C
Lube Oil Temperature Entering Oil Cooler °C
Normal Lube Oil Pressure met³/hr
Oil Cooler Water Temp. In: °C 35
Oil Cooler Water Temp.Out: °C
Oil Cooler Water Pressure drop: kPa
Main Lube Oil Pump Driver Rating kW kPa
Main Lube Oil Pump Driver Power Supply: kW
Auxiliary (Prelube) Lube Oil Pump Driver: kW Advise TEFC
Strainer Screen: micron
Oil Filter Efficiency: % at micron Duplex Oil Filter
Fuel System:
Commercial grade Diesel Fuel Oil
Max Allowed Sulfur Content %
Fuel Filter: Duplex w. Water Separator.
Cooling System:
Jacket Water Heater kW Advise
Jacket Water Heater Power Supply VAC
Jacket Coolant Type & % concentration
Lo Temp. Coolant Temperature In (Hot side) °C -
Lo Temp. Coolant Temperature Out (Hot side) °C -
Hi Temp. Coolant Temperature In (Hot side) °C -
Hi Temp. Coolant Temperature Out (Hot side) °C -
Coolant Flow Rate: lit/min
Starting System:
By Oversized Battery via 24VDC Heavy Duty Motor AmpHr
Minimum Number of Starts/ Cranking time: 4 each 30sec. Long
Governor
Solid State isochronous type Woodward or Equal
Complete with Automatic Load sharing module
Physical Data:
Overall Dimensions: LngxWdXHi mxmxm
Engine Set Dry Weight kgs kgs
Engine Weight without skid & flywheel kgs
Flywheel weight kgs
Heaviest engine part, top overhaul: Part kgs
Jacket Capacity liters
Oil Sump Capacity including filters & Coolers liters
Auxiliary Coolant system Capacity liters
Recommended Distance Between Engines: m
Recommended Overhead Clearance: m
Engine Generator Submittal Data Sheet - 3.3 KV
Al Sowwah Island
Engine Auxiliaries Requirements Unit Specified Proposed / Comments

Alternator
Manufacturer: Advise
Model Designation:
Type: A.C. Synchronous Unit
Mounting Configuration: Horizontal Foot Mounted
Enclosure: ODP; IP22
Enclosure: Optional IP55
Cooling: Water cooled
Standard: IEC (or NEMA)
Location: Indoors
Ambient Design Temperatures: Max 53°C / Min -20°C
Elevation, Design: 1000 m ASL
Duty: Continuous
Operation: Continuous
Supply: Non Sinusoidal
Amount non sinusoidal Load: kVA Advise
Rated Voltage: V 3,300 Volt
Rated Apparent Power: kVA Advise
Alternator terminals , efficiency % 96% Min.
Rated Mechanical Power Input: kW Advise
Rated Electrical Power Output: kW Advise
Rated Current: Amp Advise
Rated Power Factor: 0.94
Rated Speed: RPM 1500
Frequency: 50 Hz
Overspeed Capability& Duration min 125% Nom. Speed & min.
Insulation, Vacuum Pressure Impregnated: Class H
Temperature Rise above 50°C, by Resistance °C Class F (155 Deg C)
Designed to be driven directly by: Reciprocating Engine
Sustained Short Circuit Current & Duration Advise

Overload Capability: Amount,Duration & Freqency Advise


Efficiency at P.F. 1.0 and Loads: 100%; 75%; 50%; 25%
Efficiency at P.F. 0.8 and Loads: 100%; 75%; 50%; 25%
Reactances & Time Constants: List
Excitation:Permanent Magnet Brushless, Integral
AVR type: Built in the machine
Bearing type: Split Sleeve or Roller Split Sleeve Steel Backed
Bearing Lubrication: Oil Force Feed/or Grease Detail:
Alternator Cooling: Air Cooled
Air Supply Temperature 50°C
Largest starting load 1500 KW / Soft Starter
Manximum Volt Drop allowed 15 % 1 second
Accessories:

3 Pole Main In-Line Circuit Breaker with Shunt trip A/VAC/I2t Advise
Lubrcation pump size when used: kW/VAC Advise
Space Heater Size: kW/VAC Advise
Insulated non drive end bearing Include
Bearing RTD's: Two each 100 ohm Pt
RTD in Air flow Stream: One 100 ohm Pt
Hi Volt Differential CT's detail: Include
Coupling Type: Min s.f.≥3.0 Detail:
Winding RTD's Six 100 ohm Pt
Synchronization unit, load shedding/sharing unit Detail:
Physical Dimensions:
Overall Size: mm Lng x Wd x Hi
Weight: kgs Advise
Rotor weght: kgs Advise
Heaviest Component weight (Maintenance) kgs Advise
Engine Auxiliaries:
Spring Isolators Include

Engine Cooling System:


Engine Coolant Circulating Pump(s) Type: Advise
External Electric Type or Shaft driven Pump(s): Shaft Driven
Pump Driver Power Supply: Volt/ph/Hz For Electric Driven Pumps
Engine Generator Submittal Data Sheet - 3.3 KV
Al Sowwah Island
Engine Auxiliaries Requirements Unit Specified Proposed / Comments

Engine Cooling System:


Engine Coolant Circulating Pump(s) Type: Advise
External Electric Type or Shaft driven Pump(s): Shaft Driven
Pump Driver Power Supply: Volt/ph/Hz For Electric Driven Pumps
Pump Flow Rate: lit/min Advise
Pump Head kPa Advise
Power Input / Driver rating kW Advise

Heat Exchangers:
Heat Exchangers, type Plate & Frame
Water Supply, Cold side: Cooling Tower Water
Heat Exchangers, Circuit Arrangement Parallel Connection
Cold side Water Temp. In 35°C (95°F)
Exchanger Cold Side Water Temp. Out: °C Advise
Exchanger Cold Side Water Flow Rate: m³/hr Advise
Exchanger Cold Side Water Presuure drop: kPa Advise
Exchanger Hot Side Water Presuure drop: kPa Advise
Dimensions (LgxWdxHi) : mxmxm Advise
Weight: Dry (Operating) kgs Advise
Number of Plates : Advise
Materials: Plates (Gaskets) Advise
Flanged Connections: In (Out) Cold Side inch Advise
Flanged Connections: In (Out) Hot Side inch Advise

Engine Starting Auxiliaries:


Air Volume & Pressure Per Start / Unit: Advise Scfm / psig
Number of Air Starter Sets:
Number of Compressors per set: Advise
Compressor Type & Stages: Advise

Compressor Capacity: Scfm / psig Advise/Advise lit.


Compressor Motor Rating: Kw Advise/Advise
Compressor Motor Power Supply: 415V, 3ph, 50Hz
No. of Receivers per set & Receiver Volume: /Lit. Advise/Advise lit³.
Receiver Pressure: barg Advise
Receiver Design Pressure & Temperature: barg/°C Advise
Design Standard & Coding: Advise
Complete w. Relief Valves & Automatic Drains Relief Valve Settings(barg)

Exhaust Gas Heat Water Heater:


Manufacturer:
Model Designation:
Type: Horizontal Shell & Tube
Quantity:
Duty Each Unit: kw
External Effective Heat Transfer Area: m²
Surface Ratio: (External/Internal):
Tube Side: Exhaust Gas
Mass Flow Rate: kg/hr
Inlet Temperature: °C
OutletTemperature: °C
Inlet Pressure: kPa
Pressure Drop: kPa
Number of Passes:
Number of Tubes:
Tube size & Tubewall thickness: mmO.D./(mm)
Design Pressure & Temperature: Min:≥ 1.5psig / 900°F
Corrosion Allowance: Advise
Gas Inlet & Outlet Connection Size:(Flanged) mm
Shell Side: Water
Mass Flow Rate: m³/Hr 61.05
Minimum allowed mass flow rate: m³/Hr
Maximum allowed mass flowrate: m³/Hr
Inlet Temperature: °C
OutletTemperature: °C Tout≥124°C
Water Pressure Drop: kPa
Design Pressure & Temperature: 250psig /300°F
Corrosion Allowance: 2mm
Water Volume when full: liters
Connection Sizes: In / Out mm

Room Cooling auxilliaries:


Engine Generator Submittal Data Sheet - 3.3 KV
Al Sowwah Island
Engine Auxiliaries Requirements Unit Specified Proposed / Comments
2 inch cleanable aluminium Filter Advise
Sound attenuators - Intake side Advise
Roof upblast ventillation fans Advise

Control Center:
Industrial Grade Arranged for Interface with PLC In Central Control Room
Nema 12 Dustproof Enclosure: Provide Required Interface
24 VDC Control Circuit:
Battery charger with indication kW/VAC Advise
Battery Type / Life Cycle Avise
Containing All necessary Safety, Operating,
Monitoring, Metering and Alarming Devices:
As a minimum to include:
Auto Start/Stop control & Emergency stop.
Safety Shut down for:
Low Oil Pressure; High coolant temperature;
Low Coolant level;Overcrank protection
Cylinder Unbalance via RTD's; Overspeed.
Minimum Readouts for:
Engine RPM; Run Time; Oil Pressure;
Coolant Temperature;System VDC; Line Volts;
L-N Volts; 3-phase Amps, Frequency;
El kW; kVA; kVAR; %kW; Power Factor
Programmable Relaing Functions:
Under/Over Volts;Under/Over Frequency;
Reverse power; 3-ph overcurrent;
Earth fault;kW level relay
Spare Alarm/Shutdown Inputs; (min 4)
Spare Indicator Lights
Engine Generator Submittal Data Sheet - 3.3 KV
Al Sowwah Island
Engine service Requirements Specified Proposed Comments

Oil Data
SAE Viscosity grade
Sulfated Ash, % Weight Low Ash content
TBN (ASTM D2896)

Oil Conumption Lit/Hr


Crank case oil Change intervals - Hours
Crank case oil change volume - Lit
Oil Filter change intervals - Hours
Oil Filter(s) cost AED / Engine

Oil Price - AED/Lit


Oil consumption & Oil Change cost AED / Hr
Other consumables
(Required a separate price list for all
To be specified by manufacturer component that are consumed prior to
1,000 hours of operation)

Total oil, & other consumables Cost- AED


Based on site condition guaranteed output
electic capacity and 90% engine load
Total oil, & other consumables - AED/Kwh factor.

Service Contract
On call service and one monthly visit or at
each 1,000 hours service contract
Labor cost AED/year/engine
Inclusive all parts other than those
Parts cost AED/year/Engine mentioned above.
Service contract labor & parts cost AED/year/Engine
Based on site condition guaranteed output
electic capacity and 90% engine load
Service contract cost AED/Kwh 0.015 Max factor.
Top End Overhaul
Other than those included in service
Intervals - Hours 12,000 Min. contract
Parts required for top end overhaul - AED/engine
Labor required for top end overhaul AED/engine
Based on site condition guaranteed output
electic capacity and 90% engine load
Top end Overhaul cost AED/Kwh 0.01 Max factor.
Major Overhaul
Intervals - Hours 24,000 Min.
Parts required for top end overhaul - AED/engine
Labor required for top end overhaul AED/engine
Based on site condition guaranteed output
electic capacity and 90% engine load
Major Overhaul cost AED/Kwh 0.01 Max factor.