Guide ElectricalCode SaskPower Interpretations 2015
Guide ElectricalCode SaskPower Interpretations 2015
ELECTRICAL CODE
Saskatchewan Interpretations
Version 1.0
(this page left intentionally blank)
Electrical Inspections
The Canadian Electrical Code Part l, Twenty-Third Edition, as supplemented and amended by these
requirements, issued under Section 5 of The Electrical Inspection Act, 1993, shall govern the
workmanship and all other matters whatever pertaining to electrical equipment and the installation of
electrical equipment in or upon any land, buildings, structures, and premises. It contains
supplementary and amendatory requirements which by their inclusion herein are adopted as
requirements under Section 5 of The Electrical Inspection Act, 1993.
Table of Contents
PREFACE AND SCOPE ................................................................................................................................................... 1
Website Information ......................................................................................................................................................... 8
Bond Notice Administration Fees..................................................................................................................................... 8
SECTION 2 - GENERAL RULES .................................................................................................................................... 9
2-004 - Permit ................................................................................................................................................................... 9
Permit Information ..................................................................................................................................................... 9
Permits for Low Voltage and Extra Low Voltage Installations .............................................................................. 9
Permits for Oil Field Installations ........................................................................................................................... 10
2-012 - Inspection Request Required.............................................................................................................................. 10
2-014 - Plans and Specifications ..................................................................................................................................... 10
2-022 - Renovations of Existing Installations ................................................................................................................. 13
Connection or Reconnection .................................................................................................................................... 13
Flood Procedures ...................................................................................................................................................... 14
Electrical Systems Exposed to Fire ......................................................................................................................... 14
2-022 - Renovating of Existing Installations .................................................................................................................. 14
2-024 - Use of Approved Equipment .............................................................................................................................. 15
Labels Required for Manufactured Homes and Movable Equipment................................................................. 15
Cable Ties .................................................................................................................................................................. 15
Equipment Approval Certification ......................................................................................................................... 15
2-024 - Use of Approved Equipment - Exceptions ......................................................................................................... 15
Conditions ................................................................................................................................................................. 16
1. a) Manufactured to Canadian Standards ....................................................................................................... 16
b) Manufactured to Other than Canadian Standards ....................................................................................... 16
2. Product Identification ...................................................................................................................................... 16
3. Maintenance ...................................................................................................................................................... 16
2-024 - Use of Approved Equipment .............................................................................................................................. 17
Field Inspection Certification .................................................................................................................................. 17
Field Inspection Reports .......................................................................................................................................... 17
Certification Marks .................................................................................................................................................. 19
Certification Body..................................................................................................................................................... 22
2-030 - Deviation or Postponement ................................................................................................................................ 25
2-100(3) - Marking of Equipment .................................................................................................................................. 25
2-106 - Rebuilt Equipment ............................................................................................................................................. 25
Retrofit kits and installation requirements ............................................................................................................ 25
Hazardous Location Luminaires ............................................................................................................................. 26
2-200 - Protection of Equipment .................................................................................................................................... 26
Commercial Automobile Receptacles ..................................................................................................................... 26
2-300 - General Requirements for Maintenance and Operation ..................................................................................... 27
2-306 - Shock and Flash Protection ................................................................................................................................ 27
2-324 - Electrical Equipment near Combustible Gas Equipment (see also 6-408) ......................................................... 27
SECTION 4 - CONDUCTORS........................................................................................................................................ 28
4-004 & 4-006 - Application of New Changes to Conductor Sizing .............................................................................. 28
Application Examples ............................................................................................................................................... 28
4-004(23) - Service Conductors for Common Residential Services ............................................................................... 28
Table 39 ..................................................................................................................................................................... 28
D8 Tables with 75° Calculations .................................................................................................................................... 29
D9 Tables with 75° Calculations .................................................................................................................................... 30
D10 Tables with 75° Calculations .................................................................................................................................. 31
D11 Tables with 75° Calculations .................................................................................................................................. 33
4-006 - Termination Temperature Limitations ............................................................................................................... 34
4-010 - Induced Voltages and Currents in Metal Armour or Sheaths of Single Conductor Cables ................................ 35
4-024 - Harmonics - Sizing Neutral Conductors ............................................................................................................ 36
4-038(3) - Colour Coding of Conductors........................................................................................................................ 36
12-120(1) - Horizontal............................................................................................................................................... 48
12-120(2)(4) - Vertical............................................................................................................................................... 48
12-510 - Running of Cable Between Boxes & Fittings .................................................................................................. 48
12-610 - Terminating Armoured Cable .......................................................................................................................... 49
12-910(4) - Conductors in Conduit and Tubing ............................................................................................................. 49
12-910 - Tables .......................................................................................................................................................... 50
12-1118 - Expansion of Rigid PVC Conduit .................................................................................................................. 51
Rules 12-1012, 12-1118, 12-1214 and Appendix B notes ....................................................................................... 51
12-1404 - Restrictions on Use of EMT ........................................................................................................................... 51
12-1414 - Provision for Bonding Continuity .................................................................................................................. 51
12-2200 - Clearance for the Installation of Cable Tray .................................................................................................. 51
12-2200(6) .................................................................................................................................................................. 51
12-2200(7) .................................................................................................................................................................. 51
12-2200(8) .................................................................................................................................................................. 52
12-2202 & 36-100(3) - Conductors of Different Voltages in Cable Tray ...................................................................... 52
12-2208(3) - Provisions for Bonding .............................................................................................................................. 52
12-2250 - Cable Bus ....................................................................................................................................................... 52
12-3000(2)(3) - Continuity of Cables and Conduits Entering Non-Metallic Boxes ....................................................... 52
12-3000(10) & 12-3002(2) ............................................................................................................................................. 52
SECTION 14 - PROTECTION AND CONTROL ........................................................................................................ 53
14-100(g) - Loading Cables ............................................................................................................................................ 53
14-104(1) - Adjustable Main Breakers ........................................................................................................................... 53
14-104(2) - Rating of Overcurrent Devices .................................................................................................................... 53
SECTION 16 - CLASS 1 AND CLASS 2 CIRCUITS ................................................................................................... 53
16-008 - Hazardous Locations ........................................................................................................................................ 53
SECTION 18 - HAZARDOUS LOCATIONS ................................................................................................................ 54
18-006 - Ammonia Compressor Rooms ......................................................................................................................... 54
18-008 - Locations Containing an Explosive Dust Atmosphere ..................................................................................... 54
18-008 - Hazardous Area Classification - Grain Elevator .............................................................................................. 54
18-008 - Hazardous Area Classification - Main Floor Plan - Seed Cleaning Plant ........................................................ 55
18-008 - Hazardous Area Classification - Feed Mill Floor Plan .................................................................................... 56
18-008 - Bio Diesel and Canola Crushing Plants ........................................................................................................... 57
18-008 - Woodworking Plants and Sawmills ................................................................................................................. 57
18-052 - Marking of Equipment ..................................................................................................................................... 58
18-068 - Combustible gas detection ............................................................................................................................... 58
18-104 - Sealing Zone 1 ................................................................................................................................................. 59
Cable Seals ................................................................................................................................................................ 60
18-154(3)(b) - Sealing Zone 2 ........................................................................................................................................ 60
Cable Seals ................................................................................................................................................................ 60
SECTION 20 - FLAMMABLE LIQUID AND GAS DISPENSING AND SERVICE STATIONS, GARAGES,
BULK STORAGE PLANTS, FINISHING PROCESSES AND AIRCRAFT HANGARS ............. 61
20-004 - Island Gas Pump .............................................................................................................................................. 61
20-062 - Compressed Natural Gas Refueling Stations, Compressors and Storage Facilities ......................................... 62
20-100 - Commercial Repair Garages ............................................................................................................................ 62
20-102(1) - Hazardous Area Commercial Repair Garages ............................................................................................. 62
20-102(3) - Clarification of Pits or Depressions Below Floor Level .............................................................................. 62
20-110(2) - Equipment Above the Hazardous Area ....................................................................................................... 62
20-200 - Anhydrous Ammonia ....................................................................................................................................... 62
20-300 - Finishing Processes .......................................................................................................................................... 62
Applies to Areas Where: .......................................................................................................................................... 63
20-302 - Paint Mixing Rooms ........................................................................................................................................ 63
DEFINITIONS AS PER NFPA 33 .......................................................................................................................... 63
Website Information
Electrical Inspection Act: http://www.qp.gov.sk.ca/documents/English/Statutes/Statutes/E6-3.pdf
Generator Brochure
When defects are due, a bond notice will be issued and a $125.00 administration fee as per Table 4
of the Electric Fee schedule, will be assessed. The invoice will be issued to the contractor at the
same time the bond notice is issued to the applicable bond company for completion of said defect.
2-004 - Permit
Permit Information
It is the responsibility of the contractor to ensure that the information given on the permit application
is accurate and complete. Inaccurate details may result in delayed service connects. In an effort to
make the permit process more efficient, please follow these simple rules:
1. If a utility connection or reconnection is required, mark the appropriate YES box on the permit.
2. If there is no action required by the utility staff, mark the NO box.
3. Ensure the address where the work was performed is accurate and complete. Additional
information is required where no civic address is available (i.e. beaches, new subdivisions,
oilfield lease sites and reserves).
4. Supply work/cell contact phone number in the work description. Failure to provide accurate
and legible information on any permit application could result in the following:
Section 16 of The Electrical Inspection Act, 1993 and Section 7 of The Electrical Inspection
Regulations specifies that all permit applications must be accompanied by the
appropriate permit fee.
All low voltage and extra low voltage installations including lighting, “Home Automation control
wiring” process controls, control/communication cable tray and conduit systems, solar powered
systems, cathodic protection and SCADA systems require permits. The Electrical Inspections
Regulations (available at the Queen’s Printer) have been amended to exempt the requirement of an
Electrical Permit for the installation of communication cabling.
“code” means the latest prescribed edition of the Canadian Electrical Code within the meaning of
subsection 5(2) of the Act;
“communication system” means a communication system as defined in Section 0 of the code;
“control circuit” means a control circuit as defined in Section 0 of the code;
“hazardous location” means a location to which Section 18, 19 (2015 Oil & Gas Code) and 20 of the
code applies;
“patient care area” means an area to which Section 24 of the code applies.
6.1(2)
Subsection 16(2) of the Act does not apply to the following types of work of electrical installation:
All low voltage and extra low voltage installations including lighting, process controls, solar
powered systems and SCADA systems require permits.
Two (2) weeks’ notice is required, and the contractor shall be present to provide access, for an
inspection for the following installations to be approved before concealment, operation and/or utility
connection:
a. main service and/or feeders 600 amps or larger;
b. medical facilities that contain patient care areas;
c. high voltage services, including grounding;
d. renewable energy production such as solar and wind;
e. buildings housing livestock or poultry;
f. high voltage neon signs and outline lighting;
g. sewage lift and treatment plants; and
h. irrigation systems.
Note: 1. The electrical contractor shall ensure that the plans have been submitted to Electrical
Inspections.
2. The electrical contractor shall ensure that any main service and/or feeder conductor/cable
changes made during construction be re-submitted to Electrical Inspections.
3. Where plans have not been submitted and reviewed by Electrical Inspections,
service energization may be denied.
4 Plans are entered in the queue and reviewed in the order they are received.
Submissions missing any of the following information will be moved back in the
queue.
5. Construction set of electrical plans should be submitted prior to construction or at
least 6 weeks prior to the required pre-inspection and the service energization. The
standard turnaround time for review process is approximately four (4) weeks. For
high voltage submissions, the review process is approximately six (6) weeks. The
review process timeline may be longer depending on the number of submissions
received.
6. Upon completion of review, the Plans Review Transmittal Slip will be issued to the
submitter.
NOTE - A copy of Plans Review Transmittal Slip should be made available at the time of the
inspection.
1. One set of construction electrical plans and specifications, as required by Section 19 of The
Electrical Inspections Act, 1993 or as requested by the Electrical Inspections department, shall
be submitted and reviewed by the Electrical Inspections department for:
a. wiring installations of public buildings, and other buildings in which public safety is
involved;
b. main service and or feeders where ampacity is 600A or larger;
c. all renewable energy systems installations (Note: Only 5 KW and larger will be reviewed
with Plans Review Transmittal Slip);
d. sewage lift and treatment facilities;
e. Class A, B and C health care facilities as indicated by Z32-09, including identification of the
patient care areas (See Section 24 in the Saskatchewan Interpretation for definitions);
f. hazardous installations covered by Sections 18, 19 (2015 Oil & Gas Code) and 20 (excluding
single oil well sites);
g. high voltage installations covered by Section 36;
h. generation systems over 12 KW; or
i. any other installation as deemed necessary by the Electrical Inspections department.
• main and feeder conductor type and sizes including installation method i.e.
underground (as per D Tables and Diagrams), conduit, free air, bundled or
raceway;
• panel schedules indicating current and voltage ratings;
• breaker/fuse size;
• conductor material (copper or aluminum);
• maximum short circuit current available at main service;
• grounding and bonding details; and
• transformer ratings, primary and secondary overcurrent protection devices and
conductor sizes.
o Hazardous area classification drawings, which shall include the Auto Ignition
Temperature (AIT) of the hazardous product present at the site
o Patient care areas (clearly identify the different patient care levels)
o Calculated loads
o Cable schedule
o Cable buss
o Electrical equipment layout
o Voltage drop calculation for feeders
b) For high voltage (over 750 V) installations, in addition to the applicable items in (a), the
following information shall be submitted:
o Electrical arrangement complete with plan, elevation, profile views and physical
arrangement of the electrical equipment dimensions to clearly indicate the electrical,
physical and work clearances and relative locations of the equipment;
o Fencing arrangement and details;
o Grounding details (includes NGR wiring details);
o Ground Potential Rise (GPR) study;
o Provisions for metering equipment; and
o Other design information and documents as requested by Electrical Inspections.
(c) Plans submission for renewable energy system shall include, but not limited to:
SaskPower
Gas & Electrical Inspections Division
#177-1621 Albert Street
Regina, SK S4P 0S1
Connection or Reconnection
Where a permit is required for an electrical service alteration or for a reconnection of a service
which has been disconnected for more than twelve (12) months, the service shall be made to comply
with the requirements of the current Canadian Electrical Code. NOTE - Wooden masts will no
longer be connected when a permit is required.
A pre-inspection and plans may also be required in accordance with 2-012 and 2-014.
Flood Procedures
When restoring power to a flood damaged premise, there are several conditions to be aware of and
processes to comply with. An Electrical Contractor must make the electrical system safe to be
reconnected. A permit must be submitted and a SaskPower Electrical Inspector must be
notified before reconnection. All work must meet the requirements of the current Canadian
Electrical Code. When electrical equipment is exposed to water, corrosion is enhanced rapidly. The
equipment may look safe on the outside, but it can be extremely dangerous to reuse.
1. Circuits and equipment that were subjected to the flood must be disconnected and isolated before
power can be restored.
2. If the service (panel box, etc.) has been exposed to water, it must be replaced or completely
disassembled and cleaned. All the breakers must be replaced and the damaged breakers must be
destroyed. When service equipment is replaced, the entire service must be brought up to current
Canadian Electrical Code.
3. All meter sockets must be securely mounted.
4. Grounding must be checked and if repairs are required, they must meet the requirements of the
current Canadian Electrical Code. Ground clamps should be cleaned or replaced.
5. All submerged conductors, cable, equipment, receptacles, switches, etc. must be replaced and the
damaged material destroyed.
6. Conduit systems that have been flooded shall be cleaned as good as possible and a bond wire
will have to be installed with the new conductors.
7. Furnaces and water heaters must be checked over by a qualified Gas Contractor.
When a building has had a fire and the panel has been exposed to smoke and or water, all of the
breakers must be replaced and the old ones destroyed. If the panel has not been damaged by heat
etc., it may be thoroughly cleaned and reused. All receptacles, switches, lighting and heating fixtures
that have been exposed to the smoke and/or water must be replaced and the old ones destroyed. Any
wiring that may have been exposed to flames or heat in excess of its maximum temperature rating
must be replaced. All repair/replacement work must meet the requirements of the current Canadian
Electrical Code.
Skids and movable equipment that have been wired off site shall have a suitable, weatherproof if
required, label affixed to the electrical panel or skid. The label shall include the Saskatchewan
Electrical Contractor’s name, the permit number that was issued for the installation and the date.
Manufactured homes (Ready To Move Homes) shall have a label affixed to the electrical panel or
the inside of the kitchen cabinet. The label shall include the Saskatchewan Electrical Contractor’s
name, the permit number that was issued for the installation and the date. If you require labels,
please contact your local electrical inspector to make arrangements.
Cable Ties
The Canadian Electrical Code mandates the use of approved cable ties, straps or other devices to
support cables and raceways. However, cable ties used for securing need not be approved.
“Securing” should not be confused with “support”. For example, a cable in a horizontal cable tray is
supported by the cable tray and may be secured to the tray with cable ties. In the case of a vertical
cable tray, the cable must be supported by an APPROVED clamp or fastener with the exception of
short drops of 1.5 meters or less. See rule 12-510, Appendix B for approved cable ties.
All electrical equipment requires an overall approval from a Saskatchewan recognized Certification
Body prior to being connected or reconnected electrically. This includes Mobile Homes, Ready to
Move Homes (RTM), as well as any other manufactured product (new or used). For a complete list
of approved certification bodies and certification marks, please visit the website at
www.saskpower.com.
There may be occasions where certification standards do not exist to approve electrical equipment
to. A deviation shall be applied for in accordance with Rule 2-030.
In the specific situation of liquid-filled transformers, certification organizations have yet to identify a
demand for developing a product certification program around this particular electrical equipment.
Consequently, certified liquid-filled transformers are not available.
Conditions
Owners/users required to use liquid-filled transformers are permitted to deviate from Rule 2-024 of
the Canadian Electrical Code provided they meet the following conditions:
Liquid-filled transformers are acceptable when the manufacturer declares that they have
manufactured, inspected and tested the transformer to the requirements of the appropriate and
current Canadian standards. These standards include, but are not limited, to:
CAN/CSA-C2 Single Phase and Three Phase Distribution Transformers
CAN/CSA-C88 Power Transformers and Reactors
CAN/CSA-C227.3 Low Profile, Single Phase, Dead Front Pad-mounted,
Distribution Transformers
CAN/CSA-C227.4 Three Phase, Dead Front Pad-mounted, Distribution
Transformers
Where liquid-filled transformers are manufactured to other than Canadian standards, the
manufacturer must declare that the product has equivalent safety performance as one
manufactured to Canadian standards. Alternatively, a licensed engineering professional may
evaluate and accept the product standard to which the liquid-filled transformer was
manufactured if it compares favorably with the appropriate Canadian standards concerning
safety performance.
2. Product Identification
In addition to meeting the requirements of Rule 2-100 of the Canadian Electrical Code, the
liquid-filled transformer must identify the standard to which it was manufactured.
The following documentation of appropriate marking must also accompany the product;
• a manufacturer’s declaration stating that they have manufactured the product to one or more
appropriate Canadian standards, or
• when manufactured to other than Canadian standards:
i. a manufacturer’s declaration that the product has equivalent safety performance as one
manufactured to the appropriate Canadian standards, or
ii. a licensed engineering professional’s evaluation report indicating the product as having
equivalent safety performance as one manufactured to appropriate Canadian standards.
3. Maintenance
The owner of the equipment shall ensure the product is maintained to industry standards and
manufacturer’s specifications.
All electrical equipment shall be approved as per Rule 2-024 and Appendix B note with the
exception as per Rule 16-222.
For a list of current recognized field certification labels for the Province of Saskatchewan, contact
SaskPower Electrical Inspections at our Toll-Free number 1-888-757-6937, or visit us online at
www.saskpower.com.
Field Inspection reports on skids or moveable equipment shall become part of the equipment and
shall be made available on request. Report shall remain with the equipment.
ELECTRICAL
SAFETY LabTest
AUTHORITY Certification
(ESA)
CSA
QPS
International
ENTELA
ÉVALUATION SUR LE
FIELD EVALUATION
ETL Intertek CHAMP INTERTEK
C 123456
www.qai.org
TÜV
Rheinland of
TÜV America
North
Inc.
America,
Inc.
Underwriter’s
Nemko
Laboratories of
Canada Inc.
Canada
Name of
Certification Certification Marks
Body
The CSA certification mark alone without any identifier indicates products
approved to Canadian National Standards. If another country’s identifier is
present (i.e. US, NRTL), then the small ‘c’ Canadian identifier is required to
indicate that the product also complies with Canadian National Standards.
CSA
International
The ‘Blue Flame’ certification mark is a Canada only mark indicating
compliance to Canadian National Standards. They do not require a small ‘c’
Canadian identifier.
The QPS certification mark requires the small ‘c’ Canadian identifier to
QPS indicate compliance to Canadian National Standards. Identifiers for other
Evaluation countries may be present but in all cases, the small ‘c’ is required
Services Inc.
The MET certification mark requires the small ‘c’ Canadian identifier to
Met indicate compliance to Canadian National Standards. Identifiers for other
Laboratories countries may be present but in all cases, the small ‘c’ is required.
The ETL Intertek Entela certification mark requires the small ‘c’ Canadian
identifier at the 8 o’clock position to indicate compliance to Canadian
National Standards. Identifiers for other countries may be present but in all
cases, the small ‘c’ is required.
Intertek
Testing
Services NA
ETL Intertek Semko has 2 certification marks; the ETL mark and the WH
Ltd. (ETL)
mark. Each mark requires the small ‘c’ Canadian identifier to indicate
(Entela)
compliance to Canadian National Standards.
Identifiers for other countries may be present but in all cases, the small ‘c’ is
required.
The QAI certification mark requires the small ‘c’ Canadian identifier to
Quality
indicate compliance to Canadian National Standards. Identifiers for other
Auditing
countries may be present but in all cases, the small ‘c’ is required.
Institute
The TÜV Product Service certification mark requires the small ‘c’ Canadian
TÜV Product
identifier to indicate compliance to Canadian National Standards. Identifiers
Service
for other countries may be present but in all cases, the small ‘c’ is required.
Name of
Certification Certification Marks
Body
The TÜV Rheinland certification mark requires the small ‘c’ Canadian
TÜV
identifier to indicate compliance to Canadian National Standards.
Rheinland of
Identifiers for other countries may be present but in all cases, the small ‘c’
North America
is required.
The Curtis – Straus LLC certification mark requires the small ‘c’ Canadian
Curtis-Straus identifier to indicate compliance to Canadian National Standards.
LLC Identifiers for other countries may be present but in all cases, the small ‘c’
is required.
The NSF International certification mark requires the small ‘c’ Canadian
NSF identifier to indicate compliance to Canadian National Standards.
International Identifiers for other countries may be present but in all cases, the small ‘c’
is required.
The Nemko Canada certification mark requires the small ‘c’ Canadian
Nemko identifier to indicate compliance to Canadian National Standards.
Canada Inc. Identifiers for other countries may be present but in all cases, the small ‘c’
is required.
The Nemko CCL Inc. certification mark requires the small ‘c’ Canadian
Nemko CCL identifier to indicate compliance to Canadian National Standards.
Inc. Identifiers for other countries may be present but in all cases, the small ‘c’
is required
LabTest The LabTest certification mark requires the small ‘c’ Canadian identifier to
Certification indicate compliance to Canadian National Standards. Identifiers for other
Inc. countries may be present but in all cases, the small ‘c’ is required.
Name of
Certification Certification Marks
Body
ENEFEN
Energy The ENEFEN certification mark is a Canada only mark indicating
Efficiency compliance to Canadian National Standards. It does not require a small ‘c’
Engineering Canadian identifier.
Ltd.
The SGS North America Inc. certification mark requires the small ‘c’
SGS NORTH Canadian identifier to indicate compliance to Canadian National Standards.
AMERICA, Identifiers for other countries may be present but in all cases, the small ‘c’ is
INC. required.
ELECTRICAL The ESAFE certification mark requires the small ‘c’ Canadian identifier to
SAFETY indicate compliance to Canadian National Standards.
AUTHORITY Identifiers for other countries may be present but in all cases, the small ‘c’ is
(ESAFE) required.
SPECIAL/FIELD INSPECTION
Certification Body
AGENCIES
SPECIAL/FIELD INSPECTION
Certification Body
AGENCIES
SPECIAL/FIELD INSPECTION
Certification Body
AGENCIES
Requests for special permission shall be made in writing to the Chief Electrical Inspector, giving all
details pertaining to the requests. If acceptable, permission applying to the particular installation
will be confirmed in writing.
Labels shall be on the exterior and readily visible without opening equipment doors
With the application of energy efficiency programs in Saskatchewan, high efficiency lighting
technologies and various lighting retrofit kits are popular. There are several options for retrofitting
standard tubular fluorescent luminaries, with more energy efficient lamps.
The program that is in place where fluorescent luminaries that are suitable for T12 lamps are
modified to accept T8 or T5 lamps are as follows:
• Luminaries that have modifications done to the reflectors or lamp holders shall be recertified
and labeled by an accredited certification organization.
• The retrofit of luminaries may be accepted under the original certification when the following
conditions apply:
- the work is covered by an electrical permit;
- the replacement equipment bears the mark of a recognized certification agency;
- the replacement equipment is rated for the application and draws no more power than the
original equipment; and
- the replacement equipment is physically compatible with the luminaire with no
modifications.
• Please note that in all cases, each retrofitted luminaire must be provided with a label containing
the following information:
- voltage;
- amperage;
- date of install;
- installed by (contractor name); and
- permit number.
Retrofit kits specified above require a luminaire conversion and usually involve replacing the lamp,
rewiring the luminaire and in some cases, replacing an existing ballast with an LED driver, or
directly connecting the lamp to the supply circuit.
Although there are differences in installation of various retrofit kits, for all of them it is very
important to consider the following requirements:
• disconnect the fluorescent luminaire from the power source before starting the retrofit
installation;
• the retrofit kits are installed in accordance with manufacturer’s wiring installation instruction.
Hazardous location luminaire certifications investigate all components to ensure they are not, or will
not become an ignition source.
Electrical Inspections requires that luminaire retrofit kits be certified to the appropriate standard.
Field modifications to luminaires including internal wiring re-work bypassing existing ballast and
wiring directly to the socket with phase voltage, shall be field certified by an approved inspection
body.
Receptacles shall be installed with mechanical protection to prevent damage by vehicles by one of
the following or other equivalent means:
c. A reinforced concrete post with a dimension of not less than 300 mm may be used and shall be
installed to a height of not less than 750 mm and to a depth of not less than 750 mm below grade.
The receptacles and conduit shall be installed on the face of the post not exposed to vehicular
damage. The receptacles may, if desired, be installed on the face of the post exposed to vehicles
provided the conduit and outlet box are installed within the post. Mounting height of the
receptacles shall not be less than 750 mm above finished grade. As an alternate to the concrete
post, a treated wooden post of minimum 150 mm x 150 mm may be used; or
d. Bollards or permanently installed curb stops, mounted 1.2m from the center of the curb stop to
the pedestal or receptacle, for drive in parking locations and placed in front of the receptacles to
prevent vehicles from coming in contact with receptacles, shall be accepted as mechanical
protection.
Conductors for wiring of these receptacles shall have insulation or covering suitable for installation
and use at temperatures down to minus 40 degrees C except for conductors approved for and
installed underground.
Currently there is a concern with free standing services falling over from a lack of support. Free
standing services shall meet the following requirements with all posts set into a minimum depth of
750mm and additional support to deal with any cantilever forces placed upon the structure.
a) 100A - 200A services shall be supported on a minimum of 2 pressure treated 4x4 posts
with a ¾” pressure treated backing.
b) 400A - 800A services shall be supported on a minimum of 3 pressure treated 4x6 posts
with a ¾ “ pressure treated backing.
c) 1000A and larger - same as (b) and shall have additional support as required.
Contractors are required to field mark equipment requiring adjustment, examination, servicing or
maintenance while energized with a warning label identifying potential electric shock and arc flash
hazard. This applies to all new equipment as well as used equipment that is being returned to
service. See Appendix B for labeling requirements.
2-324 - Electrical Equipment near Combustible Gas Equipment (see also 6-408)
The clearance around a natural gas regulator relief vent to arc-producing electrical equipment shall
be 1 meter and 3 meters for propane regulator relief vents as per CSA B149.1-15. Note – This
clearance is a spherical radius.
Revenue meters, hot tub and air-conditioning disconnects are examples of arc-producing electrical
equipment.
SECTION 4 - CONDUCTORS
Application Examples
Examples 1 to 3 below illustrate how to apply correction factors to the ampacity for the temperature
rating of the conductor (90°C).
Table 39
Minimum permitted size for 3-wire 120/240 V and 120/208 V service conductors for single
dwellings, or feeder conductors supplying single dwelling units of row housing of apartment and
similar buildings and terminating on equipment having a conductor termination temperature of not
less than 75 °C [See Rule 4-004(23)]
* These ampacities are the ampacities given in Tables 2 and 4 for 75°C, increased by 5% in accordance with Rule
8-106(1). See Note 2
Notes:
(1) This Table applies only to conductors, sized in accordance with Rules 8-200(1), 8-200(2), and 8-202(1)
(2) The 5% allowance in Rule 8-106 (1) cannot be applied to these values as the 5% allowance has already been added
to the applicable 75°C ampacities from Tables 2 and 4
(3) If the calculated load exceeds the limit shown in the table, the next larger size conductor shall be used
Example 1
Find the minimum size of service conductors required for a service with the following criteria:
Because our main breaker does not have a maximum conductor termination temperature
marked on it, [4-006(2)(b)], we have to derate the conductors for 75 ̊C. As per Note (2) under
Table D10B. “Underground ampacities for a conductor temperature of 75 ̊C may be obtained
by multiplying the appropriate ampacity at 90 ̊C conductor temperature by the derating factor
0.886”
From the column “4/phase, Detail 4” we multiply the values by 0.886 until we find one that
exceeds 475 amps.
552 amps (1750 MCM) x 0.886 = 489 amps
This service requires 4 conductors of 1750 MCM ACWU90 per phase.
Example 2
Find the minimum size of service conductors required for a service with the following criteria:
Where a conductor is terminated on equipment with a 60°C or 75°C rating, the maximum conductor
ampacity shall be based on the 60°C or 75°C column of Tables 1, 2, 3 or 4.
When equipment termination temperature rating is not marked on the equipment it is to be:
• All relevant correction factors being determined from Rule 4-004, such as Table 5A, will apply
to ampacity rating from the equipment termination temperature rating not the insulation
temperature rating when the equipment termination temperature rating is required to be used.
• High voltage equipment’s termination temperature rating when not marked you are allowed to
consult the manufacturer.
• Equipment termination temperature rating applies to the first 1.2 m of conductor from the
connection point on the equipment.
4-010 - Induced Voltages and Currents in Metal Armour or Sheaths of Single Conductor
Cables
Although the Canadian Electrical Code, Part I does not specifically mention harmonics, harmonics
cause heating in the neutral conductor. Harmonics caused by certain types of non-linear loads (e.g.
office computers, printers, variable speed motor drives, or certain types of electric discharge
lighting) should be taken into consideration when sizing neutral conductors.
Colour coding of branch circuit conductors and service conductors are not a mandatory requirement.
This rule states that where colour coding is required, the colours shall be red, black and blue. The
SaskPower Electric Service Requirements, Clause 3.6.1(b) states that where termination is made by
SaskPower such as splitter box or CT metering, conductors must be colour coded. If CT metering is
used after the main disconnect, then colour coding must be used to that point.
The maximum number of consumer services from a single supply service is four. Where more than
four meters are required, the contractor must make arrangements with the utility and meet Utility
requirements.
1. The utility will run two services to the same location on a building. The Electrical Contractor
can install two weatherproof splitters with a maximum of four meter sockets from each splitter;
providing a maximum of eight meters on a building. Splitter sizes may vary;
2. The utility will run one service to each end of a building. The Electrical Contractor can install
one weatherproof splitter on each end and four meter sockets; providing a maximum of eight
meters on a building. Splitter sizes may vary; or
3. Install an approved metering electrical room.
Note: If the two services are permitted, then they will require a label stating that there are two
services and the location of each.
6-112(2) - For the purpose of this rule ‘ground normally accessible to pedestrians’ includes patios
and decks.
6-112(4) - Appendix B note to Rule 6-112(4) states an acceptable manner for mast support is one
where three (3) support clamps are used, of these, the upper most is required to be a complete
through bolt assembly consisting of a minimum 12 mm bolt, nut and washer.
As an alternative to the “through bolt” requirement, with the permission of the district electrical
inspector, a unistrut support may be allowed to be lag bolted to the exterior of the building (into
structural members) for mast support. A rigid 2-hole strap and spring nuts shall be used on the mast
to secure it to the unistrut. This may be allowed on a case by case basis, after review and
acceptance by the local inspector. It should only be considered when it is impractical or impossible
to install the normal through bolt support.
200A and 400A dual lug meter sockets may be installed where a customer wants two consumer
services and is acceptable to the Utility. The subdivision of the consumer services can be
accomplished within the dual lug meter socket provided that the total current rating of the two
consumer service disconnects does not exceed the ampere rating of the meter socket.
In rural areas where the 400A self-contained meter socket is used, a service rated disconnect(s) is
required immediately after the meter socket.
e.g. 1-400A or 2-200A disconnects, etc.
Each consumer’s service shall be provided with a single service box, except where a panelboard can
employ no more than two single-pole breakers, one two-pole breaker, or one three-pole breaker and
is service entrance rated.
6-206(1)(c) - Panels
Insulated exterior walls are considered an undesirable location for recessing of panels.
Panelboards shall be installed in the building being served and the length of unfused service
conductors shall not exceed six (6) conduit meters. Where the service box or other consumer’s
service equipment is located beyond six (6) conduit meters from the point where unfused service
conductors enter the building, the conductors shall be run in threaded rigid metal conduit for the
entire length inside the building.
Note: Metallic service conduits or service cables with metallic armor require bonding bushings in
the main service. See 10-604 and 10-606 - Assuring Continuity at Service Equipment on page 44.
1. The service disconnecting means shall be permitted to be placed on the outside of the building
or on a pole, provided it is:
a. installed in an enclosure approved for the location or protected against the weather;
b. protected against mechanical damage if it is located less than 2 m above ground; and
c. service entrance rated.
2. Grounding must be done at the service disconnect (neutral grounded), after the disconnect the
neutral must be insulated and isolated from the bond. See Rule 10-200 Page 42 & 43
NOTE: The SaskPower supplied F cabinet breaker shall not be considered as overcurrent protection
for the service or cables.
The oil field well controller shall not be considered a service disconnect unless approved as such.
This deviation has been removed from the oil and gas code.
1. The service disconnecting means shall be permitted to be placed on the outside of the building,
on a pole, or at the first well site, provided it is:
a. installed in an enclosure approved for the location or protected against the weather;
b. protected against mechanical damage if it is located less than 2 m above ground; and
c. service entrance rated.
2. Grounding must be done at the F cabinet and a bond conductor carried to each individual service
at the well site. All electrical equipment beyond the service disconnect shall be bonded together
in accordance with Table 16A and each site shall have a ground plate or two ground rods
installed with a minimum #6 copper for an equipotential plane.
NOTE: The SaskPower supplied F cabinet breaker shall not be considered as overcurrent protection
for the service or cables and are not permitted to be operated by ‘other than SaskPower district staff’.
Service conductors installed underneath a house trailer/mobile home must be approved for the
location and supported to the underside of the mobile home or buried. Unarmoured service
conductors must be installed in a raceway from the point where they issue from the earth.
For the purposes of 6-206(1)(c), the 6 m rule does not apply to underneath the mobile home.
Caution must be taken by the Electrical Contractor when installing a customer owned underground
service from the meter socket to the panel location. The consumer’s underground cable must be
installed tight to the basement wall anywhere within 1.5 meters of the meter socket location. This
will prevent the cable from being damaged when the utility trenches in their underground service
cable from the pole or pedestal to the socket. Once the cable is past the 1.5 meter distance, it may
then be installed out away from the basement wall.
As per 12-012(11) & (12), the installation will also require frost sleeves at both ends and marking
tape must be installed in the cable trench.
Underground service entrance cable as described in Table 19 shall be allowed to be supplied from a
branch circuit overcurrent device when used as an underground feeder to a new service.
It is recommended that the sealing be performed on the warm side to prevent condensation
build-up in the conduit. Conduit may be sealed on both the warm and the cold side.
The grounded circuit conductor must be brought into the CT cabinet and terminated to meet
metering requirements.
Furnace, water heater, air exchanger, dryer and similar exhaust vents shall not be installed directly
above or directly below or within 1 m horizontally of a meter socket.
Basic load – the load of lighting and receptacle circuits, based on the outside dimensions of a
specific area of building occupancy, as listed in Table 14.
Calculated load – the load calculated in accordance with the applicable requirements of Section 8
Demonstrated Load - historical maximum demand watt information recorded over at least a 24
month period for the same type of facility equated to watts per m2.
Precautions must be taken to prevent any services or branch circuits from exceeding 5% voltage
drop from the utility to the end use, with no feeder or branch circuit exceeding 3%. The calculation
of voltage drop on services and branch circuits is based on the connected load, or 80% of the
overcurrent device for unknown loads. See Rule 8-102 and Table D-3 in the CEC and Table D-23 as
shown below.
2015 Saskatchewan Interpretations Page 39
Electrical Inspections
For Aluminum Conductors, find the correct size copper and add 2 AWG sizes
Table 68
This refers to general purpose circuits (general purpose receptacles)
not lighting circuits or appliance circuits.
Maximum conductor length (meter) measured from the supply side of the consumer’s service to the
furthest point of utilization on a circuit using 90˚C rated copper conductor at 30˚C ambient
temperature for 120V single phase ac circuits (2 wire circuits)
Overcurrent
AWG
Protection
(Cu)
Setting/Rating
15A 20A
#14 38m
#12 60m 50m
#10 96m 78m
Water heaters are considered continuous loads and, therefore, the circuit conductor and the
overcurrent device shall be loaded to a maximum of 80%. Example - if the water heater is rated at
3000 watts on 240 volts (12.5A), you will require a #12 AWG conductor and a 20 amp breaker.
8-200 & 8-202 - Demand for Electric Vehicle Charging (see also 86-300)
Single Dwellings
8-202(3)(d) - Any electric vehicle charging equipment not located in dwelling units with demand of
100%.
The maximum number of “unspecified load” or “general purpose” receptacles on a branch circuit is
12 regardless of the circuit rating.
Ground fault indication activated by a ground fault shall be labeled and visible to persons monitoring
the status of the system regardless of other monitoring systems being implemented. In oil field
distribution, all loads require ground fault indication lights at each site.
For the purposes of Rule 10-200, the term ‘objectionable flow of current’ shall be defined as “any
current that flows over conductors for which they were not intended and/or designed to
accommodate; such as neutral current over bonding and/or grounding conductors, neutral current
over metallic piping”. Caution shall be exercised to prevent this situation from occurring.
An example of this is where the interconnection of system neutrals and the bonding of metallic
objects creates a path by which, all of or part of, the neutral current can flow through the bonding
and/or grounding conductors.
Electrical Inspections has become aware of some unsafe conditions due to parallel neutral current
return paths. In an effort to minimize this potential hazard, Inspections will now require the
following methods of grounding and bonding for low voltage services (not exceeding 750V).
Note: Buildings housing livestock are mandated to have a bonding conductor to be run with the
feeder conductors as well as a recommended grounding electrode at the building as per Figure 1.
Note 1 - Consumer owned transformer is grounded in accordance with Section 10 and the protective
bond is sized to Table 16A and is carried with the main conductors beyond this point. This is because
there will be known primary protection installed on this installation.
All other equipment grounding is for the purpose of establishing an equipotential plane.
Figure 1
The service point of connection may be at the meter socket, (overhead or underground services),
utility transformer or the customer owned splitter.
Note 1 - The protective bond on the line side of the consumer overcurrent protection shall be sized as per
Table 16A.
- Where multiple conductors are used, the protective bond conductors shall be paralleled as well.
Figure 2
For solidly grounded systems, the system grounded circuit conductor/neutral shall be installed from
the system to the main service, whether neutral loads are being served or not. This conductor, when
neutral loads are not being served, shall be sized as per Rule 10-814.
If a neutral is not required or utilized, the bond or bare conductor incorporated in the cable may be
acceptable as the system grounded circuit conductor on the line side of the service.
When an NGR is installed on the service, the neutral conductor should not be brought into the main
switchgear, unless otherwise required for metering purposes, or to service line to neutral loads.
NGR systems are not solidly grounded systems. The conductor from the transformer to the NGR
must take the most direct route and is not required to enter the main service disconnect. Rule 10-
1108 provides a number of conditions that must be met with regards to this conductor:
The Xo point of many transformers are being installed without a connection to the transformer
enclosure. The Xo shall be grounded as per Rule 10-106 and the grounding conductor shall be sized
as per Rule 10-812. The connection between the Xo and the enclosure shall be electrically
continuous to provide a fault current return path to the Xo of the transformer secondary. This
conductor or busbar shall be sized as per Table 16A for conductors or 16B for busbars.
10-208(1)(b) - Grounding Connections for Two or More Buildings or Structures Supplied from
a Single Service
• The non-current-carrying metal parts of the electrical equipment in or on the building or structure
shall be bonded to ground by a bonding conductor run with the feeder or branch circuit
conductors. If USEB is used, the concentric neutral shall be taped to isolate it from the cabinet
and the bonding conductor. The bond screw in the panel must be removed.
• To create an equal potential plane at the building, a grounding electrode should be installed and
connected to the panel bonding system. The neutral shall remain isolated.
The area around buildings housing livestock and livestock watering bowls is considered to be a
corrosive environment and aluminum wiring shall not be allowed.
When a furnace or similar piece of equipment is being replaced, the Electrical Contractor is
responsible for bonding the gas line as required by the Canadian Electrical Code. The branch circuit
cable, providing it has an internal bond conductor and the low voltage thermostat cable, does not
require replacement. Also see Section 26, Rule 26-806(1)(5)(6)(7), page 78.
Caution: Some new furnaces require 20 amp circuits.
The requirements for bonding are more restrictive at services than downstream from the main
disconnect. Service equipment and enclosures may be called upon to carry heavy fault currents in
the event of a line-to-ground fault. The service conductors in these enclosures have only short
circuit protection provided by the overcurrent device on the line side of the utility transformer.
While there are various options available to assure the continuity of service equipment and
enclosures, the use of a Bonding Bushing is the only acceptable method to ensure the bonding of
metal conduits or the metal armour of cables that use locknuts as a method of attachment to an
enclosure. It is important to recognize that concentric or eccentric knockouts in enclosures such as
panelboards have never been investigated for their ability to carry fault current.
All weatherproof splitters must be bonded. This may be achieved by bonding the enclosure to the
neutral when on the line side of the service disconnect. When the splitter or junction box is on the
branch circuit side, the enclosure shall be bonded with a bond conductor or a metallic raceway.
One ground plate, two ground rods or a field assembled electrode are required for:
• a temporary service;
• bus shelter;
• phone booth;
• cable television distribution equipment;
• signs; or
• other similar installations: and
• row housing such as semi-detached, duplex, triplex or fourplex;
• additional services on farms;
• acreages; or
• single family dwellings.
Be aware of 10-200 and the new grounding drawings Figure 1 & Figure 2
Recommended practices for the installation of a lightning protection system, including lightning
rods, interconnecting conductors and ground electrodes, are given in CAN/CSA-B72. Other national
and international industry-recognized standards on lightning protection may also be available. Also
as per Rule 12-016 where lightning down conductors are installed, electrical wiring shall, where
practicable, be kept at least 2 m from such conductors, except where bonding is provided in
accordance with Rule 10-702.
Note: Lightning protection system installations are to be installed by a licensed contractor and
require an electrical permit.
10-802(2) – Bare aluminum shall not be installed in corrosive locations such as direct earth burial or
masonry.
Ground fault indication activated by a ground fault detection shall be labeled and visible to persons
monitoring the status of the system regardless of other monitoring systems being implemented.
These Rules speak to ungrounded systems and impedance grounded systems. Our department has
become aware that, oftentimes, the grounding electrodes of the system supply and the facility are not
being connected (bonded together). It is felt that, unless there are extenuating circumstances in play,
these electrodes should always be bonded together. The reasoning is that, without this connection,
unsafe conditions can be present. These unsafe conditions are concerns over dangerous ‘touch’ and
‘step’ potentials and also the inability of the detection devices to function as designed. In the
‘ungrounded’ scenario, the fault detection device would not sense a fault at the source. With respect
to an ‘impedance grounded system’, the fault at the source would not flow through the impedance
device, thereby not allowing the detective devices of the impedance grounding device to recognize
the fault and perform alerting functions.
An example of ‘an extenuating circumstance’ is where the Utility is not mandated by the Canadian
Electrical Code to provide a conductor for the purposes of this interconnection. We would still
suggest that this connection be provided, by others, to mitigate the unsafe conditions described
above.
As always, should anyone have questions or concerns, contact the Electrical Inspections Department.
The conductor connecting the neutral grounding device to the neutral point of the transformer,
generator or grounding transformer shall meet the requirements of Rule 10-1108 and should not be
installed to the main switchgear, unless otherwise required for metering purposes or to facilitate
neutral loads as per subrule (4).
NGR systems are not solidly grounded systems. The conductor from the transformer/source to the
NGR must take the most direct route and is not required to enter the main service disconnect. Rule
10-1108 provides a number of conditions that must be met with regard to this conductor.
The addition of subrule (5) mandates that the path from the neutral point through the neutral
grounding device to the system grounding electrode shall be continuous.
When a ceiling space such as a truss floor system is used as a return air space, the wiring in this
space must be FT-4 rated; i.e. Armoured cable.
Electrical wiring shall not be installed within 600 mm of a utility natural gas line.
Electrical wiring may be installed in the same trench as customer-owned propane or natural gas lines
provided the conductors are placed at a greater depth and a separation of at least 300 mm of earth or
150 mm if a treated plank is installed between the piping and conductor.
Customer owned propane or natural gas lines refers to customer lines supplying customer premises.
Customer owned propane or natural gas lines are to be buried at a minimum of 381 mm (15 in.) and,
if subject to vehicular traffic, a minimum of 600 mm.
All underground raceways or cables subject to movement require provisions to be made to prevent
damage to the conductors or the electrical equipment. The intent of this rule is to avoid damage to
the raceway or cable (during settlement/frost).
Underground installations must have a suitable marking tape buried halfway between the cable and
grade level and the tape must extend the entire length of the trench.
12-120(1) - Horizontal
Permanently installed cables and conduits supplying motors, pumps, pressure switches or any other
electrical equipment shall be supported as required by Section 12. Cables and conduits where
exposed and subject to damage must be supported off of the ground by an approved method such as
cable tray, strut, etc. Cables must be supported within 300 mm of any junction box (this includes
oil wells). When installing cables, you must ensure that there is no stress on the connectors from
the weight of the cable.
12-120(2)(4) - Vertical
Vertical runs of armoured or sheathed cable such as TECK90, RA90, RC90, AC90 and ACWU90
shall have the internal cable assembly supported at intervals not exceeding those specified in Table
21 or by:
a. incorporating a bend or bends equivalent to a total of not less than 90 degrees at intervals not
exceeding the distances specified in Table 21;
b. installation of a horizontal run of the cable not less than the length of the vertical run; or
c. use of cable that is specifically designed for vertical runs.
The design and construction of cable types such as TECK90, RA90, RC90, AC90 and ACWU90 do
not provide internal support between the sheath or armour and internal cable assembly. Horizontal
runs of TECK90, RA90, RC90, AC90 and ACWU90 that equal or exceed the vertical length or that
incorporate a bend or bends equivalent to a total of not less than 90 degrees reduces the strain on
conductor terminations.
The use of cable ties shall be of the specific type approved for the purpose.
Type 1 and Type 11* Approved type of cable tie but not specifically approved to provide primary
support for a flexible conduit, flexible tubing, or cable in accordance with the
Code. Examples of uses: in approved equipment; to bundle wires for circuit
identification or to maintain critical spacing in cabinets, or to otherwise
provide supplemental means for routing wires, flexible conduits, flexible
tubing or cables.
Type 2 or Type 21* Approved type of cable tie but not specifically approved to provide primary
support for a flexible conduit, flexible tubing, or cable in accordance with the
Code. Examples of uses: in approved equipment; to bundle wires for circuit
identification or to maintain critical spacing in cabinets, or to otherwise
provide supplemental means for routing wires, flexible conduits, flexible
tubing or cables.
Type 2 also identified Approved type of cable tie but not specifically approved to provide primary
as AH-2 support for a flexible conduit, flexible tubing, or cable in accordance with the
Code. Examples of uses: in approved equipment; to bundle wires for circuit
identification or to maintain critical spacing in cabinets, or to otherwise
provide supplemental means for routing wires, flexible conduits, flexible
tubing or cables, and suitable for use in air-handling spaces (plenums) in
accordance with Rules 12-010 (3), (4), and (5), and 12-020.
Type 2S or Type 21S† Specifically approved to provide primary support for a flexible conduit,
flexible tubing, or cable in accordance with the Code.
Type 2S or Type 21S† Specifically approved to provide primary support for a flexible conduit,
also identified as AH-2 flexible tubing, or cable in accordance with the Code, and suitable for use in
air-handling spaces (plenums) in accordance with Rules 12-010 (3), (4), (5),
and 12-020.
Note:
* For the purpose of this Code, Type 1 is identical to Type 11, and Type 2 is identical to Type 21,
† For the purpose of this Code, Type 2S is identical to Type 21S
ACWU or other metallic armoured cables without an inner protective jacket shall incorporate an
anti-short or other approved protective devices.
Table 6 was revised to Tables 6A to 6K to cover the maximum number of stranded conductors of
one size in conduit and tubing. New Tables were added to correspond with the different stranded
conductor insulation types and sizes given in Tables 10A and 10B.
Tables 9A to 9J covering the diameter and cross-sectional area of conduit and tubing were added and
revised to correspond with the dimensions required from each Standard for the specific type of
conduit and tubing.
Calculating fill utilizing values from Tables 9A to 9J and Table 10C will give the maximum results
for fill using solid conductors. See charts below as examples.
Notes - These are for 600V unjacketed wires as listed in column 1
12-910 - Tables
PVC conduit shall be installed as per manufacturer’s specifications and the CEC. For example,
assuming a temperature change of 70 degrees C, this would mean a minimum of one expansion joint
or more may be required depending on the maximum range of the expansion joint. See Rule 12-
1012 and Appendix B.
Conduits shall be installed as per manufacture’s specifications and the CEC. The formula to
determine if excessive expansion requires mitigation is as follows:
Example:
For a 20m run of rigid PVC conduit when the minimum expected temperature is -400C and the
maximum expected temperature is 300C the total expansion is:
ET= 20m x (40 + 30) x 0.520 = 73mm. So, as per the Rules, this exceeds the maximum
allowed of 45mm. Therefore, depending on the travel of the expansion joint, one or more
would be required.
EMT shall not be used in car wash bay area’s due to salt and chemical contaminants. [See also 22-
200(1)]
Bonding conductors are required for EMT installations in the following uses:
(a) concrete or masonry slabs in contact with the earth;
(b) a wet location; or
(c) outdoor locations.
12-2200(7) - Cable trays shall be permitted to have reduced clearances through chases, under
grating, under process pipes, and other such obstructions.
12-2200(8) - At least one expansion joint shall be installed in any cable tray run where the expansion
of the cable tray, due to the maximum probable temperature change during and after installation, can
damage the cable tray as per the manufacturer’s instructions.
The requirements for the installation of Teck cable and tray cable of different voltages that run
adjacent to each other in cable trays are as follows:
1. A barrier is not required to separate Teck cable or armored cable of different voltages that are
installed in the same cable tray.
2. A barrier is only required when tray cables type TC of different voltages are installed in the
same cable tray, if the voltage in one or more cables exceed 750 volts.
Where Non-Jacketed interlocking metal armour/continuous metal sheath cable is installed in cable
tray, bonding is not required for the tray as long as it is labelled “INTERLOCKING METAL
ARMOUR OR CONTINUOUS METAL SHEATH CABLES ONLY” every 10M or less.
Metal cable tray must be bonded to ground when containing only PVC or similar jacketed armoured
cables i.e. Teck or ACWU cable.
Cable bus is a self-contained engineered system incorporating a special tray, cables, cable supports
and cover. Rules apply only to the installation of cable bus as a complete system approved for the
purpose.
A complete set of engineering and installation drawings must be submitted to the Electrical
Inspections Department.
Entry of metallic conduit or cables into non-conductive junction boxes, i.e. fiberglass or PVC,
requires bonding bushings and all bushings must be bonded together. Metallic fittings used in a non-
;
Where a pendant ceiling fan and all possible accessories weigh less than 16 kg and are intended to be
supported on an outlet box, the outlet box shall be approved and marked for fan support and:
Pendant ceiling fan and all possible accessories weighing 16 kg or more shall be supported
independent of the outlet box.
12-3000(10) & 12-3002(2) - Floor boxes shall be installed in accordance with the manufacturer’s
installation instructions for the type of floor intended. Flush mounted floor box covers shall be
specifically approved for the type of floor intended.
Caution must be taken to prevent overloading of cables which do not have customer protection on
the supply side. Example - on a farm service center, where the feeder cable terminates in an exterior
splitter for the purpose of supplying more than one service, the total amperage of all main breakers
may not exceed the ampacity of the feeder cable.
a) Ensure the trip settings for the adjustable overcurrent protection device are documented and on-
site for the inspection;
b) A lamacoid plate with the overcurrent setting displayed on the main breaker is required; and
c) Feeder markings may be required.
1. The rating or setting of overcurrent devices shall not exceed the allowable ampacity of the
conductors they protect; and
2. Except as provided by other sections of the Code, the rating of overcurrent protection shall not
exceed:
a. 15 A for No. 14 AWG copper conductors;
b. 20 A for No. 12 AWG copper conductors;
c. 30 A for No. 10 AWG copper conductors;
d. 15 A for No. 12 AWG aluminum conductors; and
e. 25 A for No. 10 AWG aluminum conductors.
Extra low-voltage power circuits installed in hazardous locations on oil field sites (i.e. Solar and 12
volt equipment) must be installed in accordance with the applicable rules of Section 18.
18-008 - Hazardous Area Classification - Main Floor Plan - Seed Cleaning Plant
Recently, there has been an increased interest in the development of bio diesel facilities throughout
the province. SaskPower Inspections wants to inform all Electrical Contractors of items that may
affect an installation.
These facilities must be classified by an Electrical Engineering firm to the proper classification of
the Canadian Electrical Code. Plans must be submitted to Electrical Inspections Plans review.
As per Rule 18-008 of the CEC, Canola crushing is a Zone 20 location unless engineered otherwise,
and all wiring must meet the minimum Canadian Electrical Code requirements for the installation.
Canola storage and product transferring would fall under the same area classification.
In the process of creating bio diesel, an additive must be added. If that product is methanol or
another volatile additive, a hazard arises. The process must now meet the intent of Rule 18-006
classification; the area classification is either Zone 0, 1 or 2 depending on the engineering area
classification. Storage of methanol is under the same area classification. Bio diesel storage is the
same as regular diesel and must also meet all other provincial codes and rules.
SaskPower Inspections wants to maintain a safe installation for both the facility and its employees.
All electrical work must be completed by a Saskatchewan Licensed Electrical Contractor and meet
the requirements of the Canadian Electrical Code.
The CEC classifies these areas as Zone 22 locations without adequate dust collection. Areas may be
reclassified by a Professional Engineer. For the purposes of this rule, non-commercial residential
garages and farm shops may not be considered wood working plants.
The following will be permitted where good housekeeping habits and adequate dust collection
equipment is installed:
a. Panel boxes, controllers, etc. shall be dust tight or in dust tight enclosures.
b. Wall surface wiring shall be threaded rigid, EMT (with rain-tight connectors) or Teck cable with
dust-tight Teck connectors.
c. Ceiling surface wiring may be ordinary location wiring methods.
d. Boxes shall comply with Rule18-302(2).
e. Concealed wiring may be type AC or NM cable.
f. Concealed boxes and fittings may be ordinary type.
g. Switch and receptacle covers shall be of the weatherproof type.
h. Where duplex receptacles are used, a separate self-closing cover will be required for each section
of the receptacle.
i. General purpose fluorescent lighting fixtures may be installed:
i) if mounted directly on the ceiling; or
ii) if suspended and provided with adequate dust shields to prevent the accumulation of dust.
CSA has adopted the IEC Standard for Equipment Protection Levels (EPL’s) as a requirement for
marking on equipment in Hazardous Locations. This marking system will now appear on new
hazardous location equipment.
The intent of this rule is not to declassify an area; it is only to be used where suitable equipment
approved for the area is not available with proper classification for a hazardous area.
Cable Seals
A cable entering or leaving a Zone 1 location must be sealed where it first terminates in the
hazardous location regardless of the type of box it enters.
Cable Seals
When a cable is leaving the hazardous area from a box that was not required to be explosion proof, a
seal is not required regardless of the cable length, except if the cable is terminating in a non-
hazardous location with a negative atmospheric pressure greater than 0.2 kPa or unless engineered
otherwise.
Cables and conduits that are ran through the Zone 1 area need to meet the wiring methods and
sealing requirements of Section 18 whether they are associated with the pump or not.
20-062 - Compressed Natural Gas Refueling Stations, Compressors and Storage Facilities
Compressed natural gas refueling stations, compressors and storage facilities shall be classified as
shown in Table 64.
Section 20 now only applies to commercial garages where vehicles powered by gasoline, propane, or
other flammable fuels are serviced or repaired.
All adjacent rooms not suitably cut off with a 50 mm barrier are classified as hazardous up to 50 mm
above the parking floor.
“Any area below grade where every day work does not take place; i.e. sump pit, etc.”
For the purpose of Rule 20-102(2), a Below Grade Room is defined as:
“Any area where daily work and storage of product takes place; i.e. vehicle service area, storage
areas, etc.”
“Reclassification” of any areas with regards to ventilation must be done through a Professional
Engineer, complete with stamped drawings.
This rule had called for the use of totally enclosed type light fixtures below 3.6 m in a commercial
repair garage but has been relaxed to being protected from mechanical injury by a guard or by
location.
Anhydrous ammonia is considered to be a volatile flammable liquid and, as such, shall be wired in
accordance with Rules 20-202 to 20-212, regardless of the aggregate capacity of the tank.
We are starting to see the use of “water base” or “waterborne” paints in automotive and other
finishing processes. While the base coat may be “water base” or “waterborne”, other components of
the paint are flammable and therefore Section 20 still applies, unless it can be proven with the MSDS
sheets that there are no flammable components involved.
• Paints, lacquers or other flammable finishes and fiberglass processes are regularly or frequently
applied by spraying, dipping, brushing or by other means;
• volatile flammable solvents or thinners are used; or
• readily ignitable deposits or residues from such paints, lacquers or finishes may occur.
All paint mixing rooms are classified as Class I, Zone 1 locations unless it can be proven that all the
products involved are non-flammable.
SPRAY AREA - Any area in which dangerous quantities of flammable or combustible vapours,
mists, residues, dusts or deposits are present due to the operation of spray processes. It can be either
enclosed or unenclosed and includes:
a. any area in the direct path of a spray application process;
b. the interior of any exhaust plenum and any exhaust duct leading from the spray process;
c. the interior of any limited finishing workstation, spray booth or spray room, as herein defined;
and
d. the interior of any recirculation particulate filter, solvent concentrator unit, solvent distillation
(recovery) unit, or recirculation air supply unit.
UNENCLOSED SPRAY AREA - Any spray area that is not confined by a limited finishing
workstation, spray booth or spray room, as herein defined.
SPRAY BOOTH - A power-ventilated enclosure for a spray application operation or process that
confines and limits the escape of the material being sprayed, including vapours, mists, dusts and
residues that are produced by the spraying operation and conducts or directs these material to an
exhaust system.
SPRAY ROOM - A power-ventilated fully enclosed room used exclusively for open spraying of
flammable or combustible materials.
VENTILATION - Movement of air that is provided for the prevention of fire and explosion. It is
considered adequate if it is sufficient to prevent accumulation of significant quantities of vapour-air
mixtures in concentration over one-fourth of the lower flammable limit.
FLUIDIZED BED - A chamber holding powder coating material that is aerated from below to form
an air-supported, expanded cloud of the powder. The object or material being coated is preheated,
then immersed into the cloud.
All greenhouses are considered a Category 1 location. EMT with wet location fittings will be
permitted. The area classification may be reduced to a standard location if ventilation and humidity
controls are present.
All walk-in freezers are a Category 1 location. All walk-in coolers are standard locations.
See Rule 12-1414 provisions for bonding using EMT for Category 1 locations.
Car washes are classified as Category 1 locations. All wiring methods and equipment must be
approved for wet locations.
EMT shall not be used in car wash bay areas’ due to salt and chemical contaminants. (See also Rule
12-1404)
All bulk granular fertilizer storage areas are subject to corrosion from a combination of the fertilizer
dust and moisture. All equipment must be approved for the location in accordance with Rule 2-116.
Raceways shall be PVC, or aluminum, with fittings and enclosure entries of such design as to not
constitute dissimilar metals in contact with each other, and to exclude dust.
Teck 90 cable with non-corrosive fittings shall be permitted to be installed in bulk fertilizer storage
structures.
Wiring in buildings housing livestock or poultry shall be the type listed in Table 19 for Category 1
and Category 2 locations.
With adequate ventilation, wiring approved for a damp location as per Table 19 may be used.
Note: Aluminum conductors and Bx (AC 90, ACWU) cables are not approved for use in buildings
housing livestock. Non-metallic sheathed cable is not approved for installation in a continuous
raceway system.
Wiring Methods
See also 10-208(1)(b)
The wiring methods that are acceptable in buildings housing livestock or poultry are:
1. PVC Conduit along with PVC boxes, straps and approved expansion joints as required. Wire
within the conduit must be approved for a wet location or damp location if the barn is equipped
with adequate humidity control;
2. Teck 90 Cable along with approved connectors, non-corrosive boxes and straps. Note the
electrical continuity of the metal armour must be maintained throughout the cable runs; or
3. Non-Metallic Sheath Cable cannot be used in any location where it may be susceptible to
damage by rodents; and.
4. All screws and equipment must be of the corrosion resistant type.
Non-metallic sheath cable cannot be run inside the walls, ceiling/attics or any other concealed space
in a barn, office, tack room or similar area attached to or within the barn unless provided with
mechanical protection.
When non-metallic sheath cable is used and it has to pass through a location where it may be
exposed to rodents, it must be provided with mechanical protection in the form of rigid steel, rigid
non-metallic conduit or other suitable material when:
1. Installed in exposed locations within 300 mm above any horizontal surface; or
2. Installed in exposed locations on the sides of floor joists or other structural members less than
100 mm below the upper surface.
NOTE: When an office, tack room, riding arena, sales arena or similar room is attached or within
the barn, the wiring methods are the same as the rest of the building. If the room is separated from
the barn by vapour tight walls, ceiling, floor and a sealed door, normal equipment (i.e. panel,
lighting, etc.) may be installed in the interior of this room.
A hospital so designated by Canada or one of its Provinces or Territories, where patients are
accommodated on the basis of medical need and are provided with continuing medical care and
supporting diagnostic and therapeutic services.
A facility where residents, as a result of physical or mental disabilities, are unable to function
independently and are accommodated due to a need for daily care by health care professionals.
Note: Class B Facilities provide, e.g. extended, multi-level, hospice, psychiatric or intermediate
care. The definition includes rehabilitation facilities.
A facility where ambulatory patients are accommodated on the basis of medical need and are
provided with supportive, diagnostic and treatment services.
Note: Class C Facilities include, e.g. outpatient and surgical clinics, dental offices, doctors’ clinics,
private residences and group homes.
Patient Care Areas are defined by the CAN/CSA-Z32 standard and include, but are not limited to,
walk-in medical clinics, dental clinics, chiropractic clinics, optometrists and others. The CEC
definition of a health care facility was changed to recognize that more and more treatment and
testing, previously done in hospitals, is now being done in these facilities. This means that the
specific rooms of a clinic in which treatment is given must be wired in accordance with Section 24
methods.
The health region, clinic or hospital administrators are the personnel who will determine the area use
for their facilities.
Plans shall be submitted with indication of different patient care levels, patient care
environments (basic, intermediate or critical) and branch circuit wiring details. See Rule 2-
014
A branch circuit that supplies receptacles or permanently connected electrical equipment described
in Rule 24-302 shall not supply receptacles or permanently connected electrical equipment that are
not part of the essential electrical system.
A panelboard that supplies branch circuits in a patient care environment shall have an insulated
copper bond conductor installed with the circuit conductors supplying the panelboard unless
incorporated in the cable assembly supplying the panel.
The minimum size equipment bonding conductor shall be sized in accordance with Table 16A, and
not smaller than the minimum size required for circuit conductors. The minimum size circuit
conductor shall be not smaller than No. 12 AWG.
Examples:
1. 40A equipment requires No. 8 AWG (45A) conductor in conduit, this would require a #10
bonding conductor to conform to Table 16A.
2. 5A equipment or a receptacle circuit would require No. 12 AWG circuit conductors and a No. 12
AWG bond conductor.
Rules 24-104(2) and 4-036 excludes the use of three wire armoured cables, other than ISO-ground
cable, as the bonding conductor needs to be insulated and shall have a continuous outer finish that is
either green or green with one or more yellow stripes.
Non-metallic conduit, NMD cable and armoured cables with a PVC inner jacket (Teck), provide
sufficient insulation to permit the use of a bare copper bonding conductor, minimum 12 AWG.
If they could become energized, exposed non-current carrying metal parts of non-electrical
equipment, in a patient care environment, shall be bonded to ground using a copper bonding
conductor sized in accordance with Table 16A by connection to equipment bonding conductor or 16
B for a bonding busbar for that patient care environment.
Examples of such equipment are metal parts of medical gas equipment, support arms, consoles, etc.
Isolated ground receptacles shall not be used in any patient care area.
The requirement of 2-wire circuits (i.e. dedicated grounded circuit conductors/neutral) applies to the
patient care environments within intermediate and critical care areas.
A zone in a patient care area that has been preselected for the accommodation of a patient bed, table
or other supporting mechanism, and for the accommodation of equipment involved in patient
treatment and which includes space within the room 1.5 meters beyond the perimeter of the bed in its
normal location and to within 2.3 meters of the floor. The patient environment is a zone fixed to the
supporting mechanism and does not move with the patient as the patient moves through the health
care facilities.
kVar Cap Fuse kVar Cap Fuse kVar Cap Amps Fuse
Amps PC or MC Amps PC or MC PC or MC
Breaker Breaker Breaker
5 12 20 5 6.01 15 10 9.62 15
10 24.1 40 10 12 20 20 19.2 30
15 36.1 50 15 18 30 25 24.1 40
25 30 50 40 38.5 70
60 144 200
Note – For Reference Only. Use manufacturer provided data to design installations
In a retrofit where an existing service is upgraded at the same location, the new panel need not be
lowered. If the location is otherwise undesirable, reference 6-206(1)(c), the new panel shall be made
to comply with the current CEC and not located in an insulated exterior wall.
In all new installations in dwelling units, with the exception of the main breaker or disconnect
switch, no branch circuit overcurrent device shall be located at a height greater than 1.7 m above the
finished floor.
26-700(11) - Receptacles
All 5-15R and 5-20R receptacles, located within 1.5 meters of any sink, shall be protected by a
GFCI.
26-700(12) - All receptacles of CSA Configuration 5-15R and 5-20R installed in a child care facility
shall be tamper-resistant receptacles. For the purpose of this rule “child care facility” means a
supervised area containing one or more rooms intended for the designated use of providing
educational and personal care services to children.
26-700(13) - Notwithstanding subrule (12), receptacles dedicated for stationary appliances such that
the receptacle is rendered inaccessible or those located 2 m from the floor or finished grade shall not
be required to be tamper resistant.
Receptacles exposed to weather shall be provided with wet location cover plates as follows:
1. Receptacles of configurations 5-15R, 5-20R, 5-20RA, 6-15R, 6-20R and 6-20RA shall have a
wet location cover plate that is approved for wet locations whether or not a plug is inserted into
the receptacle and marked “Extra Duty”;
2. Notwithstanding the requirements in subrule (1) when these receptacles are installed facing
downward, at an angle of 45° or less from the horizontal, cover plates marked “Wet Location
Only When Cover Closed” shall be permitted; and
3. Where receptacles exposed to the weather are installed on surface-mounted outlet boxes, the
cover plates shall be held in place by four screws or by some other equivalent means.
A receptacle is now required, for maintenance purposes, on all commercial or industrial buildings
that have rooftop electrical equipment such as RTU’s, ventilation, solar panels, etc. This receptacle
shall be:
For the purposes of this Rule, “finished wall” means any wall finished to within 450 mm of the floor
with drywall, wood paneling or other like material.
No reference is made to the drywall being taped or painted, only that it be installed.
In a basement, regardless of how it is finished, if the gypsum is installed then the receptacles are
required.
Note: If the basement is of Styrofoam block or is insulated with Styrofoam, the National Building
Code may require these walls to be finished.
The intent of this rule is that all receptacles installed outdoors of residential occupancies and within
2.5 meters of finished grade, shall be protected by a GFCI. This includes receptacles installed on
buildings or structures associated with the residential occupancy such as garages, carports, sheds,
posts and fences.
At least one receptacle installed at each permanently fixed island counter space with a continuous
long dimension of 600 mm or greater and a short dimension of 300 mm or greater.
At least one receptacle installed at each peninsular counter space with a continuous long dimension
of 600 mm or greater and a short dimension of 300 mm or greater.
Where a dining area forms part of a kitchen, a sufficient number of duplex receptacles shall be
installed as per subrule (a). These receptacles shall be connected to a separate circuit as per
Rule 26-724(e).
All 5-15R and 5-20R receptacles in a dwelling unit shall be tamper resistant with the exception of
receptacles located over 2 m above the floor and receptacles located behind stationary appliances.
This includes receptacles installed on buildings or structures associated with the residential
occupancy such as garages, carports, sheds, posts and fences.
At least one dedicated separate circuit is required for all outdoor receptacles. More than one
dedicated circuit may be installed for outdoor receptacles, but there shall be no interconnection of
indoor and outdoor receptacles. This does not include the receptacles on a balcony of apartment
buildings.
As per rule 26-710 all 5-15R or 5-20R receptacles installed within 2.5 m of the finished grade shall
be protected by a GFCI and as per Rule 26-724, protected by an AFCI.
Receptacles located in parking lots of apartments, or similar multi-family dwellings, installed solely
for the use of automobile heater receptacles in accordance with Rule 8-400, are not required to be
protected by a GFCI. (See also Rule 2-200)
At least one receptacle shall be provided in a garage for cord connected garage door openers, and
located adjacent to and within 1 m of each garage door opener.
The ampere rating of the branch circuit wiring supplying receptacles with CSA Configuration 5-20R
shall be 20A.
Arc fault protection as defined in Rule 26-720 is required for all branch circuits in new construction
or renovations/additions of dwelling units. Except for receptacles listed in Rule 26-724(f) which
includes:
- Bathroom receptacles
- Refrigerator receptacles
- Kitchen receptacles
- Island receptacles
- Peninsula receptacles
- A single receptacle for a sump pump that does not supply any other receptacles.
A dwelling unit with permanently installed cooking facilities (i.e. gas or electric range, cooktop) is
deemed to have a cooking facility and thus requires arc fault protection.
An “outlet branch circuit type arc fault circuit interrupter” may be used (instead of an AFCI breaker)
when installed as per Rule 26-724(g).
Newly constructed rooms require all receptacles to be arc fault protected and receptacles added to an
existing room shall also require arc fault protection.
Cord connected hot plates and/or microwaves do not constitute a cooking facility
The furnace shall be provided with a dedicated circuit. The disconnect shall be located as required
by the CEC. Garage unit heaters must also meet all these requirements. See also Section 10, Rule
10-406(4) on page 43.
Electrical Inspections shall be notified regarding submersible pump installations in bodies of water
where the voltage exceeds 150 volts-to-ground.
The area around the submersible pump shall be protected from public access by isolation and so
marked with a series double buoy systems to accommodate different water levels.
Signage marked (WARNING DANGER HIGH VOLTAGE [480 VOLT] SUBMERSIBLE PUMP)
shall be attached to both buoys and the controller structure facing the river.
Supply conductors to a motor connection box shall have an insulation temperature rating equal to or
greater than that required by Table 37 (example: heating circulating pumps, automotive car lifts).
When there is a discrepancy between the manufacturer and the values in Table 37, the higher value
shall be used.
Services for the supply of motors shall be sized in accordance with Section 28 of the CEC.
The service calculation is based on the total number of fans permanently wired into the electrical
panel. The motor disconnect shall be installed within sight of and within 9 meters of the motor, or
be lockable at the source. If receptacles are installed to plug in the motors, then the service may be
calculated by the number of fans to be utilized at one time.
Lock off devices shall be an Original Equipment Manufacturer device designed for the
disconnecting means.
Subject to Supply Authority approval, the yard light may be mounted on the transformer pole,
provided:
The pole mount yard light may be fed from the splitter with a minimum #14 AWG cable approved
for the location. A pigtail socket and a 15A fuse (located in the splitter) may be used as overcurrent
protection.
32-000 - Scope
Installation of smoke alarms, carbon monoxide detectors, fire alarm systems and fire pumps shall
meet the requirements of Section 32 of the CEC.
New rule allows conductors in PVC as a wiring method for fire alarm systems and does not have to
be encased in concrete.
Note: Not allowed for fire pumps, conductors for fire pumps in PVC must still be encased in 50 mm
of concrete.
Conductors shall be installed to be entirely independent of all other wiring, except for connection to:
- point of supply;
- a signal;
- an ancillary device; and
- a communication circuit.
32-110 - Smoke Alarms and Carbon Monoxide (CO) Detectors in Dwelling Units
New construction of residential units shall be pre-wired for interconnected smoke alarms. CO
alarms shall be installed as required by the National Building Code. CO alarms will be required in
residences with fuel burning appliances or an attached garage.
The National Building Code requires smoke alarms to be permanently connected to an electrical
circuit. This circuit may be 120 volt or an extra low voltage system. In either case, the circuit must
be permanently installed and supplied from a lighting branch circuit. This circuit must not be arc-
faulted or ground fault protected. As per Rule 32-102(3) this circuit must be kept totally
independent of all other wiring. In the case of an extra low voltage circuit, the transformer must be
permanently connected.
The requirements for smoke alarms are specified in the Code and in Part 9 of the 2010 edition of the
National Building Code of Canada (see Articles 9.10.19 and 9.10.21.7).
Location Requirements
Smoke alarms must be installed on each floor level, including basements, 900 mm or more above or
below an adjacent floor level. Each bedroom must be protected by a smoke alarm in each bedroom
and one outside the bedrooms installed within 5 m of the bedroom doors. This measurement must be
made along the corridors and through the bedroom door, not through walls or openings in walls.
The maximum distance between smoke alarms on the same floor in rooms other than bedrooms is 15
m. This measurement must be made along corridors and through doorways, not through walls or
openings in walls.
Smoke alarms must be installed on the ceiling or near the ceiling (see Article 9.10.19.2 of the
National Building Code of Canada).
The requirements for CO alarms are specified in the Code and in the 2010 edition of the National
Building Code of Canada (see Articles 6.2.4, 9.32.3.8 and 9.32.3.9).
Location Requirements
If the unit/suite in a residential occupancy contains a fuel-burning appliance or shares a wall with a
storage garage, a CO alarm must be located inside each bedroom or outside each bedroom within 5
m of each bedroom door, measured following corridors and doorways (see Articles 8.2.4 and
9.32.3.9 of the National Building Code of Canada).
Where an on-site electrical transfer switch is used to provide emergency power supply to fire pump
equipment, this transfer switch shall be used solely for the fire pump.
This rule previously called for Load Break Disconnects, other than the draw-out type, to have
contacts visible for inspection in the open and closed positions. This has been changed to only
require being visible in the open position.
In accordance with the manufacturer’s instructions, when a receptacle is required for an outdoor
wheelchair lift, it shall be a single receptacle connected to a separate circuit and shall not be arc fault
or ground fault protected.
(3)(b)Where a generator is used, it shall be arranged to start automatically without failure and
without undue delay upon the failure of the normal power supply to any transfer switch connected to
the generator.
I.E. - fire pump, life safety system, emergency or backup power...etc.
All power, control and communication conductors between an emergency generator and electrical
equipment required to be installed as a part of the emergency power supply and located outside the
generator room shall be protected against fire exposure to provide continued operation in
compliance with the National Building Code (NBC) of Canada.
The requirement of one (1) hour fire rating is per the NBC and may be achieved by using cable with
at least one (1) hour fire rating, encasing in concrete with thickness to achieve this rating or being in
a shaft with a one (1) hour fire rating.
Where an emergency generator is installed to supply power to life safety systems as defined in 46-
002, a selective coordination report will be required and submitted to Electrical Inspections. The
intent of selective coordination is to isolate the faulted circuit due to overcurrent or short circuit
while maintaining power to the rest of the electrical distribution. This includes, but is not limited to,
the following systems or circuits: fire alarms, lighting, elevators and fire pumps in health care
facilities, commercial buildings, industrial facilities, public buildings, etc.
A sample selection for a 20 KW furnace follows: The ampacity of the conductors supplying the
furnace and the size of the overcurrent devices are determined by applying Rule 62-114.
The overcurrent device for the service must be sized so that the total connected load of the heating
equipment does not exceed 80% of the rating of the overcurrent device in accordance with subrule
(6). In this case, the load is 83.3 amps; the minimum size of overcurrent device is 83.3/0.8 = 104
Amperes. The next available fuse is 125 A.
Since this fuse is supplying a heating load, Rule 14-610 requires that the fuses be a time delay type
or HRC Form I.
The conductor size is determined by applying Rule 62-114(7). The conductor must have the
ampacity sufficient to carry the load and must have an ampacity rating at least 80% of the rating or
setting of the branch circuit overcurrent device. A conductor rated at 100 amperes, i.e. #3 AWG
R90 (Column 3 of Table 2) would satisfy these requirements.
Based on the conduit fill requirements of Rule 12-910 and Tables 6 through 10, it can be determined
that the 2 #3 AWG R90 conductors require a 1” diameter conduit.
(4) Electric furnace loads shall be deemed to have a demand factor of 100% when calculating service
size for residential occupancy.
Table 67 has been added to the code to provide installation clearance requirements for space heating
systems (i.e. in-floor systems). See drawings in Appendix B.
Each unit requires a single disconnect or if more than 1 circuit is required, the disconnects must be
grouped together, i.e. Geothermal systems.
The disconnect(s) must be within sight of the unit and within 9 meters. This does not include
internal disconnects that are part of the central unit.
Ground fault protection is required to de-energize all normally ungrounded conductors of fixed
infrared heaters with a ground fault setting sufficient to allow normal operation of the heater.
Please refer to 2-014 Plans Review Requirements for Section 64 – Renewable Energy Systems.
Conductors of renewable energy systems shall be separated from different systems in accordance
with Rules 12-904(2) and 12-3030.
For the purpose of this Rule, multiple inverters and associated components connected to the same
renewable source are considered as one generation source and associated wiring may be contained in
the same raceway.
Where circuit conductors are connected to more than one source, all overcurrent devices shall be
located in such a way that they provide overcurrent protection from all sources.
Overcurrent devices marked or approved only for AC use shall not be used in DC circuits.
Equipment acceptable for automotive, marine and telecommunications applications, although used in
these DC systems, is not suitable for use in permanent renewable energy systems meeting the
requirements of this Code.
Circuit breakers that are marked “Line” and “Load” have been evaluated for connection only in the
direction marked.
Circuit breakers without “Line” and “Load” have been evaluated for connection in both directions.
A single, effective disconnecting means shall be provided to disconnect all ungrounded conductors
of a renewable energy system simultaneously from all other conductors in a building or structure.
• Photovoltaic combiners with source circuits require an output circuit disconnecting means;
• Disconnecting means must be located within 2 m of the photovoltaic combiner; and
• For photovoltaic combiners with source circuit fuses, the photovoltaic output circuit
disconnecting means shall be located integral with or within 2 m of the combiner and
interlocked with the combiner door.
Except as provided for by Rule 64-210, conductors for DC renewable energy sources or supply
circuits of a utility-interactive inverter, installed inside a building or structure, shall be contained in
metallic raceways, metal enclosures or cables with a metal armor from the point of penetration of the
building to the first readily accessible disconnecting means.
The inverter installation/instruction manual should be consulted to determine whether the inverter is
to be used with a grounded or ungrounded solar photovoltaic array.
An inverter designed for use with a grounded PV array is called an isolated inverter. The term
isolated means an internal transformer isolates the AC circuits from the DC circuits in the inverter.
A non-isolated or transformerless inverter would require the PV array to be ungrounded.
Ground fault protection is required for grounded DC supply circuits with a renewable energy system
of 50V or greater. This ground fault protection shall:
• detect a ground fault;
• interrupt the fault current;
• indicate that there was a ground fault; and
• open all ungrounded PV conductors or disconnect or turn off the connected equipment.
Renewable energy systems are permitted to operate with ungrounded source and supply circuits if
the system complies with the following:
• All source and supply conductors must have overcurrent protection (positive and negative
conductors);
• Conductors must be in metal-sheathed cables or metallic raceways;
• Inverters or charge controllers must be suitable for the purpose;
• The system must be provided with ground fault protection; and
• A suitable warning must be installed at each junction box, disconnect or any other device
where these circuits can be exposed during service. See Rule 64-066(1)(c) Appendix “B” for
an equivalent wording example.
Legend
Legend
Legend
Legend
The installation of a #6 copper bond conductor, continuous from the module bonding system, to the
system ground in conjunction with and external to the feeder cable, shall be installed to meet the
intent of this rule for the removal of combiner boxes, inverters or other equipment.
For interactive system(s) at the points of interconnection, each disconnecting means shall be marked
with the maximum AC output operating voltage and current.
In buildings with a utility service and a renewable energy system, where practical their disconnects
shall be grouped. Where not practicable, permanent plaques shall be posted on or near each
disconnecting means indicating the location of all other service boxes supplying power to the
building. See also 64-072
The maximum current of the inverter output circuit shall be the inverter continuous output rating.
Some inverters may also have specifications listing sustained maximum output currents. The higher
of the two output ratings shall be used.
Each inverter must have a dedicated circuit breaker or fusible disconnecting means and rated as
applicable for the voltage and current.
Example
The AC output conductors connected to this inverter must be sized for a minimum of 37.5 Amps.
Single phase inverters shall not be connected to a three-phase utility system unless:
• The inverters used are certified as utility interconnected and approved for use in three-phase
systems;
• The single-phase inverters are connected to provide three-phase balanced output;
• The installation complies with Rules 84-008 and 84-018;
• Confirmation that the installation is acceptable to the supply authority; and
• The installation meets the inverter manufacturer’s requirements.
(1) The output of a utility-interactive inverter shall be connected to the supply authority system in
accordance with Section 84.
(2) The output of a utility-interactive inverter is allowed to be connected to the line side of the
service disconnecting means at a dual lug meter socket or other source(s).
The output of a utility-interactive inverter is allowed to be connected to the load side of the service
disconnecting means provided that each source interconnection is made at a dedicated circuit breaker
or fused disconnecting means. This point of connection shall be positioned at the opposite (load)
end of the panelboard, busbar or conductor from the input feeder location or main circuit breaker
location.
The sum of the overcurrent devices supplying power to a busbar or conductor is allowed to exceed
the rating of the busbar or conductor to a maximum of 120%.
The sum of the overcurrent devices supplying power to a busbar or conductor is allowed to exceed
the rating of the busbar or conductor to a maximum of 125%.
A warning sign for a photovoltaic system shall be in capital letters with a minimum height of 9.5
mm, in white on a red background. See also 64-072
For the application of this Rule, photovoltaic modules are considered inaccessible to the public
where they are:
- located within a fenced enclosure in accordance with Rule 26-304, 26-312, and 26-314;
- guarded by locked doors;
- elevated 3 m or more above grade level or above any surface that a person can stand on; or
- where access is restricted by other effective means.
• The wiring for a solar PV installation is deemed inaccessible to the public and not readily
accessible if it is:
o contained in a raceway;
o contained behind screening or guarding;
o elevated 3 m or more above grade level; or
o located within a fenced enclosure in accordance with Rule 26-304, 26-312, and 26-314
• Flexible cords suitable for extra hard usage shall be permitted for interconnection of modules in
accordance with Rule 64-210(1);
• Conductors approved as part of an approved panel assembly shall be permitted for the module
interconnections in accordance with Rule 64-210(2);
• RPV conductors shall be permitted for the module interconnections if they are contained in a
raceway;
• Conductors and cables shall be supported 300 mm from every box and at intervals not more than
1 m throughout the run;
• Where DC arc-fault protection is not located at the module, conductors or cables installed on or
above a building shall be provided with mechanical protection against damage from rodents by
enclosing them in material such as expanded metal, solid metal, screening or other acceptable
protection; and
• Types RPV and RPVU conductors installed inside a building or structure shall be contained in a
raceway.
2015 Saskatchewan Interpretations Page 93
Electrical Inspections
Reversal of DC sources can create series circuits that will produce voltages well in excess of the
rated system voltage.
DC photovoltaic circuits installed between the photovoltaic modules and the inverter shall be
identified:
• red for positive/black for negative;
• black conductors manufactured with permanent surface printing indicating the polarity of the
conductor; or
• RPV or RPVU conductors; +/-, Pos/Neg or Positive/Negative.
Field marking or labeling of single conductors shall not be allowed. Field colour-coding for multi-
conductor cables shall be permitted, provided the colour-coding for conductors are located at every
point where the separate conductors are accessible.
64-214 - Overcurrent Protection for Apparatus and Conductors (Solar Photovoltaic Systems)
Overcurrent protection for PV strings shall not be greater than the maximum fuse rating on the
module nameplate. The overcurrent protection for individual photovoltaic source circuits shall not
be greater than 100% of the rated short-circuit current of that source circuit. Where this value does
not correspond to the standard rating, the next higher standard size can be used.
Overcurrent devices for photovoltaic source circuits shall be accessible and grouped where
practicable.
Photovoltaic systems with DC source or output circuits, or both, and operating at a maximum system
voltage of 80V or greater, shall be protected by:
a) a DC arc-fault circuit interrupter; or
b) other system equipment approved to provide equivalent protection.
A photovoltaic system rapid shutdown device shall be provided for a photovoltaic system installed
on buildings or structures where the photovoltaic source or output conductors installed on or in
buildings are more than 1.5 m in length or more than 3 m from the photovoltaic array.
A photovoltaic system rapid shutdown device shall limit photovoltaic source or output circuits to not
more than 30 volts and 240 VA within 10 seconds of rapid shutdown initiation.
The intent of this Rule is to have a disconnecting means for the output circuit of a photovoltaic
combiner capable of making and interrupting its full load rating and that may be opened with safety
to the operator with a fault on the system [see Rule 64-060(12)].
If the utility disconnect serves a dual function as a rapid shutdown, it shall be labeled as such.
E.g. systems using micro-inverters or optimizers
2015 Saskatchewan Interpretations Page 94
Electrical Inspections
64-220 - Attachment Plugs and Similar Wiring Devices (Solar Photovoltaic Systems)
Attachment plugs connected to cables between photovoltaic modules in readily accessible locations
and over 30V shall require a tool to open the connector. When connectors and attachment plugs are
used to interconnect modules or arrays, they shall be used in such a manner that the blades of the
attachment plug are not energized when withdrawn. Only attachment plugs approved as a mated
pair from the same manufacturer shall be interconnected.
All exposed metal parts of photovoltaic modules shall be bonded to ground in accordance with the
module or bonding connector manufacturer’s installation instructions. During the approval process,
all components such as bonding clips, brackets, hardware, lugs, etc. used for bonding are tested in
accordance with CSA-C22.2, No. 61730-2.
These bonding connections shall be arranged so that removal of a photovoltaic module from a source
circuit does not interrupt a bonding conductor to other equipment.
Note: 1. All labels and diagrams must be installed before the installation will be approved. All labels and
diagrams installed outdoors and exposed to the weather shall meet the requirements listed under
Rule 64-074.
2. All wiring must be done by a licensed Saskatchewan Electrical Contractor and be covered by an
appropriate electrical permit. Homeowner Permits are not allowed.
3. It is the responsibility of the Electrical Contractor to arrange for an inspection 2 weeks prior to
requesting a network service connection.
4. When Network Metering is installed, the Local Utility must approve all connection diagrams
before the installation begins.
5. All renewable energy installations require electrical construction plans to be submitted to
Electrical Inspections and reviewed before approval will be granted. See Rule 2-014.
Note: 1. All labels and diagrams must be installed before the installation will be approved. All labels and
diagrams installed outdoors and exposed to the weather shall meet the requirements listed under
Rule 64-074.
2. All wiring must be done by a licensed Saskatchewan Electrical Contractor and be covered by an
appropriate electrical permit. Homeowner Permits are not allowed.
3. It is the responsibility of the Electrical Contractor to arrange for an inspection 2 weeks prior to
requesting a network service connection.
4. When Network Metering is installed, the Local Utility must approve all connection diagrams
before the installation begins.
5. All renewable energy installations require electrical construction plans to be submitted to
Electrical Inspections and reviewed before approval will be granted. See Rule 2-014.
Note: 1. All labels and diagrams must be installed before the installation will be approved. All labels and
diagrams installed outdoors and exposed to the weather shall meet the requirements listed under
Rule 64-074.
2. On services above 400 Amp – the labels required by Rule 84-030 will need to be installed at the
meter and at the main switch.
3. All wiring must be done by a licensed Saskatchewan Electrical Contractor and be covered by an
appropriate electrical permit. Homeowner Permits are not allowed.
4. It is the responsibility of the Electrical Contractor to arrange for an inspection 2 weeks prior to
requesting a network service connection.
5. When Network Metering is installed, the Local Utility must approve all connection diagrams
before the installation begins.
6. All renewable energy installations require electrical construction plans to be submitted to
Electrical Inspections and reviewed before approval will be granted. See Rule 2-014.
66-404 - Receptacles
Receptacles having CSA configuration 5-15R or 5-20R installed in itinerant midways, carnivals,
fairs and festivals and intended to supply loads in outdoor or damp locations shall be protected by
ground fault circuit interrupters of the Class A type.
Electric utilities may not permit open service conductors to be located directly over a pool, hot tub or
spa.
A structure that will adequately provide a permanent barrier between overhead conductors and the
hot tub shall be acceptable as protection from overhead lines crossing above a hot tub. If the
structure is metal and within 1.5M of the hot tub, it shall be bonded to ground.
Spas and Hot Tubs require Class A GFCI protection regardless of equipment location.
No other (unrelated) equipment is to be fed from a circuit feeding a hydro massage bathtub.
Access must be provided to all electrical equipment including the pump motor.
See Rule 2-122 - Minimum 400 mm x 400 mm access panel.
Storable swimming pool - means a pool constructed in such a manner that it may be readily
disassembled for storage and reassembled to its original integrity.
Spa, or hot tub - means a pool or tub designed for the immersion of persons in heated water
circulated in a closed system incorporating a filter, heater, pump and with or without a motor-
driven blower but not intended to be filled and drained with each use.
Decorative Pool or baptismal pool - means a pool that could be used as a wading pool or the
immersion of persons, that is larger than 1.5 m in any dimension, and that is readily accessible to
the public.
Underground Wiring (includes underground telephone, cable TV and Power Utility service cables)
The horizontal separation between the inside walls of an in ground pool or splash pad and
underground conductors, except for bonding conductors or conductors supplying electrical
equipment associated with the pool and protected by a ground fault circuit interrupter, shall not be
less than:
Type of Installation Conductors Buried Conductors in non-conducting
Directly in earth Ducts
Communications conductors 1.5m 1m
Power Conductors:
0 - 750 V 1.5m 1.0m
751 - 15,000 V 3.0m 1.5m
15,001 - 28,000 V 6.0m 2.0m
Receptacles located between 1.5 m and 3 m of the inside walls of a pool shall be protected by a
ground fault circuit interrupter outside of the 3 m distance.
Ground fault circuit interrupters shall not be installed closer than 3 m to the pool water unless the
ground fault circuit interrupter is an integral part of an approved factory built spa or hot tub and is
located behind a barrier that will prevent the occupant of the tub from contacting the device.
Other Electrical Equipment (air conditioning equipment, pumps, etc.)
Electrical equipment located within 3 m of the inside walls of the pool and not suitably separated
from the pool area by a fence, wall or other permanent barrier, shall be protected by a ground fault
circuit interrupter.
Electrical Utility Meter
A swimming pool or hot tub shall not be located within 3 m of the Electrical Utility meter unless it
is suitably separated from the pool area by a fence, wall or other permanent barrier that provides no
less than 1 m clearance about the electric meter. (Metal poles used for pool servicing can present a
shock hazard to persons in the pool area coming in contact with the electric service equipment)
Lighting
Lighting installed below, or within 3 m of the pool surface or walls, and not suitably separated from
the pool area by a fence, wall, or other permanent barrier shall be electrically protected by a ground
fault circuit interrupter.
Standards or supports for lighting shall not be installed within 3 m of the inside walls of a
swimming pool unless a ground fault circuit interrupter protects such lighting.
Bonding to ground
Pool reinforcing steel and the pool shell shall be bonded at four equally spaced points around the
pool. All metallic components associated with the pool and metallic fences within 1.5 m of the
pool shall be bonded to ground by a copper conductor.
When doing a service or feeder calculation for an RV park, the calculated load is considered a
continuous load as per Rule 8-104.
72-102(2),(3),(4)
Campground service calculation Example A
A campground has 30 sites. 10 of the sites have a pedestal with a 50A, 240V receptacle and a 30A, 120V
receptacle. 20 of the sites have a pedestal with a 30A, 120V receptacle and a 15A, 120V receptacle. Panel A
is protected by a 100A breaker (rated at 80%) and serves the shower building. Panel B is protected by a
100A breaker (rated at 100%) and serves site lighting, etc.
What size 120/1240V service is required?
This campground would require an 800Amp service with a 100% rated main breaker; or
This campground could install a 1000Amp 80% rated main breaker.
72-102(2),(3),(4)
Campground service calculation Example B
A campground has 40 sites. 14 of the sites have a pedestal with a 50A, 208V single phase receptacle and a
30A, 120V receptacle. 17 of the sites have a pedestal with a 30A, 120V receptacle and a 15A, 120V
receptacle. 9 of the sites have a 20A, 120V receptacle. Panel A is a 120/208V single phase panel with a 60A
breaker (rated at 80%) and serves the shower building. Panel B is a 120/208V 3 phase panel protected by a
150A breaker (rated at 100%) and serves the site lighting etc.
What size 120/208V service is required?
76-000 - Scope
This section of the code covers temporary wiring installations for buildings or projects under
construction or demolition and experimental or testing facilities of a temporary nature.
Temporary Services must have a service entrance rated main breaker and be grounded with two
ground rods, one ground plate or a field assembled grounding electrode. (See Rule 10-700)
Temporary Services are allowed to be connected for no more than 24 months in accordance with the
Electrical Service Requirements (ESR).
76-016 - Receptacles
All temporary service receptacles of 5-15R and 5-20R are to be ground fault protected. In use ‘extra
duty’ covers will not be required on temporary construction services.
Receptacles installed in a building under construction that are part of the permanent wiring system
will not require ground fault protection.
A cathodic rectifier shall be fed from a separate circuit. The new rule has removed the lockable
requirement.
(1) A separate disconnecting means shall be installed at a point readily accessible to the users and
within sight of and within 15 m of a rectifier unit of a cathodic protection system.
(2) Notwithstanding subrule (1), a disconnecting means integral to the rectifier unit shall be
permitted to serve as the disconnecting means required in subrule (1) provided the rectifier enclosure
is rendered inaccessible to unauthorized persons by an external lockable cover.
(3) The disconnecting means referred to in subrule (1) shall be labeled in a conspicuous, legible and
permanent manner identifying it as the disconnecting means for a cathodic protection system.
As with all electrical equipment, portable generators and associated equipment must be approved
and carry the mark of a recognized certification agency. Although recommended in the manuals of
many power take-off generators, welding cable is not an approved wiring method and will not be
accepted.
Generators and associated equipment (i.e. transfer switches, etc.) must be installed by a licensed
electrical contractor and the appropriate permit must be submitted. Plans may be required for review
as per Rule 2-014
The following diagrams show typical generator installation configurations. For other installation
configurations contact a licensed electrical contractor or a SaskPower Gas and Electrical Inspections.
(ii) is clearly marked as being of the double insulated type or is supplied from a class A
ground fault interrupting device.
Notes
1. Rewiring or tampering with a generator unit voids CSA certification.
2. Conductors must be sized to match the maximum output of the generator.
3. Follow generator manufacturer’s installation, grounding and operation instructions.
4. A transfer switch must be capable of switching the neutral when the generator neutral is
bonded to the frame.
5. Permission is required from your local SaskPower District Office to install this recessed male
connector on a transformer pole.
6. A portable electric power plant that is operated at voltages exceeding 240 volts to ground or is
rated in excess of 12.0 kW shall be grounded as per Section 10 of the current Canadian
Electrical Code.
This diagram should show the physical location of the interconnected sources, the interlocks
between the switching equipment and isolation points so that personnel are able to isolate the
section being serviced.
See Figure 12, Rule 64-002 in Appendix B for an illustration of an interconnected photovoltaic
system.
Installations for oil and gas fields shall comply with Section 19, Code for Electrical Installations at
Oil and Gas Facilities, Fourth Edition, 2015, as published and distributed by SaskPower. It is
available on our website at www.saskpower.com.
MINING INSTALLATIONS
Standards Applications
Canadian Electrical Code, Part 1 C22.1 – Safety Standards for Electrical Installations
The electrical works, facilities and plant that are on surface and are used for housing, maintenance,
and processing of extracted minerals
Supplemental to the requirements of C22.1, including the electrical works, facilities and plant that
are both underground and on surface that are used in the extraction of minerals
License required
8(1) Subject to subsection (2), no person shall do any work of electrical installation unless he holds a
license.
License
23(1) No employer shall do any work of electrical installation unless he holds an employer’s license.
(2) An employer’s license may be issued to a person who employs at least one individual who holds
a journeyman’s license;
(3) No employer shall require or permit any apprentice or other unlicensed individual to perform any
work of electrical installation except as an assistant to, and under the supervision of, a journeyman.
All surface and sub-surface electrical equipment requires an overall approval from a Saskatchewan
recognized Certification Body prior to being electrically connected or reconnected (2015
Saskatchewan Interpretations pg. 17-24), and must bear evidence of the approval or certification.
Report of Accident
“Where an accident involving an electrical installation or electrical equipment occurs and results in
a death or injury of a person or in a fire or an explosion, the contractor or the contractor’s agent or
the owner of the electrical equipment or the owner’s agent shall immediately notify the chief
inspector, stating the precise location of the accident, its general nature and results”.
Investigation of Accident
The accident site to be preserved, “no part of any electrical plant or electrical equipment involved is
to be removed or its position altered by any person”, “until the written permission of an inspector has
been obtained”
Applies to Owner’s new installations installed by employees or contractors, other than maintenance
replacement of existing equipment.
(3) Flexible cord shall not be used (a) as a substitute for fixed wiring (i) permanently secured to any
structural member.
(1) Permanent warning notice shall be placed (b) on all high voltage cables at points of access (d) on
all exposed portions of all high voltage cables at a spacing not to exceed 10m.
Plans and diagrams shall be reviewed and updated every 4 months, and shall be posted at each power
skid, electrical room, substation, load break / switch, and distribution location.
Moose Jaw Cell 306-630-5311 880 Lillooet St. West, Box 1240
Moose Jaw S6H 4P9
Moose Jaw Cell 306-630-5788 880 Lillooet St. West, Box 1240
Moose Jaw S6H 4P9
North Battleford Cell 306-441-0511 P.O. Box 550; 9905 Thatcher Ave
North Battleford S9A 2Y7
North Battleford Cell 306-441-3219 P.O. Box 550; 9905 Thatcher Ave
North Battleford S9A 2Y7
Other Contacts:
Annex B
FROM:
AFFILIATION:
DATE:
Supporting Information:
Notes -