Compact controller 227VM

Compact controller 227VM


FläktGroup compact controller 227VM is a complete unit comprising actuator, a dynamic differential pressure sensor for
pressure-independent controls and user interface with 3-digit display which enables monitoring the air flow and setting
up values without external equipment.
The controller operating range is set to a standard value of 0 - 10V on delivery. To change operating range to 2 - 10 V see
Setting the values, quick reference guide.
The controller can also be force controlled via closing contacts (timer, presence detector, etc) to override the set min or
max air flow. It is also possible to use the controller with a CAV function.

FläktGroup 9660 GB 2019.05.23 1 (8) Specifications are subject of alteration without further notice.
Compact controller 227VM

Connection diagram User interface


Actuators are provided with color coded and numbered
wires.

BU-BN operating voltage 24 VAC/VDC On the cover of the actuator there are two selectors, value
BU-BK control signal 0...10 V / 2...10 V selector (1) and function selector (2).
BU-GY feedback signal 0...10 V / 2...10 V
Load for output GY max. 0,5 mA Also there is the 3-digit display (3) to show selected
functions, values and units.
Observe polarity on secondary of transformers. All
common and signal (–) must be connected in line.
Incorrect polarity can cause controller damage or
operation error. Provide overload protection for line
voltage and disconnect as required. Consider voltage
drops when connecting multiply actuators in parallel.
See “STRA Room controller Installation and
maintenance”-manual for detailed instructions how
to connect the actuator to FläktGroup room controller.
When using 3rd party controllers, notice that a separate
transformer should be used for the controller if the
controller power is full-wave rectified.

FläktGroup 9660 GB 2019.05.23 2 (8) Specifications are subject of alteration without further notice.
Compact controller 227VM

Setting the values, quick reference Functions, detailed description


guide 1. Value selector
The value selector allows
When actuator is connected to power supply, settings can the changing of values. The
be made. Screwdriver is needed when adjusting values position of the arrow shows
with the selectors. the value set. The changes
1. Select air flow unit: Dot on upper-right or lower-right are displayed as soon as the
corner of display indicates which units that are used, l/s selector is moved ±10° from
or m3/h. its position.
By turning the selector up
If there is need of change, turn the function selector until or down the corresponding
it points to “Flow”. values are shown.
Then turn the value selector until dot on display toggles
to other position. After the selection the display flashes 2. Function Selector
three dashes (- - -) twice for indication that new setting is The function selector allows
stored. choosing the function
2. Setting up Vmax: Turn the function selector until it depending on its position.
points to “Vmax”. Then turn the value selector until If there is no function
desired air flow is shown on display. After the selection selected the display will
the display flashes twice for indication that new Vmax show three dashes(- - -).
setting is stored.
3. Setting up Vmin: Turn the function selector until it
points to “Vmin”. Then turn the value selector until Flow
desired air flow is shown on display. After the selection Shows the actual flow in selected units, m3/h or l/s. This
the display flashes twice for indication that new Vmin display matches with the feedback signal U.
setting is stored.
The display starts flashing if the servomotor hits an end
4. Select input signal range: Turn the function selector stop before matching actual to reference flow.
until it points to “Mode”. Currently valid range is shown
on display, 0-n for 0-10V range or 2-n for 2-10V range. An overflow (measuring pressure difference higher than
If there is need of change, turn the value selector until 300Pa) is indicated in the display by a small circle, see
desired value is shown on display. After the selection section Display.
the new range is saved and the display flashes twice for Turning the value selector allows unit selection. The
indication. appropriate dot on display is toggled as indicator.
Note! Setting or not setting the intermediate position
Dot on upper-right corner
Vbtw has no effect on the operation of the actuator when
of display: unit of flow used
0-10 / 2-10 VDC control voltage is used. Vbtw is activated
is l/s.
only when forced control signal is used.
Dot on lower-right corner
of display: unit of flow used
is m 3 /h.

Vmin
Allows to set the desired minimum flow for the external
reference signal Y=0V/2V by turning the value selector.
Selected value is shown on display in m3/h or l/s.

Vbtw
Enables the setting of desired intermediate position flow
for the external forced control signal (negative rectified
half wave from 24VAC supply) by turning the value
selector. Selected value is shown on display in m3/h or l/s.

Vmax
Allows to set the desired maximum flow for the external
reference signal Y=10V by turning the value selector.
Selected value is shown on display in m3/h or l/s.

FläktGroup 9660 GB 2019.05.23 3 (8) Specifications are subject of alteration without further notice.
Compact controller 227VM

Test Input signals (analog)


Opens the diagnose menu. All outside input signals on Y The input signal Y allows to control the VAV actuator
are neglected and the controller only operates according according to the selected mode of operation.
to the selected override function. All override functions
In mode 0…10VDC the input signal Y matches to the
are disabled after a time-out of 10 hours.
following flows:
The display toggles after the selection of the function
between the actual flow (8s showing time) and the
function (2s showing time). OFF-mode toggles with Y-
signal. and the flows match to
Selecting another function will disable the Diag function Y = 0VDC as (Vmin) and Y = 10VDC as (Vmax)
and set it automatically to OFF.
Turning the value selector allows Diag function selection.
The appropriate symbols on display are toggled as
indicator.
In mode 2…10VDC the input signal Y matches to the
following flows:
oP(en)
opens the damper

cL(ose) and the flows match to


closes the damper Y = 2VDC as (Vmin) and Y = 10VDC as (Vmax)

8
Hi(gh)
forces the actuator to V max
Mode 2…10VDC includes special feature to close damper
with input signal Y = 0VDC.
Lo(w) See also Fig 1. “Reference Signal Y”
forces the actuator to V min

on
Test mode is switched on.
The actuator stays in the
current position.
oFF
Test mode is switched
off. The actuator starts
controlling according to
external signal Y.

Mode
Allows to set the input signal range (0…10V or 2…10V)
by turning the value selector. The feedback signal range of Fig. 1. Reference signal Y
U corresponds to Y.

0-n ... signal range is 0-10V

2-n ... signal range is 2-10V

Adr
Not in use.

Vnom
Shows factory set duct size. End user cannot change the
value.

FläktGroup 9660 GB 2019.05.23 4 (8) Specifications are subject of alteration without further notice.
Compact controller 227VM

Output signals (analog) Forced controls


In mode 0…10VDC the output signal U matches to the The controller can be force controlled to following
following flows: positions via closing contacts (see fig. 3):
(Close) Y= connected to ground conductor of 24 VAC
supply (only with mode 2-10 VDC)
(Vmin) Y= disconnected
where Vnom is size dependent nominal flow (Vbtw) Y= neg. rectified half wave from 24VAC supply
and to calculate the actual flow Vact from the feedback (Vmax) Y= full wave from 24VAC supply
signal U:
(Open) Y= pos. rectified half wave from 24VAC supply

In mode 2…10VDC the output signal U matches to the


following flows:

And to calculate the actual flow Vact from the feedback


signal U:

See also Fig 2. “Actual air volume flow U”


Fig. 3. Forced control alternatives

Fig. 2. Actual air volume flow U

FläktGroup 9660 GB 2019.05.23 5 (8) Specifications are subject of alteration without further notice.
Compact controller 227VM

Setting the controller to a constant Display


air flow The display (3) uses 7-segment numbers in full 3-digits.
The controller can be set to a constant air flow neglecting Additional signs include a small circle, three square dots
all analog inputs Y. This functionality can be used as an and two rectangular slashes.
advanced diagnostic function.
To activate this function Vmax needs to be set to 0.
The Diag dot in the display appears and the controller
uses Vmin as the constant air flow to control to. Use Vmin The square dots are used with the externally printed
function to set desired constant air flow. text to visualize certain functions or units (m 3 /h, l/
s). It is meant to denote the unit of the value shown in
the display. In the shown case it could be m 3 /h, l/s or
activated Diag (diagnostic function).
An overflow (differential pressure above 300Pa or 1.2 in
WC) is indicated in the display by a small circle at the first
digit.
If the controller tries to match reference and actual flow
this is shown as flashing dot of the chosen unit.
If the controller cannot meet reference and actual flow
and therefore hits an end stop the complete display starts
flashing to indicate this problem.
The rectangular slashes are used to define the thousand
separators. See following examples:

1 l/s

10 l/s

100 l/s

1000 l/s

2500 l/s

FläktGroup 9660 GB 2019.05.23 6 (8) Specifications are subject of alteration without further notice.
Compact controller 227VM

Technical data Dimensions


Power supply 24 VAC/VDC ± 20%, 50/60 Hz
67,5
Over voltage Up to 40 VDC, max. 5 sec.
Power consumption 4 VA/5Nm, 4.5 VA/10Nm 11,5
Input signal Proportional to [V min ...V max ] Ø6
0 - 10 / 2 - 10 VDC, or
0 - 20 / 4 - 20 mA
with 500 Ω resistor and override 44 66
controls
Input impedance >50 kΩ 23
Feedback signal 0 - 10 / 2 - 10 VDC
proportional to air volume flow 2

Permissible ambient 15,5 17,5


- working temperature 0 °C to 50 °C (32 °F to 122 °F) 147
- storage temperature -20 °C to 80 °C (-4 °F to 176 °F)
- humidity 5-95% RH, non-condensing
12

30 5 65

115

FläktGroup 9660 GB 2019.05.23 7 (8) Specifications are subject of alteration without further notice.
Compact controller 227VM

Wiring

Parallel control of two flow variators

Master-Slave control of two flow variators

Note that when applying master-slave control, nominal flow of the master must be equal or smaller than the nominal
flow of the slave.
Vnommaster = Vnomslave -> Vminslave = 0 and Vmaxslave = Vnomslave
Vnommaster < Vnomslave -> Vminslave = 0 and Vmaxslave = Vnommaster
Vnommaster > Vnomslave

Control of a single flow variator from one flow sensor unit

CAV Constant air volume