0% found this document useful (0 votes)
20 views

Modbus Card Detailed Draw

Modbus Card detailed drawing

Uploaded by

debaditya2008
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
20 views

Modbus Card Detailed Draw

Modbus Card detailed drawing

Uploaded by

debaditya2008
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 20

Dräger

REGARD
Modbus Card

Instructions for Use


REGARD Modbus Card 1

CONTENTS
1 INTRODUCTION ....................................................................................................... 3
1.1 Description ................................................................................................. 3
1.2 Modbus communications ............................................................................ 3
1.3 Configuration and passwords ...................................................................... 3

2 FACILITIES AND CONFIGURATION......................................................................... 4


2.1 Indicators and controls................................................................................ 4
2.2 Modbus interfaces ...................................................................................... 5
2.2.1 RS-232 interface ......................................................................... 5
2.2.2 RS-422 interface ......................................................................... 5
2.2.3 RS-485 interface ......................................................................... 5
2.3 Manual communications checks ................................................................. 5

3 INSTALLATION AND CONNECTIONS ...................................................................... 6


3.1 Fitting the Modbus card .............................................................................. 6
3.2 RS-232 and RS-422/RS-485 interface terminals ......................................... 6
3.3 Interface selection ...................................................................................... 6

4 SYSTEM CONFIGURATION ..................................................................................... 7


4.1 Configure Regard master card and channel cards....................................... 7
4.2 Configure Modbus card............................................................................... 7
4.2.1 Set baud rate and parity .............................................................. 7
4.2.2 Set Regard communications checksum (CRC or CSUM)............. 7
4.2.3 Set Modbus slave number........................................................... 7
4.2.4 Enable/disable exceptions ........................................................... 7
4.2.5 Set gas level range ..................................................................... 7
4.3 Test communications.................................................................................. 7
4.4 Save settings.............................................................................................. 7

5 COMMANDS REFERENCE ........................................................................................ 8

APPENDIX A: OPERATIONAL FAULTS .......................................................................11

APPENDIX B: SPECIFICATIONS .................................................................................12


Operating conditions.........................................................................................12
Backplane terminals .........................................................................................12

APPENDIX C: RS-232, RS-422 AND RS-485 CONNECTIONS....................................13


RS-232 connection to PC-AT 9-way serial interface..........................................13
RS-232 connection to PC 25-way serial interface .............................................13
RS-422 connection ...........................................................................................13
RS-485 connection ...........................................................................................13

APPENDIX D: MODBUS IMPLEMENTATION...............................................................14


Function 02 – read alarm data ..........................................................................14
Function 04 – read gas level and alarm data ....................................................15
Function 06 – acknowledge / reset alarms (V2.0 only) ......................................16
Other functions .................................................................................................16

APPENDIX E: COMMANDS SUMMARY.......................................................................17


2 REGARD Modbus Card

Scope of this manual


This manual describes how to install, configure and use the Regard Modbus® card. You
should already be familiar with setting up Regard channel cards and master cards. You
should also have some knowledge of the Modbus protocol.

Changes in issue 4
• Connection diagrams for RS-232, RS-422 and RS-485 interfaces revised.

Changes introduced in version 1.8 of the Regard Modbus card software:


• New command 52-4 (BAUD): select communications data rate with Modbus Master.

Changes introduced in version 1.9 of the Regard Modbus card software


• New command 52-6 (CKSM): select CRC or CSUM error checking on Regard system
• New command 52-5 (PRTY): select communications parity setting with Modbus
Master
• New command 52-7 (MEAS): select signed or unsigned gas levels
• Modbus function 02 can read 1499 bits
• Modbus function 04 can read 99 words

Changes in issue 5
New feature introduced in version 2.0 of the Regard Modbus card software:
• Modbus function 06 allows alarms on Regard system to be acknowledged or reset
through the Regard Modbus card.

®
Modbus is a registered trademark of AEG Schneider Automation.
REGARD Modbus Card 3

1 INTRODUCTION
1.1 Description
The Regard Modbus card is a Modbus RTU interface for Regard systems, allowing
Regard channel card alarm and gas level information to be accessed by any system with
a Modbus interface. Connection to the Regard Modbus card is via an RS-232, RS-422 or
RS-485 interface.

The Modbus card operates in conjunction with a Regard master card. The master card
communicates with each channel card, regularly requesting alarm and gas level
information. The Modbus card listens to this information and maintains a table of alarm
and gas level information for each channel card.

Gas level and alarm information for all Regard channel cards on the same RS-485 bus
as the Modbus card will be available, provided that each channel card is correctly
configured and communicating with the Regard master card.

1.2 Modbus communications


The Modbus protocol is a standard for communication between Modbus compatible
devices (e.g. PLCs). Communication between Modbus devices is controlled by a
Modbus master, which makes Modbus requests to the Modbus slave(s).

The Regard Modbus card acts as a Modbus slave, supporting a subset of the Modbus
protocol sufficient to provide Regard alarm and gas level information. The Regard
Modbus card supports RTU transmission mode only.

Note that Regard master and slave cards are not the same as Modbus masters and
slaves; only the Regard Modbus card understands the Modbus protocol.

1.3 Configuration and passwords


Modbus cards are configured using a command mode similar to other Regard cards,
except that the Modbus card only has two access levels: read level and configuration
level.

The password for configuration level is factory set as “CCCC”. No password is needed
for access to read level.
4 REGARD Modbus Card

2 FACILITIES AND CONFIGURATION


2.1 Indicators and controls
LED Indicates
A3, A2, A1 No function
Fault No function
Power Steady: dc supply on
Flashing: operational fault—see Appendix A
Inhibit Steady: card in command mode

Push button Function


R Enter command mode
ñ Used in command mode to
ò select a command or option

LED display
The display shows “_ _ _ _” or “GATE” when the card is in normal operation. At other
times it may display error messages and is used during card configuration.

Alarm LEDs A3 A2 and A1 and Fault LED


These LEDs have no function on the Regard Modbus card.

Power LED The Power LED remains steadily lit when the dc supply to the card is on and the card is
operating normally. A flashing Power LED indicates an operational fault on the card.
(See Appendix A.)

Inhibit LED The Inhibit LED lights when the card is put into command mode. Unlike Regard channel
cards, command mode does not inhibit any function of the Modbus card. There is no
automatic time-out from command mode.

R (Reset) The Reset button is used to enter command mode and choose commands and
configuration options while in command mode.

ñ and ò The ñ and ò push buttons are used in command mode to select commands and
configuration settings. When the card is not in command mode these push buttons have
no function.
REGARD Modbus Card 5

2.2 Modbus interfaces


The Regard Modbus card has RS-232 and RS-422/RS-485 hardware interfaces, with
selection by a switch on the card. Only one interface can be used at a time.

If more than one Modbus card is to be connected to a Modbus master use RS-422 or
RS-485. The RS-485 interface can only be used if the Modbus master correctly controls
handshaking, otherwise use RS-422.

Connections between the Regard Modbus card and a Modbus master for each interface
are shown in Appendix C.

2.2.1 RS-232 interface


The three-wire RS-232 interface can be used to connect one Modbus master to one
Modbus slave. The RS-232 interface is the simplest to use - almost all computers and
Modbus systems have an RS-232 interface.

2.2.2 RS-422 interface


RS-422 uses four wires plus ground. It can be used to connect one Modbus master to a
number of Modbus slaves, and can support much longer line lengths than RS-232. Other
Modbus slaves must be able to control handshaking on the interface.

2.2.3 RS-485 interface


RS-485 is similar to RS-422 but uses two wires plus ground, and can be used to connect
one Modbus master to more than one Modbus slave. Both the Modbus master and other
Modbus slaves must be able to control handshaking on the interface.

2.3 Manual communications checks


The Modbus card will not indicate or report a communication failure of the Regard
system or of the Modbus system. Two commands are available which allow manual
checking of communications:
• Command 14–7 can be used to verify that the Modbus card is receiving the
information on the Regard RS-485 bus correctly.
• Command 14–8 can be used to verify reception of Modbus requests from the Modbus
master.
6 REGARD Modbus Card

3 INSTALLATION AND CONNECTIONS


3.1 Fitting the Modbus card
The Modbus card can be fitted in any free slot in the Regard cardframe except the power
supply slot.

3.2 RS-232 and RS-422/RS-485 interface terminals

1 

2  NO CONNECTION

3 
4 

5  NO CONNECTION

6 
7 

8  NO CONNECTION

9 
Tx 10 

Rx 11  RS232 Rx/Tx

Gnd 12 
Rx B 13 
 RS422/485 Rx
Rx A 14 
Tx B 15 
 RS422/485 Tx
Tx A 16 

The Modbus card has no measuring head input, remote reset input, analogue output or
relays.

3.3 Interface selection


Use SW2 to select the RS-232 or RS-422/RS-485 interface.

Interface SW2 position


RS-232 DOWN
RS-422 UP
RS-485 UP
REGARD Modbus Card 7

4 SYSTEM CONFIGURATION
4.1 Configure Regard master card and channel cards
For correct operation of the Modbus card, the Regard master card and channel cards
must be correctly configured.

4.2 Configure Modbus card


4.2.1 Set baud rate and parity
The baud rate and parity setting of the Modbus card must be the same as used on the
Modbus master. Use commands 52-4 and 52-5 to set the baud rate and parity
respectively.

4.2.2 Set Regard communications checksum (CRC or CSUM)


The Modbus card must use the same communications checksum as the rest of the
Regard system. Use command 52-6 to set the checksum.

4.2.3 Set Modbus slave number


If more than one Modbus slave is connected to a Modbus master, the Modbus slave
number for each slave must be set. Use command 52–1 on the Modbus card to set the
Modbus slave number for the card.

4.2.4 Enable/disable exceptions


Normally, any attempt by the Modbus master to access information on a Regard channel
card which is not present will result in a Modbus exception. If the Modbus Master cannot
be configured to access only the Regard channel cards which are present, use
commands 52–2 and 52–3 to suppress exceptions.

4.2.5 Set gas level range


The gas level can be sent to the Modbus master as either signed (-32768 to +32767) or
unsigned (0 to +32767). When set unsigned, negative gas levels are sent as zero. Use
command 52-7 to select signed or unsigned gas levels.

4.3 Test communications


Ensure that the Modbus card is successfully maintaining information for each Regard
channel card. Use command 14–7 and ensure that ‘Y’ is displayed for each channel
card. If not, check that the correct communications checksum has been selected.

Ensure that the Modbus card is successfully receiving and responding to requests from
the Modbus master. Use command 14–8 to confirm that the count of successful requests
increments regularly as the Modbus master operates. If the count remains at zero,
ensure that the Modbus master and Modbus card are configured to the correct
communications format. Check that the Modbus master is attempting communications
with the correct Modbus slave number. Check that the switch on the Modbus card is set
correctly.

4.4 Save settings


Use command 00–2 to save the configuration settings.
8 REGARD Modbus Card

5 COMMANDS REFERENCE
Commands that are only available in software version 1.8 or 1.9 are identified by the
software version after the command. All commands are available in v1.7.

00–0 QUIT Quit command mode


Exits command mode without saving the configuration settings.

1. Select 00–0 and press Reset.


2. The display will show QUIT and then show NO.
3. Use ñ or ò to change the display to YES and press Reset.

00–1 P.WD Enter password


1. Select 00–1 and press Reset.
2. When the display shows ???? use ñ and ò to select the first letter of the password.
3. Press Reset to enter the first letter. The second letter will then flash.
4. Use ñ and ò to enter the second letter and press Reset again.
5. Enter the third and fourth letters in the same way.
6. When the Reset button is pressed after the fourth letter has been set, the display will
show CFG if the configuration password was entered, or BAD if an invalid password
was entered. The display then returns to 00–1.

If an invalid password is entered, the card will remain at read level. Press Reset again to
enter another password.

00–2 SAVE Save configuration settings


1. Select 00–2 and press Reset.
2. The display will show SAVE and then show NO.
3. Use ñ or ò to change the display to YES and press Reset.
4. The display will show WAIT while the settings are written to EEPROM, then OK,
confirming that the settings have been saved.

If there are no new configuration settings to save, the display will show NO! at step 2.
Pressing ñ or ò will have no effect. Press Reset to return to 00–2.

00–3 PCHG Change password


Allows you to change the configuration level password.

1. Select 00–3 and press Reset.


2. The display changes to “????”. If you press Reset now the password remains
unchanged.
3. Use ñ, ò and Reset to enter a new password in the same way as command 00–1.

The new password becomes effective immediately but only becomes permanent when
you save the new settings using command 00–2.
REGARD Modbus Card 9

14–0 TLED Test LEDs and display


1. Select 14–0 and press Reset.
2. The LEDs and display will flash. Pressing ñ or ò has no effect.
3. Press Reset again to stop the LEDs and display flashing.

The Modbus card only uses the Power and Inhibit LEDs: the other LEDs are always unlit.

14–7 TSLV Test Regard communications


Tests that the Modbus card is correctly receiving the data on the RS-485 bus between
the Regard master card and channel cards.

1. Select 14–7 and press Reset.


3. The display will show the channel card number 01, followed by Y if communication
with that card is OK, or N if it is not. A question mark (?) after the channel card
number means that there is no channel card of that number.
4. Press ñ or ò to select different channel card numbers.
5. Press Reset to end testing.

14–8 TBUS Test Modbus communications


Tests that the Modbus card is successfully receiving and responding to requests from the
Modbus master.

1. Select 14–8 and press Reset.


3. The display will show a count of requests from the Modbus master which have been
responded to by the Modbus card.
4. Press ñ or ò to reset the count to zero.
5. Press Reset to end testing.

52–1 GATE Set Modbus slave number


Sets the Modbus slave number for the Modbus card for communications with the
Modbus master. Can be set between 1 and 247.

1. Select 52–1 and press Reset.


2. The display will show the current Modbus slave number.
3. Press ñ or ò to change the number.
4. Press Reset.

52–2 BAD2 Control function 02 exceptions


Modbus function 02 is used to access ‘bit’ data.

Normally, an attempt by the Modbus master to request bit data for a Regard channel
which is not present will return exception code 04. If the Modbus master cannot be
configured to request bits only for those Regard channel cards which are present (some
Modbus masters can only make bit requests in multiples of 8 or 16, for example), then
exceptions can be suppressed. The Modbus card will then reply with data even if the
channel card is not present. The data returned for non-existent channels will be invalid.

1. Select 52–2 and press Reset.


2. The display will show the current setting: YES or NO.
3. Press ñ or ò to change the setting; select ‘NO’ to suppress exceptions.
4. Press Reset.
10 REGARD Modbus Card

52–3 BAD4 Control function 04 exceptions


Modbus function 04 is used to access ‘register’ data.

Normally, an attempt by the Modbus master to request register data for a Regard
channel which is not present will return exception code 04. Suppressing exception code
04 for this function forces the Modbus card to reply with data even if the channel card is
not present. The data returned for non-existent channels will be invalid.

1. Select 52–3 and press Reset.


2. The display will show the current setting: YES or NO.
3. Press ñ or ò to change the setting; select ‘NO’ to suppress exceptions.
4. Press Reset.

52–4 BAUD Select baud rate (v1.8, v1.9)


Select 9600 or 4800 baud data rate for communications with Modbus Master.

1. Select 52–4 and press Reset.


2. The display will show the current setting: 4800 or 9600.
3. Press ñ or ò to change the setting.
4. Press Reset.

52–5 PRTY Select Parity (v1.9)


Select NONE, ODD or EVEN parity for communications with Modbus master.

1. Select 52–5 and press Reset.


2. The display will show the current setting: NONE, ODD or EVEN.
3. Press ñ or ò to change the setting.
4. Press Reset.

52–6 CKSM Select Regard communications checksum (v1.9)


1. Select 52–6 and press Reset.
2. The display will show the current setting: CRC or CSUM.
3. Press ñ or ò to change the setting.
4. Press Reset.

52–7 MEAS Select gas level format (v1.9)


Select signed (SIGN) or un-signed (UNSN) gas level.

1. Select 52–7 and press Reset.


2. The display will show the current setting: SIGN or UNSN.
3. Press ñ or ò to change the setting.
4. Press Reset.

60–1 DISP Display off


ON: display shows “GATE”. OFF: display shows “_ _ _ _”.

1. Select 60–1 and press Reset.


2. The display will show the current setting: ON or OFF.
3. Press ñ or ò to change the setting.
4. Press Reset.
REGARD Modbus Card 11

APPENDIX A: OPERATIONAL FAULTS


An operational fault is a fault in the cards circuitry or operation. The Power LED will flash
once a second and the display will alternate between normal and one of the fault codes
in the following table.

Operational faults are latching and non-acknowledgeable. Press Reset to clear the fault
indication once the fault itself has cleared; if pressing Reset does not clear the fault
indication then the fault is still present.

Operational faults on the Modbus card are not classed as advisory or critical.

Fault Meaning Remedy


code
FLTB Button fault. Check all front panel buttons.
One of the front panel buttons appears to be
continuously pressed.
FLTD Data error. Use command 00–2 to try to
save new settings. If this
Configuration settings have been corrupted.
does not clear the fault,
Modbus communications may not operate replace card.
reliably. Default configuration settings will be
used.
FLTE EEPROM failure. Replace card.
Configuration settings have been lost.
Default configuration settings will be used.
FLTI Internal configuration settings error. Replace card if fault recurs.
Corruption of the configuration settings in
RAM occurred. Settings have been corrected
from values in EEPROM.
FLTM Microcontroller failure. Hold down Reset for 5
seconds to try to restart card.
Card has stopped working. FLTM alternates
If successful, watchdog reset
with a fault code identifying the fault.
will occur.
Replace card if fault recurs.
FLTW Watchdog reset. Check power supply if more
than one card affected,
An unknown error has caused the card to
otherwise replace card.
reset. The card will continue to operate
normally.
12 REGARD Modbus Card

APPENDIX B: SPECIFICATIONS
Operating conditions
Operating ranges
Supply voltage 18 – 30V DC, unregulated
Temperature 0 – 50°C
Humidity 0 – 90% RH, non-condensing
Vibration To BS 2011 Part 2.1Fc

Current consumption
Typical 125mA
Maximum 200mA

Weight 200g

Backplane terminals

1 

2  NO CONNECTION

3 
4 

5  NO CONNECTION

6 
7 

8  NO CONNECTION

9 
Tx 10 

Rx 11  RS232 Rx/Tx

Gnd 12 
Rx B 13 
 RS422/485 Rx
Rx A 14 
Tx B 15 
 RS422/485 Tx
Tx A 16 
REGARD Modbus Card 13

APPENDIX C: RS-232, RS-422 AND RS-485 CONNECTIONS


WARNING: Accidental connection of a Regard 4-20, Ex or HART card to the PC's serial interface
will damage the PC. Take care to insert only a Modbus card in the slot wired to the PC.

RS-232 connection to PC-AT 9-way serial interface

PC (9-way)
Tx 10 2 RxD
Rx 11 3 TxD
GND 12 5 GND
7 RTS
8 CTS

RS-232 connection to PC 25-way serial interface

PC (25-way)
Tx 10 3 RxD
Rx 11 2 TxD
GND 12 7 GND
4 RTS
5 CTS

RS-422 connection
Note. Pin numbers for Modbus master not shown: refer to Modbus master instructions.
Modbus master

GND 12 GND
Rx B 13 Tx B
Rx A 14 Tx A
Tx B 15 Rx B
Tx A 16 Rx A

RS-485 connection
Note. Pin numbers for Modbus master not shown: refer to Modbus master instructions.
Modbus master

GND 12 GND
Rx B 13 B
Rx A 14 A
Tx B 15
Tx A 16
14 REGARD Modbus Card

APPENDIX D: MODBUS IMPLEMENTATION


The Regard Modbus card uses RTU transmission mode.

Function 02 – read alarm data


Modbus function 02 reads channel card alarm information. Up to 1499 bits can be read
by one command.

Each channel card alarm (A1, A2, A3 and Fault) has three status bits:
• TRIPPED – indicates alarm trip status (1 = tripped);
• ACTIVE – indicates relay alarm state (1 = relay in alarm state);
(If a relay is disabled, the ACTIVE bit reflects the state of the relay if it were not
disabled.)
• UN-ACKNOWLEDGED – indicates whether an alarm has been acknowledged (1 = un-
acknowledged).

Each channel card also has three additional status bits:


• INHIBIT – indicates that the channel card is in alarm inhibit (1 = inhibit);
• HCAL – indicates that the 4-20mA measuring head connected to the channel card is
in calibration mode (1 = calibration mode);
• CRITICAL FAULT – indicates that the channel card has a critical card fault (1 = critical
fault).

Digital addresses
10001-10099 A1 TRIPPED status for channels 01-99
10101-10199 A1 ACTIVE status for channels 01-99
10201-10299 A1 UN-ACKNOWLEDGED status for channels 01-99
10301-10399 A2 TRIPPED status for channels 01-99
10401-10499 A2 ACTIVE status for channels 01-99
10501-10599 A2 UN-ACKNOWLEDGED status for channels 01-99
10601-10699 A3 TRIPPED status for channels 01-99
10701-10799 A3 ACTIVE status for channels 01-99
10801-10899 A3 UN-ACKNOWLEDGED status for channels 01-99
10901-10999 Fault alarm TRIPPED status for channels 01-99
11001-11099 Fault alarm ACTIVE status for channels 01-99
11101-11199 Fault alarm UN-ACKNOWLEDGED status for channels 01-99
11201-11299 INHIBIT status for channels 01-99
11301-11399 HCAL status for channels 01-99
11401-11499 CRITICAL FAULT status for channels 01-99

Attempting to read a digital with an address greater than 11499 will result in Modbus
exception code 02 (illegal data address).

Reading a digital with addresses 10100, 10200 etc. will always return 0.

Modbus exception code 04 (slave device failure) is returned if the data from any channel
has not been updated for more than 40 seconds. Command 52–2 can be used to prevent
exception code 04 being returned by this function.

Caution! Suppressing exception code 04 may result in out of date information.


REGARD Modbus Card 15

Function 04 – read gas level and alarm data


Modbus function 04 reads the gas level and the alarms status for each channel card. Up
to 99 words can be read by one command.

Register addresses
30001–30099 Gas level word for channels 01–99
31001–31099 Alarms status word for channels 01–99

The gas level word takes a value in the range –32768 to +32767. This corresponds to
the gas level on the channel card display, ignoring any decimal point. (For example, for
a display of 20.9, the word value will be 209.) Normally the value will be between –20%
and +100% of the gas range. If the gas level display on the channel card is at or above
full scale, the word value will be +32767. If unsigned gas levels have been selected the
range is 0 to +32767. Negative gas levels are set to 0.

The alarm status word contains the alarm and channel status bits:

Bit
0 A1 UN-ACKNOWLEDGED status
1 A1 ACTIVE status
2 A1 TRIPPED status
3 CRITICAL FAULT Status

4 A2 UN-ACKNOWLEDGED status
5 A2 ACTIVE status
6 A2 TRIPPED status
7 HCAL status
8 A3 UN-ACKNOWLEDGED status
9 A3 ACTIVE status
10 A3 TRIPPED status
11 INHIBIT status

12 Fault alarm UN-ACKNOWLEDGED status


13 Fault alarm ACTIVE status
14 Fault alarm TRIPPED status
15 Channel card not responding

Reads to register addresses 30100 to 31000 inclusive, or to addresses greater than


31099 will result in exception code 02 (illegal data address).

Modbus exception code 04 (slave device failure) is returned for reads to addresses
30001 to 30099 if the data from any channel has not been updated for more than 40
seconds. Command 52–3 can be used to suppress exception code 04 for this function.

Caution! Suppressing exception code 04 may result in out of information.

For reads to addresses 31001 to 31099, exception code 04 is not returned, but bit 15 is
set to 1 if the data from any channel has not been updated for more than 40 seconds.
16 REGARD Modbus Card

Function 06 – acknowledge / reset alarms (V2.0 only)


This function allows a Modbus Master to acknowledge or reset alarms in a Regard
system.

Writing “1” to register address 40100 will send a alarm accept message on the Regard
RS-485 bus. This is equivalent to pressing R on the Regard Master card.

This function is only available in Regard Modbus card software version 2.0.

Writing to register addresses other than 40100 will generate exception code 02. Writing
a data value other than 1 to register 40100 will generate exception code 03.

Caution! If another “external” device (e.g. a PC) transmits on the Regard RS-485 bus when this
function is used, data collisions may occur on the RS-485 bus, causing both the alarm
acknowledge and the other devices action to fail.

Other functions
Attempts to use Modbus functions 01, 03, 05 or 07 will give Modbus exception code 01
(illegal function). Attempts to use any other Modbus function will give no response.
REGARD Modbus Card 17

APPENDIX E: COMMANDS SUMMARY


Cmd. Command Function Command level Default
No. name Read Config setting
00–0 QUIT Quit command mode • •
00–1 P.WD Enter password • •
00–2 SAVE Save settings •
00–3 PCHG Change password •
14–0 TLED Test display & LEDs • •
14–7 TSLV Test Regard communications • •
14–8 TBUS Test Modbus communications • •
52–1 GATE Set Modbus slave number o • 01
52–2 BAD2 Suppress function 02 exceptions o • YES
52–3 BAD4 Suppress function 04 exceptions o • YES
52–4 BAUD Set baud rate o • 4800
52–5 PRTY Set parity setting o • NONE
52–6 CKSM Set Regard communications checksum • CRC
52–7 MEAS Set gas level range o • SIGN
60–1 DISP Turn normal display on or off • OFF

• Command can be accessed and setting changed.


o Command can be accessed but setting cannot be changed.
Draeger Ltd Draeger Safety, Inc.
Kitty Brewster Industrial Estate P.O. Box 120
Blyth, Northumberland Pittsburgh, PA 15230
NE24 4RG USA
England
Tel. +1 412 787 8383
Tel. +44 1670 352891 Fax +1 412 787 2207
Fax +44 1670 356266

Dräger Sicherheitstechnik GmbH Draeger South East Asia Pte, Ltd.


Revalstrasse 1 67, Ayer Rajah Crescent #06-03
D-23560 Lübeck SGP-0513 Singapore
Germany Singapore

Tel. +49 451 882 2794 Tel. +65 872 9288


Fax +49 451 882 4991 Fax +65 773 2033

Draeger Industrie S.A. Beijing Fortune Draeger Safety


3c, route de la Fédération Equipment Company Limited
F-67025 Strasbourg Cedex Jixiang Lu B Area
France Beijing Tianzhu Airport Industrial Zone
Houshayu, Shunyi County
Tel. +33 3 88 40 76 76 Beijing 101300, PR China
Fax +33 3 88 40 76 67
Tel. +8610 6949 8000
Fax +8610 6949 8006

http://www.draeger.com

Manual P/N 4205742


Issue 5 - July 1999
Subject to alteration

For use with Modbus card software versions 1.7, 1.8, 1.9 & 2.0

You might also like