PE8 User Manual
PE8 User Manual
INDEX
INDEX ......................................................................................................................................2
Introduction...............................................................................................................................3
Mains & Battery........................................................................................................................4
Connecting the mains............................................................................................................4
Connecting the batteries........................................................................................................4
Charger Short Circuit Protection...........................................................................................4
Detectors & sounders ................................................................................................................5
Wiring the detectors ..............................................................................................................5
Diode Bases...........................................................................................................................5
Zone Short Circuit Protection ...............................................................................................5
Wiring the sounders ..............................................................................................................5
Setting a Sounder Activation Delay......................................................................................6
Other Connections.....................................................................................................................7
Fire Relay..............................................................................................................................7
Fault Relay ............................................................................................................................7
Class Change Input ...............................................................................................................7
Display & Controls ...................................................................................................................8
Display ..................................................................................................................................9
Controls...............................................................................................................................10
Alarm Condition & Resetting an alarm ..................................................................................11
What to do in the event of a fire..........................................................................................11
Resetting from an alarm condition......................................................................................11
Fault display & fault-finding ..................................................................................................12
Fault Finding .......................................................................................................................12
Supply fault .....................................................................................................................12
Zone Fault .......................................................................................................................13
Sounder Circuit Fault ......................................................................................................13
Earth Fault.......................................................................................................................14
System Fault....................................................................................................................14
Disablement ............................................................................................................................15
TO PROGRAMME ZONE (OR SOUNDERS) AS DISABLED.......................................15
Test Mode ...............................................................................................................................16
TO PROGRAMME ZONE IN TEST .................................................................................16
Optional Repeater Driver ........................................................................................................17
Battery Calculation .................................................................................................................18
Sample Calculation .............................................................................................................18
Specifications ..........................................................................................................................19
Electrical Specifications......................................................................................................19
Enclosure Specifications .....................................................................................................19
Fuse Ratings........................................................................................................................19
Log Book ................................................................................................................................20
MAINTENANCE WORK ..................................................................................................20
FALSE ALARMS...............................................................................................................21
ALL OTHER EVENTS ......................................................................................................22
Introduction
The Premier Elite 4 to 8 zone panels have been designed to meet the requirement
of an easy to use fully functional fire alarm control panel.
Each version has 2 sounder circuits, an alarm relay , and a fault relay.
There is an option to add a zonal output board, which can be used to drive zonal
relays, or a hard wired repeater panel.
There is no configuration, simply connect the detectors & sounders and apply
power.
The Premier Elite range also includes a low cost 1 & 2 zone version These panels
are NOT covered in this manual. They have a separate manual.
The Mains supply to the FACP is fixed wiring, using Fire resisting 3-core cable
(Between 1 mm² and 2.5mm²) or a suitable 3-conductor system, fed from an
isolating double pole switch fused spur, fused at 3A. IT SHOULD NOT BE
CONNECTED THROUGH AN RCD. This should be secure from unauthorised
operation and be marked ‘FIRE ALARM: DO NOT SWITCH OFF’. The supply must
be exclusive to the Fire Panel. MAKE SURE ANY SPARE ENTRY HOLES ARE
COVERED WITH THE GROMMETS PROVIDED
The –ve of the other battery is connected to the black battery lead.
The –ve of the first battery is connected to the +ve of the second battery using the
link wire supplied.
Although there are many sizes of suitable battery, the sizes we usually recommend
are 12V 2Ah for standard backup, or 12V 7Ah for extended backup (72 hour or
more) , and the enclosure has been designed to hold these two battery sizes.
BATTERY
INTERCONNECTING TO PCB
TO PCB CABLE
BATTERY
INTERCONNECTING
CABLE CLAMP
The Premier Elite has an intelligent charger, that senses if too much current is being
drawn (for instance in the case of totally discharged batteries, or the charger leads
being shorted together). In such an event, the Premier Elite 4-8 zone panel will turn
off the power to its charger circuit.
The panel also turns off the charger when the batteries are disconnected.
Approved Document No: GLT.MAN-119 PAGE 4
Issue : 1 Author: NRPJ Date: 22/11/2006
INSTRUCTION MANUAL – 4 to 8 ZONE FIRE ALARM PANEL
Zone -
-R L2 -R L2 -R L2
1N4002 End of
EARTH
EARTH
EARTH
line diode.
L1
IN
UT
L 1O IN
L1 UT
L1O IN
L1 UT
L1 O
Stripe to +ve
Zone +
When common bases are used, call points should be connected to the start of the zone, so that
removing a detector head will not remove power from the call points.
Diode Bases
The Premier Elite 4-8 zone can also be used with diode bases. Diode bases allow call points &
detectors to be mixed on the same zone without any restrictions. The diode (also known as a
continuity diode) passes power to the downline detectors and call points, if a detector head is
removed for any reason.
SND+
SND-
SOUNDER SOUNDER SOUNDER SOUNDER
10K
++ -- ++ -- ++ -- ++ -- End of
Line Resistor
On the Premier Elite there is the option to delay the sounder activation in the event
of a fire. This might be useful in schools or clubs where the responsible person
might want to verify the alarm, before having a “mass evacuation” of the building. A
false alarm can be reset before the sounders operate. If it is a true alarm, the
sounders can be started before the timer finishes by pressing the DELAY
OVERRIDE BUTTON.
To set a delay open the panel door using Alan Key provided and set switch 7 (SW7)
using a terminal screw driver to the delay required
When a delay is set, the panel will show GENERAL DISABLEMENT and DEL
(sounder DELay)
Other Connections
The Premier Elite also has the following connections:-
Fire Relay
The Premier Elite has one volt free change over relay that operates on an
alarm. It is rated at 1Amp, SELV. The relay remains operated until the panel
has been reset.
Fault Relay
The Premier Elite has one volt free change over relay that operates on any
fault condition. The Relay is Normally energised, so that it gives a signal in the
event of total power failure (Mains & Battery back-up). It is rated at 1Amp,
SELV. The relay remains operated until the fault has been cleared.
The class change input on a Premier Elite 4-8 zone F.A.C.P. will remotely
operate the sounder circuits.
It can also be used as a simple way of linking 2 control panels. You would link
from the fire relay on one panel to the class change on the other, and vice
versa.
Operating Instructions
To Reset From Fire Condition:
Normal Operation: After all detectors and manual call points have been
Under normal conditions, the system will be silent and the green returned to normal, turn the key switch to the "CONTROLS
"POWER" LED will be on. ENABLED" position and press button 1 to stop the fire
Fire Condition: sounders. Press button 2 to silence the internal fault buzzer
In a fire condition, the "GEN FIRE" LED and the specific zones(s) and then press button 3 to RESET the system.
"FIRE" LED will be on and the internal panel buzzer will sound.
Fault Condition: Silence Fault Tone
In any fault condition, the "GEN FAULT" LED and the specific zone If the panel is showing a fault condition, turn the key
fault(s) LED will be on and the internal fault buzzer will sound. switch to the "CONTROLS ENABLED" position and press
Disabled Condition: button 2 (SILENCE FAULT CONDITION). If new faults are
In the disabled condition, the "GEN DISABLEMENT" LED and the subsequently detected, the specific fault(s) LED will be
specific zone(s) LED will be on. on and the internal fault buzzer will sound. CALL
Start/Stop Fire Sounders: ENGINEER.
To start or stop the fire sounders, turn the key switch to the
"CONTROLS ENABLED" position and press button 1 . Pressing External Sounder Delay Override:
this button again will toggle between stop/start sounders. When the panel is in a Fire Condition and the system has been configured
with delayed alarm function, the "DEL" LED will be on. At the end of the delay
period the "DEL" LED will go off and the fire sounders will then operate. This
delay may be overridden by pressing the “DELAY OVERRIDE" button.
FAULT TONE
It should be noted that the Yellow zonal indication LEDs are used to indicate
several conditions. They are used for:-
Display
GEN FLT & CONSTANT YELLOW There is a problem with either the mains supply or the battery backup
SUPPLY FLT FLASHING YELLOW
GEN FLT & CONSTANT YELLOW There is a wiring problem. One of the cables is touching the earth screen.
EARTH FLT FLASHING YELLOW
GEN FLT & CONSTANT YELLOW There is an open circuit fault in the wiring of the zone indicated.
ZONAL FLT FLASHING YELLOW
GEN FLT & CONSTANT YELLOW There is a short circuit fault in the wiring of the zone indicated.
ZONAL FLT FLASHING YELLOW
GEN S/C FLASHING YELLOW
GEN FLT & CONSTANT YELLOW There is an open circuit fault in the wiring of one or both of the sounder
SND FLT FLASHING YELLOW circuits
GEN FLT & CONSTANT YELLOW There is a short circuit fault in the wiring of one or both of the sounder
SND FLT FLASHING YELLOW circuits
GEN S/C FLASHING YELLOW
GEN FLT & CONSTANT YELLOW A processor fault has occurred. To reset, turn keyswitch on then back off. If
SYSTEM FLT CONSTANT YELLOW problem persists, consult your dealer.
GEN FIRE & CONSTANT RED A fire has occurred in the zone indicated.
ZONE FIRE CONSTANT RED The sounders will be active.
GEN FIRE & CONSTANT RED A fire has occurred in the zone indicated.
ZONE FIRE & CONSTANT RED The sounders have a delay set, and will become active after the
GEN DISABLE CONSTANT YELLOW programmed delay. To override the display, press delay override.
& DEL CONSTANT YELLOW
GEN DISABLE FLASHING YELLOW The panel is ready for selecting disable or test mode
(FAST – 4 HZ)
GEN DISABLE FLASHING YELLOW The user is scrolling through zones to select which one to disable/or user
ZONE DISABLE (SLOW – 0.5 HZ) has just enabled the zone.
GEN DISABLE CONSTANT YELLOW The Sounders are delayed by the amount set on the rotary switch.
DEL CONSTANT YELLOW
Controls
Note that the controls can only be used after the keyswitch has been turned to
the ON position.
1. Follow the building evacuation procedure, and check that everyone has
left the building safely.
2. The building fire officer or responsible person should CAREFULLY
enter the building, and locate the area of the alarm from the fire alarm
panel.
3. Investigate to determine the cause of the alarm. Look for the detector
in the zone in alarm that signalled the fire. The detector that signalled
an alarm will have its RED ALARM LED on.
4. If a small fire is found, a suitably trained person could tackle this with a
suitable fire extinguisher.
5. If a larger fire is found, leave the building immediately, and contact the
fire brigade.
6. If no fire is found, make a note of the detector that signalled fire, and
look for anything nearby that could be the cause of the activation, eg
cooking, or use of a hot air gun etc.
7. Record findings in the fire alarm log book.
1 Press Stop/Start sounder button (BUTTON 1). This will silence the external
sounders.
2 Press Silence Fault Tone button (BUTTON 2). This will silence the panel`s
internal buzzer.
3 Press the Reset button (BUTTON 3). This will return the panel to it`s normal
condition.
If the panel goes straight back into alarm, then the cause of the alarm has not been
cleared. This could be a detector still exposed to smoke, or a call point still in the active
position. Press Buttons 1 & 2 on the panel, then investigate for a call point, or detector
that still has it`s RED ALARM LED on. Reset the call point, or clear the smoke. If the
problem persists, contact an engineer.
Most of these faults will need to be checked by an engineer, but the system
can be checked for a removed detector by the responsible person.
All faults in the Premier Elite are NON-LATCHING. IE they can not be reset
with the reset button. They will clear automatically when the fault has been
fixed.
The exception is a SYSTEM FAULT, which means that the processor may
have crashed, and may or may not have restarted correctly.
Fault Finding
Supply fault
Zone Fault
NO
Earth Fault
An EARTH fault indicates that something is shorting to earth (usually through the cable
screen). Disconnect the earth screens one at a time to determine the problem line.
(Note: connecting other equipment , eg an oscilloscope or PC, to the panel can give an earth
fault)
The voltage between battery –Ve and earth should be 14-16 volts. If it is not, the voltage
should indicate what is shorting to earth.
System Fault
This will result in the panel attempting to correct itself. Should this fault occur, the System
Fault LED, General Fault LED, General Fault relay and fault internal buzzer will be constantly
active until the control keyswitch is turned from off position to control enable position. This
should cause this fault condition to reset. If not, consult your supplier.
Disablement
The Premier Elite 4-8 zone allows any zone, or the sounder circuit to be disabled to aid
commissioning and assist routine maintenance work.
When a zone (or sounder cct) is disabled, the panel will not respond to any fault or fire signals
it receives from that zone. This might be used if the system requires routine maintenance, and
the customer needs the system to continue running, but doesn’t want spurious false alarms.
The panel will respond in the usual manner to any events in any non-disabled zones.
Press Engineer switch and the GENERAL DISABLEMENT LED will come on (flashing fast);
Press Scroll switch and the GENERAL DISABLEMENT LED will flash slowly. The panel is
now in SELECT DISABLEMENT MODE.
Press scroll button again. Zone 1 DISABLEMENT LED will be lit. Continue to press scroll until
the desired Zone or sounder is lit. Press the Engineer button. The GENERAL
DISABLEMENT LED will be lit constantly indicating that this zone (or sounder) is now
disabled.
If more than one zone needs to be disabled, then press scroll again until the required zone is
selected.
If the panel needs to be taken out of SELECT DISABLEMENT MODE (eg to silence a fault on
another part of the system), turn the keyswitch off, then back on again.
Once all the work has been done the zones need to be enabled again. If the panel is still in
SELECT DISABLEMENT MODE, jump to paragraph 8, otherwise, turn the keyswitch to
controls enabled, press engineer button (GENERAL DISABLEMENT LED will flash fast).
Press scroll and it will return to being on steady. The panel is now in SELECT
DISABLEMENT MODE
Press the scroll button until the disabled zone has been selected. Press engineer button.
Scroll to any other disabled zone and enable in the same way. When all zones are enabled
again, the GENERAL DISABLEMENT LED will flash slowly. Turn the keyswitch to off to return
the system to normal.
Test Mode
To aid commissioning and assist routine maintenance check, a non-latching ‘one man test’ facility is
available.
When a detector or manual call point is triggered on any zone in Test, the Alarm sounders operate for
approximately seven seconds on and seven seconds off. This cycle continues until the cause of the
Alarm is removed (either by the test smoke clearing from the detector or the manual call point being
reset), at which point, the detector circuit also automatically resets.
Should an Alarm occur on a zone that is not programmed to test, the Alarm will be processed in the
normal way. The testing of the zone in test will temporarily be suspended until the Alarm(s) from the
other zones are reset. At this point, zone retesting may resume.
The Premier Elite has a connection to fit an optional Zonal Output Card. The
card fits next to the display PCB on the fire alarm panel door.
Zonal
Output
Card
Zonal Card
Connection
1 As a stand alone board that has zonal 29 Volt outputs, suitable for
connecting relays etc.
+V – Supply Voltage
0V – Supply ground
GA – General Alarm signal
CF – Common Fault Signal
TN – Buzzer Active Signal (tone)
Battery Calculation
Here are the current consumption of the Premier Elite panels in various
conditions:-
Control Panel Model Mains Fail, Mains Fail, Mains fail,
buzzer sounding buzzer silenced panel in alarm
Premier Elite 4-8 Zone 50mA 31mA 163mA
Sample Calculation
A Premier Elite 4 zone panel has the following items connected:-
Zone 1: 2 x MCP, 8 x Optical, 2 x heat detector
Zone 2: 1 x MCP, 7 x Optical, 1 x heat detector
Zone 3: 3 x MCP, 9 x Optical, 1 x heat detector
Zone 4: 1 x MCP, 10 x Optical, 0 x heat detector
Sounder CCT 1: 10 x Maxitone sounder
Sounder CCT 2: 12 x Maxitone sounder
Where:
TALM = Maximum time in hours required for the alarm [½ hour is most common time]
IALM = Total Alarm Current in amps for all alarm devices connected to the alarm circuits
TSBY = Standby time in hours for the system after mains failure [normally 24, 48 or 72 hr]
ISBY = Quiescent current in amps of control panel in fault condition [because of mains failure]
PLUS all detection zones.
Specifications
Electrical Specifications
Enclosure Specifications
DESCRIPTION VALUE
Fuse Ratings
Log Book
MAINTENANCE WORK
DATE TIME ZONE / LOCATION REASON FOR WORK WORK CARRIED OUT ADDITIONAL WORK REQUIRED SIGNED
FALSE ALARMS
DATE TIME ZONE / CAUSE (IF KNOWN) MAINTENANCE MAINTENANCE CATEGORY OF FURTHER SIGNED
LOCATION OR ACTIVITIES IN VISIT NEEDED FINDINGS FALSE ALARM ACTION
ALARM AREA (YES/NO) REQUIRED