Ha028121 5
Ha028121 5
Options Manual
E U ROT H E R M
© 2004 Eurotherm Limited
All rights are strictly reserved. No part of this document may be reproduced, modified, or transmitted
in any form by any means, nor may it be stored in a retrieval system other than for the purpose to act as
an aid in operating the equipment to which the document relates, without the prior written permission
of Eurotherm limited.
Eurotherm Limited pursues a policy of continuous development and product improvement. The speci-
fications in this document may therefore be changed without notice. The information in this document
is given in good faith, but is intended for guidance only. Eurotherm Limited will accept no responsibil-
ity for any losses arising from errors in this document.
GRAPHICS RECORDER/DATA ACQUISITION AND LOGGING UNIT: OPTIONS MANUAL
OPTIONS MANUAL
Effectivity
This manual refers to a number of different recorders and data acquisition units, not all of which support all the op-
tions described herein. If an option is not supported (or not fitted), it does not appear in the configuration menu.
Note that this manual deals with ‘stand alone’ options such as maths, totalisers etc. Those options which are exten-
sions of basic configuration, such as Circular Charts, Auditor Pack and Log Scales are described in the User Guide
supplied with the recorder.
For Remote Viewer and Communications option descriptions (including ASCII Printer Output), please refer to the
Serial Communications and Remote Viewer User guide: HA028122
For recorders which are being operated under Remote Viewer software, any mention, in this manual, of ‘Push’,
‘Touch’ or ‘Operate’ should be read ‘Click-on’.
The User Guide, or Installation and Operation Manual supplied with the unit specifies the Software Version to which
this (options) manual relates.
HA028121 Options
Issue 5 Nov 04 Page 1
GRAPHICS RECORDER/DATA ACQUISITION AND LOGGING UNIT: OPTIONS MANUAL
GRAPHICS RECORDER
OPTIONS MANUAL
LIST OF CONTENTS
Section Page
1 BATCH RECORDING OPTION .............................................................. 7
1.1 INTRODUCTION .......................................................................................... 7
1.1.1 Auditor Pack messages ......................................................................... 7
1.2 CONFIGURATION ....................................................................................... 8
SCOPE ............................................................................................... 8
ENABLE .............................................................................................. 8
BATCH MODE ..................................................................................... 8
BATCH FIELDS ..................................................................................... 8
FIELD 1 ............................................................................................... 8
BATCH NUMBER ................................................................................. 9
FIELDS 2 TO 6 ..................................................................................... 9
ON START LOG ................................................................................... 9
ON STOP LOG .................................................................................... 9
ON NEW CLEAR ................................................................................. 9
NAME FILES BY BATCH ........................................................................ 9
1.3 OPERATION ................................................................................................ 10
1.3.1 Operator initiation .............................................................................. 10
BATCH MESSAGE DISPLAY ................................................................... 11
1.3.2 Non-operator initiation ......................................................................... 12
JOB INITIATION .................................................................................. 12
COUNTER INITIATION ......................................................................... 12
MODBUS INITIATION .......................................................................... 12
1.3.3 Event sources ........................................................................................ 12
Options HA028121
Page 2 Issue 5 Nov 04
GRAPHICS RECORDER/DATA ACQUISITION AND LOGGING UNIT: OPTIONS MANUAL
HA028121 Options
Issue 5 Nov 04 Page 3
GRAPHICS RECORDER/DATA ACQUISITION AND LOGGING UNIT: OPTIONS MANUAL
3 MATHS .............................................................................................. 44
3.1 CONFIGURATION ....................................................................................... 44
3.1.1 Maths number ..................................................................................... 44
3.1.2 Value .................................................................................................. 44
3.1.3 Reset Now .......................................................................................... 44
3.1.4 Function .............................................................................................. 45
3.1.5 Scale Low / Scale High ........................................................................ 48
3.1.6 PV Format ........................................................................................... 48
3.1.7 Remaining configuration items ............................................................... 48
3.2 FUNCTION DETAILS ..................................................................................... 48
3.2.1 Polynomial fit. ...................................................................................... 48
3.2.2 Fvalue ................................................................................................. 49
Application Note ................................................................................. 49
3.2.3 Linear Mass flow .................................................................................. 50
SCALING FACTOR ............................................................................... 50
SPECIFIC GAS CONSTANT .................................................................. 50
COMPRESSIBILITY FACTOR (Z-FACTOR) ................................................. 51
CONFIGURABLE PARAMETERS ............................................................. 51
3.2.4 Root Mass flow .................................................................................... 52
SCALING FACTOR ............................................................................... 52
SPECIFIC GAS CONSTANT .................................................................. 52
COMPRESSIBILITY FACTOR (Z-FACTOR) ................................................. 52
CONFIGURABLE PARAMETERS ............................................................. 53
3.2.5 Rolling Average ................................................................................... 54
3.2.6 Mean Kinetic Temperature (MKT) ........................................................... 54
CONFIGURABLE ITEMS ........................................................................ 55
3.2.7 Saturated Steam Mass Flow .................................................................. 56
PARAMETERS ...................................................................................... 56
PRESSURE UNITS CONVERSION .......................................................... 57
3.2.8 Saturated Steam Heat Flow ................................................................... 58
PARAMETERS ...................................................................................... 58
3.2.9 Saturated Steam Heat Consumed .......................................................... 59
PARAMETERS ...................................................................................... 60
3.2.10 Group MKT ....................................................................................... 60
3.2.11 Rate-of-change .................................................................................... 61
3.2.12 Oxygen (O2) correction ..................................................................... 62
APPLICATION NOTE ............................................................................ 62
3.2.13 Relative Humidity ................................................................................ 63
3.2.14 Zirconia probe .................................................................................. 64
OXYGEN CONCENTRATION ............................................................... 64
OXYGEN POTENTIAL .......................................................................... 66
3.2.15 Group Minimum ................................................................................ 68
DESCRIPTORS ..................................................................................... 68
3.3 MODBUS ADDRESSING ............................................................................... 69
3.3.1 Maths channel configuration data .......................................................... 69
3.3.2 Maths Channel Run-Time data ............................................................... 70
3.3.3 IEEE 32-bit channel configuration data ................................................... 70
3.3.4 IEEE Area Maths Channel run-time data ................................................. 71
Options HA028121
Page 4 Issue 5 Nov 04
GRAPHICS RECORDER/DATA ACQUISITION AND LOGGING UNIT: OPTIONS MANUAL
HA028121 Options
Issue 5 Nov 04 Page 5
GRAPHICS RECORDER/DATA ACQUISITION AND LOGGING UNIT: OPTIONS MANUAL
Options HA028121
Page 6 Issue 5 Nov 04
GRAPHICS RECORDER/DATA ACQUISITION AND LOGGING UNIT: OPTIONS MANUAL
1.1 INTRODUCTION
Batch records form a part of recording history and are included in the normal archiving process to ‘disk’ or to a re-
mote PC (section 4.1 of the User Guide supplied with the unit). Batches can be initiated directly by the operator (if
access permission is granted), automatically whenever a specified counter changes value, by job or remotely via
MODBUS/TCP.
Batches can be defined as start/stop, or continuous and can incorporate all channels, or just those associated with a
Group. For start/stop batches, the batch record starts when the batch is started, and continues until it is stopped. For
continuous batches, the batch record starts when the batch is started and continues until the next batch is started, or
until batch recording is disabled.
When using 'PC review' software the 'Go to Batch' feature can be used to select a particular batch record.
If ' Name files by Batch' is enabled (section 1.2.8), a separate history file is created for each batch.
Where DD/MM/YY is the date, HH:MM:SS is the time, and User Full name is either the current user name or security
level (e.g. Engineer). A similar message is printed at Batch Stop. (There are no stop messages associated with con-
tinuous batch selection).
In addition to the above start/stop messages, up to six lines of text can, if required, be printed on the ‘chart’ at the start
of a batch and, if required, at the end of a batch. The messages are in two parts, which for the sake of this document,
are called ‘Headings’ and ‘Values’ The Headings are entered in Fields 1 to 6 in Batch Configuration (section 1.2).
The Values associated with these headings are entered by the operator at initiation (section 1.3).
If the Auditor Pack option is fitted a Config/Security Revision message appears immediately after the Batch Start
message:
HA028121 Options
Issue 5 Nov 04 Page 7
GRAPHICS RECORDER/DATA ACQUISITION AND LOGGING UNIT: OPTIONS MANUAL
1.2 CONFIGURATION
Select
Instrument Scope Group Instrument
or Group
Groups Group 1) Group 1
Channels Enable
Views Select
Batch mode Start/Stop Start/Stop
or Continuous
Archive
Batch Fields 4
Events
Field 1 Batch Number:
Event Buttons
Select
Messages
Batch number: Use Counter Counter or Text
Select Counter
User Linearisations Counter Counter 1 (Appears only if 'Use
Counter' selected)
SCOPE
Allows the user to define all configured channels (instrument) or just those in a particular group, for batch control. If
'Group' is selected, a further picklist appears allowing a specific group to be selected. If multiple groups are not
available, this list contains only group 1.
ENABLE
Allows the batch function to be switched on or off.
BATCH MODE
Allows batch mode to be selected as Continuous or Start/Stop.
BATCH FIELDS
Allows the maximum number of messages to be printed at batch start/stop to be selected between one and six.
FIELD 1
This field is the first of up to six which can be used as headings for batch information. Headings can be up to 20 char-
acters long (including spaces). In the example shown in Figure 1.2, Heading 1 has been entered as ‘Batch Number:’.
When initiating the batch, the operator has to enter a value to be associated with this heading (see section 1.3 Opera-
tion, below), unless 'Use Counter' is selected in the following 'Batch Number' field.
Options HA028121
Page 8 Issue 5 Nov 04
GRAPHICS RECORDER/DATA ACQUISITION AND LOGGING UNIT: OPTIONS MANUAL
BATCH NUMBER
This allows the Value entered for Field 1's heading to be selected as 'Use Text' or 'Use Counter'.
USE TEXT. When Text is selected, the value for field 1 is entered by the operator on initiation of the batch.
USE COUNTER. When Counter is selected, a further field appears ('counter') allowing a specific counter to be se-
lected from a picklist. The selected counter initiates a new batch whenever it changes value, and the counter value is
appended to the text associated with Field 1.
FIELDS 2 TO 6
Fields 2 to 6 are also used as headings for batch information. Values for these headings must be entered by the opera-
tor prior to Batch initiation. See also ‘On new clear’, below. Headings can be up to 20 characters long (including
spaces).
ON START LOG
This defines how many of the selected Fields are to be printed at batch start. An entry of ‘1’ means that only Field 1
will be printed. An entry of ‘2’ means that Fields 1 and 2 will be used, and so on. An entry of 0 means that only the
‘Batch Start’ message (section 1.1 above) will be printed. It is not possible to print only, say, Field 3. If Field 3 is
required, it must be preceded by Fields 1 and 2.
ON STOP LOG
As for On start log, above, but for batch stop. This item appears only if Start/Stop is selected as batch mode.
ON NEW CLEAR
For 'Use Text' Batches only, this allows the user to clear none or more of the batch entries at each batch start. In the
example above, if the user enters a batch number of say 001130.001, with Customer Name: FishesRus, Operator
name: Marvin, Supervisor: Fred, then setting ‘On New Clear’ to ‘1’, causes the batch number to be cleared, and to
have to be re-entered, each time a new batch is started.
In a similar way, setting ‘On New Clear’ to ‘2’ means that the batch number value and the Customer Name: value to
be cleared. A new batch cannot be started without new values first being entered.
For example, if a batch name of 001130.001 is amongst the items archived to disk, then this file will appear in the
form:
Group Name~001130.001~HHHHHHHHHHHHHHHH,
Where HH----HH is a 16 digit hex code* used by the recorder and by review software to identify the file. If name
files by batch is not selected, the Batch name is not included, and the file will appear as:
Group Name~HHHHHHHHHHHHHHHH,
*The HHH--HHH code contains the following information:
H H H 6H H H H 2H H 2 H H H H 6H H H
HA028121 Options
Issue 5 Nov 04 Page 9
GRAPHICS RECORDER/DATA ACQUISITION AND LOGGING UNIT: OPTIONS MANUAL
1.3 OPERATION
This section describes how the operator initiates a new batch. Batches can be initiated from any of the trend, bar-
graph or numeric display modes, but the start/stop and other messages appear only on the Trend Graph screen, and its
associated trend history display. Batch information and status are retained whilst power is off.
To initiate a batch, either Option Menu
a) Operate the Option key, then press ‘Batch’ in the Option
menu* which appears, or Batch
b) Touch the (dark green) message area at the top of the screen.
Note
*Note: The option menu is context sensitive, so its appearance may
differ from the example shown Faceplates On/Off
‘Values’ can now be entered for these headings by entering strings of up to 60 characters (including spaces). This is
done, as usual, by touching the empty field and using the resulting pop-up keyboard to type-in the entry. Once the
entries are complete, operation of the Start button initiates batch recording. Operation of the Store button saves the
configuration for later initiation by counter or via MODBUS/TCP, if either option is fitted.
The Values entry page is replaced by the batch status page (figure 1.3.1b), this time showing details of the batch in
progress. This page allows the batch to be stopped or a new one triggered.
Batch
Supervisor: Fred
Options HA028121
Page 10 Issue 5 Nov 04
GRAPHICS RECORDER/DATA ACQUISITION AND LOGGING UNIT: OPTIONS MANUAL
Batch
The messages are displayed on the Graph Trend display as shown in figure 1.3.1c, below. This figure uses the exam-
ple given in the previous sections, and uses only four messages. Further messages would appear above message 4.
The figure also shows that time and date are added to the messages, and that the currently running batch number is
given in the Group name area. Touching this area calls the Batch status page.
Engineer
Group 1 14:25:59
Batch Number 001130.001 30/11/00
Channel 1 Touching this area calls the 700.87
400.00 480.00 560.00 batch status
640.00 page 720.00 800.00
14:24:33
30/11/00
14:19:11
30/11/00
HA028121 Options
Issue 5 Nov 04 Page 11
GRAPHICS RECORDER/DATA ACQUISITION AND LOGGING UNIT: OPTIONS MANUAL
JOB INITIATION
As described in section 4.7.9 of the User Guide supplied with the unit, a job can be set up to initiate a batch whenever
the job source becomes active. If 'Scope' is set to 'Group' a specific group can be selected (default = Group 1) and the
job will act only on the batch associated with this group.
COUNTER INITIATION
If Batch Number is selected as 'Use Counter', (section 1.2) then a new batch will automatically be started whenever
the selected counter changes value (increment, decrement or preset). The new value of the counter is used as the
value associated with Field 1.
For the other fields to have values printed on the chart, these must have been entered as described above for Operator
initiation, then the 'Store' button touched.
The 'On new clear' setting (section 1.2) is ignored, the stored values being used each new batch.
MODBUS INITIATION
In order to initiate batch recording via MODBUS/TCP, a Batch Start flag has to be set (value = 0001). For Scope =
Group (section 1.2), the flag for the specified group must be set. For Scope = Instrument any group's Batch Start flag
may be used.
The address of the flag for group 1 is decimal 42364; the address for group N is {42364 + 629(N-1)}
For further details of the Modbus option see section 2 of the Communications Manual.
If Batch mode = Start/Stop (section 1.2), batches can also be stopped via MODBUS. The address for group 1 is
42365; the address for group N is {42364 + 629(N-1)}. Again the value must be set to 0001.
As described in section 4.3.6 of the User Guide (Event Configuration), ‘Batch Start’, ‘Batch Running’ and ‘Batch
Stop’ can be selected as event sources. If 'Scope' = 'Group' in Batch configuration (described above), then the user
can select which group's batch is to be used as the event source.
Options HA028121
Page 12 Issue 5 Nov 04
GRAPHICS RECORDER/DATA ACQUISITION AND LOGGING UNIT: OPTIONS MANUAL
2 SCREEN BUILDER
Note: This option is not available with all models.
2.1 INTRODUCTION
This option allows the user to create screen layouts using recorder data, simple drawing tools, text and/or imported
image files. The option comes in two variants, known as ‘Lite’ and ‘Full’.
2.1.1 Versions
FULL
The Full version offers 24 user screens editable from the operator interface plus up to 100 extra screens which can
be created only at the remote viewer. Once created, such screens (25 to 124) can be copied or moved to one or
more of screens 1 to 24, thus becoming accessible at the instrument’s operator interface. (For the data acquisition
and logging unit, which has no operator interface other than Remote Viewer, there is no distinction between screens
1 to 24 and screens 25 to 124.)
When creating any of the screens at the remote viewer, a number of extra features are available to speed up the
screen creation process. These ‘Quick-build’ features include the ability to edit the position and size of a screen
component using familiar ‘click and drag’ mouse techniques, and the ability to ‘clone’ components. See section
2.5.1 for details.
LITE
The lite version is identical with the full version with the following exceptions:
1. There are only 6 user screens, all accessible from the user interface (if fitted).
2. The remote viewer does not include the ‘Quick-build’ features.
HA028121 Options
Issue 5 Nov 04 Page 13
GRAPHICS RECORDER/DATA ACQUISITION AND LOGGING UNIT: OPTIONS MANUAL
As shown in figure 2.1, the user screens can be included in the display mode selection menus, described in section 3.4
of the User Guide supplied with the unit, and a User screen can be selected as the 'Home page'.
Note: Circular Trend option displays are not supported in User screens with this release of software.
The Save/Restore screen (figure 2.1.3) includes the categories 'Import screen' and ‘Export screen’.
Save
Restore
See section 4.2 of the User
New
Guide for descriptions of
other Save/Restore func- Text
Options HA028121
Page 14 Issue 5 Nov 04
GRAPHICS RECORDER/DATA ACQUISITION AND LOGGING UNIT: OPTIONS MANUAL
IMPORTING SCREENS
Touching the filename area, allows a previously created user screen to be selected either from the Flash memory or
from disk to be imported. The User Screen picklist allows the user to define which User screen is to be 'replaced' by
the imported file.
EXPORTING SCREENS
Allows user screens to be exported to Flash memory, or disk, The operator can assign a suitable filename before
exporting.
The following description is an attempt to show how to create a simple screen layout. The technique used is to define
an object, then to specify its size, and where its top left corner is to be located on the screen.
The option offers two levels of sophistication - basic and advanced. The basic system defines size, position, fill col-
our etc. for components (section 2.3.1). Advanced parameters allow a more sophisticated fine-tuning of the appear-
ance of the components
As implied in figure 2.2.3a, screen component position and dimensions can be specified as percentage, absolute pixels
or relative pixels. Percentage is ‘percentage of screen size'. Absolute pixels allow position and/or dimensions to be
defined as an absolute number of pixels. Relative pixels are the same as absolute pixels, except that if the display is
rescaled on, say, a pc screen, the absolute pixel object will remain unchanged, whereas the relative pixel object will
scale appropriately. Similarly, for transfer from a VGA screen recorder to a 1/4VGA recorder or vice-versa.
HA028121 Options
Issue 5 Nov 04 Page 15
GRAPHICS RECORDER/DATA ACQUISITION AND LOGGING UNIT: OPTIONS MANUAL
Table 2.2.2 shows the selectable screen components, their default top-left corner positions, widths/heights and draw
order. All these components are described in section 2.4 below.
Options HA028121
Page 16 Issue 5 Nov 04
GRAPHICS RECORDER/DATA ACQUISITION AND LOGGING UNIT: OPTIONS MANUAL
2.2.3 Example
To produce a new display screen with channels one to four inclusive each displayed as an independent bar graph
across the width of the screen, with Group 1 vertical trend display below. To achieve the above, the following items
will be required:
1. Bar1: Horizontal bargraph with X = 0, Y = 0, Width = 100, Height = 10, channel = Channel 1
2. Bar2: Horizontal bargraph with X = 0, Y = 12, Width = 100, Height = 10, channel = Channel 2
3. Bar3: Horizontal bargraph with X = 0, Y = 24, Width = 100, Height = 10, channel = Channel 3
4. Bar4: Horizontal bargraph with X = 0, Y = 36, Width = 100, Height = 10, channel = Channel 4
5. Group 1: Vertical trend group with X = 25, Y = 48, Width = 50, Height = 50. Group name to appear above display.
Batch
Note
1. Ensure that one or more user screens is enabled in
Edit Screen
views Configuration (section 2.1). If necessary, call
Component Property Editor - Screen 1
the required User screen to the display using the Root Component picklist field
Add Del main_1.2
menu 'Goto View' menu. Identifier main_1.2
Last Error
Add/Delete component keys Page Title
X Position 0
2. Press the Option key to call the Option Menu. Y Position 0
%
Component properties %
(Fields vary according to Width 100 %
component type)
Height 100 %
3. Press ‘Edit Screen’ to call the ‘Component Property Background Colour -1
Draw Order -1 Dimension picklist.
Editor’ page to the display. This display contains the Component Type Main
Select %, absolute pixels,
or relative pixels.
basic properties of the ‘Main’ (background) screen Save Discard New Close
onto which the required components are to be overlaid.
Note: This may take some seconds, according to the Usr Screen Options
Edit level Basic
complexity of the configuration Component info on screen
Quick entry to edit
HA028121 Options
Issue 5 Nov 04 Page 17
GRAPHICS RECORDER/DATA ACQUISITION AND LOGGING UNIT: OPTIONS MANUAL
KEY DESCRIPTIONS
Add Calls the Component selection list
Del Deletes (after confirmation) the component in the Identifier field (except the Main pane which cannot be de-
leted).
Save Causes all changes made since the last ‘Save’ to be applied to the screen.
Discard Causes all changes made since the last ‘Save’ to be discarded, after confirmation.
New Removes (after confirmation) all components from the current list and generates a new, empty background
(main) page to be worked on. This change is permanent and cannot be 'Discarded'.
Close Closes the component properties page and displays the screen currently being edited. If this key is operated
whilst there are still unapplied changes, a confirmation pop-up appears (Save Discard, Cancel).
Note: When working on the full version from remote viewer, further keys appear (e.g. Goto Canvas). These
are fully explained in section 2.5.1.
Edit level
Allows Basic or Advanced edit level to be selected for further use.
Component info on screen
Enabling this box causes a component description to appear at the top left corner of each component. This de-
scription is in the form: Identifier(X,Y)+[∂X,∂Y], where X and Y defines the top left corner position in pixels,
and ∂X and ∂Y are the width and height of the component in pixels. The identifier is the component name as
appears in the Identifier field of the Component Property Editor page.
Quick entry to edit
If selected, this function allows direct entry from the user screen being edited to the Component Property editor
page, without the options menu first appearing offering the choice of ‘Batch’ or ‘Edit Screen’.
If Quick entry is selected, the option menu does not appear when the option key is touched. The Batch status
page can be called by touching the ‘Page Name’ (Dark Green) area at the top of the screen, as an alternative to the
option menu.
Note: When working on the full version from remote viewer, further items appear (e.g. Use Last Properties).
These are fully explained in section 2.5.2.
Options HA028121
Page 18 Issue 5 Nov 04
GRAPHICS RECORDER/DATA ACQUISITION AND LOGGING UNIT: OPTIONS MANUAL
PROCEDURE
List of component types
Group Vertical Trend (gr_vtrend)
1. Operate the ‘Add’ key to call the Component Group Horizontal Trend (gr_htrend)
selection list. Group Vertical Bargraph (gr_ver_bar)
Group Horizontal Bargraph (gr_hor_bar)
Group Numeric (gr_num)
Y Position 0 %
Width 50 %
Height 50 %
Background Colour -1
Draw Order 30
Component Type Group Vertical Trend (gr_vtrend)
6. Touch the Identifier field, then enter the name Component Property Editor
‘Group 1’ ‘Ok’ using the pop-up keyboard which Add Del gr_vtrend_6.1
appears. Identifier Group 1
Last Error
Group Number 1) Group 1
7. In Group Number, select: 1) Group 1
Show Title Bar Yes
X Position 0 %
8. Title bar is selected on (yes), as required
Y Position 0 %
Width 50 %
9 Enter the X (25%) and Y (48%) co-ordinates,
Height 50 %
using the same technique as was used for the
Background Colour -1
Identifier field in step 6. The default dimensions Draw order 30
(50 x 50%) are as required. Component Type Group Vertical Trend (gr_vtrend)
HA028121 Options
Issue 5 Nov 04 Page 19
GRAPHICS RECORDER/DATA ACQUISITION AND LOGGING UNIT: OPTIONS MANUAL
Identifier Bar 1
13. In the Identifier field, enter the name ‘Bar 1’ Last Error
using the pop-up keyboard. (To enter numbers, Channel 1) Channel 1
touch the 'Numeric' tab under the keyboard, X Position 0 %
then touch the required number.) Y Position 0 %
Width 100 %
14. The channel number is as required Height 10 %
Background Colour -1
15. Touch the width field and enter a value of 100. Foreground Colour -1
Draw Order 20
16. Touch the height field and enter ‘10’ Component Type Channel Horizontal Bargraph (ch_hor_bar)
18. Touch the component picklist field and select Component Property Editor
another bargraph. Add Del ch_hor_bar_4.2
Identifier Bar 2
19. In a similar way to that described for Bar 1
Last Error
a) enter the identifier ‘Bar 2’ Channel 2) Channel 2
b) select Channel 2 from the picklist X Position 0 %
c) enter a Y value of 12 Y Position 12 %
d) enter width = 100%; height = 10%.
Width 100 %
Height 10 %
20. Similarly configure Bar 3 and Bar 4, using the Background Colour -1
appropriate Y values (24 and 36) and Channel Forground Colour -1
selection (3 and 4). Draw Order -1
Component Type Channel Horizontal Bargraph (ch_hor_bar)
21 Finally, press 'Save', then ‘Close’, to reveal the Save Discard New Close
display page.
Engineer Group 1 . User Screen 1 10:22:50
Batch Number:001130.010 18/02/04
Channel 1 0.4187 ˚C
0.0000 1.0000
Channel 2 0.3316 ˚C
0.0000 1.0000
Channel 3 0.1427 ˚C
0.0000 1.0000
Channel 4 0.6293 ˚C
0.0000 1.0000
Group 1
Channel 1 0.4187˚C
0.0000 0.2000 0.4000 0.6000 0.8000 1.0000
10:20:28
18/02/04
Options HA028121
Page 20 Issue 5 Nov 04
GRAPHICS RECORDER/DATA ACQUISITION AND LOGGING UNIT: OPTIONS MANUAL
In order to provide a degree of contrast, the background colour of the ‘Main’ page can be changed to a darker colour
as shown for colour 22 in figure 2.2.3c, below. Figure 2.2.3d on the next page, shows the relevant component property
pages.
Engineer Group 1 . User Screen 1 10:22:50
Batch Number:001130.010 18/02/04
Channel 1 0.4187 ˚C
0.0000 1.0000
Channel 2 0.3316 ˚C
0.0000 1.0000
Channel 3 0.1427 ˚C
0.0000 1.0000
Channel 4 0.6293 ˚C
0.0000 1.0000
Group 1
Channel 1 0.4187˚C
0.0000 0.2000 0.4000 0.6000 0.8000 1.0000
10:20:28
18/02/04
HA028121 Options
Issue 5 Nov 04 Page 21
GRAPHICS RECORDER/DATA ACQUISITION AND LOGGING UNIT: OPTIONS MANUAL
Identifier main_1.2
Last Error
Page Title
X Position 0 %
Y Position 0 %
Width 100 %
Height 100 %
Background Colour -1 Touch background
Draw Order 1 colour field
Component Type Main
22
0 1 2 3 4 5 6 7
8 9 10 11 12 13 14 15
16 17 18 19 20 21 22 23
24 25 26 yellow
Goes 27 when28touched
29 30 31
32 33 34 35 36 37 38 39
40 41 42 43 44 45 46 47
Show additional colours
48 49 50 51 52 53 54 55
Colour list Add. Colour
Note: The Add(itional) colours tab calls a supplementary palette to the display. This includes default colour
(-1), flashing colours, and Windows® colours for use with user screens and Remote Viewer (Communications
manual, section 1), to match recorder colours with Windows® colours.
Options HA028121
Page 22 Issue 5 Nov 04
GRAPHICS RECORDER/DATA ACQUISITION AND LOGGING UNIT: OPTIONS MANUAL
Parameter Description
Arc Angle For Arcs only, the number of degrees of arc drawn anti-clockwise (counter-clockwise) from the Start
Angle. Negative angles draw clockwise.See figure2.4.20a for definitions.
Arc Height For Rounded Rectangles only, this is double the vertical distance from the corner of the (unrounded)
rectangle at which the curve is to start. To draw ‘circular’ corners, this value must be 3/2 times the
Arc Width. The Arc height value must be less than half the Rectangle height. Percent units are
relative to the rectangle height, not the screen height.
Arc Width For Rounded Rectangles only, this is double the horizontal distance from the corner of the
(unrounded) rectangle at which the curve is to start. To draw ‘circular’ corners, this value must be 2/3
the Arc Height. The Arc width value must be less than half the Rectangle width. Percent units are
relative to the rectangle width, not the screen width.
Background colour The fill colour of solid objects; the background colour for the main page, trend charts, text messages
etc. For Bargraphs, the colour ‘behind’ the bar.
Button Text For operator buttons, Dialogue Action and Navigation Action. Allows button text to be entered.
Event button text is defined in Event Button Configuration, described in section 4.3.7 of the User
Guide.
Channel Allows a channel to be selected for bargraph, numeric, value etc. display.
Draw edge If set to ‘Yes’, this causes the outline shape of a solid object to be drawn in the foreground colour. If
set to ‘No’, the object’s outline is not drawn.
Draw Order Allows a layer scheme to be introduced. Item with higher draw order values are overlaid on compo-
nents with lower draw order values. The Draw Order feature is included specifically to allow a
dynamic element (such as a bargraph) to be placed ‘on top of’ a background, static image. A dy-
namic element is always drawn on top all other elements at update time. . When one or more dy-
namic elements are placed on top of one another, the results are unpredictable.
Edit Parameter For operator buttons, allows the user to select the parameter type (e.g Channel N Alarm 1) to be
edited when the button is operated. The parameter number (N) is entered in the ‘N value’ field.
Event Button For Event buttons, this allows the user to assign an Event button to the User Screen Button to be
displayed.
Feature For ‘Channel data’ only, allows the type of data to be displayed (e.g. Current value), to be selected
from a pick-list.
Fill Area If set to ‘Yes’, this causes a solid object to be filled with the background colour. If set to ‘No’, the
inside of the object is transparent. If ‘draw edge’ is also set to ‘No’, the object is invisible.
Foreground Colour The line colour of solid objects. The bar colour of bargraphs (default = normal point colour). The
colour of Text and of numeric values. Where applicable, this overrides channel colour.
HA028121 Options
Issue 5 Nov 04 Page 23
GRAPHICS RECORDER/DATA ACQUISITION AND LOGGING UNIT: OPTIONS MANUAL
Parameter Description
Group number Allows a group to be selected for group trend, bargraph and numeric displays, and for Dialogue
action buttons. Select specific group, or '0' to follow current display group. If multiple groups are
not fitted, this allows only group 1 to be selected.
Height Height of a component, measured downwards from the component’s ‘Y position’. Negative values
measure upwards.
Identifier Component name. Initially as in the Add Component list, but editable by the user.
Image File Allows a file name to be entered when importing GIF or JPG images.
Last error A text message describing the last error to occur for this component. The component must be re-
edited in order to clear the problem.
N Value See ‘Edit parameter’ above.
Page Title Allows a name for the current user screen to be entered in ‘Main’. This name appears at the top of
the screen, and in the Screen number picklist for navigation action buttons.
Screen Number For navigation action buttons, allows a screen to be selected. When the button is operated, the
instrument will switch to the selected display screen.
Show Title Bar When set to ‘Yes’, group displays (e.g. Group Vertical Trend) display a title bar across the top of the
component, giving the selected group’s descriptor. Selecting ‘Show Title Bar’ to ‘No’, removes the
title bar from the display
Start Angle For Arcs only, defines a start point for ‘Arc Angle’ above. See figure2.4.20a for definitions.
Text Allows a text string to be entered for display at the screen
Width The width of a component measured rightwards from the component’s “X osition’. Negative values
measure leftwards.
X points Defines the X co-ordinates for polylines and polygons. Must match the number of Y-points for
correct interpretation
X position Distance between the left edge of the screen and the left edge of the component.
Y points Defines the Y co-ordinates for polylines and polygons. Must match the number of X-points for
correct interpretation
Y position Distance between the top edge of the screen and the top edge of the component.
Options HA028121
Page 24 Issue 5 Nov 04
GRAPHICS RECORDER/DATA ACQUISITION AND LOGGING UNIT: OPTIONS MANUAL
The selection of the Advanced properties set, is carried out from the Properties Options page as described in section
2.3.1, above. Advanced properties are in addition to the basic properties described above, not a replacement for them.
HA028121 Options
Issue 5 Nov 04 Page 25
GRAPHICS RECORDER/DATA ACQUISITION AND LOGGING UNIT: OPTIONS MANUAL
Options HA028121
Page 26 Issue 5 Nov 04
GRAPHICS RECORDER/DATA ACQUISITION AND LOGGING UNIT: OPTIONS MANUAL
HA028121 Options
Issue 5 Nov 04 Page 27
GRAPHICS RECORDER/DATA ACQUISITION AND LOGGING UNIT: OPTIONS MANUAL
Options HA028121
Page 28 Issue 5 Nov 04
GRAPHICS RECORDER/DATA ACQUISITION AND LOGGING UNIT: OPTIONS MANUAL
The examples below are alternatives - only one style can be chosen for each group bargraph display.
Show Alarm Marks Yes/No Allows channel scale alarm marks to be displayed (yes) or not (no).
Alarm Marks Colour, described above, allows the user to select a colour
for the alarm marks.
Time Marker colour Default Allows a colour to be selected for time/date printing on a trend chart
Time Marker interval Default Number of horizontal grid lines between successive time markers.
Trend Padding Default For group trend only. Normal trends are 1 pixel wide. Setting a padding
value of N, adds N pixels on each side of the central pixel. For example,
a padding value of 2 would produce traces 5 pixels wide. Applies to all
channels in the group.
Units Font List of fonts For Channel Numeric displays only, if Faceplate Style is set to ‘Custom’,
then Units Font allows the Channel Units font to be selected from a
picklist.
Update when Value changes Action is taken when the value associated with the component changes
Always The component is redrawn, continuously, at the display update rate.
Vertical alignment Centred/bottom/top Allows text to be positioned relative to its height setting
Value Font List of fonts For Channel Numeric displays only, if Faceplate Style is set to ‘Custom’,
then Value Font allows the Channel Value font to be selected from a
picklist.
HA028121 Options
Issue 5 Nov 04 Page 29
GRAPHICS RECORDER/DATA ACQUISITION AND LOGGING UNIT: OPTIONS MANUAL
Options HA028121
Page 30 Issue 5 Nov 04
GRAPHICS RECORDER/DATA ACQUISITION AND LOGGING UNIT: OPTIONS MANUAL
This section defines all the available components listed in table 2.2.2 in terms of their parameters. The components
occur in the order in which they appear in the list.
This produces a display which mimics a recorder chart, for a selected group. All the functions (e.g. trend history) de-
scribed in, sections 3.4.1 and 3.4.2 of the User Guide, are available. The following unique parameters (fully described
in table 2.3.2) are available for configuration:
Produces a vertical bargraph for a selected group in a format defined by ‘Bargraph Style’ and ‘Scale style’ described
in table 2.3.2. The number of rows of bars can also be defined by the user, according to the overall size of the display,
number of channels etc. The default value of zero means that the recorder will display what it ‘believes’ to be the most
ergonomic number of rows.
The recorder attempts to fit as many channel bars as possible into the width of the display. The default minimum
width of a column is 6 mm. If there are more channels than can be fitted into the display, a scroll bar device appears
at the bottom edge to allow ‘hidden’ bars to be accessed.
The recorder attempts to fit as many faceplates as possible into the height of the display. If there are more faceplates
than can be fitted into the display, a scroll bar device appears to allow ‘hidden’ faceplates to be accessed.
Produces a group horizontal bargraph, for a selected group, in a format defined by ‘Bargraph Style’ and ‘Scale style’
described in table 2.3.2. The number of columns can also be defined by the user, according to the overall size of the
display, minimum width, number of channels etc.
The recorder attempts to fit as many channels as possible into the height of the display, according to the specified
minimum height (default = 12mm). If there are more channels than can be fitted into the display, a scroll bar appears
at the right edge to allow ‘hidden’ channels to be accessed.
HA028121 Options
Issue 5 Nov 04 Page 31
GRAPHICS RECORDER/DATA ACQUISITION AND LOGGING UNIT: OPTIONS MANUAL
This produces a display of a selected group's numeric values, in one of a number of formats, as described in
‘Faceplate Style’ in table 2.3.2 above. The number of columns can also be defined by the user, according to the overall
size of the display, number of channels etc. The default value of zero means that the recorder will display what it ‘be-
lieves’ to be the most ergonomic number of columns.
The recorder attempts to fit as many channels as possible into the height of the display, according to the specified
minimum height (default = 12mm.). If there are more channels than can be fitted into the display, a scroll bar appears
at the right edge to allow ‘hidden’ channels to be accessed.
For a specified channel, this produces a dynamic horizontal or vertical bargraph display of channel value, in a format
defined by ‘Bargraph Style’ and ‘Scale style’ described in table 2.3.2
For a specified channel, allows the channel faceplate to be displayed in one of a number of formats, as described in
‘Faceplate Style’ in table 2.3.2 above.
For a specified channel, allows one of : Current value, Descriptor, Units, Span low or Span high to be selected for
display.
This displays a pushbutton which can have one of three actions assigned to it:
1. Call the Login page.
2. Call the Batch Status page
3. Call the Operator Note dialogue box.
For Batch and Operator Note use, a Group number can be selected.
This displays a pushbutton, the purpose of which is to call a different display screen. A Group and a screen can both
be specified, so this button provides a shortcut version of the ‘Goto group’ and ‘Goto View’ keys of the root menu.
Options HA028121
Page 32 Issue 5 Nov 04
GRAPHICS RECORDER/DATA ACQUISITION AND LOGGING UNIT: OPTIONS MANUAL
This displays a user pushbutton. The legend on the pushbutton, and the task it is to carry out, are defined in the button
configuration. If the text is too long for the width of the button, the text is truncated (e.g. Reset Ave...). Possible tasks
are as follows (assuming that the relevant options are fitted):
In all the above, N represents any number between 1 and the maximum number available for the relevant type of
point. (Point is an umbrella term for input channel, a maths channel, a totaliser, etc.)
When the button is operated a ‘confirmation’ page appears allowing, for example, the value of a constant to be edited
before operating the ‘Apply’ button.
Notes:
1 If the point being accessed is not suitably configured, the ‘confirmation’ page is blank. For example, if
the Operator button is configured to change, say, the threshold (SP) of Alarm 2 on Channel 6, and either
Channel 6 is Configured ‘Off’, or alarm 2 is ‘Off’, then the Confirmation page will not have a
configurable area allowing the user to enter the required new value.
2. Any signing or authorizing that normally applies to the item being edited, also applies when changes are
being made by means of the Operator button.
This displays a pushbutton, to be used as a source for an event. The button name, its action (latching or unlatching),
and whether or not the operation of the button needs signing or authorizing are set up in Event Button configuration,
described in section 4.3.7 of the User Guide. The actions taken when the button is operated are set up in Event con-
figuration, described in section 4.3.6 of the User Guide. Signing and Authorizing are as described in section 4.4.2
(Management) of the User Guide.
Ack Alarms
Figure 2.4.11 Typical Event Button
2.4.12 Image
This allows a GIF or JPG image file to be loaded from (e.g.) the floppy disk drive. Once this has been done, the im-
age size and shape can be edited to fill the screen area, and bargraphs, text messages etc. can be superimposed on the
image.
Notes:
1 Only Gifs in Gif87a format are supported by the unit.
2. Because of memory constraints, only six of user screens 1 to 24 may have images embedded in them
HA028121 Options
Issue 5 Nov 04 Page 33
GRAPHICS RECORDER/DATA ACQUISITION AND LOGGING UNIT: OPTIONS MANUAL
2.4.13 Text
If width and height are left with the default values of zero, the text will start at the specified start point and fit in the
space between there and the right edge of the screen, in a single line (left justified (ranged) as a default). If the text
string is too long, it is truncated. The text appears in the specified foreground colour, superimposed on a 'box' of
background colour which is the same width of the text string.
If width and height are defined, then the text will fill the defined width and any remaining text is truncated. The text
appears in the foreground colour (default black), over a field of background colour (default grey).
Advanced properties allow the text to be set to range left, range right or be centred, at the top, bottom or centre of the
field, and for the foreground and background colours to be swapped.
Similar to a rectangle described in section 2.4.15, but offers the user the opportunity to draw rectangles with curved
corners. The horizontal and vertical curve angles are specified separately, and the aspect ratio of the screen should be
taken into account when working in percentage units.
Note: The rounded rectangle will draw incorrectly if either of the arc height /width settings are greater than
half the rectangle height/width settings.
Height
Width
2.4.15 Rectangle
This draws a rectangle on the display page. If the height and width of the rectangle are defined in the default ‘per-
centage units’, then entering equal values for height and width will result in a rectangle with the same aspect ratio as
that of the screen, not a square as might be expected. Because the screen height is approximately 2/3 the width, the
rectangle height should be 3/2 the rectangle width to produce a square. (The actual height/width ratio is 535/800 =
0.669 for large frame units or 214/320 = 0.669 for small frame units).
Using pixels as the measuring units obviates this problem as pixels are square.
Options HA028121
Page 34 Issue 5 Nov 04
GRAPHICS RECORDER/DATA ACQUISITION AND LOGGING UNIT: OPTIONS MANUAL
Similar to closed polygons, described in section 2.4.17 below, but the first and last points are not automatically
joined, and the drawn item cannot be filled and the line width cannot be specified - it is always one pixel.
Note: When working in percentage units, it should be remembered that vertical percentage units are only 2/3
the size of horizontal percentage units - this affecting the appearance of the drawn item.
Example: To draw an (old fashioned) electronic resistor icon (Units = Absolute pixels)
Press 'Apply', then 'Close' to produce a red ‘sawtooth’ outline, as depicted in figure 2.4.16 below.
Point1 Point 12
X=0; y=0 X=100; y=0
HA028121 Options
Issue 5 Nov 04 Page 35
GRAPHICS RECORDER/DATA ACQUISITION AND LOGGING UNIT: OPTIONS MANUAL
This allows a number of pairs of points to be entered, which, if valid, will then be joined by straight lines. The first
and last points are automatically joined, by the recorder. The shape, drawn in the specified foreground colour, with
the specified line width, can be filled with the specified background colour.
Note: When working in percentage units, it should be remembered that vertical percentage units are only 2/3
the size of horizontal percentage units - this affecting the appearance of the drawn item
Example: To draw a left pointing solid arrow, positioned with its point at the centre of the screen.
Access the component page as described in section 2.2.3, select ‘polygon - closed area’ and press Ok. In the proper-
ties page, carry out the following configuration (units = %):
Press Apply, then Close to produce a dark green arrow, with pale green outline, as depicted in figure 2.4.17 below.
Point 2
X=10; y=-15
Point 3
X=10; y=-5 Point 4
X=30; y=-5
Point 1
X= 0; y= 0
Point 5
Point 6 X=30; y= 5
X=10; y= 5
Point 7
X=10; y= 15
Options HA028121
Page 36 Issue 5 Nov 04
GRAPHICS RECORDER/DATA ACQUISITION AND LOGGING UNIT: OPTIONS MANUAL
2.4.18 Oval
Similar to an arc with an arc angle of 360 degrees, but arcs cannot be filled,
If the height and width of the oval are defined in the default ‘percentage units’, then entering equal values for height
and width will result in an oval with the same aspect ratio as that of the screen, not a circle as might be expected. Be-
cause the screen height is approximately 2/3 the width, the oval height should be 3/2 its width to produce a circle.
(The actual height/width ratio = 0.669).
2.4.19 Line
This causes a straight line of user-definable thickness to be drawn between the points (X position; Y position) and (X
position + width; Y position + height)
Notes:
1 Y increases downwards; X increases rightwards
2 Height = 2/3 width if measuring in percent
Example
To draw an approximation to a St.Andrew’s cross (saltire):
Access the component page as described in section 2.2.3, select ‘Line’ and press Add, then Ok.
HA028121 Options
Issue 5 Nov 04 Page 37
GRAPHICS RECORDER/DATA ACQUISITION AND LOGGING UNIT: OPTIONS MANUAL
2.4.20 Arc
This causes a curved line of user-definable thickness to be drawn anti-clockwise between start angle and (start angle +
arc angle). The origin (‘centre’) of the arc is (X position + 1/2 Width) ; (Y position + 1/2 Height). Arcs cannot be
filled.
Notes:
1 Angle increases anticlockwise
2 Height = 2/3 width if measuring in percent
3 Arcs cannot be filled - the shading in the figure is included for clarity only
X/Y Position
Arc end point
1/2 Height
Arc Start point
= Start angle
= Arc angle
1/2 Width
Example
An arc definition of:
X position = 50%, Y position = 50%, Width = 50%, Height = 50%, Start angle = 0; Arc angle 270 would produce the
curve depicted in figure 2.4.20b, below.
Group 1 User Screen 1 09:12:19
Engineer 13/12/00
Batch Number:001130.010
X position;
y position Width
Height
Start of arc
End of arc
Options HA028121
Page 38 Issue 5 Nov 04
GRAPHICS RECORDER/DATA ACQUISITION AND LOGGING UNIT: OPTIONS MANUAL
Notes:
1 This description applies only to the Full version of Screen Builder. For the ’Lite’ version, there is no
difference between screen creation at a Remote Viewer, and screen creation at the Instrument’s user inter-
face.
2. See the Communications manual HA028122 for details of Remote viewer.
The major differences between creating User screens via Remote Viewer software, and creating User Screens at the
instrument’s user interface are as follows: (Clearly, these differences are not relevant to instruments whose only op-
erator interface is the Remote Viewer.)
HA028121 Options
Issue 5 Nov 04 Page 39
GRAPHICS RECORDER/DATA ACQUISITION AND LOGGING UNIT: OPTIONS MANUAL
When using Remote viewer and Screen Builder Full version, the Component Property Editor is as shown in figure
2.5.1.
Component Property Editor - Screen 1
I d e n t i f i e r main_1.1
Last Error
Page Title
X Position 0 %
Y Position 0 %
W i d t h 100 %
H e i g h t 100 %
Background Colour -1
Draw Order 1
C o m p o n e n t T y p e Main
Options HA028121
Page 40 Issue 5 Nov 04
GRAPHICS RECORDER/DATA ACQUISITION AND LOGGING UNIT: OPTIONS MANUAL
TOP OF SCREEN
Add Used to call the list of component types
Del Used to delete the current component. ‘Greyed’ for ‘Main’ as this cannot be deleted.
Copy Used to copy the current component to the pasteboard. ‘Greyed’ for ‘Main’ as this cannot be Copied.
Paste Used to ‘paste’ the copied component to the screen. The copied item is placed 1% to the right of, and
1% below, the source component. ‘Greyed’ until a component Copy action has taken place.
HA028121 Options
Issue 5 Nov 04 Page 41
GRAPHICS RECORDER/DATA ACQUISITION AND LOGGING UNIT: OPTIONS MANUAL
Operation of the Options key whilst the Component Property Editor is on display, calls the User Screen options page.
Edit level
Allows Basic or Advanced edit level to be selected for further use.
Component info on screen
Enabling this box causes a component description to appear at the top left corner of each component. This de-
scription is in the form: Identifier(X,Y)+[∂X,∂Y], where X and Y defines the top left corner position in pixels,
and ∂X and ∂Y are the width and height of the component in pixels. The identifier is the component name as
appears in the Identifier field of the Component Property Editor page.
Quick entry to edit
If selected, this function allows direct entry from the user screen being edited to the Component Property editor
page, without the options menu first appearing offering the choice of ‘Batch’ or ‘Edit Screen’.
If Quick entry is selected, the option menu does not appear when the option key is touched. The Batch status
page can be called by touching the ‘Page Name’ (Dark Green) area at the top of the screen, as an alternative to the
option menu.
Quick entry has no effect on screens other than user screens.
Use Last properties
If selected, then all the common attributes (e.g. position, size, colours etc.) of the most recently edited object are
applied to the next component to be added.
Positioning Grid
Causes a grid to appear on the ‘Goto canvas’ screen to help in component layout
Positioning tip
If enabled, then hovering over the highlighted item in a ‘goto Canvas’ screen causes the coordinates of the top left
corner of the component to appear, in whatever units (%, pixels etc.) are selected for the component. The first
number gives the ‘X’(left-right) co-ordinate; the second gives the ‘Y’ (up-down) position.
Clicking the left mouse key within a component causes the coordinates of the top left corner of the component to
appear, in whatever units (%, pixels etc.) are selected for the component.
Clicking the left mouse key outside a component, shows the co-ordinates of the mouse cursor tip. To see these co-
ordinates within a component, the mouse must be click-dragged from outside the component.
Options HA028121
Page 42 Issue 5 Nov 04
GRAPHICS RECORDER/DATA ACQUISITION AND LOGGING UNIT: OPTIONS MANUAL
The physical display screen size is approximately 245 mm across and 164 mm high. For the purposes of the user
screens option, this area can be divided into a 100 x 100 array for percentage measurement or into a pixel array, 800
across by 535 vertically.
The physical display screen size is approximately 100 mm across and 76 mm high. For the purposes of the user
screens option, this area can be divided into a 100 x 100 array for percentage measurement or into a pixel array, 320
across by 214 vertically.
Error codes 1 to F may appear at the top left corner of the screen. The following codes are currently implemented,
and if more than one occurs at the same time, the code numbers are added. For example, Error code 6 would mean
that codes 4 and 2 had both occurred.
HA028121 Options
Issue 5 Nov 04 Page 43
GRAPHICS RECORDER/DATA ACQUISITION AND LOGGING UNIT: OPTIONS MANUAL
3 MATHS
3.1 CONFIGURATION
This feature allows a range of mathematical functions to be performed. Group average, Group maximum and Group
minimum, require Multiple Groups to be fitted for correct operation. Figure 3.1 shows a typical configuration page -
the selected maths function determines which configuration fields actually appear.
Select maths
Maths Number 1) Fo 1 channel number
Figure 3.1 Maths configuration menu (typical - varies from function to function)
Allows the user to select the required maths channel for configuration.
3.1.2 Value
This field shows the current value of the selected maths channel. If the channel has not yet been configured, the
value reads 'Off'.
This button appears only after a resettable function has been selected. Operation of the button sets the maths value to
zero.
Options HA028121
Page 44 Issue 5 Nov 04
GRAPHICS RECORDER/DATA ACQUISITION AND LOGGING UNIT: OPTIONS MANUAL
3.1.4 Function
This picklist allows the relevant maths function to be selected. In the following description, the word 'channel' is used
as an umbrella term for input channels, maths channels, totalisers etc.
Off Allows the function to be disabled. Once 'Apply' has been actioned, all configuration for this
Maths number is lost.
Constant Allows a maths channel to be set to a constant value.
Add Allows any channel or a constant value to be added to any other.
Subtract Allows any channel or a constant value to be subtracted from any other.
Multiply Allows any channel or a constant value to be multiplied by any other.
Divide Allows any channel or a constant value to be divided by any other. Should the value of the
divisor pass through zero, 'Maths Channel N error' and 'Maths Channel Failure' messages
appear.
Group average* The instantaneous value of all the channels in the source group added together and divided by
the number of channels in the group. For example, in a group of four channels whose instanta-
neous values are 4, 8, 2 and 6, the group maximum is (4 + 8 + 2 + 6) / 4 = 5. The relevant
source group is selected by picklist. Should a channel return a non-valid value, it is excluded
from the calculation, and the result of the function is the average of the remaining channels.
Group minimum* The lowest value of any of the channels in the source group. For example, in a group of four
channels whose instantaneous values are 4, 8, 2 and 6, the group minimum is 2. The required
source group is selected by picklist. Should a channel return a non-valid value, it is excluded
from the calculation, and the result of the function is the minimum of the remaining channels.
See section 3.2.15, for more details.
Group maximum* The highest value of any of the channels in the source group. For example, in a group of four
channels whose instantaneous values are 4, 8, 2 and 6, the group maximum is 8. The required
source group is selected by picklist. Should a channel return a non-valid value, it is excluded
from the calculation, and the result of the function is the maximum of the remaining channels.
*Note: If a maths channel with a Group function is contained within its own source group, then it will
act on itself as well as on the other group contents, thus changing the calculation.
For example, if Group 1 were to contain channel 1, channel 2 and maths channel 1, where maths
channel 1 had the function 'Group Maximum' for Group 1, then the Group Maximum would become a
latching function, showing the highest value ever reached by channel 1, channel 2 or maths channel 1
since the group was configured. In order to trace the instantaneous highest value, channel 1 and
channel 2 would have to be contained in e.g. Group 1, and the group maximum channel contained in,
say, Group 2, but with a source of 'Group 1'.
Comms Allows a process value for the maths channel to be communicated over the Modbus link
Stopwatch This causes the value of the maths channel to increment in milliseconds. The value can be
displayed in milliseconds (PV format = numeric), or in HH:MM:SS (PV format = elapsed
time).
The value can be held, using a ‘Disable’ job or set to zero either using a ‘reset’ job or by the
operation of the ‘Reset now’ button in the maths configuration page. See section 4.7 of the
User Guide for a description of jobs.
The function value is retained during power off.
Note: The scale low and high values are displayed in numeric format for both numeric and elapsed
time display formats
HA028121 Options
Issue 5 Nov 04 Page 45
GRAPHICS RECORDER/DATA ACQUISITION AND LOGGING UNIT: OPTIONS MANUAL
Copy Copies the value of a selected point to the maths channel being configured. Allows extra
alarms to be set up for the copied point.
Polynomial Provides a polynomial curve fit for the specified point, using up to 8 orders, See section 3.2.1
below, for further details.
Fvalue This function calculates ‘equivalent time at sterilizing temperature’ for temperatures above and
below the sterilising temperature. FO (dry) and FH (steam) sterilizing calculations can be
carried out, by entering the correct constant - see section 3.2.2 below, for further details. The
value can be held, using a ‘Disable’ job or set to zero (prior to the next run) using a ‘reset’ job.
See section 4.7 of the User Guide for a description of jobs. The function value is retained
during power off.
Switch Allows two channels (‘A’ and ‘B’) to be selected as alternative sources for the selected maths
channel to copy. The maths channel copies source ‘A’, unless a ‘Switch to B’ job is active on
the maths channel. See section 4.7 of the User Guide for Job descriptions.
Linear Mass Flow This function calculates mass flow from linear-type transducer outputs. See section 3.2.3
below, for further details.
Root Mass Flow This function calculates mass flow from square root-type transducer outputs. See section 3.2.4
below, for further details.
Rolling Average This takes the average value of a single channel over a specified number of readings taken at a
specified interval. See section 3.2.5 below, for further details. The function value is retained
during power off.
MKT Mean Kinetic Temperature. A single calculation to simulate non-isothermal effects of varia-
tions in storage temperature. See section 3.2.6, below for further details.
10 to the power Output = 10 raised to the power of the selected input value.
Group Latched Minimum Outputs the minimum value reached by any of the points in a selected source group since last
reset. The function ignores points that are not producing valid PV. A disable job stops the
function reading its input. A reset job sets the function to the current minimum value within
the group. Note that for proper operation, the maths function must be in a group which is not
the source group. If this is not the case, it will always see itself as the lowest valued point in
the group, and Reset operations will have no useful effect.
Group Latched Maximum As for Group Latched Minimum, above, but outputs the maximum value of the source group.
Sample and Hold This function is initiated by a trigger job. At trigger time, the selected point value is sampled,
and its value at trigger time is output continuously by this function. On reset, the PV becomes
'No data'.
Square Root Outputs the square root of the value of the selected point.
High Select Allows two points to be selected as inputs. The output of the function is the value of that input
point which currently has the higher value.
Low Select Allows two points to be selected as inputs. The output of the function is the value of that input
point which currently has the lower value.
Saturated Steam Mass Flow Calculates mass flow in kg/s for saturated steam, using either the steam temperature (Celsius)
or pressure (MPa) as appropriate to the process. See section 3.2.7 for details.
Saturated Steam Heat Flow Calculates the energy flow in kJ/s for saturated steam, using either the steam temperature
(Celsius) or pressure (MPa) as appropriate to the process. See section 3.2.8 for details.
Saturated Steam Heat Consumed
Calculates the heat consumed in kJ/s for saturated steam, using the inlet steam temperature
(Celsius) or pressure (MPa) (as appropriate to the process), and the return (condensate)
temperature. See section 3.2.9 for details.
Group MKT Calculates Mean Kinetic Temperature of a specified group of channels See section 3.2.10 for
details.
Options HA028121
Page 46 Issue 5 Nov 04
GRAPHICS RECORDER/DATA ACQUISITION AND LOGGING UNIT: OPTIONS MANUAL
Log Base 10 Takes log10 of selected input. (For example: Input = 2 gives maths function value = 0.3010)
Log Base e Takes loge of selected input. (For example: Input = 2 gives maths function value = 0.6931)
e to the power Takes natural antilog of input. (For example: Input = 0.6931 gives maths function value = 2)
Modulus This function copies the magnitude of the input value, without the sign. For example, the
modulus of value +100 = +100; the modulus of -100 = +100.
Channel Maximum Maths function value is the maximum value the input point has reached since last reset. When
reset, the value is reset to the current input value.
Channel Minimum Maths function value is the maximum value the input point has reached since last reset. When
reset, the value is reset to the current input value.
Channel Average Takes the average value of the selected channel over a specified time period. The time period
must be a multiple of 125 msecs. For example, a period of 0.2 seconds would be rejected, but
a period of 0.25 seconds would be accepted.
Rate of change Produces a value for the speed at which a signal changes over a specified period. See section
3.2.11 for further details.
O2 Correction This function carries out O2 correction of gas measurements for use in Continuous Emissions
Monitoring applications. See section 3.2.12 for details.
Relative Humidity This uses wet and dry bulb temeratures and atmospheric pressure inputs to produce a percent-
age Relative Humidity reading. See section 3.2.13 for details.
Zirconia probe Allows oxygen concentration and oxygen potential to be determined by solving the Nernst
oxygen equation. See section 3.2.14 for details.
Timestamp When triggered by an event or alarm job, this causes the current number of milliseconds since
00:00 hrs on 1st January 1970 to appear as the function value (1.047 x 1012 at time of writing
- 7th Mar 2003). If the selected PV format is date or time, the result is displayed as date or
time, respectively.
Config Revision Number* Allows the Configuration Revision number to be used as the input to a maths channel. When
this maths channel is included in a group, the user can determine the Configuration Revision
number obtaining at any time in the history record.
Security Revision Number* Allows the Security Revision number to be used as the input to a maths channel. When this
maths channel is included in a group, the user can determine the Security Revision number
obtaining at any time in the history record.
*Note: See section 4.6.5 of the User Guide for a description of the Configuration and Security
Revision numbers.
HA028121 Options
Issue 5 Nov 04 Page 47
GRAPHICS RECORDER/DATA ACQUISITION AND LOGGING UNIT: OPTIONS MANUAL
The 'zero' and full scale values for the maths function, as displayed.
If A/B switching is enabled, a second set of scale low and scale high values can be entered. 'A' values are used dur-
ing normal operation. 'B' values are switched to by job action, as described in section 4.7 of the User Guide.
3.1.6 PV Format
† Notes
1. Strictly this is a number less than 10, as 10 would be 1.0E1.
2. There must be at least one number after the decimal point.
The remaining configuration items are identical with the relevant items in Input Channel configuration (section 4.3.3
of the User Guide).
Options HA028121
Page 48 Issue 5 Nov 04
GRAPHICS RECORDER/DATA ACQUISITION AND LOGGING UNIT: OPTIONS MANUAL
3.2.2 Fvalue
To calculate the equivalent time at Sterilizing Temperature (for temperatures below, at and above Sterilizing Tempera-
ture) both in dry (FH) and steam (FO) sterilizing environments, using the following equation:
ma t − Target temp
Fval t = Fval t −1 + T × 10 Z
User configuration consists of entering the channel which is measuring temperature, the relevant sterilizing tempera-
ture and temperature interval (Z-value) and a low cut-off value, if required.
Figure 3.2.2 shows the configuration fields for measuring Fo, using channel 1 as the temperature input channel, Fo
values for target temperature (121.1˚C) and z-value (10˚C), and 75˚C as the low cut-off value, below which killing
credits are not to be counted.
Function fValue
F value of Channel 1
Sterilizing Temp 121.1
Temperature interval 10
Low cut off 75
Application Note
To ensure that sterilizer loads which contain materials with differing thermal inertias are thoroughly sterilized, a typi-
cal sterilizer has up to 12 different measuring points within the load. To ensure accuracy, the temperature sensors
should be calibrated, and the channel adjustment facility used to compensate for any inaccuracies found.
If each of the inputs is used to compute an F value, each of these values can then be used as an input to a Group
Minimum function, with a high absolute alarm set at the correct F value. The alarm output can be used to sound a
warning, or an associated relay can be linked into the autoclave control system to signify the end of a sterilization
cycle.
HA028121 Options
Issue 5 Nov 04 Page 49
GRAPHICS RECORDER/DATA ACQUISITION AND LOGGING UNIT: OPTIONS MANUAL
Note: The overall accuracy of a flow measurement installation depends on a number of factors outside the
control of the recorder manufacturer. For this reason, the recorder manufacturer takes no responsibility for
the accuracy of the results obtained using the mass flow equations implemented in the maths pack.
SCALING FACTOR
This is determind from an assumed value of Qm at a known Flow, AbsP and Temp. The value is chosen to give an
output within the range low scale to high scale.
RG
Gas
(J/kg-K)
Air 287.1
Ammonia 488.2
Carbon dioxide 188.9
Carbon monoxide 296.8
Ethylene 296.4
Hydrogen 4116.0
Methane 518.4
Nitrogen 296.8
Oxygen 259.8
Propane 188.5
Steam 461.4
Options HA028121
Page 50 Issue 5 Nov 04
GRAPHICS RECORDER/DATA ACQUISITION AND LOGGING UNIT: OPTIONS MANUAL
CONFIGURABLE PARAMETERS
Figure 3.2.3 shows the relevant part of the configuration menu for a maths channel with ‘Linear Mass Flow’ function
selected.
Flow Allows the input channel measuring the flowmeter output to be entered
Temperature Allows the input channel measuring the fluid temperature (Kelvins) to be entered
Absolute Pressure Allows the input channel measuring the absolute gas pressure (kPa(A)) to be entered
Scale o/p Full scale output from the flowmeter in flowmeter units (S)
Ma Full scale input range set for ‘Flow’ channel in flowmeter units (mamax)
Gas Constant the relevant gas constant in J/kg-K
Z The compressibility factor described above.
HA028121 Options
Issue 5 Nov 04 Page 51
GRAPHICS RECORDER/DATA ACQUISITION AND LOGGING UNIT: OPTIONS MANUAL
Note: The overall accuracy of a flow measurement installation depends on a number of factors outside
the control of the recorder manufacturer. For this reason, the recorder manufacturer takes no responsi-
bility for the accuracy of the results obtained using the mass flow equations implemented in the maths
pack.
SCALING FACTOR
This is determind from an assumed value of Qm at a known DeltaP, AbsP and Temp. The value is chosen to give an
output within the range low scale to high scale.
Options HA028121
Page 52 Issue 5 Nov 04
GRAPHICS RECORDER/DATA ACQUISITION AND LOGGING UNIT: OPTIONS MANUAL
CONFIGURABLE PARAMETERS
Figure 3.2.4 shows the relevant part of the configuration menu for a maths channel with ‘Root Mass Flow’ function
selected.
Delta Pressure Allows the input channel measuring the differential pressure output from the orifice plate to be entered
Temperature Allows the input channel measuring the fluid temperature (Kelvins) at the upstream tapping to be en-
tered
Absolute Pressure Allows the input channel measuring the absolute gas pressure (kPa(A)) to be entered
Scale o/p Full scale output from the flowmeter in flowmeter units (S)
Ma Full scale input range set for ‘Flow’ channel in flowmeter units (mamax)
Gas Constant The relevant gas constant in J/kg-K
Z The compressibility factor described above.
HA028121 Options
Issue 5 Nov 04 Page 53
GRAPHICS RECORDER/DATA ACQUISITION AND LOGGING UNIT: OPTIONS MANUAL
This calculates the average value of the last R samples of a channel, taken at N second intervals, where R and N can
be defined by the user. At initiation, up to the time of the first sample reading, the displayed value is the average of
the channel sampled every iteration (i.e at 8 Hz.).
The number of readings over which the average can be taken is limited by the amount of free RAM instantaneously
available, and is thus dependent on the overall configuration of the recorder. An instrument alarm is generated if there
is insufficient free RAM available - see section 3.1.3 for details.
MKT is defined as 'the isothermal temperature that corresponds to the kinetic effects of time-temperature distribution'.
The recorder calculates MKT, using the equation below:
- ∆H
R
Tk = - ∆H - ∆H - ∆H - ∆H
ln e RT1max + e RT1min + ... + e RTNmax + e RTNmin
2N
where: Tk = The required mean kinetic temperature in Kelvins
∆H = The heat of activation
R= The universal gas constant
T1max = The highest temperature reached during the first measurement period (in Kelvins)
T1min = The lowest temperature reached during the first measurement period (in Kelvins)
TNmax = The highest temperature reached during the Nth measurement period (in Kelvins)
TNmin = The lowest temperature reached during the Nth measurement period (in Kelvins)
N= The total number of measurement periods
As described in 'Configurable items, below, this is simplified for the recorder user , to four entries viz:: The number
of the channel measuring temperature, the number of samples to be used, the time between the samples and the rel-
evant 'Heat of Activation'.
Note: The input temperature must be in Kelvins. This can be achieved either by setting the relevant chan-
nel's units to Kelvins, or by using a further maths channel to convert the measuring units to Kelvins.
(K = ˚C + 273.15 or K = 0.555(˚F -32) + 273.15).
Options HA028121
Page 54 Issue 5 Nov 04
GRAPHICS RECORDER/DATA ACQUISITION AND LOGGING UNIT: OPTIONS MANUAL
CONFIGURABLE ITEMS
Figure 3.2.6 shows the configurable items for the MKT function.
Notes
1 This function produces a 'rolling' result. I.E. when the final (Nth) sample has been taken, the next sample
(N + 1)th replaces Sample 1, the (N + 2th) sample replaces Sample 2, and so on.
2 During the first sample, the current minimum and maximum values of temperature are entered into the
equation at the recorder iteration rate (i.e. 8Hz).
3. The number of readings over which the value can be taken is limited by the amount of free RAM instan-
taneously available, and is thus dependent on the overall configuration of the recorder. An instrument
alarm is generated if there is insufficient free RAM available - see section 3.1.3 for details.
HA028121 Options
Issue 5 Nov 04 Page 55
GRAPHICS RECORDER/DATA ACQUISITION AND LOGGING UNIT: OPTIONS MANUAL
VLT and ∆VT are available from published tables (note 2), but the recorder user need only enter 'values' for measured
flow and either the temperature or the pressure of the steam. These 'values' can be constants, input channels or maths
channels. Figure 3.2.7a and accompanying parameter descriptions give full details.
PARAMETERS
Flow Select 'Constant' or the number of the channel supplying the measured flow rate. If 'Constant' selected, a
further 'box' allows the value for the constant to be entered.
Use Allows the user to select Temperature (˚C) or Pressure (MPa) for the calculation.
Temperature Appears only if Use = Temperature. Select 'Constant' or the number of the channel supplying the steam
temperature. If 'Constant' is selected, a further 'box' allows a value for the constant to be entered.
Pressure Appears only if Use = Pressure. Select 'Constant' or the number of the channel supplying the steam pres-
sure. If 'Constant' is selected, a further 'box' allows a value for the constant to be entered.
Table 3.2.7 gives multipliers for converting some common pressure units to MPa. More details may be
found at websites http://www.ex.ac.uk/cimt/dictunit/ccpress.htm and http://www.onlineconversion.com/
pressure.htm, amongst others.
Dryness Enter a value between 0 and 100 to represent the dryness of the steam. 0 = no vapour; 100 = no liquid.
Notes:
1 The units of kg/sec and m3/sec are used above for simplicity. In fact any time unit can be used. For ex-
ample if the measured flow is in m3/hour, then the Mass flow will be in kg/hour.
2. ASME Steam tables 1999, from IAPWF IF97.
Options HA028121
Page 56 Issue 5 Nov 04
GRAPHICS RECORDER/DATA ACQUISITION AND LOGGING UNIT: OPTIONS MANUAL
There is a wide range of pressure measuring units in use throughout the world. The following table gives a multipli-
cation factor for converting some common units to MPa (MegaPascals), to four significant figures. Further conver-
sion factors can be found at the websites given on the previous page. (Where the conversion is to Pascals, not to
MegaPascals, the factors given have to be divided by 1,000,000.)
The table above shows multiplying factors to convert common pressure units to MPa. This conversion is carried out
as follows:
Example: A pressure transducer, connected to input channel 3 gives an output in the range10 to 100 PSI. The input to
a steam equation in maths channel 1 requires the pressure units to be MPa. To convert, set up a further maths channel
(e.g. No. 2) as shown below, then use maths channel 2 as the source channel for the pressure input to the steam equa-
tion.
The suggested scale low/high values are based on the resulting pressure range in MPa - i.e 0.06895 to 0.6895.
HA028121 Options
Issue 5 Nov 04 Page 57
GRAPHICS RECORDER/DATA ACQUISITION AND LOGGING UNIT: OPTIONS MANUAL
where, QEt = Heat energy flow (in kJ/sec), at time ‘t’ (Note 1)
Flowt = Measured flow in m3/sec (Note 1)
VLT = Volume of liquid per kg of steam (m3/kg) at temperature T ˚C
∆VT = VVT - VLT, where VVT is the volume of vapour per kg of steam at temperature T ˚C
d= Dryness factor between 0 (no vapour) and 100 (no liquid)
hLT = Enthalpy of the liquid in kJ/kg at temperature T ˚C
∆hT = hVT - hLT, where hVT is the enthalpy of vapour in kJ/kg vapour at temperature T ˚C
VLT and ∆VT; hLT and ∆hT are available from published tables (note 2), but the recorder user needs only to enter 'val-
ues' for measured flow and either the temperature or the pressure of the steam. These 'values' can be constants, input
channels or maths channels. Figure 3.2.8 and accompanying parameter descriptions give full details.
PARAMETERS
Flow Select 'Constant' or the number of the channel supplying the measured flow rate. If 'Constant' selected, a
further 'box' allows the value for the constant to be entered.
Use Allows the user to select Temperature (˚C) or Pressure (MPa) for the calculation.
Temperature Appears only if Use = Temperature. Select 'Constant' or the number of the channel supplying the steam
temperature. If 'Constant' is selected, a further 'box' allows a value for the constant to be entered.
Pressure (note 3) Appears only if Use = Pressure. Select 'Constant' or the number of the channel supplying the steam pres-
sure. If 'Constant' is selected, a further 'box' allows a value for the constant to be entered.
Dryness Enter a value between 0 and 100 to represent the dryness of the steam. 0 = no vapour; 100 = no liquid.
Notes:
1 The units of kg/sec and m3/sec are used above for simplicity. In fact any time unit can be used. For ex-
ample if the measured flow is in m3/hour, then the Mass flow will be in kg/hour.
2. ASME Steam tables 1999, from IAPWF IF97.
3. See section 3.2.7, above, for details of pressure unit conversion
Options HA028121
Page 58 Issue 5 Nov 04
GRAPHICS RECORDER/DATA ACQUISITION AND LOGGING UNIT: OPTIONS MANUAL
Note: The overall accuracy of a flow measurement installation depends on a number of factors outside the
control of the recorder manufacturer. For this reason, the recorder manufacturer takes no responsibility for
the accuracy of the results obtained using the mass flow equations implemented in the maths pack.
VLT1 and ∆VT1; hLT1, ∆hLT2 and ∆hT1 are available from published tables (note 2), but the recorder user needs only to
enter 'values' for measured flow, either the temperature or the pressure of the steam and the temperature of the con-
densate. These 'values' can be constants, input channels or maths channels. Figure 3.2.9b and accompanying param-
eter descriptions give full details.
Figure 3.2.9a is a simplified sketch of a typical installation, showing where flow rate, pressure and temperature read-
ings are taken.
Steam supply
Inlet
Inlet pressure
flow
or temperature
Heat Heat
exchanger exchanger
Process 1 Process 2
Condensate
temperature
Steam Steam
Trap Trap
Condensate
Notes:
1 The units of kg/sec and m3/sec are used above for simplicity. In fact any time unit can be used. For ex-
ample if the measured flow is in m3/hour, then the Mass flow will be in kg/hour.
2. ASME Steam tables 1999, from IAPWF IF97.
HA028121 Options
Issue 5 Nov 04 Page 59
GRAPHICS RECORDER/DATA ACQUISITION AND LOGGING UNIT: OPTIONS MANUAL
PARAMETERS
Inlet Flow Select 'Constant' or the number of the channel supplying the measured flow rate. If 'Constant' se-
lected, a further 'box' allows the value for the constant to be entered.
Use Allows the user to select Temperature (˚C) or Pressure (MPa) for the calculation.
Inlet Temperature Appears only if Use = Temperature. Select 'Constant' or the number of the channel supplying the
steam temperature. If 'Constant' is selected, a further 'box' allows a value for the constant to be
entered.
Inlet Pressure Appears only if Use = Pressure. Select 'Constant' or the number of the channel supplying the steam
pressure. If 'Constant' is selected, a further 'box' allows a value for the constant to be entered.
Inlet Dryness Enter a value between 0 and 100 to represent the dryness of the steam. 0 = no vapour; 100 = no
liquid.
Return Temperature Select 'Constant' or the number of the channel supplying the condensate temperature If 'Constant'
is selected, a further 'box' allows a value for the constant to be entered.
*Note: See section 3.2.7, above, for details of pressure unit conversion
Similar in operation to MKT, described in section 3.2.6, above, except that the MKT is derived from a specified group
of points rather than a single point.
For each sample period, the maximum and minimum values reached by any point(s) within the specified group are
saved, and used as inputs to the Equation.
Options HA028121
Page 60 Issue 5 Nov 04
GRAPHICS RECORDER/DATA ACQUISITION AND LOGGING UNIT: OPTIONS MANUAL
3.2.11 Rate-of-change
*Note: For channels being read over Modbus, the ‘priority intervals’ set in the Modbus Master configuration
menu (section 3 of the Communications Manual) may cause the readings to be inaccurate or to be continu-
ously zero. For this reason, a minimum sample period of 1 second is recommended.
Reset now
HA028121 Options
Issue 5 Nov 04 Page 61
GRAPHICS RECORDER/DATA ACQUISITION AND LOGGING UNIT: OPTIONS MANUAL
This function carries out O2 correction of gas measurements for use in Continuous Emissions Monitoring applications.
The equation calculated is:
20.9% − Specified O2
Correction = × Measured Gas
20.9% − Measured O2
where,
Specified O2 = specified oxygen entered as a constant 5-digit value (prescribed for the particular process).
Measured O2 = measured oxygen,, entered as a channel number (gas analyser input) (See application note,
below).
Measured Gas = the measured gas, entered as a channel number (gas analyser input).
APPLICATION NOTE
Some Authorities allow Oxygen correction to be made ONLY if the Measured Oxygen value is above a limit specified
by such Authorities.
For the oxygen correction function to conform with this requirement it is necessary to 'Filter' the Measured Oxygen
value using a High Select function, with 'Measured Oxygen' and the Specified Limit constant as its inputs. The output
from this function (derived channel number) is then used as the 'Measured oxygen' value.
Options HA028121
Page 62 Issue 5 Nov 04
GRAPHICS RECORDER/DATA ACQUISITION AND LOGGING UNIT: OPTIONS MANUAL
This determines the percentage relative humidity from wet and dry temperature and atmospheric pressure inputs.
Standard temperature and pressure at sea level are defined as 1.01325 Bar, and 15˚C. Pressure varies with height as
indicated in table 3.2.13. The standard psychrometric constant is 0.000666 (6.66 x 10-4).
HA028121 Options
Issue 5 Nov 04 Page 63
GRAPHICS RECORDER/DATA ACQUISITION AND LOGGING UNIT: OPTIONS MANUAL
A zirconia (oxygen) probe consists of two platinum electrodes bonded to a pellet or cylinder of zirconia. At elevated
temperatures, such a probe develops an emf across it which is proportional to probe temperature and to the log of the
difference in oxygen partial pressure between its two ends.
OXYGEN CONCENTRATION
In order to measure oxygen concentrations, one end of the probe is inserted into the atmosphere to be measured,
whilst the other is subjected to a reference atmosphere. For most applications, air provides a suitable reference (refer-
ence input = 20.95 for air).
The temperature of the probe is normally measured using a type K or type R thermocouple. The temperature efect on
the thermocouple is such, that for successful operation the probe temperature must be greater than 973K (700˚C).
Figure 3.2.14a shows the configuration menu. Figure 3.2.14b shows oxygen concentration versus probe emf for vari-
ous temperatures.
The channel which is measuring the probe output would nornally need to be set to: Input Type = mV; Input low = 0;
imput high = 100..
Options HA028121
Page 64 Issue 5 Nov 04
GRAPHICS RECORDER/DATA ACQUISITION AND LOGGING UNIT: OPTIONS MANUAL
100 1
8
6
10 1
8
6
4
Percent Oxygen
1 1
8
6
15
00
14 ˚C
00
˚C 2
13
00
12
˚C
00
11
˚C
00
10
˚C
00
0.1 1
˚C
90
0˚
80
8
C
0 ˚C
70
0 ˚C
60
6
0 ˚C
500
400
˚C
4
300
˚C
˚C
0.01 1
0 20 40 60 80 100 120 140 160 180 200
HA028121 Options
Issue 5 Nov 04 Page 65
GRAPHICS RECORDER/DATA ACQUISITION AND LOGGING UNIT: OPTIONS MANUAL
OXYGEN POTENTIAL
The oxygen potential of an atmosphere is a measurement of its ability to oxidise or reduce. for any alament, a value
of oxygen potential (free energy of formation) is known. Above this value, the material will oxidise, below it, no
oxidisation will occur. Figure 3.2.14c, below, is a free energy diagram for a number of oxidising processes.
It can be shown that, because the oxygen potential of air is essentially constant over the range 870 to 1450 kelvins, the
zirconia probe output is proportional to the oxygen potential of an atmospher, according to:
E = (10.84 × T) + 40 mV (in the range 870 to 1450 K)
Thus, it is possible to measure oxygen potential directly from a zirconia probe, usin a standard input channel of the
instrument, scaled in units of oxygen potential. A typical configuration might be:
Input Type = mV; Input low = 40; Input high = 1124; Scale low = -100; Scale high = 0; Units kCal. Such a configu-
ration would be suitable over the temperature range 873 to 1473 K (600 to 1200 ˚C).
Options HA028121
Page 66 Issue 5 Nov 04
GRAPHICS RECORDER/DATA ACQUISITION AND LOGGING UNIT: OPTIONS MANUAL
Air O3
6F
e2 100
M →
2
+O 200
uO O4
2C e3
→ 4F m 6FeO + O2 → 2Fe3O4
u+
O2 300
2C M
M 2 NiO 400
→
O i+
O2 M
→ 2Cu 2 2N m 500
-50 + O2
4Cu CO 2
→2 600
T + O2
2CO H O
→2 2
S2 + 2O2 → 2SO 2 Sn
O2
2H 2
+ O2 700
→
O2
CoO Sn+ 800
→2
+ O2 2FeO
2Co O → 900
2 Fe + 2 M
Oxygen potential (kilocalories)
C + O2 → CO2
T 1000
-100 m
O5
1100
2C
+O → 2Ta 2
2 →2 O2
CO +5
b 2Zn
O 4Ta 1200
→
milliVolts
M O2
2Z
n+ 1300
M m
M r O3
2C 2 T T 1400
→ t m
O2 O
r +3 → 2Mn M 1500
4C + O2
2Mn
-150 1600
V 2O 3
→2 1700
O2
+3
4V
SiO 2 M 1800
→
O2
t Si +
1900
T l O3
iO 2 2A 2
→T → 2000
O2 O2
Ti + +3
l
4A 2100
M
-200
T M 2200
B
M 2300
eO
gO 2B
→
2M O2 2400
T → e+
ZrO 2 +O
2 2B ThO
2
→ g →
+ O2 2M T + O2
2500
Zr Th
2600
-250 2700
2800
2900
HA028121 Options
Issue 5 Nov 04 Page 67
GRAPHICS RECORDER/DATA ACQUISITION AND LOGGING UNIT: OPTIONS MANUAL
The following description assumes a group name of ‘Furnace 1’, which contains four channels with descriptors ‘Temp
1’, ‘Temp 2’, ‘Temp 3’ and ‘Temp 4’
The output of the Group Minimum function is the current lowest value of any of the points in the source group. The
required source group is selected by picklist. Should a point return a non-valid value, it is excluded from the calcula-
tion, and the result of the function is the minimum of the remaining points.
DESCRIPTORS
As a part of the Group Minimum function configuration, it is possible to select one of two types of descriptor: ‘User
Defined’ and ‘Minimum Channel’. Figure 3.2.15, below shows the relevant area of the configuration page.
The ‘Maths Number’ field which normally copies the maths channel descriptor, contains instead the text: ‘N) Group N
minimum’, where ‘Group N’ is the default name of the source group.
A typical application of the ‘Minimum channel descriptor’ would be to include the descriptor in a message sent to the
chart on a regular basis by a Timer function. Section 4.3.8 of the User Guide describes the entry of the messages, and
section 6 of this Options manual describes the setting up of timers.
Note: The Group configuration checkboxes for maths channels with‘’Minimum Channel Descriptor’ se-
lected, are ‘greyed’. thus preventing such channels from being used as inputs to thir own source group. See
section 4.3.2 of the User Guide for Group configuration details.
Options HA028121
Page 68 Issue 5 Nov 04
GRAPHICS RECORDER/DATA ACQUISITION AND LOGGING UNIT: OPTIONS MANUAL
For units fitted with the Modbus TCP comms option, the following table gives hex addresses for maths channel 1
Generally: Maths channel N parameter address = maths channel 1 parameter address + 162 (N-1) (decimal).
For full details of the Modbus implementation, see section 2 of the User Guide.
Note: A/B switching not supported for this
3.3.1 Maths channel configuration data software version.
Span, Zone, Colour etc. are all setting A
CHANNEL 1
Note: Alarms 3 and 4 are available only for instruments fitted with 32MB SRAM.
HA028121 Options
Issue 5 Nov 04 Page 69
GRAPHICS RECORDER/DATA ACQUISITION AND LOGGING UNIT: OPTIONS MANUAL
CHANNEL 1
Parameter Description Type Access Start Addr. Register
Name Hex (Dec) Length
Ch1 value Current process value (PV) Scaled Read/Write A2BA (41658) 1
Ch1 status Channel status Enum Read only A2BB (41659) 1
0 = Good PV 5 = Ranging error
1 = Channel off 6 = Overflow
2 = Over range 7 = Bad PV
3 = Under range 8 = No data
4 = Hardware error
Ch1 Alarms Alarm information Uint16 - A2BC (41660) 1
Bit 0: 0 = Alarm 1 inactive; 1 = Alarm 1 active Read only
Bit 1: 0 = No alarm 1 Ack. required; 1 = Ack. required Read only
Bit 2: 1 = Acknowledge alarm 1 Read/Write
Bit 3: Spare
Bit 4: 0 = Alarm 2 inactive; 1 = Alarm 2 active Read only
Bit 5: 0 = No Alarm 2 Ack. required; 1 = Ack. required Read only
Bit 6: 1 = Acknowledge alarm 2 Read/Write
Bit 7: Spare
Bit 8: 0 = Alarm 3 inactive; 1 = Alarm 3 active Read only
Bit 9: 0 = No alarm 3 Ack. required; 1 = Ack. required Read only
Bit 10: 1 = Acknowledge alarm 3 Read/Write
Bit 11: Spare
Bit 12: 0 = Alarm 4 inactive; 1 = Alarm 4 active Read only
Bit 13: 0 = No Alarm 4 Ack. required; 1 = Ack. required Read only
Bit 14: 1 = Acknowledge alarm 4 Read/Write
Bit 15: Spare
The following table shows addresses for the specified 32-bit floating-point values, for Maths channel 1. Generally,
Parameter address for channel N = Parameter address for channel 1 + 36(N-1) (decimal).
CHANNEL 1
Parameter Description Type Access Start Addr. Register
Name Hex (Dec) Length
Ch1 span high Upper span value (Display full scale) Float Read only DF73 (57203) 2
Ch1 span low Lower span value (display ‘zero’) Float Read only DF75 (57205) 2
Ch1 Zone high Zone upper value (% of ‘chart’ width) Float Read only DF77 (57207) 2
Ch1 Zone low Zone lower value (% of ‘chart’ width) Float Read only DF79 (57209) 2
Ch1 Alarm 1 setpoint Trigger setpoint for alarm 1 Float Read/Write DF7B (57211) 2
Ch1 Alarm 2 setpoint Trigger setpoint for alarm 2 Float Read/Write DF7D (57213) 2
Ch 1Alarm 3 setpoint Trigger setpoint for alarm 3 Float Read/Write DF7F (57215) 2
Ch 1Alarm 4 setpoint Trigger setpoint for alarm 4 Float Read/Write DF81 (57217) 2
Spare DF83 (57219) 20
Note: Alarms 3 and 4 are available only for instruments fitted with 32MB SRAM.
Options HA028121
Page 70 Issue 5 Nov 04
GRAPHICS RECORDER/DATA ACQUISITION AND LOGGING UNIT: OPTIONS MANUAL
The following table gives addresses for the specified 32-bit floating-point values, for maths channel 1. Generally,
Parameter address for channel N = Parameter address for channel 1 + 4(N-1) (decimal).
CHANNEL 1
Parameter Description Type Access Start Addr. Register
Name Hex (Dec) Length
Channel 1 value Current process value (PV) Float Read/Write F9EF (63983) 2
Channel 1 status Channel status Enum Read only F9F1 (63985) 1
0 = Good PV 5 = Ranging error
1 = Channel off 6 = Overflow
2 = Over range 7 = Bad PV
3 = Under range 8 = No data
4 = Hardware error
Channel 1 Alarms Alarm information Uint16 - F9F2 (63986) 1
Bit 0: 0 = Alarm 1 inactive; 1 = Alarm 1 active Read only
Bit 1: 0 = No alarm 1 Ack. required; 1 = Ack. required Read only
Bit 2: 1 = Acknowledge alarm 1 Read/Write
Bit 3: Spare
Bit 4: 0 = Alarm 2 inactive; 1 = Alarm 2 active Read only
Bit 5: 0 = No Alarm 2 Ack. required; 1 = Ack. required Read only
Bit 6: 1 = Acknowledge alarm 2 Read/Write
Bit 7: Spare
Bit 8: 0 = Alarm 3 inactive; 1 = Alarm 3 active Read only
Bit 9: 0 = No alarm 3 Ack. required; 1 = Ack. required Read only
Bit 10: 1 = Acknowledge alarm 3 Read/Write
Bit 11: Spare
Bit 12: 0 = Alarm 4 inactive; 1 = Alarm 4 active Read only
Bit 13: 0 = No Alarm 4 Ack. required; 1 = Ack. required Read only
Bit 14: 1 = Acknowledge alarm 4 Read/Write
Bit 15: Spare
Note: Alarms 3 and 4 are available only for instruments fitted with 32MB SRAM.
HA028121 Options
Issue 5 Nov 04 Page 71
GRAPHICS RECORDER/DATA ACQUISITION AND LOGGING UNIT: OPTIONS MANUAL
4 TOTALISER OPTION
4.1 INTRODUCTION
Each totaliser allows the user to maintain a running total of any input channel, or of any maths channel. Using the
maths functions, it is possible to totalise combinations of input channels, so the value of two channels added together,
or the difference between two channels could be totalised if required. The totaliser equation is :
ma t
tot t = tot t-1 +
PSF × USF
where tott = totaliser value this sample*
tott-1 = totaliser value last sample*
mat = value of totalised channel this sample*
PSF = Period Scaling Factor (See Period scaler description below)
USF = Units Scaling Factor (See Unit scaler description below)
1
*Note: Time between samples (seconds) =
sample rate of recorder (Hz)
See ‘Update information’ in Annex A for details.
4.2 CONFIGURATION
Totaliser Number Allows any of the available totalisers to be selected from the picklist, for configuration.
Total of Allows an input channel or a maths channel to be selected as the source to be totalised.
Low Cutoff The value of the source channel (in engineering units) below which it is not to be totalised.
High Cutoff The value of the source channel (in engineering units) above which it is not to be totalised.
Preset Allows the entry of a 10-character positive, or nine-character negative value from which the
totaliser is to start counting.
Direction of counting is defined by the sign of the Unit scaler viz: + = increment; - = decre-
ment.
Preset now Operation of this key initiates the totaliser preset.
Options HA028121
Page 72 Issue 5 Nov 04
GRAPHICS RECORDER/DATA ACQUISITION AND LOGGING UNIT: OPTIONS MANUAL
Preset now
Period scaler 1
Unit scaler 1
Descriptor Totaliser 1
A/B Switching
Scale Low 0 Units (totaliser)
Scale High 1 Units (totaliser)
Scale Type None Select None, Linear or Log (if log
scales option fitted)
Zone Low 1 %
Zone High 100 %
PV format Numeric Select Numeric or Scientific
Max Decimal Digits 4
Colour 0
Alarm Number 1 Select Alarm number
Select: Off,
Enable Off Unlatched,
Latched,
Job Number 1 Select Job number Trigger
Apply Discard
Period Scaler The totaliser equation works in seconds. If the totalised channel units are other than ‘per
second’ a period scaler other than the default (1) must be entered. For example, if the input
channel is in litres per hour, then the period scaler would have to be the number of seconds in
an hour (3600).
Unit Scaler If, for example, the input channel is in litres per hour, the totalised value will be in litres,
unless the unit scaler is set to a value other than 1. If it is more convenient, the totalised value
can be in thousands of litres by setting the unit scaler to 1000. Setting the unit scaler negative
causes the totaliser to decrement rather than increment.
Scale Low/High The 'zero' and full scale values for the totaliser, as traced on the screen.
If A/B switching is enabled, a second set of scale low and scale high values can be entered.
'A' values are used during normal operation. 'B' values are switched to by job action, as
described in section 4.7 of the User Guide.
The remaining configuration items are identical with the relevant items in Input Channel configuration (section 4.3.3
of the User Guide). For job information, see section 4.7 of the User Guide.
HA028121 Options
Issue 5 Nov 04 Page 73
GRAPHICS RECORDER/DATA ACQUISITION AND LOGGING UNIT: OPTIONS MANUAL
For units fitted with the Modbus TCP comms option, the following table gives addresses for totaliser 1 configuration
data
Generally: Totaliser N parameter address = totaliser 1 parameter address + 162 (N-1) (decimal).
For full details of the Modbus implementation, see section 2 of the Communications Manual.
Note: A/B switching not supported for this
4.3.1 Totaliser configuration data software version.
Span, Zone, Colour etc. are all setting A
TOTALISER 1
Note: Alarms 3 and 4 are available only for instruments fitted with 32MB SRAM.
Options HA028121
Page 74 Issue 5 Nov 04
GRAPHICS RECORDER/DATA ACQUISITION AND LOGGING UNIT: OPTIONS MANUAL
TOTALISER 1
Parameter Description Type Access Start Addr. Register
Name Hex (Dec) Length
Value Current process value (PV) Scaled Read/Write A3E6 (41958) 1
Status Channel status Enum Read only A3E7 (41959) 1
0 = Good PV 5 = Ranging error
1 = Channel off 6 = Overflow
2 = Over range 7 = Bad PV
3 = Under range 8 = No data
4 = Hardware error
Alarms Alarm information Uint16 - A3E8 (41960) 1
Bit 0: 0 = Alarm 1 inactive; 1 = Alarm 1 active Read only
Bit 1: 0 = No alarm 1 Ack. required; 1 = Ack. required Read only
Bit 2: 1 = Acknowledge alarm 1 Read/Write
Bit 3: Spare
Bit 4: 0 = Alarm 2 inactive; 1 = Alarm 2 active Read only
Bit 5: 0 = No Alarm 2 Ack. required; 1 = Ack. required Read only
Bit 6: 1 = Acknowledge alarm 2 Read/Write
Bit 7: Spare
Bit 8: 0 = Alarm 3 inactive; 1 = Alarm 3 active Read only
Bit 9: 0 = No alarm 3 Ack. required; 1 = Ack. required Read only
Bit 10: 1 = Acknowledge alarm 3 Read/Write
Bit 11: Spare
Bit 12: 0 = Alarm 4 inactive; 1 = Alarm 4 active Read only
Bit 13: 0 = No Alarm 4 Ack. required; 1 = Ack. required Read only
Bit 14: 1 = Acknowledge alarm 4 Read/Write
Bit 15: Spare
The following table gives addresses for the specified 32-bit floating-point values, for Totaliser 1. Generally, Param-
eter address for totaliser N = Parameter address for totaliser 1 + 36(N-1) (decimal).
TOTALISER 1
Parameter Description Type Access Start Addr. Register
Name Hex (Dec) Length
Span high Upper span value (Display full scale) Float Read only ED83 (60803) 2
Span low Lower span value (display ‘zero’) Float Read only ED85 (60805) 2
Zone high Zone upper value (% of ‘chart’ width) Float Read only ED87 (60807) 2
Zone low Zone lower value (% of ‘chart’ width) Float Read only ED89 (60809) 2
Alarm 1 setpoint Trigger setpoint for alarm 1 Float Read/Write ED8B (60811) 2
Alarm 2 setpoint Trigger setpoint for alarm 2 Float Read/Write ED8D (60813) 2
Alarm 3 setpoint Trigger setpoint for alarm 3 Float Read/Write ED8F (60815) 2
Alarm 4 setpoint Trigger setpoint for alarm 4 Float Read/Write ED91 (60817) 2
Spare ED93 (60819) 20
Note: Alarms 3 and 4 are available only for instruments fitted with 32MB SRAM.
HA028121 Options
Issue 5 Nov 04 Page 75
GRAPHICS RECORDER/DATA ACQUISITION AND LOGGING UNIT: OPTIONS MANUAL
The following table gives addresses for the specified 32-bit floating-point values, for totaliser 1. Generally, Parameter
address for totaliser N = Parameter address for totaliser 1 + 4(N-1) (decimal).
TOTALISER 1
Parameter Description Type Access Start Addr. Register
Name Hex (Dec) Length
Totaliser 1 value Current process value (PV) Float Read/Write FB7F (64383) 2
Totaliser 1 status Channel status Enum Read only FB81 (64385) 1
0 = Good PV 5 = Ranging error
1 = Channel off 6 = Overflow
2 = Over range 7 = Bad PV
3 = Under range 8 = No data
4 = Hardware error
Totaliser 1 Alarms Alarm information Uint16 - FB82 (64386) 1
Bit 0: 0 = Alarm 1 inactive; 1 = Alarm 1 active Read only
Bit 1: 0 = No alarm 1 Ack. required; 1 = Ack. required Read only
Bit 2: 1 = Acknowledge alarm 1 Read/Write
Bit 3: Spare
Bit 4: 0 = Alarm 2 inactive; 1 = Alarm 2 active Read only
Bit 5: 0 = No Alarm 2 Ack. required; 1 = Ack. required Read only
Bit 6: 1 = Acknowledge alarm 2 Read/Write
Bit 7: Spare
Bit 8: 0 = Alarm 3 inactive; 1 = Alarm 3 active Read only
Bit 9: 0 = No alarm 3 Ack. required; 1 = Ack. required Read only
Bit 10: 1 = Acknowledge alarm 3 Read/Write
Bit 11: Spare
Bit 12: 0 = Alarm 4 inactive; 1 = Alarm 4 active Read only
Bit 13: 0 = No Alarm 4 Ack. required; 1 = Ack. required Read only
Bit 14: 1 = Acknowledge alarm 4 Read/Write
Bit 15: Spare
Note: Alarms 3 and 4 are available only for instruments fitted with 32MB SRAM.
Options HA028121
Page 76 Issue 5 Nov 04
GRAPHICS RECORDER/DATA ACQUISITION AND LOGGING UNIT: OPTIONS MANUAL
5 COUNTER OPTION
5.1 INTRODUCTION
This option introduces a number (depends on recorder model) of counters, which can be preset, disabled, incremented
or decremented by Job action (see section 4.7 of the User Guide for Job details). If access is permitted, the user can
preset the counter to a selected value, as and when required, from the configuration page.
If the Batch option is fitted (section 1), then batches can be started when a specified counter changes value, and if this
is done, the batch number is the value of the specified counter.
5.2 CONFIGURATION
Figure 5.2 shows a typical (enabled) counter configuration page. The page is accessed from the Root menu/Operator/
Config menu.
Counter number 1) Counter 1 Select counter
number
Enable
Value OFF Units
Units Units
Preset 0 Units
Preset now
Descriptor Counter 1
A/B Switching
Scale Low 0 Units
Scale High 1 Units
Scale Type None Select None or Linear
Zone Low 0 %
Zone High 100 %
Colour 0
Alarm Number 1 Select Alarm number
Select: Off,
Enable Off Unlatched,
Latched,
Job Number 1 Select Job number Trigger
Apply Discard
Counter number Allows any of the available counters to be selected for configuration
Enable Allows the user to start/stop counting by enabling/disabling the counter.
Value Shows the current dynamic value of the counter
Units Allows a text string of up to 5 characters to be entered as a units description
Preset Allows a counter value to be entered for manual or job action preset.
Scale low/high The values to appear at the scale endpoints. If A/B switching is enabled, a second set of scale
low and scale high values can be entered. 'A' values are used during normal operation. 'B'
values are switched to by job action, as described in section 4.7 of the User Guide.
The remaining configuration items are as described for input channels in section 4.3.3 of the User Guide.
Note: An absolute high alarm (for example) with a threshold of 10, will not be triggered until the
value exceeds 10 (i.e. counter value = 11). In order to trip the alarm at 10, a threshold lower than 10
must be entered (e.g. threshold = 9.5). A similar situation exists for absolute low and deviation alarms.
HA028121 Options
Issue 5 Nov 04 Page 77
GRAPHICS RECORDER/DATA ACQUISITION AND LOGGING UNIT: OPTIONS MANUAL
For units fitted with the Modbus TCP comms option, the following table gives ddresses for counter 1 configuration
data.
Generally: Counter N parameter address = counter 1 parameter address + 162 (N-1) (decimal).
For full details of the Modbus implementation, see section 2 of the Communications Manual.
Note: A/B switching not supported for this
5.3.1 Counter configuration data software version.
Span, Zone, Colour etc. are all setting A
COUNTER 1
Note: Alarms 3 and 4 are available only for instruments fitted with 32MB SRAM.
Options HA028121
Page 78 Issue 5 Nov 04
GRAPHICS RECORDER/DATA ACQUISITION AND LOGGING UNIT: OPTIONS MANUAL
COUNTER 1
Parameter Description Type Access Start Addr. Register
Name Hex (Dec) Length
Value Current process value (PV) Scaled Read/Write A47C (42108) 1
Status Channel status Enum Read only A47D (42109) 1
0 = Good PV 5 = Ranging error
1 = Channel off 6 = Overflow
2 = Over range 7 = Bad PV
3 = Under range 8 = No data
4 = Hardware error
Alarms Alarm information Uint16 - A47E (42110) 1
Bit 0: 0 = Alarm 1 inactive; 1 = Alarm 1 active Read only
Bit 1: 0 = No alarm 1 Ack. required; 1 = Ack. required Read only
Bit 2: 1 = Acknowledge alarm 1 Read/Write
Bit 3: Spare
Bit 4: 0 = Alarm 2 inactive; 1 = Alarm 2 active Read only
Bit 5: 0 = No Alarm 2 Ack. required; 1 = Ack. required Read only
Bit 6: 1 = Acknowledge alarm 2 Read/Write
Bit 7: Spare
Bit 8: 0 = Alarm 3 inactive; 1 = Alarm 3 active Read only
Bit 9: 0 = No alarm 3 Ack. required; 1 = Ack. required Read only
Bit 10: 1 = Acknowledge alarm 3 Read/Write
Bit 11: Spare
Bit 12: 0 = Alarm 4 inactive; 1 = Alarm 4 active Read only
Bit 13: 0 = No Alarm 4 Ack. required; 1 = Ack. required Read only
Bit 14: 1 = Acknowledge alarm 4 Read/Write
Bit 15: Spare
The following table gives addresses for the specified 32-bit floating-point values, for Counter 1. Generally, Parameter
address for counter N = Parameter address for counter 1 + 36(N-1) (decimal).
COUNTER 1
Parameter Description Type Access Start Addr. Register
Name Hex (Dec) Length
Span high Upper span value (Display full scale) Float Read only F48B (62603) 2
Span low Lower span value (display ‘zero’) Float Read only F48D (62605) 2
Zone high Zone upper value (% of ‘chart’ width) Float Read only F48F (62607) 2
Zone low Zone lower value (% of ‘chart’ width) Float Read only F491 (62609) 2
Alarm 1 setpoint Trigger setpoint for alarm 1 Float Read/Write F493 (62611) 2
Alarm 2 setpoint Trigger setpoint for alarm 2 Float Read/Write F495 (62613) 2
Alarm 3 setpoint Trigger setpoint for alarm 3 Float Read/Write F497 (62615) 2
Alarm 4 setpoint Trigger setpoint for alarm 4 Float Read/Write F499 (62617) 2
Spare F49B (62619) 20
Note: Alarms 3 and 4 are available only for instruments fitted with 32MB SRAM.
HA028121 Options
Issue 5 Nov 04 Page 79
GRAPHICS RECORDER/DATA ACQUISITION AND LOGGING UNIT: OPTIONS MANUAL
The following table gives addresses for the specified 32-bit floating-point values, for counter 1. Generally, Parameter
address for counter N = Parameter address for counter 1 + 4(N-1) (decimal).
COUNTER 1
Parameter Description Type Access Start Addr. Register
Name Hex (Dec) Length
Counter 1 value Current process value (PV) Float Read/Write FC47 (64583) 2
Counter 1 status Channel status Enum Read only FC49 (64585) 1
0 = Good PV 5 = Ranging error
1 = Channel off 6 = Overflow
2 = Over range 7 = Bad PV
3 = Under range 8 = No data
4 = Hardware error
Counter 1 Alarms Alarm information Uint16 - FC4A (64586) 1
Bit 0: 0 = Alarm 1 inactive; 1 = Alarm 1 active Read only
Bit 1: 0 = No alarm 1 Ack. required; 1 = Ack. required Read only
Bit 2: 1 = Acknowledge alarm 1 Read/Write
Bit 3: Spare
Bit 4: 0 = Alarm 2 inactive; 1 = Alarm 2 active Read only
Bit 5: 0 = No Alarm 2 Ack. required; 1 = Ack. required Read only
Bit 6: 1 = Acknowledge alarm 2 Read/Write
Bit 7: Spare
Bit 8: 0 = Alarm 3 inactive; 1 = Alarm 3 active Read only
Bit 9: 0 = No alarm 3 Ack. required; 1 = Ack. required Read only
Bit 10: 1 = Acknowledge alarm 3 Read/Write
Bit 11: Spare
Bit 12: 0 = Alarm 4 inactive; 1 = Alarm 4 active Read only
Bit 13: 0 = No Alarm 4 Ack. required; 1 = Ack. required Read only
Bit 14: 1 = Acknowledge alarm 4 Read/Write
Bit 15: Spare
Note: Alarms 3 and 4 are available only for instruments fitted with 32MB SRAM.
Options HA028121
Page 80 Issue 5 Nov 04
GRAPHICS RECORDER/DATA ACQUISITION AND LOGGING UNIT: OPTIONS MANUAL
6 TIMERS OPTION
6.1 INTRODUCTION
This option offers a number of count-down timers which can be used for general timing purposes. The timers can be
either one-shot or repeating, and can be initiated in the following ways:
1. directly by the operator from the configuration page (if access permission is granted),
2. by job action (see section 4.7 of the User Guide),
3. at a predefined time/date,
4. every ‘time period’, where the ‘time period’ can be configured to be anything from 1 second to 1 year. For exam-
ple, setting seconds to ‘30’ and leaving all other fields ‘Any’, the timer will start every minute on the half minute.
Setting seconds to ‘30’ and minutes to ‘0’ will cause the timer to start at 30 seconds past each hour.
Note: Times are not adjusted for Daylight Saving changes. Thus if the timer is set to trigger on a daily,
weekly, etc, basis, then, during 'Summer Time', the trigger will occur an hour late (i.e. at 01:00 hrs. instead of
at midnight).
The full range of jobs is available as described in section 4.7 of the User Guide. 'Timer Active' is defined as an inter-
nal event trigger (see section 4.3.6 of the User Guide).
6.2 CONFIGURATION
Figure 6.2 shows a typical timer configuration display. The page is accessed from the Root menu/Operator/Config
menu.
Start now
Descriptor Timer 1
Self start
Date Any
Month Any These fields appear
Hour Midnight only if 'Self start' is
enabled.
Minute Any
Second Any
Duration 60 Seconds
Repeat after 0 Seconds
Job Number 1 Select Job number
Select Job
Category No Action category
Apply Discard
HA028121 Options
Issue 5 Nov 04 Page 81
GRAPHICS RECORDER/DATA ACQUISITION AND LOGGING UNIT: OPTIONS MANUAL
Note: If Month = ‘Any’, and Day = 31, then the timer will not be triggered in February, April, June,
September or November. Similarly, if Day = 30, the timer will not be triggered in February, and so on.
SELF-START EXAMPLE
To preset Totaliser number 1 to zero, daily, at midnight:
Options HA028121
Page 82 Issue 5 Nov 04
GRAPHICS RECORDER/DATA ACQUISITION AND LOGGING UNIT: OPTIONS MANUAL
7 EVENT INPUTS
Note: This option is not supported by all models. The maximum number of event inputs is model dependent.
7.1 INTRODUCTION
Each Event input option board offers six isolated event input circuits. Inputs can either be switch closures or voltage
levels.
Section 4.3.6 'Event Configuration' in the User Guide, describes the use of events, and how they can be ANDed and
ORed together to perform logic functions if required. Job lists can be triggered by any event, either 'internal' or as a
result of external events wired to the event input board. If this option is fitted, ‘Event Input Board’ appears as an
event source.
If ‘Event Input Board’ is selected as a source, the ‘Board’ number and the event ‘Input’ number on that board must be
specified.
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22
1 2 3 4 5 6 C 1 2 3 4 5 6 C
HA028121 Options
Issue 5 Nov 04 Page 83
GRAPHICS RECORDER/DATA ACQUISITION AND LOGGING UNIT: OPTIONS MANUAL
Figure 7.3 shows wiring details for the six discrete event inputs.
1 2 3 4 5 6 C 1 2 3 4 5 6 C
Input 6 shown;
2 to 30 V
inputs 1 to 5 identical
0.8 to -30 V
User 0V
7.4 SPECIFICATION
Safety isolation
Safety Isolation (dc to 65 Hz: BS EN61010) Installation category II; Pollution degree 2 (see page 1 for definitions)
Event input to event input: 0V
Event input to ground: 100V RMS or dc (double insulation)
Operating levels
Voltage levels An event is considered to be ‘Active’ if the voltage at its input terminal is between +0.8 and - 30 V with respect to the
‘C’ terminal. It is considered ‘Inactive’ if the voltage is between +2V and +30V. Status is not guaranteed for voltages
between the above values
Maximum input voltage ± 30V with respect to ‘C’
Maximum input frequency 4 Hz
Current sink requirements (Voltage i/p) 10mA
Contact closures
Contact resistances An event is considered to be ‘Active’ if the resistance between its input termninal and the ‘C’ terminal is less than
35kΩ. It is considered ‘Inactive’ if the resistance is greater 200kΩ. Status is not guaranteed for resistances between
the above values
Minimum durations
Recognition time The minimum time for which the contact closure must be maintained is 62.5 msec. This protects against switch
‘bounce’, and against most transients. Transients lasting more than 62.5 msec will cause a trigger to occur, lasting one
iteration period (125 msec)
Options HA028121
Page 84 Issue 5 Nov 04
GRAPHICS RECORDER/DATA ACQUISITION AND LOGGING UNIT: OPTIONS MANUAL
8.1 INTRODUCTION
WARNING!
Transmitter power supplies must not be used with dc supply voltages.
Notes:
1. Transmitter power supplies are not suitable for use with low-voltage ac supplies.
2 The transmitter power supply is available only with 100 mm. recorders.
This option consists of a circuit board, terminal block and suitable wiring inside a long terminal cover at the rear of a
100mm recorder. The board supplies three mutually isolated dc supplies (nominal 25 Volts) each of which is intended
to power a single 0 to 20 mA or 4 to 20 mA current loop.
8.2 FUSING
The circuit board is protected by a 20 mm anti-surge (type T) fuse, the value of which depends on the supply voltage
as shown in table 8.2.1, below.
Access to the output wiring and to the fuse is achieved by isolating the recorder from mains power and opening the
terminal cover (after removing its securing screw). The process is fully described below.
HA028121 Options
Issue 5 Nov 04 Page 85
GRAPHICS RECORDER/DATA ACQUISITION AND LOGGING UNIT: OPTIONS MANUAL
Power cord
to recorder
Cable clamp
Cover securing
screw
Fuse
Figure 8.2.2a retaining screw location Figure 8.2.2b Inside the terminal cover
4 The fuse is located as shown in figure 8.2.2b. User wiring to the terminal block (figures 8.2.3a/b) can be carried
out now, or the terminal cover can be removed for convenience, as described in steps 5 onwards below.
5. Unplug the IEC connector from the rear of the recorder connector panel
6. Remove the cable clamp, retaining the fixings for later re-assembly.
7. Close the terminal cover, and lift it off, as indicated in figure 8.2.2c.
Recorder Terminal
Body cover
View on right hand
side of recorder
Lift off
Options HA028121
Page 86 Issue 5 Nov 04
GRAPHICS RECORDER/DATA ACQUISITION AND LOGGING UNIT: OPTIONS MANUAL
Figure 8.2.3a shows the terminal block pinout, and figure 8.2.3b shows typical applications wiring.
Power cord
to recorder
USER CONNECTIONS
O/P1 O/P2 O/P3
+ + +
Recorder rear
terminal panel
Transmitter Power Supply
Channel input
100 250 PCB
0 mA 0V 0V V+ V- I
4 mA 0.4 V 1.0 V
Black
R
Black
Black
Red
Red
Red
20 mA 2.0 V 5.0V
Voltages generated by
various currents for
R = 100 and R =250
User terminal block
+ + +
- + Other transmitters
HA028121 Options
Issue 5 Nov 04 Page 87
GRAPHICS RECORDER/DATA ACQUISITION AND LOGGING UNIT: OPTIONS MANUAL
9.1 INTRODUCTION
The transmitter power supply shares the same board as the Relay/ethernet option, and is therefore available only if the
Relay/Ethernet option is also fitted. The option is capable of supplying, continuously, a total of 120 mA at a nominal
24 Volts. This allows up to six 0 to 20 mA or 4 to 20 mA transmitters to be powered.
9. 2 PINOUT
Pinout is from a two-pin plug at the rear of the recorder, as shown in figure 9.3.1, below
WARNING!
The transmitter power supply is not isolated – the 0 Volt terminals are connected to Chassis ground.
V+ 0V
Non-isolated
TRS connector
Options HA028121
Page 88 Issue 5 Nov 04
GRAPHICS RECORDER/DATA ACQUISITION AND LOGGING UNIT: OPTIONS MANUAL
9.3 WIRING
- + - +
Transmitter Transmitter
1 2
HA028121 Options
Issue 5 Nov 04 Page 89
GRAPHICS RECORDER/DATA ACQUISITION AND LOGGING UNIT: OPTIONS MANUAL
Note: Portable case options are not available for some Models
The various options described below come provided in a rugged carrying case as depicted in figure 10, below,
It is possible that input/output circuits can carry high voltages, and this might prove dangerous if the safety earth con-
nection to the recorder is not in place (e.g. the plug is pulled out) at any time whilst such hazardous voltages are
present. Therefore, the following warning must be complied with:
* WARNING
For portable case instruments only:
All I/O connections must be SELV (33V ac RMS, 46,7V ac peak, 70Vdc) unless the integrity of the instru-
ment safety earth is maintained for as long as the I/O is connected to the recorder.
430 mm
190 mm 384.8 mm
40.5 mm
11:52:59
Engineer G r o u p n a m e 22/08/01
C h a n 7 0 0
nel 1 . 8 7
4 0 0 . 0 0 4 8 0 . 0 0 5 6 0 . 0 0 6 4 0 . 0 0 7 2 0 . 0 0 8 0 0 . 0 0
11:52:04
22/08/00
11:49:24
22/08/00
mm
11:46:44
22/08/00
240 mm 15 mm
300 mm
Top view
174
mm
38
mm
Note: To maintain CE compliance, the clip-on Ferrite supplied, must be attached to the mains lead (line cord)
Options HA028121
Page 90 Issue 5 Nov 04
GRAPHICS RECORDER/DATA ACQUISITION AND LOGGING UNIT: OPTIONS MANUAL
10.1.1 Introduction
The basic portable case option provides up to 12 input channels and up to four option boards.
10.1.2 Wiring
Figure 10.1.2a, below, gives back panel connector layouts for the recorder.
8 1
Ethernet connector
(RJ45)
Supply
Option board 1 Option board 2
1 22
Option board 3 Option board 4
22
Input channels 7 to 12
V V I V V I V V I V V I V V I V V I
+ + + + + +
1 Ch7 Ch8 Ch9 Ch10 Ch11 Ch12 22
Input channels 1 to 6
V V I V V I V V I V V I V V I V V I
+ + + + + +
1 Ch1 Ch2 Ch3 Ch4 Ch5 Ch6 22
SUPPLY VOLTAGE
Caution
Before powering the recorder, check that the supply voltage, to be applied, lies within the range specified
on the serial number label at the rear of the recorder.
As shown in Figure 10.1.2a, above, the line supply is terminated using an IEC connector at the rear of the case. A
socket is required to mate with the plug fitted at the recorder. Minimum recommended conductor size is 16/0.2
(0.5mm2) (20AWG).
SIGNAL WIRING
Input and typical options pinouts are as shown in figure 10.1.2a, above. For full I/O wiring details, refer to Section
1.2 of the User Guide supplied with the instrument.
INTERNAL WIRING
Figure 10.1.2b, below, shows details of the wiring between the portable case rear panel and the recorder rear panel.
HA028121 Options
Issue 5 Nov 04 Page 91
GRAPHICS RECORDER/DATA ACQUISITION AND LOGGING UNIT: OPTIONS MANUAL
Portable case
Recorder back panel
Ethernet
connector
1
1
2
Option board 1
2
3
3
4
4
5
5
6
6
7
7
8
8
9
9
10
10
11
Top connector 11
12
12
13
13
14
Option board 2
14
15
15
16
16
17
17
18
18
19
19
20
20
21
21
22
22
1 1
2
Option board 3
2
3
3
4
4
5
5
6 6
7 7
8
8
9 9
10 10
11 11
12 12
13 13
14
Option board 4
14
15 15
16 16
17 17
18 18
19 19
20 20
21 21
22 22
1
1
2
V+ 2 V+ Input board 2
V- 3 V-
3
I 4 I
4
V+ 5 V+
5
6 V- 6 V-
7 I 7 I
V+ 8 V+
8
9 V- 9 V-
I 10 I
10
11
CJ
12 12
sensor
V+ 13 V+
13
V- 14 V-
14
15 I 15 I
V+ 16 V+
16
V- 17 V-
17
18 I 18 I
V+ 19 V+
19
V- 20 V-
20
I 21 I
21
22
22
1
1
2
V+ 2 V+ Input board 1
V- 3 V-
3
I 4 I
4
V+ 5 V+
5
V- 6 V-
6
I 7 I
7
V+ 8 V+
8
V- 9 V-
9
I 10 I
10
11
CJ
12 12
sensor
V+ 13 V+
13
V- 14 V-
14
I 15 I
15
V+ 16 V+
16
V- 17 V-
17
Bottom connector 18
I 18 I
V+ 19 V+
19
V- 20 V-
20
I 21 I
21
22
22
Options HA028121
Page 92 Issue 5 Nov 04
GRAPHICS RECORDER/DATA ACQUISITION AND LOGGING UNIT: OPTIONS MANUAL
This option is identical with the basic option described in section 10.1, above except that one of the four option slots
is used for TRS output. The TRS pinout is given in figure 10.2, below.
Note: Only one transmitter power supply can be fitted in the portable case, and may be terminated only at
option slot 2 OR option slot 4.
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22
+V 0V +V 0V +V 0V
Figure 10.2.1 shows wiring details between the recorder and the back panel connectors.
HA028121 Options
Issue 5 Nov 04 Page 93
GRAPHICS RECORDER/DATA ACQUISITION AND LOGGING UNIT: OPTIONS MANUAL
Portable case
Recorder back panel
Ethernet
connector
1
1
2
Option board 1
2
3
3
4
4
5
5
6
6
7
7
8
8
9
9
10
10
11
Top connector 11
12
12
13
13
14
Option board 2
14
15
15
16
16
17
17
18
18
19
19
20
20
21
21
22
22
1
1
2
Option board 3
2
3
3
4
4
5
5
6
6
7
7
8
8
9
9
10
10
11
11
12
12
13
13
24V 14
14
0V 15
15
16
16
24V 17
17
0V 18
18
19
19
24V 20
20
0V 21
21
22
22 TRS
Terminal
block
1
1
2
V+ 2 V+ Input board 2
V- 3 V-
3
I 4 I
4
V+ 5 V+
5
V- 6 V-
6
I 7 I
7
V+ 8 V+
8
V- 9 V-
9
I 10 I
10
11
CJ 12 12
sensor V+ 13 V+
13
V- 14 V-
14
I 15 I
15
V+ 16 V+
16
V- 17 V-
17
I 18 I
18
V+ 19 V+
19
V- 20 V-
20
I 21 I
21
22
22
1
1
2
V+ 2 V+ Input board 1
V- 3 V-
3
I 4 I
4
V+ 5 V+
5
V- 6 V-
6
I 7 I
7
V+ 8 V+
8
V- 9 V-
9
I 10 I
10
11
CJ 12
12
sensor V+ 13 V+
13
V- 14 V-
14
I 15 I
15
V+ 16 V+
Bottom connector 16
17
V- 17 V-
I 18 I
18
V+ 19 V+
19
V- 20 V-
20
I 21 I
21
22
22
Options HA028121
Page 94 Issue 5 Nov 04
GRAPHICS RECORDER/DATA ACQUISITION AND LOGGING UNIT: OPTIONS MANUAL
10.3.1 Introduction
This option is supplied as a six-channel, 100 mm recorder in a rugged portable case, configured for five type-T ther-
mocouples and one pressure transducer. The option comes complete with pressure transducer, insertion tubes and
miniature plugs for type T thermocouples. As supplied, the recorder is for use with small, unwrapped utensil sterilis-
ers. The default configuration for the thermocouples is: Function = Type T, Input range = 0 to 150˚C, and for the
transducer: Input range = -1 to + 3 bar.
10.3.2 Wiring
SUPPLY VOLTAGE
Caution
Before powering the recorder, check that the supply voltage, to be applied, lies within the range specified
on the serial number label at the rear of the recorder.
As shown in Figure 10.3.2a, below, the line supply is terminated using an IEC connector at the rear of the case. A
socket is required to mate with the plug fitted at the recorder. Minimum recommended conductor size is 16/0.2
(0.5mm2) (20AWG).
SIGNAL WIRING
Signal wiring consists of wiring the thermocouples to the relevant plugs and plugging them and the (pre-wired) pres-
sure transducer in. Figure 10.3.2a shows the arrangement of the sockets at the rear of a six-channel recorder, and
figure 10.3.2b shows the wiring of the thermocouple plugs.
8 1 Supply E
+ wire
T/C type T colours
BS4937:1993
BS1843:1952 IEC584-3:1989
+ White Brown
Blue White
wire Sheath Blue Brown
HA028121 Options
Issue 5 Nov 04 Page 95
GRAPHICS RECORDER/DATA ACQUISITION AND LOGGING UNIT: OPTIONS MANUAL
INTERNAL WIRING
Figure 10.3.2c shows the internal wiring between the portable case connectors and the recorder rear panel.
L Brown L
Line supply
N Blue N
(100 to 240V) PSU
(50/60 Hz) E E
Chassis ground Green/Yellow
(safety earth)
Earth
Transmitter PSU
L Brown
N Blue
+ Red Terminal
Block
O/P 3 Black
+ Red
O/P 2 Black
+ Red
O/P 1 Black
1 Input
+ 2 V+ Board
Con 1 3 V-
-
4
5 V+
+
Con 2 6 V-
- 7
+ 8 V+
Con 3 9 V-
-
10
CJ 11
sensor
12
+ 13 V+
Con 4 14 V-
-
15
+ 16 V+
Con 5 17 V-
-
18
+ V+ 19
Con 6 Shunt V- 20
-
Wiring from thermocouple 21
connectors to input terminals
22
is in thermocouple wire
Ethernet
connector
Pressure transducer
Input range -1 to 3 Bar G
Output range 4 to 20 mA
Supply voltage range 12 to 32V dc
Non linearity/hysteresis ≤0.25% span
Safety isolation
DC to 65 Hz: BS EN61010 (Installation category II; Pollution degree 2 (see page 3 for definitions)
Channel to channel: S.E.L.V. (i.e. 30V dc or RMS) to earth
Channel to ground S.E.L.V. (i.e. 30V dc or RMS) to earth
Options HA028121
Page 96 Issue 5 Nov 04
GRAPHICS RECORDER/DATA ACQUISITION AND LOGGING UNIT: OPTIONS MANUAL
10.4.1 Introduction
This option allows the connection of up to 12 type J, K or T thermocouples together with up to two option boards.
Transmitter power supply is not available with this option.
The type of thermocouple (the same for all channels) must be specified at time of order. Each thermocouple input
channel will be configured at the factory for the specified type of thermocouple and will be set to a range of 0 to 100
degrees Celsius.
Thermocouple-style connectors with copper terminals can also be fitted, for use with non-thermocouple inputs. For
such channels the recorder is pre-configured as: Function = Linear, Input range = 0 to 1 Volt.
10.4.2 Wiring
SUPPLY VOLTAGE
Caution
Before powering the recorder, check that the supply voltage, to be applied, lies within the range specified
on the serial number label at the rear of the recorder.
As shown in Figure 10.4.2a, below, the line supply is terminated using an IEC connector at the rear of the case. A
socket is required to mate with the plug fitted at the recorder. Minimum recommended conductor size is 16/0.2
(0.5mm2) (20AWG).
SIGNAL WIRING
Signal wiring consists of connecting the transducer wires into the correct type of plug, and inserting the plugs into the
relevant socket at the rear of the recorder.
Figure 10.4.2a shows the arrangement of the connectors at the rear panel. Figure 10.4.2b shows Thermocouple wiring
details, and Figure 10.4.2c shows the wiring between the portable case rear panel and the recorder.
8 1 Supply E
1 22
Con7 Con8 Con9 Con10 Con11 Con12
HA028121 Options
Issue 5 Nov 04 Page 97
GRAPHICS RECORDER/DATA ACQUISITION AND LOGGING UNIT: OPTIONS MANUAL
THERMOCOUPLE WIRING
+ wire
wire
Options HA028121
Page 98 Issue 5 Nov 04
GRAPHICS RECORDER/DATA ACQUISITION AND LOGGING UNIT: OPTIONS MANUAL
Portable case
Recorder back panel
Ethernet
connector
1
1
2
Option board 1
2
3
3
4
4
5
5
6
6
7
7
8
Options 8
9
9
connector 10
10
11
11
12
12
13
13
14
Option board 2
14
15
15
16
16
17
17
18
18
19
19
20
20
21
21
22
22
1
+ 2 V+ Input board 2
CON 7 - 3 V-
4 I
+ 5 V+
CON 8 - 6 V-
7 I
+ 8 V+
CON 9 - 9 V-
10 I
11
CJ
12
sensor
+ 13 V+
CON 10 - 14 V-
15 I
+ 16 V+
CON 11 - 17 V-
18 I
+ 19 V+
CON 12 - 20 V-
21 I
22
1
+ 2 V+ Input board 1
CON 1 - 3 V-
4 I
+ 5 V+
CON 2 - 6 V-
7 I
+ 8 V+
CON 3 - 9 V-
10 I
11
CJ
12
sensor
+ 13 V+
CON 4 - 14 V-
15 I
+ 16 V+
CON 5 - 17 V-
18 I
+ 19 V+
CON 6 - 20 V-
21 I
22
Safety isolation
DC to 65 Hz: BS EN61010 (Installation category II; Pollution degree 2 (see page 3 for definitions)
Channel to channel: S.E.L.V. (i.e. 30V dc or RMS) to earth
Channel to ground S.E.L.V. (i.e. 30V dc or RMS) to earth
HA028121 Options
Issue 5 Nov 04 Page 99
GRAPHICS RECORDER/DATA ACQUISITION AND LOGGING UNIT: OPTIONS MANUAL
Some of the portable case options described in this manual can be ordered for use with 24V (nom.) supply voltages.
In such cases, the supply voltage part of the wiring diagrams is replaced with that shown in figure 10.5a unless other-
wise stated. The low voltage supply is terminated by a three pin plug, as shown in figure 10.5b.
3 Brown
20 to 54V dc or Recorder power
20 to 42V ac 2 Blue supply
(45 to 400 Hz RMS)
Earth 1 0V (Violet)
Earth
Chassis
Ground
24V Earth 0V
Supply connector:
8 1
20 to 52Vdc or
Ethernet connector 20 to 42V(RMS)
(RJ45)
1 22
Option board 3 Option board 4
22
Input channels 7 to 12
V V I V V I V V I V V I V V I V V I
+ + + + + +
1 Ch7 Ch8 Ch9 Ch10 Ch11 Ch12 22
Input channels 1 to 6
V V I V V I V V I V V I V V I V V I
+ + + + + +
1 Ch1 Ch2 Ch3 Ch4 Ch5 Ch6 22
Options HA028121
Page 100 Issue 5 Nov 04
GRAPHICS RECORDER/DATA ACQUISITION AND LOGGING UNIT: OPTIONS MANUAL
11 EMAIL
This option allows e-mails to be sent by the instrument to one or more recipients. The user can enter 10 recipient e-
mail addresses in each of five mailing lists, giving a maximum of 50 addresses, 10 of which can be sent to at any one
time. A Recipient can appear in as many lists as required.
A number of e-mails can be set up, but which of these e-mails is sent, is defined during job or Event Button configura-
tion. Any function capable of triggering a job, can cause any of the available e-mails to be sent. The number of e-
mails available depends on the instrument model.
As well as a ‘Subject’, and the body text, each e-mail can include one of the messages set up in ‘Message Configura-
tion’, and can thus include embedded values, alarm status, batch status etc., as described in section 4.3 of the User
Guide.
The figure below shows the e-mail configuration page (using fictitious names for email server/address information).
Text
Include Message
Message 3) {1},{2},{3},{4} Select Message Number
Apply Discard
HA028121 Options
Issue 5 Nov 04 Page 101
GRAPHICS RECORDER/DATA ACQUISITION AND LOGGING UNIT: OPTIONS MANUAL
This subsection contains details of the parameters that appear in the E-mail configuration page (figure 11.1 above).
Figure 11.2 (below) may also be referred-to for further explanation.
Mail Server Enter the name of the mail server or IP address here. This is the destination to which e-mails
are sent, for subsequent delivery.
Port Number This is the port number used for SMTP by the servers. Most servers use port 25 for this
function, and this value should be changed from the default only by experienced personnel.
Sender For DNS operation, this is a combination of the Local Host and Domain entries set up in the
‘Network/Name’ area of configuration described in section 4.5 of the user guide.
If Fixed I.P. Address is selected, the I.P. Address appears instead.
The unit accesses the ‘Sender’ information automatically, and it cannot be edited here. The
‘Sender’ is placed in the ‘From:’ part of the e-mail header.
Errors To An e-mail address to which any error messages can be sent for display etc. The instrument
itself cannot receive e-mails and so is unable to display (for example ‘undeliverable’) mes-
sages itself. An entry in this field must be made. The same address may be used for any
number of instruments.
Retry time The product tries repeatedly (until successful) to dispatch the e-mail until the ‘Retry time’ has
expired. If the e-mail has not been sent within this period, it is deleted, and a ‘General’
message is generated.
Recipient List Allows a list to be chosen for entry of recipient e-mail addresses
Descriptor Allows a name to be entered for the selected list.
Rcpt1 to Rcpt10 These fields allow 10 recipients’ e-mail addresses to be entered for the selected list. The first
valid address appears in the ‘To:’ part of the e-mail header; subsequent valid addresses appear
in the ‘Cc:’ part of the e-mail header.
Email Number Allows an e-mail to be selected for configuration. The number of e-mails available depends
on the instrument model.
Descriptor Allows a descriptor to be entered for the e-mail. This appears in the list of e-mails when
setting up a job, and also in the message log.
Protocol Choose one of ‘SMPT (Email)’, ‘SMS (Subject Only)’ and ‘SMS (Body Only)’. Section 11.3,
below gives some details of the application of the SMS protocol in this instrument.
SMPT (Email).
Selecting this protocol allows both a Subject and Body text to be entered.
SMS (Subject Only).
Selecting this protocol allows a subject to be entered, but the entry field for the body text is
not presented for use. Any text previously entered here, whilst another protocol was
selected, is lost.
SMS (Body Only)
Selecting this protocol allows Body text to be entered, but the Subject field is not dis-
played. Any text previously entered as a Subject, whilst another protocol was selected, is
lost.
Subject Allows the entry of up to 100 characters to appear in the ‘Subject:’ part of the e-mail header.
The field does not appear if ‘SMS Body Only’ is selected as the Protocol.
Text Allows the entry of up to 240 characters to appear as the body of the e-mail. The field does
not appear if ‘SMS Subject Only’ is selected as the Protocol. Also referred to as ‘Body Text’.
Include message If this checkbox in enabled, one of the messages in the ‘Message Configuration’ area can be
selected to appear below the body text in the e-mail.
Options HA028121
Page 102 Issue 5 Nov 04
GRAPHICS RECORDER/DATA ACQUISITION AND LOGGING UNIT: OPTIONS MANUAL
'Subject' entry
'Text' entry
Body
(body text)
Message
(if 'Include message' checked)
The figure above shows that the e-mail is in two distinct parts, the header (grey area) and the body (white area).
The header contains details of the sender, the recipient(s), the subject and the time and date.
Note: The time and date may be local to the generating instrument, or local to the recipient, depending on the
recipient’s mail host configuration
The header is important in the prevention of ‘spamming’. The instrument adheres to the RFC2822 standard with re-
spect to e-mail headers. Some servers are stricter than others, and it is not guaranteed that an e-mail generated by the
instrument will not be interpreted as a spam message by the receiving server.
From:
This contains either the ‘Local Host’ name (as defined in Network/Name Setup) and mailserver address, or the IP
address if a fixed IP address is selected in Network/Address settings. See section 4.5 of the User Guide for details of
the Network key.
To:
The first valid recipient address in the selected list.
CC:
The remaining valid addresses in the recipient list
Subject:
Contains the subject text entred during configuration. Empty if ‘SMS Body’ selected as Protocol
HA028121 Options
Issue 5 Nov 04 Page 103
GRAPHICS RECORDER/DATA ACQUISITION AND LOGGING UNIT: OPTIONS MANUAL
This contains the body text, along with any appended messages. In the example above the message has the embedded
values of Instrument name, Instrument number, channel 1 alarm 1 status, as implied by the body text.
11.3 OPERATION
1. E-mails are generated either by job or (if the relevant options are fitted) by operation of an Event Button from a
User screen (see note below).
2. Every time the sending of an e-mail is requested, a ‘General’ note is generated and appears in the message log for
all groups. The format is: Date, Time Sent <e-mail descriptor> to List N, where <e-mail descriptor> represents
the descriptor entered in the configuration page for the e-mail, and ‘List N’ is the recipient list to whom the e-
mail was sent.
3. Access to e-mails is restricted to users with ‘Full Configuration’ permission.
4. Signing/Authorizing restrictions can be applied only to e-mails generated by Event button operation, as part of
the Event button’s configuration (section 4.3 of the user guide).
5. The instrument implements the Simple Message Transfer Protocol (SMTP), incorporating Multipurpose Internet
Mail extensions.
6. The instrument does not implement the Short Message Service (SMS) protocol, though it is able to send SMS
messages to a mobile phone via an appropriate server or gateway. As some servers/gateways use the ‘subject’ as
the SMS message, and others use the body text, these alternatives are provided for in the Protocol pick list in the
Configuration page (see section 11.1).
7. A new event source ‘Email fail’ can be used to trigger a job list should an e-mail send failure occur.
Note: User screens and Event button options are not supported by all models.
Options HA028121
Page 104 Issue 5 Nov 04
GRAPHICS RECORDER/DATA ACQUISITION AND LOGGING UNIT: OPTIONS MANUAL
Both 100mm and 180mm recorders can be supplied with locking devices on their disk/PC card access flaps. The two
versions are shown below.
Note: The IP rating for recorders fitted with locks is reduced to IP20.
Door lock
Disk/PC card
access flap
Door lock
HA028121 Options
Issue 5 Nov 04 Page 105
GRAPHICS RECORDER/DATA ACQUISITION AND LOGGING UNIT: OPTIONS MANUAL
Options HA028121
Page 106 Issue 5 Nov 04
GRAPHICS RECORDER/DATA ACQUISITION AND LOGGING UNIT: OPTIONS MANUAL
INDEX
Symbols C (Cont.)
10 to the power maths function ........................................ 46 Colour
3D effect ............................................................................ 25 Alarms ........................................................................... 25
Backgrounds ................................................................. 25
A Channel ......................................................................... 25
Style .............................................................................. 26
Add .................................................................................... 41 Comma separated variable (CSV) format. See User Guide
Key ................................................................................ 18 Comms
Maths function .............................................................. 45 Maths function .............................................................. 45
Advanced Component
Edit level ................................................................. 18, 42 Definitions ..................................................................... 31
Parameters ................................................................... 25 Info on screen ......................................................... 18, 42
Alarm marks colour ........................................................... 25 Compressibility factor .................................................51, 52
Always ............................................................................... 29 Config version ..................................................................... 7
Apply key .......................................................................... 18 Configuration
Arc Batch ............................................................................... 8
Angle ............................................................................. 23 Maths channels ............................................................. 44
Definition ....................................................................... 38 Totaliser ........................................................................ 72
Height ............................................................................ 23 Continuous batch selection ................................................ 8
Width ............................................................................. 23 Copy
Auditor pack. See User guide Maths function .............................................................. 46
Screen ........................................................................... 41
B Counter ............................................................................. 77
Configuration data
Background colour ............................................................ 23 32-bit data (MODBUS) .................................... 79 to 81
Bargraph Configuration data (Modbus) ............................... 78 to 81
Channel ......................................................................... 32 Run-time data
Group 32-bit (MODBUS) ...................................................... 80
Horizontal .................................................................. 31 Run-time data (MODBUS) ................................... 79 to 81
Vertical ...................................................................... 31 Creating a user screen ..................................................... 15
Style .............................................................................. 25 CSV file format. See User Guide
Basic edit level ............................................................ 18, 42 Cutoff (High/Low) .............................................................. 72
Basic/Advanced selection .......................................... 18, 42
Batch D
As event source ............................................................ 12
Configuration .................................................................. 8 Decimal
Places ........................................................................... 26
Counter initiation ........................................................... 12
Scale ............................................................................. 29
Job initiation .................................................................. 12
Del ..................................................................................... 41
Message display ............................................................ 11
Delete key ......................................................................... 18
Modbus initiation ........................................................... 12
Deploy ............................................................................... 41
Operation ...................................................................... 10
Descriptor
Operator initiation ......................................................... 10 E-mail .......................................................................... 102
Best Fit Font ..................................................................... 25 Font ............................................................................... 26
Button Text ........................................................................ 23 Group minimum ............................................................ 68
Recipient list ............................................................... 102
C Dialogue action ................................................................. 32
Channel Discard .............................................................................. 41
Bargraph ....................................................................... 32 Key ................................................................................ 18
Data .............................................................................. 32 Display
Max/Min/Average .......................................................... 47 Alarms ........................................................................... 26
Numeric ......................................................................... 32 Bargraph ....................................................................... 27
Run-time data Descriptor ..................................................................... 27
32-bit (MODBUS) ............................................. 71 to 73 Messages ...................................................................... 27
User screen parameter ................................................. 23 Pens .............................................................................. 27
Channel cycle time ........................................................... 25 Units .............................................................................. 27
Circular charts. See User Guide Divide ................................................................................ 45
Close ................................................................................. 41 Door lock option .............................................................. 105
Draw
Edge .............................................................................. 23
Order ............................................................................. 23
HA028121 Options
Issue 5 Nov 04 Page 107
GRAPHICS RECORDER/DATA ACQUISITION AND LOGGING UNIT: OPTIONS MANUAL
E H
e to the power maths function .......................................... 47 Height ................................................................................ 24
E-mail High Select ....................................................................... 46
Access ........................................................................ 104 Horizontal
Appearance ................................................................ 103 Alignment ...................................................................... 27
Generation .................................................................. 104 Bargraph ....................................................................... 29
Message ..................................................................... 104 Faceplate ...................................................................... 29
Number ....................................................................... 102 Facplate ........................................................................ 27
Option. See Section 11 Grid total ....................................................................... 27
Edit Minor Divisions ............................................................. 27
Level ....................................................................... 18, 42 Trend mode ................................................................... 31
Parameter ..................................................................... 23 HTM2010 Quarterly Test kit .............................................. 95
Elapsed time format .......................................................... 48
Enable I
Batch ............................................................................... 8
Identifier ............................................................................ 24
Error messages (User screens) ....................................... 43
Image ................................................................................ 33
Errors To (E-mail) ........................................................... 102
File ................................................................................ 24
Event
Import ................................................................................ 41
Button ............................................................................ 23
An image ....................................................................... 33
Size, shape etc. ........................................................ 33
Key ................................................................................ 18
Inputs ................................................................... 83 to 84
Importing
Source, Batch ............................................................... 12
User screens ................................................................. 14
Export ................................................................................ 41
Include message ............................................................ 102
Key ................................................................................ 18
Exporting J
User screens ................................................................. 14
Jobs
F Disable totaliser ............................................................ 73
Preset totaliser .............................................................. 73
Faceplate
Location ........................................................................ 27 L
Style .............................................................................. 27
Feature .............................................................................. 23 Last error .......................................................................... 24
Field 1 to 6 (Batch) ............................................................. 8 Line ................................................................................... 37
Fill Area ............................................................................. 23 Thickness ...................................................................... 27
Font Style .......................................................................... 27 Lock option ..................................................................... 105
Foreground Colour ........................................................... 23 Log maths functions ......................................................... 47
Function (Maths) ............................................................... 45 Log Scales. See User guide
Fuse (Transmitter power supply) ...................................... 85 Low Select ........................................................................ 46
Fvalue ............................................................................... 46
Equation ........................................................................ 49 M
Mail Server ...................................................................... 102
G Management. See User guide
Gas constant ............................................................... 50, 52 Mass flow
Goto Canvas ..................................................................... 41 Linear ...................................................................... 46, 50
Goto Editor ........................................................................ 41 Saturated Steam ........................................................... 56
Grid Square root ............................................................. 46, 52
Line colour Maths channel
Major ......................................................................... 27 Channel data (Modbus) ....................................... 69 to 73
Minor ......................................................................... 28 Configuration
Group 32-bit data (MODBUS) .................................... 70 to 73
Average ......................................................................... 45 Function selection ......................................................... 45
Horizontal Bargraph ...................................................... 31 Modbus channel addressing ........................................ 69
Latched maximum ........................................................ 46 Run-time data (MODBUS) ................................... 70 to 73
Latched minimum ......................................................... 46 Mean kinetic temperature ................................................. 54
Maximum ...................................................................... 45 Measuring units ................................................................ 43
Minimum ....................................................................... 45 Messages
Number ......................................................................... 24 Auditor pack, Batch ........................................................ 7
Numeric display ............................................................ 32 Batch, Initiation ............................................................. 10
Trend ............................................................................. 31 Colour ........................................................................... 28
Vertical bargraph .......................................................... 31
Options HA028121
Page 108 Issue 5 Nov 04
GRAPHICS RECORDER/DATA ACQUISITION AND LOGGING UNIT: OPTIONS MANUAL
M (Cont.) P (Cont.)
Minimum Preset
Channel Descriptor ....................................................... 68 Counter ......................................................................... 77
Height ............................................................................ 28 Totaliser ........................................................................ 72
Width ............................................................................. 28 Pressure unit conversion .................................................. 57
MKT maths function .................................................... 46, 54 Properties page (User screens) ....................................... 17
Group ...................................................................... 46, 60 Protocol ........................................................................... 102
Modulus maths function ................................................... 47 PV Format ......................................................................... 48
Move Screen ..................................................................... 41
Multiply maths function ..................................................... 45 Q
N Quick Build User Screen Features ................................... 40
Quick entry to user screen edit .................................. 18, 42
N Value ............................................................................. 24
Name Files by Batch .......................................................... 9 R
Navigation action .............................................................. 32 Rate-of-change
New ................................................................................... 41 Maths function ........................................................47, 61
User Screen key ........................................................... 18 Rcpt1 to Rcpt10 .............................................................. 102
No Text .............................................................................. 29 Recipient List .................................................................. 102
Nominal height/width ........................................................ 28 Rectangle .......................................................................... 34
Notes ................................................................................. 28 Relative Humidity ........................................................47, 63
Number Remote viewer with User Screens ................................... 39
Of Batch Messages ........................................................ 8 Retry Time ...................................................................... 102
Of columns .................................................................... 28 Reversed colour ............................................................... 28
Of rows .......................................................................... 28 Revert ............................................................................... 41
Numeric Rolling Average ...........................................................46, 54
Width ............................................................................. 28 Round Rectangle .............................................................. 34
O S
O2 Correction .............................................................47, 62 Sample and hold ............................................................... 46
On Saturated Steam
New clear ........................................................................ 9 Heat Consumed ............................................................ 59
Start/Stop Log ................................................................. 9 Heat Flow ...................................................................... 58
Visibility change ............................................................ 28 Mass flow ...................................................................... 56
Operator Button ................................................................ 33 Save .................................................................................. 41
Oval ................................................................................... 37 Scale
Oxygen correction ...................................................... 47, 62 Style .............................................................................. 29
Oxygen potential ......................................................... 64, 66 Scale Divisions
Major/Minor ................................................................... 28
P Scope .................................................................................. 8
Screen
Page Title .......................................................................... 24 Number ......................................................................... 24
Paint Size ............................................................................... 43
All .................................................................................. 28 Screen builder option ............................................... 13 to 43
Background ................................................................... 28 Security Revision ................................................................ 7
Paste ................................................................................. 41 Sender ............................................................................ 102
Period scaler ..................................................................... 73 Show Title Bar ................................................................... 24
Pinout SMPT (Email) ................................................................. 102
Transmitter power supply ............................................. 88 SMS ................................................................................ 104
Pixels (Absolute/relative) .................................................. 15 (Body Only) ................................................................. 102
Polygon ............................................................................. 36 (Subject Only) ............................................................. 102
Polyline ............................................................................. 35 SMTP .............................................................................. 104
Polynomial .................................................................. 46, 48 Specific gas constant .................................................. 50, 52
Port ................................................................................. 102 Specification
Portable case Event inputs .................................................................. 84
Basic option .................................................................. 91 Pressure transducer ..................................................... 96
Basic option with TRS .................................................. 93 Square root (maths function) ............................................ 46
Dimensions ................................................................... 90 Start
HTM2010 Test kit .......................................................... 95 Angle ............................................................................. 24
Low supply voltage ..................................................... 100 Start/Stop batch selection .............................................. 8
Thermocouple option .................................................... 97 Stopwatch ......................................................................... 45
Positioning Subject ............................................................................ 102
Grid ............................................................................... 42 Subtract ............................................................................. 45
Tip ................................................................................. 42 Switch ............................................................................... 46
HA028121 Options
Issue 5 Nov 04 Page 109
GRAPHICS RECORDER/DATA ACQUISITION AND LOGGING UNIT: OPTIONS MANUAL
T V
Text .......................................................................... 24, 102 Value
User screens ................................................................. 34 Changes ........................................................................ 29
Thermocouple (Types J, K and T colours) ....................... 98 Font ............................................................................... 29
Time Vertical
Marker Alignment ...................................................................... 29
Colour ....................................................................... 29 Bargraph ....................................................................... 29
Interval ...................................................................... 29 Grand total .................................................................... 30
Timer Option ..................................................................... 81 Minor Divisions ............................................................. 30
Timestamp maths function ............................................... 47 Trend mode ................................................................... 31
Totaliser Visible
Configuration Alarm ............................................................................. 30
32-bit data (MODBUS) ............................................. 75 Channel ......................................................................... 30
Configuration data (Modbus) ........................................ 74 Operator ........................................................................ 30
Equation ........................................................................ 72 Value ............................................................................. 30
Run-time data
32-bit (MODBUS) ...................................................... 76 W
Run-time data (MODBUS) ............................................ 75
When visible ..................................................................... 30
Transmitter Power Supply
Width ................................................................................. 24
Isolated ......................................................................... 85
Wiring
Non-isolated .................................................................. 88
Event inputs .................................................................. 83
Pinout ........................................................................ 88
Transmitter power supply ............................................. 89
Trend
Isolated ..................................................................... 87
Padding ......................................................................... 29
Thickness ...................................................................... 29 X
U X points ............................................................................. 24
X position .......................................................................... 24
Units .................................................................................. 15
Conversion (Pressure) .................................................. 57 Y
Font ............................................................................... 29
Scaler ............................................................................ 73 Y points ............................................................................. 24
Update when ..................................................................... 29 Y position .......................................................................... 24
Use
Counter batch number .................................................... 9 Z
Last properties .............................................................. 42 Z Factor ....................................................................... 51, 52
Text batch number .......................................................... 9 Zirconia Probe .................................................................. 64
User defined descriptor .................................................... 68 Zirconia probe ................................................................... 47
Auditor Pack ....................................................................... 1
CSV file format. See User Guide
Circular trend option. See User Guide
Log Scales .......................................................................... 1
Management ....................................................................... 1
User guide .......................................................................... 1
User screens ............................................................ 13 to 43
Advanced parameters .................................................. 25
Basic parameters .......................................................... 23
Basic/Advanced selection ...................................... 18, 42
Component info on screens ................................... 18, 42
Component list .............................................................. 16
Creation ........................................................................ 15
Full versus lite ............................................................... 13
Importing/Exporting ...................................................... 14
Key descriptions ........................................................... 18
Properties page ............................................................ 17
Quick entry .............................................................. 18, 42
Options HA028121
Page 110 Issue 5 Nov 04
Inter-Company sales and service locations
Australia Germany Netherlands
Eurotherm Pty. Limited. Eurotherm Deutschland GmbH Eurotherm BV,
Unit 10. Ottostraße 1, Genielaan 4,
65549 Limburg 2404CH Alphen aan den Rijn,
40 Brookhollow Avenue, Tel: +49 (0) 64 31/2 98 - 0
Baulkham Hills, Fax: +49 (0) 64 31/2 98 - 1 19 The Netherlands
NSW 2153 e-mail:[email protected] Telephone: 31 172 411 752
Telephone: 61 2 9634 8444 http://www.eurotherm-deutschland.de Fax: 31 172 417 260
Fax: 61 2 9634 8555 e-mail: [email protected]
e-mail: [email protected] Great Britain http://www.eurotherm.nl
http://www.eurotherm.com.au Eurotherm Limited, Norway
Faraday Close, Eurotherm A/S,
Austria Worthing, Vollsveien 13D
West Sussex BN13 3PL 1366 Lysaker,
Eurotherm GmbH
Telephone: +44 (0)1903 695888 Postboks 227
Geiereckstraße 18/1,
Fax: +44 (0)1903 695666 NO-1326 Lysaker
A1110 Wien,
e-mail:[email protected] Norway,
Telephone: 43 1 798 76 01
or: [email protected] Telephone: 47 67 592170
Fax: 43 1 798 76 05 http://www.eurotherm.co.uk Fax: 47 67 118301
e-mail:[email protected]
http://www.eurotherm.no
http://www.eurotherm.at Hong Kong Spain
Eurotherm Limited, Eurotherm España SA,
Belgium and Luxemburg Unit D, 18/F Gee Chang Hong Centre, Pol. Ind. De Alcobendas,
Eurotherm S.A./N.V. 65, Wong Chuk Hang Road, Calle de la Granja 74,
Rue du Val-Notre-Dame 384, Aberdeen. 28108 Alcobendas,
4520 Moha (Huy) Telephone: 852 2873 3826 Madrid.
Belgium Fax: 852 2870 0148 Telephone: 34 91 661 60 01
Telephone: 32 (0) 85 274080 e-mail:[email protected] Fax: 34 91 661 90 93
Fax: 32 (0) 85 274081 http://www.eurotherm.es
e-mail: [email protected] India
http://www.eurotherm.nl Eurotherm DEL India Limited, Sweden
152, Developed Plots Estate, Eurotherm AB,
Denmark Perungudi, Lundavägen 143,
Eurotherm Danmark A/S Chennai 600 096, S-21224 Malmö.
Finsensvej 86, Telephone: 91 44 4961129 Telephone: 46 40 38 45 00
DK 2000 Fredriksberg, Fax: 91 44 4961831 Fax: 46 40 38 45 45
e-mail: [email protected]
Telephone: +45 (38) 871622 e-mail:[email protected]
http://www.eurothermdel.com
Fax: +45 (38) 872124 http://www.eurotherm.se
e-mail: [email protected]
Italy
Switzerland
Eurotherm SpA,
Finland Eurotherm Produkte (Schweiz) AG,
Via XXIV Maggio,
Eurotherm Finland, Schwerzistraße, 20,
I-22070 Guanzate,
Aurakatu 12A, CH-8807 Freienbach.
Como.
FIN-20100 Turku Telephone: 41 55 415 44 00
Telephone: 39 031 975111
Telephone: 358 2 25 06 030 Fax: 41 55 415 44 15
Fax: 39 031 977512
Fax: 358 2 25 03 201 e-mail:[email protected]
e-mail:[email protected]
http://www.eurotherm.ch
http://www.eurotherm.it
France
Eurotherm Automation Division Chessell Korea United States of America
Parc d'Affaires, Eurotherm Korea Limited, Eurotherm Recorders Inc.
6, Chemin des Joncs, J- Building 741-F Miller Drive
BP55 402-3 Leesburg
F - 69574 Dardilly, CEDEX Poongnab-Dong, VA 20175-8993
Telephone: 33 0 4 78 66 55 20 Songpa-Ku Telephone: 1 703 669 1342
Seoul, 138-040 Fax: 1 703 669 1307
Fax: 33 0 4 78 66 55 35
Telephone: 82 2 478 8507 e-mail (Sales): [email protected]
e-mail: [email protected]
Fax: 82 2 488 8508 e-mail (Technical): [email protected]
http://www.eurotherm.tm.fr
http://www.chessell.com
E U ROT H E R M
EUROTHERM LIMITED
Faraday Close, Durrington, Worthing, West Sussex, BN13 3PL
Telephone: 01903 695888 Facsimile: 01903 695666
e-mail: [email protected]
Website: http://www.eurotherm.co.uk