Current Transducer HTFS 200 ... 800-P IP N = 200 ...

800 A
For the electronic measurement of currents: DC, AC, pulsed...,
with galvanic separation between the primary circuit and the secondary
circuit.

All data are given with RL = 10 kΩ


Electrical data
Features
Primary nominal Primary current Type
RMS current measuring range ● Hall effect measuring principle
IP N (A) IP M (A) ● Galvanic separation between
200 ±300 HTFS 200-P primary and secondary circuit
400 ±600 HTFS 400-P ● Low power consumption
600 ±900 HTFS 600-P ● Single power supply +5 V
800 ±1200 HTFS 800-P ● Ratiometric offset
● Insulating plastic case recognized
Uout Output voltage (Analog) @ IP Uref ±(1.25 ∙ IP/ IP N ) V
according to UL 94-V0
IP = 0 Uref ±0.025 V
● Fixation by M3 nuts and screws
Uref Reference voltage 1)
Output voltage 1/2 UC ±0.025 V
● TA = ‒40 °C ... +105 °C.
Uref Output impedance typ. 200 Ω
Uref Load impedance ≥ 200 kΩ Advantages
RL Load resistance ≥ 2 kΩ
Rout Output internal resistance < 5 Ω ● Small size and space saving
CL Load capacitance = 4.7 nF ● Only one design for wide current
UC Supply voltage (±5 %) 5 V ratings range
IC Current consumption @ UC = 5 V 19 (typ) mA ● High immunity to external
25 (max) mA interference
● Uref IN/OUT.
Accuracy - Dynamic performance data
Applications
εtot Total error 2) @ IP N, TA = 25° C ≤ ±1 %
● Forklift drives
εL Linearity error 0 ... 1.5 × IP N ≤ ±0.5 %
● AC variable speed drives
TCUO E Temperature coefficient of UO E @ IP = 0 ≤ ±0.1 mV/K
● Static converters for DC motor
TCUref Temperature coefficient of Uref ≤ ±190 ppm/K
drives
TCS Temperature coefficient of Uout ≤ ±420 ppm/K
● Battery supplied applications
UO M Magnetic offset voltage @ IP = 0 and specified RM, ● Uninterruptible Power Supplies
after an overload of 3 × IP N DC < ±0.5 % (UPS)
Uno RMS noise voltage referred to primary (DC ... 20 MHz) < 40 mVpp ● Switched Mode Power Supplies
tD 10 Delay time to 10 % of the final output value for IP N step < 2 µs (SMPS)
tD 90 Delay time to 90 % of the final output value for IP N step < 3.5 µs ● Power supplies for welding
di/dt di/dt accurately followed >100 A/µs applications.
BW Frequency bandwidth (‒3 dB) 3) DC ... 240 kHz
Application domain
Notes: 1) It is possible to overdrive Uref with an external reference ● Industrial.
voltage between 0.5 - 2.65 V
2)
Excluding offset and magnetic offset voltage
3)
Small signal only to avoid excessive heatings of the magnetic core.

N° 74.96.44.000.0, N° 74.96.48.000.0, N° 74.96.52.000.0, N° 74.96.56.000.0 Page 1/4

16May2024/Version 13 LEM reserves the right to carry out modifications on its transducers, LEM International SA
Route du Nant-d’Avril, 152
in order to improve them. 1217 Meyrin
www.lem.com
Current Transducer HTFS 200 ... 800-P

General data
TA Ambient operating temperature ‒40 ... +105 °C
TA st Ambient storage temperature ‒40 ... +105 °C
m Mass 60 g
Standard EN 50178: 1997

Insulation coordination
Ud RMS voltage for AC insulation test, 50 Hz, 1 min 2.5 kV
Ut Partial discharge RMS test voltage (qm< 10 pC) > 1 kV
UNi Impulse withstand voltage 1.2/50 µs 4 kV
Min
dCp Creepage distance > 4 mm
dCI Clearance distance > 4 mm
CTI Comparative Tracking Index (group IIIa) > 220

Applications examples

EN 50178 IEC 61010-1

dCp, dCI, UNi Rated insulation voltage Nominal voltage


Basic insulation 300 V 300 V
Reinforced insulation 150 V 150 V

According to EN 50178 and IEC 61010-1 standards and following conditions:


● Over voltage category OV 3
● Pollution degree PD2
● Non-uniform field

Safety
This transducer must be used in limited-energy secondary circuits according to
IEC 61010-1.

This transducer must be used in electric/electronic equipment with respect to


applicable standards and safety requirements in accordance with the manufacturer’s
operating instructions.

Caution, risk of electrical shock


When operating the transducer, certain parts of the module can carry hazardous
voltage (eg. primary busbar, power supply). Ignoring this warning can lead to injury
and/or cause serious damage.
This transducer is a build-in device, whose conducting parts must be inaccessible
after installation. A protective housing or additional shield could be used.
Main supply must be able to be disconnected.

Page 2/4

16May2024/Version 13 LEM reserves the right to carry out modifications on its transducers, LEM International SA
Route du Nant-d’Avril, 152
in order to improve them. 1217 Meyrin
www.lem.com
HTFS measuring range with external Uref

800

600

400 Upper limit: IP = −160 × Uref + 720 (Uref = 0.5 ... 2.65 V)
IP (A)

200

0 Lower limit: IP = −160 × Uref + 80 (Uref = 0.5 ... 2.65 V)


-200
IP N = 200
-400
0.5 1 1.5 2 2.5

Uref (V)

1200

800
Upper limit: IP = 864 (Uref = 0.5 ... 1.8 V)
400
Upper limit: IP = −320 × Uref + 1440 (Uref = 1.8 ... 2.65 V)
IP (A)

-400
Lower limit: IP = −320 × Uref + 160 (Uref = 0.5 ... 2.65 V)
IP N = 400
-800
0.5 1 1.5 2 2.5
Uref (V)

1600

1200

800 Upper limit: IP = 1200 (Uref = 0.5 ... 2.0 V)


400 Upper limit: IP = −480 × Uref + 2160 (Uref = 2 ... 2.65 V)
IP (A)

-400
Lower limit: IP = −480 × Uref + 240 (Uref = 0.5 ... 2.65 V)
-800 IP N = 600
-1200
0.5 1 1.5 2 2.5

Uref (V)

1500

1000
Upper limit: IP = 1200 (Uref = 0.5 ... 2.625 V)
500 Upper limit: IP = −640 × Uref + 2880 (Uref = 2.625 ... 2.65 V)
IP (A)

-500 Lower limit: IP = −640 × Uref + 320 (Uref = 0.5 ... 2.4 V)
-1000 Lower limit: IP = −1200 (Uref = 2.4 ... 2.65 V)
IP N = 800
-1500
0.5 1 1.5 2 2.5

Uref (V)

Page 3/4

16May2024/Version 13 LEM reserves the right to carry out modifications on its transducers, LEM International SA
Route du Nant-d’Avril, 152
in order to improve them. 1217 Meyrin
www.lem.com
Dimensions HTFS 200 ... 800-P (in mm)

IP

Connection

Uref

Uout
IP

UC

Mechanical characteristics Remarks


● General tolerance ±0.2 mm ● Uout is positive when IP flows in the direction of arrow.
● Mounting to PCB 4 × M3 (not supplied) ● Temperature of the primary conductor should not exceed
Recommended PCB hole ⌀ 5.3 mm 120 °C.
● Fastening torque 0.6 N·m ● Must be mounted using PCB holes
● Connection to secondary 4 pins 0.5 × 0.25 mm ● Installation of the transducer must be done, unless
Recommended PCB hole ⌀ 0.7 mm otherwise specified on the datasheet, according to LEM
Transducer Generic Mounting Rules. Please refer to LEM
document N°ANE120504 available on our Web site:
https://www.lem.com/en/file/3137/download/

Page 4/4

16May2024/Version 13 LEM reserves the right to carry out modifications on its transducers, LEM International SA