Brocade SAN B5100 HardwareManual
Brocade SAN B5100 HardwareManual
03 March 2014
Brocade 5100
Hardware Reference Manual
© 2014, Brocade Communications Systems, Inc. All Rights Reserved.
Brocade, the B-wing symbol, Brocade Assurance, ADX, AnyIO, DCX, Fabric OS, FastIron, HyperEdge, ICX, MLX, MyBrocade, NetIron,
OpenScript, VCS, VDX, and Vyatta are registered trademarks, and The Effortless Network and the On-Demand Data Center are trademarks
of Brocade Communications Systems, Inc., in the United States and in other countries. Other brands and product names mentioned may be
trademarks of others.
Notice: This document is for informational purposes only and does not set forth any warranty, expressed or implied, concerning any
equipment, equipment feature, or service offered or to be offered by Brocade. Brocade reserves the right to make changes to this document
at any time, without notice, and assumes no responsibility for its use. This informational document describes features that may not be
currently available. Contact a Brocade sales office for information on feature and product availability. Export of technical data contained in
this document may require an export license from the United States government.
The authors and Brocade Communications Systems, Inc. assume no liability or responsibility to any person or entity with respect to the
accuracy of this document or any loss, cost, liability, or damages arising from the information contained herein or the computer programs that
accompany it.
The product described by this document may contain open source software covered by the GNU General Public License or other open
source license agreements. To find out which open source software is included in Brocade products, view the licensing terms applicable to
the open source software, and obtain a copy of the programming source code, please visit http://www.brocade.com/support/oscd.
Contents
Preface..................................................................................................................................... 3
Document conventions......................................................................................3
Text formatting conventions.................................................................. 3
Command syntax conventions.............................................................. 3
Notes, cautions, and warnings.............................................................. 4
Brocade resources............................................................................................ 5
Getting technical help........................................................................................5
Document feedback.......................................................................................... 6
Index.................................................................................................................................... 45
● Document conventions......................................................................................................3
● Brocade resources............................................................................................................ 5
● Getting technical help........................................................................................................5
● Document feedback.......................................................................................................... 6
Document conventions
The document conventions describe text formatting conventions, command syntax conventions, and
important notice formats used in Brocade technical documentation.
Format Description
bold text Identifies command names
Identifies keywords and operands
Identifies the names of user-manipulated GUI elements
Identifies text to enter at the GUI
Convention Description
bold text Identifies command names, keywords, and command options.
italic text Identifies a variable.
Convention Description
value In Fibre Channel products, a fixed value provided as input to a command
option is printed in plain text, for example, --show WWN.
NOTE
A note provides a tip, guidance, or advice, emphasizes important information, or provides a reference
to related information.
ATTENTION
An Attention statement indicates potential damage to hardware or data.
CAUTION
A Caution statement alerts you to situations that can be potentially hazardous to you or cause
damage to hardware, firmware, software, or data.
DANGER
A Danger statement indicates conditions or situations that can be potentially lethal or
extremely hazardous to you. Safety labels are also attached directly to products to warn of
these conditions or situations.
Brocade resources
Visit the Brocade website to locate related documentation for your product and additional Brocade
resources.
To get up-to-the-minute information on Brocade products and resources, go to MyBrocade. You can
register at no cost to obtain a user ID and password.
Release notes are available on MyBrocade under Product Downloads.
White papers, online demonstrations, and data sheets are available through the Brocade website.
Use one of the following methods to contact the Brocade Technical Assistance Center.
Preferred method of contact for non- Required for Sev 1-Critical and Sev [email protected]
urgent issues: 2-High issues:
Please include:
• My Cases through MyBrocade • Continental US:
• Problem summary
• Software downloads and 1-800-752-8061
• Serial number
licensing tools • Europe, Middle East, Africa,
and Asia Pacific: +800-AT • Installation details
• Knowledge Base
FIBREE (+800 28 34 27 33) • Environment description
• For areas unable to access toll
free number: +1-408-333-6061
• Toll-free numbers are available
in many countries.
Document feedback
To send feedback and report errors in the documentation you can use the feedback form posted with
the document or you can e-mail the documentation team.
Quality is our first concern at Brocade and we have made every effort to ensure the accuracy and
completeness of this document. However, if you find an error or an omission, or you think that a topic
needs further development, we want to hear from you. You can provide feedback in two ways:
• Through the online feedback form in the HTML documents posted on www.brocade.com.
• By sending your feedback to [email protected].
Provide the publication title, part number, and as much detail as possible, including the topic heading
and page number if applicable, as well as your suggestions for improvement.
• Expanded security for up to 16,000 hardware zones. Hardware zoning is accomplished at the port
level of the switch or by World Wide Name (WWN). Hardware zoning permits or denies delivery of
frames to any destination port address.
• Unicast, multicast (255 groups), and broadcast data traffic type, are support.
• Brocade Small Form-Factor Pluggable (SFP) or SFP+ optical transceivers support any
combination of Short Wavelength (SWL), Long Wavelength (LWL) or Extended Long Wavelength
(ELWL) optical media among the switch ports.
• Brocade Fabric Operating System (Fabric OS), which delivers distributed intelligence throughout
the network and enables a wide range of value-added applications including Brocade Advanced
Web Tools and Brocade Zoning. Optional Fabric Services include: Adaptive Networking with QoS,
Brocade Extended Fabrics, Brocade Enhanced Group Management, Brocade Fabric Watch, ISL
Trunking, Integrated Routing, and End-to-End Performance Monitoring (APM).
• Port-to-port latency minimized to 700 nanoseconds through the use of cut-through frame routing
at 8 Gbps.
• Extensive diagnostics and system monitoring capabilities, which enhance high Reliability,
Availability, and Serviceability (RAS).
• The Brocade EZSwitchSetup wizard, which makes SAN configuration a three-step point-and click
task.
Port Numbering
The Fibre Channel ports on the Brocade 5100 are numbered from left to right, in eight-port groups from
0 to 39 as illustrated in the following figure.
ATTENTION
Brocade ISL Trunking is licensed software that allows you to create trunking groups of ISLs between
adjacent switches. Trunking is supported by combining maximum of eight ports per group to form 64-
Gbps ISL trunk. The trunking port groups are 0-7, 8-15, 18-23, 24-31, and 32-39. For more information
about Brocade ISL Trunking, refer to the Brocade Fabric OS Administrator’s Guide.
The front panel has a status LED that provides the status of the entire switch, including the two power
supply/fan assembly FRUs.
NOTE
Brocade ISL Trunking is licensed software that allows you to create trunking groups of ISLs between
adjacent switches. For more information about Brocade ISL Trunking, refer to the Brocade Fabric OS
Administrator’s Guide
Electrical considerations
To install and operate the switch successfully, ensure the following:
• The primary outlet is correctly wired, protected by a circuit breaker, and grounded in accordance
with local electrical codes.
• The supply circuit, line fusing, and wire size are adequate, as specified by the electrical rating on
the switch nameplate.
• The power supply standards provided in Power supply specifications on page 32 are met.
Environmental considerations
For successful installation and operation of the switch, ensure that the following environmental
requirements are met:
• At a minimum, adequate cooling requires that you install the switch with the non-port side, which
contains the air intake vents, facing the cool-air aisle.
• All equipment in the rack should force air in the same direction to avoid intake of exhaust air.
• A maximum of 49.3 cubic meters/hour (29 cubic feet/minute) and a minimum of 37.4 cubic
meters/hour (22 cubic feet/minute) of air flow is available to the air intake vents on the non-port
side of the switch.
• The ambient air temperature does not exceed 40 ° C (104 ° F) while the switch is operating.
Cabinet considerations
For successful installation and operation of the switch in a cabinet, ensure the following cabinet
requirements are met:
• The cabinet must be a standard EIA cabinet.
• Plan a cabinet space that is one rack unit (1U) high; 4.45 cm (1.75 inches) and 48.3 cm (19
inches) wide.
• Ground all equipment in the cabinet through a reliable branch circuit connection and maintain
ground at all times. Do not rely on a secondary connection to a branch circuit, such as a power
strip.
• Ensure that airflow and temperature requirements are met on an ongoing basis, particularly if the
switch is installed in a closed or multicabinet assembly.
• Verify that the additional weight of the switch does not exceed the cabinet’s weight limits or
unbalance the cabinet in any way.
• Secure the cabinet to ensure stability in case of unexpected movement, such as an earthquake.
NOTE
You should not use tie wraps with optical cables because they are easy to over tighten.
CAUTION
Before plugging a cable to any port, be sure to discharge any static charge stored on the cable
by touching the electrical contacts to ground surface.
• Plan for rack space required for cable management before installing the switch.
• Leave at least 1 m (3.28 ft) of slack for each port cable. This provides room to remove and replace
the switch, allows for inadvertent movement of the rack, and helps prevent the cables from being
bent to less than the minimum bend radius.
• If you are using Brocade ISL Trunking, consider grouping cables by trunking groups. The cables
used in trunking groups must meet specific requirements, as described in the Fabric OS
Administrator’s Guide .
• For easier maintenance, label the fiber optic cables and record the devices to which they are
connected.
• Keep LEDs visible by routing port cables and other cables away from the LEDs.
• Use hook and loop style straps to secure and organize fiber optic cables.
ATTENTION
Do not connect the switch to the network until the IP address is correctly set. For instructions on
how to set the IP address, see Brocade 5100 configuration on page 16
ATTENTION
Power is supplied to the switch as soon as the first power supply is connected and turned on.
3. After POST is complete, verify that the switch power and status LEDs on the left of the port side of
the switch are green.
Parameter Value
Databits 8
Parity None
Stop bits 1
If ttyb is already in use, use ttya instead and enter the following string at the prompt:
tip /dev/ttya -9600
Switch IP address
You can configure the Brocade 5100 with a static IP address, or you can use a DHCP (Dynamic Host
Configuration Protocol) server to set the IP address of the switch. DHCP is enabled by default. The
Brocade 5100 supports both IPv4 and IPv6.
If you are going to use an IPv4 IP address, enter the IP address in dotted decimal notation as
prompted.
If you are going to use an IPv6 address, enter the network information in semicolon-separated
notation as prompted.
Time zones
You can set the time zone for the switch by name. You can also set country, city or time zone
parameters.
If the time zone is not set with the new options, the switch retains the offset time zone settings. The
tsTimeZone command includes an option to revert to the prior time zone format. For more information
about the --old option, see the Fabric OS Command Reference.
You can set the time zone for a switch using the tsTimeZone command. The tsTimeZone command
allows you to perform the following tasks:
• Display all of the time zones supported in the firmware
• Set the time zone based on a country and city combination or based on a time zone ID such as
PST
The time zone setting has the following characteristics:
• You can view the time zone settings. However, only those with administrative permissions can set
the time zones.
• The tsTimeZone setting automatically adjusts for Daylight Savings Time.
• Changing the time zone on a switch updates the local time zone setup and is reflected in local
time calculations.
• By default, all switches are in the GMT time zone (0,0). If all switches in a fabric are in one time
zone, it is possible for you to keep the time zone setup at the default setting.
• System services that have already started will reflect the time zone changes only after the next
reboot.
• Time zone settings persist across failover for high availability.
switch:admin> date
Fri Sep 29 17:01:48 UTC 2007
switch:admin> date "0927123007"
Thu Sep 27 12:30:00 UTC 2007
switch:admin>
The following procedure describes how to set the current time zone using timezone_fmt mode to
Central Standard time.
1. Log into the switch using the default password, which is password.
2. Enter the tsTimeZone command as follows:
switch:admin> tstimezone [--interactive]/ [, timezone_fmt]
Use timezone_fmt to set the time zone by Country/City or by time zone ID, such as PST.
The following example shows how to change the time zone to US/Central.
switch:admin> tstimezone
Time Zone : US/Pacific
switch:admin> tstimezone US/Central
switch:admin> tstimezone
Time Zone : US/Central
The following procedure describes how to set the current time zone using
interactive mode to Pacific Standard Time.
1. Type the tsTimeZone command as follows:
switch:admin> tstimezone --interactive
2. You are prompted to select a general location.
Please identify a location so that time zone rules can be set correctly.
3. Enter the appropriate number or Ctrl-D to quit.
4. At the prompt, select a country location.
5. At the prompt, enter the appropriate number to specify the time zone
region or Ctrl-D to quit.
where ntp1 is the IP address or DNS name of the first NTP server, which the switch must be able
to access. The second ntp2 is the second NTP server and is optional. The operand "<ntp1;ntp2>"
is optional; by default, this value is LOCL, which uses the local clock of the principal or primary
switch as the clock server.
switch:admin> tsclockserver
LOCL
switch:admin> tsclockserver "132.163.135.131"
switch:admin> tsclockserver
132.163.135.131
switch:admin>
The following example shows how to set up more than one NTP server using a DNS name:
switch:admin> tsclockserver
"10.32.170.1;10.32.170.2;ntp.localdomain.net"
Updating Clock Server configuration...done.
Updated with the NTP servers
Changes to the clock server value on the principal or primary FCS switch are
propagated to all switches in the fabric
LED locations
FIGURE 4 Port Side LEDs on the Brocade 5100.
LED Patterns
The following table describes the LEDs and their actions on the switch.
Power Supply No light Primary power cord is disconnected or Verify the power supply is on and
Status is not actively powered, or power seated and the power cord is
supply has failed. connected to a functioning power
source.
Flashing green (for A power supply and fan assembly fault Take one of the following actions:
more than five has occurred for one of the following
seconds) reasons: • Replace the FRU
• The power supply or fan in the • Verify that the power
assembly has failed. supply/fan assembly FRU is
• The FRU was disabled by a user. enabled
• The FRU power switch has been • Check the power switch and
turned off or the unit has been plug
unplugged.
Power Status No light System is off or there is an internal Verify the system is on. If the
power supply failure. system is on, the unit is faulty.
Contact Technical Support.
System Status No light System is off, boot is not complete, or Verify the system is on and has
boot failed. completed booting.
Steady amber (for Boot failed, the system is faulty. Perform the following steps:
more than five
seconds) Connect a serial cable to the
system.
Reboot the system.
Check the failure indicated on the
system console.
Contact Technical Support.
Port Status No light No signal or light carrier (media or Check transceiver and cable.
cable) detected.
Slow flashing green Port is online but segmented because No action required.
(flashing in two- of a loopback cable or incompatible
second intervals) switch connection.
Fast flashing green Port is online and an internal loopback No action required.
(flashing in half- diagnostic test is running.
second intervals)
Flickering green Port is online and frames are flowing No action required.
(steady with through the port.
random flashes)
Slow flashing Port is disabled (because of Verify the diagnostic tests are not
amber (flashing in diagnostics or the portDisable running. Reenable the port using
two-second command). the portEnable command.
intervals)
Steady amber (for Port is receiving light or signal carrier No action required.
more than five at 4 Gbps; but is not yet online.
seconds)
POST
The success or failure results of the diagnostic tests that run during POST can be monitored through
the error log or the command line interface.
Boot
In addition to POST, boot includes the following tasks after POST is complete:
1. Performs universal port configuration.
2. Initializes links.
3. Analyzes fabric. If any ports are connected to other switches, the switch participates in a fabric
configuration.
4. Obtains a domain ID and assigning port addresses.
5. Constructs unicast routing tables.
6. Enables normal port operation.
Installing an SFP
The Brocade 5100 only supports Brocade-branded SFPs. If you use an unqualified SFP, the
switchShow command output shows the port in a Mod_Inv state. Fabric OS also logs the issue in the
system error log.
Complete the following steps to install an SFP.
1. Making sure that the bail (wire handle) is in the unlocked position, place the SFP in the correctly
oriented position on the port, as shown in the following figure.
2. Slide the SFP into the port until you feel it click into place; then close the bail.
NOTE
Each SFP has a 10-pad gold-plated PCB-edge connector on the bottom. The correct position to
insert an SFP into the upper row of ports is with the gold edge down. The correct position to insert
an SFP into the lower row of ports is with the gold edge up.
Diagnostic tests
In addition to POST, the Fabric OS includes diagnostic tests to help you troubleshoot the hardware
and firmware. This includes tests of internal connections and circuitry, fixed media, and the
transceivers and cables in use.
The tests are implemented by command, either through a Telnet session or through a terminal set up
for a serial connection to the switch. Some tests require the ports to be connected by external cables,
to allow diagnostics to verify the serializer/deserializer interface, transceiver, and cable. Some tests
require loopback plugs.
Diagnostic tests are run at link speeds of 1, 2, 4, and 8 Gbps depending on the speed of the link being
tested.
NOTE
Diagnostic tests might temporarily lock the transmit and receive speed of the links during diagnostic
testing.
For information about specific diagnostic tests, refer to the Fabric OS Troubleshooting and Diagnostics
Guide.
• Type the psShow command at the command prompt to display power supply status as shown
below:
switch:admin> psshow
Power Supply #1 is OK
Power Supply #2 is OK
2. Use one of the following methods to determine whether a fan requires replacement:
• Check the system status LED (see LED locations section for location of system status LED). If
the system status LED is flashing amber and green, it could mean the fan has failed. The
green power supply/fan LED will also flash in the event of failure. Check the management
interface and the error log for details on the cause of status.
• In Advanced Web Tools, check the Fan Status icon background color. It will be either yellow
or red if the fan has failed. When the fan is functioning correctly, the background color is
green.
• Type the fanShow command at the command prompt to display fan status as shown below:
switch:admin> fanshow
Fan 1 is OK, speed is 7105 RPM
Fan 2 is OK, speed is 7258 RPM
For further information on replacing the power/fan units, see the Brocade 5100 Power Supply and
Fan Assembly Replacement Procedure .
Brocade Fabric Manager (option to purchase) Ethernet or serial IP over Fibre Channel
connection
For information, refer to the Fabric Manager
Administrator’s Guide .
NOTE
To achieve in-band support for IP over Fibre Channel, the software must be run on both the HBA and
the switch, and it must be supported by both the HBA and HBA driver.
● Switch components......................................................................................................... 31
● Weight and physical dimensions.....................................................................................31
● Facility requirements....................................................................................................... 32
● Power supply specifications............................................................................................ 32
● Environmental requirements........................................................................................... 33
● General specifications.....................................................................................................33
● Data transmission ranges............................................................................................... 35
● Memory specifications.....................................................................................................35
● Fibre Channel port specifications....................................................................................36
● Serial port specifications................................................................................................. 36
● Regulatory compliance....................................................................................................37
● Environmental regulation compliance............................................................................. 41
Switch components
The Brocade 5100 switch includes the following components:
• Cabinet-mountable 1U chassis, designed for a 19-inch cabinet space, with forced-air cooling that
flows from the non-port side of the switch to the port side.
• 40 Fibre Channel ports, compatible with short wavelength (SWL), long wavelength (LWL), and
extended long wavelength (ELWL) SFP transceivers
• One RJ-45 serial port on the port side of the switch
• One IEEE-compliant RJ-45 connector on the port side of the switch for use with 10/100 Mbps
Ethernet
• 40 port LEDs, 1 switch power LED, 1 switch status LED, 2 Ethernet LEDs, and 2 power supply
LEDs
• One USB port for system log file downloads or firmware upgrades
• Two universal AC input and redundant power supplies with AC switches and built-in fans
Dimension Value
Dimension Value
Weight (with two power supply/fan assembly units installed, no SFPs) 9.3 kg (20.6 lbs)
Facility requirements
The following table provides the facilities requirements that must be met for the Brocade 5100.
Type Requirements
Electrical • Primary AC input 100-240 VAC, 2.0A, 47-63 Hz; switch autosenses input voltage
• Adequate supply circuit, line fusing, and wire size, as specified by the electrical rating on
the switch nameplate
• Circuit protected by a circuit breaker and grounded in accordance with local electrical
codes
Refer to Power supply specifications on page 32 for complete power supply specifications.
Thermal • A minimum air flow of 79.8 cubic meters/hour (47 cubic ft/min.) available in the immediate
vicinity of the switch
• Ambient air temperature not exceeding 40 ° C (104 ° F) while the switch is operating
Specification Value
Inlet C13
Specification Value
Environmental requirements
The following table lists the acceptable environmental ranges for both operating and nonoperating (such
as during transportation or storage) conditions.
Ambient Temperature 0° to 40° Celsius(32° to 104° Fahrenheit) -25° to 70° Celsius(-13° to 158°
Fahrenheit)
Humidity 10% to 85% RH non-condensing, at 40° Celsius 10% to 90% RH non-condensing, at 70°
(104° Fahrenheit), with maximum gradient of Celsius (158° Fahrenheit)
10% per hour
Altitude 3,000 meters (9,842 feet) above sea level 0 to 12 kilometers (39,370 feet) above
sea level
Shock 20 G, 6 ms, half-sine wave Half sine, 33G 11ms, 3/e.g. Axis
Vibration 0.5 G sine, 0.4 grms random, 5-500 Hz 2.0 G sine, 1.1 grms random 5-500 Hz
Air flow High speed, 13,000 RPM, 49.3 CMH (29 CFM) None required
Low speed, 7000 RPM, 37.4 CMH (22 CFM)
General specifications
The following table lists the general specifications for the Brocade 5100.
Specification Description
ANSI Fibre Channel protocol FC-PH ( Fibre Channel Physical and Signalling Interface standard)
FC-IP (IP over Fibre Channel) Complies with FC-IP 2.3 of FCA profile
Aggregate switch I/O bandwidth 640 Gbps if all 40 ports are running at 8 Gbps, full duplex
The following table lists the EMC (electromagnetic compatibility) for the Brocade 5100.
Port Speed Cable Size Short Wavelength (SWL) Long Wavelength Extended Long
(microns) (LWL) Wavelength (ELWL)
9 NA NA NA
9 NA 10 km NA
Memory specifications
The Brocade 5100 has three types of memory devices.
Type Size
Boot flash 4 MB
Compact flash 1 GB
NOTE
To protect the serial port from damage, keep the cover on the port when not in use.
The serial port can be used to connect to a workstation to configure the switch IP address before
connecting the switch to a fabric or IP network. The serial port’s parameters are fixed at 9600 baud, 8
data bits, and no parity, with flow control set to None.
This connector is for initial IP address configuration and for recovery of the switch to its factory default
settings if Flash memory contents are lost. The serial port is not intended for performance of normal
administration or maintenance functions. You should only use this port to connect a terminal to the
port to re-initialize the switch defaults, restoring the switch to its factory configuration. This is required
to restore switch passwords to a known state and allow you to assign an IP address to the switch.
1 Not supported NA
2 Not supported NA
7 Not supported NA
8 Not supported NA
Regulatory compliance
This section describes the regulatory compliance requirements for the Brocade 5100 switch. It contains:
• FCC warning (US only) on page 37 next
• KCC statement (Republic of Korea) on page 37
• VCCI statement Japan on page 39
• China statement on page 38
• BSMI statement (Taiwan) on page 39
• CE statement on page 39
• Canadian requirements on page 40
• Laser compliance on page 40
• RTC battery on page 40
• Electrical safety on page 40
• Regulatory certifications on page 41
Class A device (Broadcasting Communication Device for Office Use): This device obtained EMC
registration for office use (Class A), and may be used in places other than home. Sellers and/or users
need to take note of this.
China statement
This is a Class A product based on the standard of the Voluntary Control Council for Interference by
Information Technology Equipment (VCCI). If this equipment is used in a domestic environment, radio
disturbance might arise. When such trouble occurs, the user might be required to take corrective
actions.
Warning:
This is Class A product. In a domestic environment this product may cause radio interference in which
case the user may be required to take adequate measures.
CE statement
ATTENTION
This is a Class A product. In a domestic environment, this product might cause radio interference, and
the user might be required to take corrective measures.
The standards compliance label on the Brocade 5100 contains the CE mark which indicates that this
system conforms to the provisions of the following European Council directives, laws, and standards:
• Electromagnetic Compatibility (EMC) Directive 2004/108/EEC
• Low Voltage Directive (LVD) 2006/95/EC
• EN50082-2/EN55024:1998 (European Immunity Requirements)
Canadian requirements
This Class A digital apparatus meets all requirements of the Canadian Interference-Causing
Equipment Regulations, ICES-003 Class A.
Laser compliance
This equipment contains Class 1 laser products and complies with FDA Radiation Performance
Standards, 21 CFR Subchapter I and the international laser safety standard IEC 825-2.
ATTENTION
Use only optical transceivers that are qualified by Brocade Communications Systems, Inc. and comply
with the FDA Class 1 radiation performance requirements defined in 21 CFR Subchapter I, and with
IEC 825-2. Optical products that do not comply with these standards might emit light that is hazardous
to the eyes.
RTC battery
ATTENTION
Do not attempt to replace the real-time clock (RTC) battery. There is danger of explosion if the battery
is incorrectly replaced or disposed of. Contact your switch supplier if the real-time clock begins to lose
time.
Electrical safety
ATTENTION
This switch might have more than one power cord. To reduce the risk of electric shock, disconnect
both power cords before servicing.
ATTENTION
Connect the power cord only to a grounded outlet.
ATTENTION
This product is designed for an IT power system with phase-to-phase voltage of 230V. After operation
of the protective device, the equipment is still under voltage if it is connected to an IT power system.
Regulatory certifications
The following table lists the EMC compatibility for the Brocade 5100.
China RoHS
The contents included in this section are per the requirements of the People's Republic of China-
Management Methods for Controlling Pollution by Electronic Information products.
and its customer. Brocade hereby disclaims all other warranties and representations with respect to
the information contained on this CD including the implied warranties of merchantability, fitness for a
particular purposes and non-infringement.
The EPUP assumes that the product will be used under normal conditions in accordance with the
operating manual of the product.
Fibre Channel X O O O O O
Switch
Fan, Blower X O O O O O
assemblies
PCBA cards X O O O O O
Sheet Metal X O O O O O
Chassis Assembly X O O O O O
Mechanical brackets X O O O O O
and Slides
Slot Filler X O O O O O
Cable management X O O O O O
tray
Cable Comb O O O O O O
Replacement Doors X O O O O O
Software/ O O O O O O
Documentation CDs
X indicates that the concentration of such hazardous/toxic substance in all the units of homogeneous
material of such component is higher than the SJ/T11363-2006 Requirements for Concentration Limits.
O indicates that no such substances are used or that the concentration is within the aforementioned
limits.
access
NTP 20
F
accessory kit 13 Fabric Manager 28
FCC warning (US only) 37
B Fibre Channel classes, supported 33
Fibre Channel ports
bandwidth, aggregate 33 specifications 36
Brocade Advanced Web Tools 28 Field replaceable units (FRUs) 11
front panel
Brocade Fabric Manager 28
LEDs 21
Brocade ISL Trunking 11, 12
BSMI statement (Chinese) 39
BSMI statement (Taiwan) 39 I
installing a Brocade 5100 into an EIA cabinet 16
C installing an SFP 26
installing a stand-alone Brocade 5100 15
Canadian requirements 40
interpreting POST results 25
CE statement 39
IP over Fibre Channel (FC-IP) 33
China RoHS 41
ISL trunking groups 12
China statement 38
class
items required for installation 15
Fibre Channel classes supported 33
Command line interface (CLI) 28
components, switch 31
K
configuring KCC statement 37
date and time 18
NTP 20
configuring the Brocade 5100 16 L
laser compliance 40
D latency 33
LEDs
date 19 interpreting 21
date and time 18 on front panel 21
diagnostic tests local clock 20
about 26 LOCL 20
logging
E timestamp 18
EFCM 28
EIA rack
M
requirements 32 Management Server 28
electrical safety 40 MIC statement (Republic of Korea) 37
environmental requirements 33 monitoring
event through LED activity 21