0% found this document useful (0 votes)
4 views

Transformers Tests

Uploaded by

kclarksidlao
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
4 views

Transformers Tests

Uploaded by

kclarksidlao
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 12

OPEN-CIRCUIT TEST

•The purpose of this test is to determine


no-load loss or core loss and no-load
𝐼𝑂 which is helpful in finding 𝑋𝑚 and
𝑅𝐶 .
OPEN-CIRCUIT TEST
•One winding of the transformer – whichever
is convenient but usually high voltage
winding – is left open and the other is
connected to its supply of normal voltage
and frequency.
•A wattmeter W, voltmeter V and an ammeter
A are connected in the low voltage winding
i.e. primary winding in the present case.
OPEN-CIRCUIT TEST
• With rated voltage applied to the primary, normal flux will be set up in the core, hence
normal iron losses will occur which are recorded by the wattmeter.
• As the primary no-load current 𝐼𝑂 (as measured by ammeter) is small (usually 2 to
10% of rated load current), Cu loss is negligibly small in primary and nil in secondary
(it being open).
• Hence, the wattmeter reading represents practically the core loss under no-load
condition
OPEN-CIRCUIT TEST
•The wattmeter reading 𝑊 = 𝑉𝑂𝐶 𝐼𝑜 COS ∅𝑜 = 𝑃𝑂𝐶 = 𝑃𝑐𝑜𝑟𝑒
𝑃𝑜𝑐 = 𝑉𝑜𝑐 𝐼𝑜𝑐 cos ∅𝑜
𝐼𝑐 = 𝐼𝑜 cos ∅𝑜
𝑰𝑪 𝑰𝒎 𝐼𝑚 = 𝐼𝑜 sin ∅𝑜

𝐼𝑜𝑐 = 𝐼𝑐 2 + 𝐼𝑚 2

𝑉𝑜𝑐 𝑉𝑜𝑐
𝑅𝑐 = 𝑋𝑚 =
𝐼𝑐 𝐼𝑚
SAMPLE PROBLEM 1
•A 500 kVA, 11/2.3 kV, 60 Hz transformer has been
tested and gives the following open circuit test data:
2.3 kV, 2.3 A, 4kW. Determine:
a.Core loss
b.Resistance representing core loss
c.Magnetizing reactance
SHORT-CIRCUIT TEST
•The purpose of this test is to determine
the equivalent resistance, equivalent
leakage reactance and the equivalent
impedance of the transformer
• Inthis test, one winding, usually the low-voltage
winding, is solidly short-circuited by a thick conductor SHORT-CIRCUIT TEST
(or through an ammeter which may serve the
additional purpose of indicating rated load current)
• A low voltage (usually 5 to 10% of normal primary
voltage) at correct frequency (though for cu losses it
is not essential) is applied to the primary and is
cautiously increased till full-load currents are flowing
both in primary and secondary (as indicated by the
respective ammeters)
•Since, in this test, the applied voltage is a
small percentage of the normal voltage, the SHORT-CIRCUIT TEST
mutual flux Φ produced is also a small
percentage of its normal value
•Hence, core losses are very small with the
result that the wattmeter reading represent
the full-load cu loss or 𝐼 2 𝑅 loss for the
whole transformer i.e. Both primary Cu loss
and secondary cu loss.
SHORT-CIRCUIT TEST
The wattmeter reading in the short circuit test is essentially
copper loss

Note: During the test I1 >> I0, thus the magnetizing branch
can be neglected

ROH = REQ = equivalent resistance referred to the high side


XOH = XEQ = equivalent reactance referred to the high side
ZOH = ZEQ = equivalent impedance referred to the high side
SAMPLE PROBLEM 2
•A short circuit test was performed on a 10 kva,
2000/400 V, single phase transformer. The
instruments indicated 100 V, 5A and 100 W.
Determine the secondary voltage when operating
at rated load 80% pf lagging at rated primary
voltage.

You might also like