Transformers Tests
Transformers Tests
𝐼𝑜𝑐 = 𝐼𝑐 2 + 𝐼𝑚 2
𝑉𝑜𝑐 𝑉𝑜𝑐
𝑅𝑐 = 𝑋𝑚 =
𝐼𝑐 𝐼𝑚
SAMPLE PROBLEM 1
•A 500 kVA, 11/2.3 kV, 60 Hz transformer has been
tested and gives the following open circuit test data:
2.3 kV, 2.3 A, 4kW. Determine:
a.Core loss
b.Resistance representing core loss
c.Magnetizing reactance
SHORT-CIRCUIT TEST
•The purpose of this test is to determine
the equivalent resistance, equivalent
leakage reactance and the equivalent
impedance of the transformer
• Inthis test, one winding, usually the low-voltage
winding, is solidly short-circuited by a thick conductor SHORT-CIRCUIT TEST
(or through an ammeter which may serve the
additional purpose of indicating rated load current)
• A low voltage (usually 5 to 10% of normal primary
voltage) at correct frequency (though for cu losses it
is not essential) is applied to the primary and is
cautiously increased till full-load currents are flowing
both in primary and secondary (as indicated by the
respective ammeters)
•Since, in this test, the applied voltage is a
small percentage of the normal voltage, the SHORT-CIRCUIT TEST
mutual flux Φ produced is also a small
percentage of its normal value
•Hence, core losses are very small with the
result that the wattmeter reading represent
the full-load cu loss or 𝐼 2 𝑅 loss for the
whole transformer i.e. Both primary Cu loss
and secondary cu loss.
SHORT-CIRCUIT TEST
The wattmeter reading in the short circuit test is essentially
copper loss
Note: During the test I1 >> I0, thus the magnetizing branch
can be neglected