Manual FM
Manual FM
AIR CURTAINS
Models:
FM-1209SA3/Y, FM-1212SA3/Y, FM-1215SA3/Y, FM-1218SA3/Y, FM-1220SA3/Y
A. Always disconnect, lock and tag power source before installing or servicing. Failure to
disconnect power source can result in fire, shock or serious injury.
B. Installation work and electrical wiring must be done by qualified person(s) in
accordance with all applicable codes and standards, including fire-rated construction.
C. When cutting or drilling into wall or ceiling, do not damage electrical wiring and other
hidden utilities.
D. To reduce the risk of fire or electric shock, do not use this fan with any solid-state
speed control device
E. Repair and maintenance operations can only be performed by qualified personnel.
F. Verify and ensure the rated voltage and frequency (please refer to the rating label) of
the air curtain is in compliance with the mains supply.
CONTENTS
1
1. PRODUCT INTRODUCTIONS
Air curtains are widely installed at the entrances of supermarket, theater, meeting room, hotel,
office room, storeroom etc. They can reduce penetration of insects, dust…unconditioned air into a
conditioned space by forcing an air stream over the entire entrance to create a comfortable
environment for you.
2. INSTALLATION DIMENSIONS
UNIT: mm
MODEL A B C D F G H I J
FM-1209SA3/Y 900 330 ---
440
FM-1212SA3/Y 1200 480 ---
FM-1215SA3/Y 1500 330 --- 55 90 210 190 110
FM-1218SA3/Y 1800 480 840 ---
FM-1220SA3/Y 2000 580 ---
2
3. INSTALLATION CAUTIONS
Must observe the following when installing air curtains:
3.1 Please install the unit on a sturdy 3.2 Please install the unit inside the room.
supporting structure to avoid shaking and
ensure its security (because the unit running
may cause the wall to become loose or
shake and make noise).
3.3 Don’t install the unit too low, no less than 3.4 When the entrance is wider than the
2.3 meters from the ground. unit, it is recommended to install two or
ATENCIÓN : No instale la unidad more units in parallel. In this case, provide
demasiado bajo, no menos de 2,3 metros 20-40mm gaps between the units.
del suelo.
3.5 Don’t allow gaps between the unit and 3.6 Don’t install the unit at a place where it
the wall. is splashed by water, exposed to excessive
steam, explosive gas or corrosive gas.
3
4. INSTALLATION INSTRUCTIONS
A. Installing on the concrete wall:
4.1.1 Remove the plastic parts (if the screw is 4.1.2 Determine the mounting location with
covered by the plastic parts – screw cover) the mounting plate. Secure the bolts in
and unscrew the fixing screws to remove the place. (Fill cement into the bolt holes if
mounting plate from the back of the main needed)
body.
MOUNTING PLATE
2
PLASTIC PARTS 1
1 2
4.1.3 Tighten the nuts to secure the 4.1.4 Hang the main body onto the upper
mounting plate to the wall after cement end of the mounting plate, and then tighten
setting (use the washers and nuts as the Fig the fixing screws back to the mounting plate,
shows). cover the screws with the plastic parts –
screw cover, refer to the Fig in 4.1.1.
4.2.1 Refer to step 4.1.1 and determine the 4.2.2 Hang the main body onto the upper end
mounting location with the mounting plate, then of the mounting plate, and then tighten the
securely mount the mounting plate to the fixing screws back to the mounting plate,
wooden wall with tapping screws. cover the screws with the plastic parts – screw
cover, refer to the Fig in 4.1.1.
4
C. Installing from the ceiling:
4.3.1 Remove the mounting plate from the main 4.3.2 Securely mount the ceiling brackets (not
body as per the step 4.1.1 included) as the Fig shows.
4.3.3 Fix the mounting plate to the ceiling 4.3.4 Hang the main body onto the upper end
brackets and tighten it securely as the Fig of the mounting plate, and then tighten the
shows. The position of the mounting plate can fixing screws back to the mounting plate, cover
be adjusted in vertical direction according to the screws with the plastic parts – screw cover,
need, but the max distance is 100mm. refer to the Fig in 4.1.1.
4.4.1 Fix the air curtain as per the procedure for 4.4.2 Then pipe as below Fig. Instructs.
installing on the concrete wall.
5
5. TECHNICAL PARAMETER
6. WIRING DIAGRAM
BLUE(BROWN/RED)
BLUE
YELLOW-GREEN
THERMAL CUT-OUT
7. OPERATING INSTRUCTIONS
7.1 Connect power to the unit.
7.2 Press the [on/off] button on the air curtain to turn it on at default high speed or turn it off. Press
the button [H] / [L] to select suitable speed, button [L] - Low speed, [H] - High speed. You can
also press the [on/off] button on the remote control to turn on the air curtain at default high
speed, press it again to switch the unit to low speed, and press again to turn it off.
7.3 Adjust the air deflector to obtain optimum effect.
6
8. MAINTENANCE AND CLEANING
WARNING:
A. Any service is to be performed only by qualified personnel who are familiar with local
codes and regulations and are experienced with this type of product.
B. Always unplug or disconnect the appliance from the power supply before servicing or
cleaning the unit.
C. Never use petrol, benzene, thinners or any other such chemicals for cleaning the unit.
D. Don’t allow water or any liquid to enter the motor.
8.1. Use the unit at the rated voltage and frequency indicated on the rating label.
8.2. Disconnect power source before unit installation or maintenance service.
8.3. Routine maintenance must be done every year.
8.4. Plastic parts should be cleaned with mild soap water, thoroughly remove soap film with a
clean damp cloth.
8.5. Wipe the exterior surfaces of the fan with a moistened cloth with a solution of mild detergent
and water.
8.6. Dry the case with a soft dry cloth before operating the unit.