SCSGDOC-0027, Ver 2.0-SOP For Calibration of Level Transmitter Time of Flight
SCSGDOC-0027, Ver 2.0-SOP For Calibration of Level Transmitter Time of Flight
Page 1 of 8
Document Title
SOP for Calibration of Calibration of Level Transmitter Time of Flight
SCSGDOC-0027
Revisions:
Change Description:
Version# Reason
Change the wording radar to time of flight.
2.0 Effective date column was locked by signatures. Make it editable with new
revision. Training not required.
Authors Group:
Pua Wee Siong Service Manager Service
Pua Wee
Pua Wee Siong
CN = Pua Wee Siong email =
[email protected]
Approvers:
Digitally signed by:
Siong Chiat Soh
Page 2 of 8
Document Title
SOP for Calibration of Calibration of Level Transmitter Time of Flight
SCSGDOC-0027
Contents
1.0 Introduction & Purpose ............................................................................................................................. 4
2.0 Warning and Cautions .............................................................................................................................. 4
3.0 References ................................................................................................................................................. 4
4.0 Term & Definitions.................................................................................................................................... 4
5.0 Tools and Equipment ................................................................................................................................ 4
6.0 Preparation………………………………………………………………………………………………………………………………… 5
7.0 Operation Steps ………………………………………………………………………………………………………………………….5
8.0 Reporting………………………….………………………………………………………………………………………………………..7
9.0 Handover………………………………….………………………………………………………………………………………………..7
10.0 Interval………………………………….…………………………………………………………………………………………………..7
Page 3 of 8
Document Title
SOP for Calibration of Calibration of Level Transmitter Time of Flight
SCSGDOC-0027
• Both the operator and the person responsible for the process should be informed that a Service job will be
carried out
• A permit to work should be obtained before commencement of any service activities.
• If applicable, before disconnecting any sensor that is attached to the process, determine what chemical or
liquid is being measured (observe safety data sheet).
• Be aware of the temperature of machines, pipes and construction before touching it.
• Be aware of the extreme ambient temperature at the place of performing calibration.
• Never open a process fitting or loosen flange bolts before you have confirmed it is safe to do so.
• Be sure not to disturb the process when disconnecting inputs/outputs.
• Be aware of the local safety instructions and always work according to Endress+Hauser Standard
Operating Procedure of Health and Safety
• Ensure tools, equipment and the end-user processes are protected from cross contamination. Consider
and plan necessary cleaning steps before and after a calibration.
• When service requiring chemicals (e.g. as reagents for standard operation or for cleaning purposes),
always follow and observe the safety regulations stated in the safety data sheet
3.0 References
Term Definition
UUT Unit under test
Page 4 of 8
Document Title
SOP for Calibration of Calibration of Level Transmitter Time of Flight
SCSGDOC-0027
6.0 Preparation
• Before starting a calibration, perform a visual inspection of the measuring instrument to ensure that the
instruments are not damaged or require repair. If there is any doubt, it is advisable to postpone
calibration of device until proper functioning of the instrument is restored.
• Ensure tank is re-pressurize.
• In case any change of UUT settings is needed before or during calibration be sure to store or record
original settings.
• Record the ‘as found’ value before commencement of calibration steps.
• Save as found parameter setting.
Figure 7.1
Page 5 of 8
Document Title
SOP for Calibration of Calibration of Level Transmitter Time of Flight
SCSGDOC-0027
Figure 7.2
Page 6 of 8
Document Title
SOP for Calibration of Calibration of Level Transmitter Time of Flight
SCSGDOC-0027
8.0 Reporting
• Do use only standard reports generating tools and calibration certificate templates provided by
Endress+Hauser Service Office unless other is agreed with the end-user.
• Ensure that all the fields in issued Calibration Certificates are filled.
• Once adjustment of UUT was performed to resolve non-conformity this should be reported in detail.
Calibration procedure must be repeated and “as left” calibration results should be filed alongside the
original “as found” results in Calibration Certificate.
9.0 Handover
• Do not perform adjustment or repair of device to resolve non-conformity until this is agreed with the
end-user.
• Should adjustment be necessary and possible with the device, the specific procedure from the
manufacturer’s operating and maintenance manual should be followed.
• Prior to returning the instrument to end-user, any internal settings that have been changed to enable
calibration must be re-installed to their original values.
• Affix a calibration label to the UUT after job completion.
• Calibration Certificates should be passed to end-user either as signed printouts or as files with
electronic signature. A copy of every Calibration Certificate file should remain at Endress+Hauser
storage. Wherever established, Calibration Certificates should be stored in Calibration and
Maintenance Management System and/or Plant Assets Management System linked to a UUT record.
10.0 Interval
The calibration interval depends on the application, the function of the instruments in the process as well as
the user requirements and the manufacturer’s specifications. The calibration intervals are determined by
end-user. Endress+Hauser may provide consulting on calibration intervals or calibration management
services on request.
No recalibration date is to be included on the Calibration Certificate or label unless agreed upon by the end-
user.
Page 7 of 8
Document Title
SOP for Calibration of Calibration of Level Transmitter Time of Flight
SCSGDOC-0027
This document and its content are the property of Endress+Hauser Consult AG and its licensors
(“Endress+Hauser”); copyright laws in various countries may apply.
Any reproduction or distribution of this document (including parts of it) is prohibited without the prior written
consent of Endress+Hauser.
Any trademarks and trade names mentioned in this document remain the sole property of Endress+Hauser or
the relevant owner.
All other intellectual property rights, particularly but not limited to patents and patent applications shall be
reserved and no license or other right to use whatsoever shall be granted hereunder.
This document shall only be legally binding in connection with a separate agreement between the service
provider and the customer. The contractual obligations stipulated in such separate agreement shall prevail.