P-011 Relay Protection Relay

2. Type designation

Control power supply voltage (AC220V、


AC230V,AC240V,AC380V,AC400V,AC415V)

Rated current: 5,10,40,100,400,800

None: communication interface is not available


T: RS485 interfac

None: 4mA~20mA analog transformation is not


available
M: 4mA~20mA analog transmission

Specification code

Design sequence No.

Motor protection relay

Company code

3. Operating conditions
NJBK7 Motor Protection Relay 3.1 Altitude: Not more than 2000m.

3.2 Ambient air condition: -5℃~+40℃, and the average value in


1. General
24 hours shall not exceed +35℃.
NJBK7-800 series motor protection relay (hereinafter referred
3.3 When the maximum temperature is +40℃, the relative
to as "Protector") is applicable for overload protection,locked
humidity of air shall not exceed 50% and higher relative
rotor protection,phase failure protection, three-phase imbalance
humidity is allowable at lower temperature comparatively
protection,undercurrent protection,grounding protection , PTC
(e.g the air humidity may reach 90% when the temperature
temperature protection and communication failure protection
is +20℃). Special measures shall be taken to deal with
for AC electromotors of a frequency of 50Hz with a rated
occasianal condensation caused by variation in temperature.
insulation voltage of up to 690V and a rated operating current
of 1A~800A during long-term and discontinuous operation, 3.4 Pollution class: 3.
This protector is provided with RS485 interface and 4mA~20mA
3.5 The slope degree between installing and verical plane shall not
current loop transmitter interface for network communication
exceed ±5°.
and performs remote monitor control on the motor and fault
query through opper computer. This protector is usually used 3.6 Explosion hazard-free media, in which there are no gasses
to combine with AC contactor. that are capable of corroding metals and damage the
This product conforms to IEC60947-4-1. insulation and not conducting dust.

3.7 Areas with rain-and-snow-proof equipment and without


water vapor.

3.8 Areas without noticeable shaking, impact and vibration.

3.9 Installation class: Ⅲ.

3.10 Enclosure protection class:IP20.

4. Technical data
4.1 Main circuit: Rated insulatin voltage AC690V and rated frequency is 50Hz, rated impulse withstand voltage 1.2/50μs、4kV,rated
current 1A~800A.

Model rated current (A) current setting range (A) Appropriate motor power (kW)

5 1~5 0.5~2.5
10 2~10 1~5
40 8~40 4~20
100 20~100 10~50
400 80~400 40~200
800 200~800 100~400
Protection Relay Relay P-012

4.2 Auxiliary circuit: Rated insulation voltage is AC480V,and the rated frequency is 50Hz,rated impulse withstand voltage 1.2/50μs、2.5kV.

Application class AC-15


Rated operating voltage Ue (V) 240 480
Rated operating current Ie (A) 1.5 0.75
Rated thermal current Ith (A) 5

4.3 Structural features


4.3.1 Set the parameters by button with current、trip level、locked rotor 、start delay ,etc.
4.3.2 Show the information by LED display with current、setting parameters、malfunction ,etc.
4.3.3 Show the current status(running、malfunction、stop、set)by LED display.
4.3.4 Start、stop、star delta can be controlled by one key.
4.3.5 Overload protection,locked rotor protection,phase failure protection, three-phase imbalance protection,undercurrent protection,
grounding protection , PTC temperature protection and communication failure protection are available.
4.3.6 The host adopted panel installation while the transformer is rail installation or by screw.
4.3.7 The terminals are pluggable that is easy for connecting.
4.3.8 Abundant current specification,suit for motors with different power.
4.3.9 4mA~20mA current loop transmitter interface.
4.3.10 Modbus communication function,monitor and control in long distance.
4.3.11 Power consumption: ≤3VA.

5. Protection charactersitics
5.1 Operating characteristics of overload protection

Overload multiple
1.05 1.2 1.5 2 5 6 7.2 Note
Overload Operation
cur ve time (s)
Kr=1 No action 63 40 22 3.6 2.5 1.8 In conformity with Class 5
Kr=2 No action 125 80 45 7.2 5 3.5 In conformity with Class 10A
Kr=3 No action 250 160 90 14 10 6.9 In conformity with Class 10
Kr=4 No action 500 320 180 29 20 14 In conformity with Class 20
Kr=5 No action 750 480 270 43 30 21 In conformity with Class 30

5.2 Rotor locking operation characteristic Tripping characteristic curve


If the maximum current ≥ setting current value × set multiplying
factor for rotor locking, the protector will operate, and the
actuation time will be the set actuation time for rotor locking.
G
100min
5.3 Phase failure operation characteristic
50min
If the current value of any phase of the three phases is 25%
lower than the current that is setting,the protector will operate 20min
with the actuation time ≤3s.
10min
5.4 Current imbalance operation characteristic
If the three-phase current value of main loop conforms to 5min

following formula, the protector will operate, with the actuation


2min
time≤3s.
3 1min
M ax I i - Iavg 50s
i=1 ×100% ≥ Set current unbalancerate
I avg Kr=5
20s
Hereinto: Ii- Effective value per phase current
10s Kr=4
Iavg- Mean value of the three phases of currents
5s Kr=3
5.5 Undercurrent protection characteristic
Kr=2
If the minimum current ≤ setting current value × set multiplying
2s
factor for undercurrent, the protector will operate, and the Kr=1

actuation time will be the set actuation time for undercurrent. 1s


1 2 5 8
5.6 Ground protection operation characteristic ×Iset
The protector performs ground fault protection through the
external zero-sequence transducer. When the zero-sequence
current is in range of (0.9~1.1)set current , the protector will
operate, with the actuation time ≤1s.