Air System Sizing Summary for IMAM-01-BED ROOM

Project Name: CIV-003 FINAL 10-02-2018 02/11/2018


Prepared by: HTCO 10:51Õ

Air System Information


Air System Name IMAM-01-BED ROOM Number of zones 1
Equipment Class TERM Floor Area 172.2 ft²
Air System Type 2P-FC Location Doha, Qatar

Sizing Calculation Information


Calculation Months Jan to Dec Zone CFM Sizing Sum of space airflow rates
Sizing Data Calculated Space CFM Sizing Individual peak space loads

Cooling Coil Sizing Data


No cooling coil loads occurred during this calculation.

Ventilation Fan Sizing Data


Actual max CFM 21 CFM Fan motor BHP 0.00 BHP
Standard CFM 21 CFM Fan motor kW 0.00 kW
Actual max CFM/ft² 0.12 CFM/ft² Fan static 0.12 in wg

Outdoor Ventilation Air Data


Design airflow CFM 21 CFM CFM/person 4.67 CFM/person
CFM/ft² 0.12 CFM/ft²

Hourly Analysis Program v4.90 Page 1 of 42


Zone Sizing Summary for IMAM-01-BED ROOM
Project Name: CIV-003 FINAL 10-02-2018 02/11/2018
Prepared by: HTCO 10:51Õ

Air System Information


Air System Name IMAM-01-BED ROOM Number of zones 1
Equipment Class TERM Floor Area 172.2 ft²
Air System Type 2P-FC Location Doha, Qatar

Sizing Calculation Information


Calculation Months Jan to Dec Zone CFM Sizing Sum of space airflow rates
Sizing Data Calculated Space CFM Sizing Individual peak space loads

Zone Sizing Data

Maximum Maximum Zone


Cooling Design Minimum Heating Floor
Sensible Airflow Airflow Time of Load Area Zone
Zone Name (MBH) (CFM) (CFM) Peak Load (MBH) (ft²) CFM/ft²
Zone 1 6.5 344 344 Aug 1600 0.4 172.2 2.00

Terminal Unit Sizing Data - Cooling

Total Sens Coil Coil Water Time


Coil Coil Entering Leaving Flow of
Load Load DB / WB DB / WB @ 16.2 °F Peak
Zone Name (MBH) (MBH) (°F) (°F) (gpm) Load
Zone 1 11.0 6.4 73.2 / 66.0 55.9 / 55.3 1.36 Aug 1600

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Heating Htg Coil


Heating Coil Water Fan OA Vent
Coil Ent/Lvg Flow Design Fan Fan Design
Load DB @20.0 °F Airflow Motor Motor Airflow
Zone Name (MBH) (°F) (gpm) (CFM) (BHP) (kW) (CFM)
Zone 1 0.0 -1.0 / -1.0 0.00 344 0.012 0.010 21

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (MBH) Load (CFM) (MBH) (ft²) CFM/ft²
Zone 1
IMAM-01-BED ROOM 1 6.5 Aug 1600 344 0.4 172.2 2.00

Hourly Analysis Program v4.90 Page 2 of 42


Air System Design Load Summary for IMAM-01-BED ROOM
Project Name: CIV-003 FINAL 10-02-2018 02/11/2018
Prepared by: HTCO 10:51Õ

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Aug 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 114.4 °F / 85.9 °F HEATING OA DB / WB 51.0 °F / 42.8 °F
Sensible Latent Sensible Latent
ZONE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 4 ft² 83 - 4 ft² - -
Wall Transmission 140 ft² 235 - 140 ft² 141 -
Roof Transmission 172 ft² 114 - 172 ft² 144 -
Window Transmission 4 ft² 49 - 4 ft² 23 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 0 ft² 0 - 0 ft² 0 -
Floor Transmission 172 ft² 0 - 172 ft² 92 -
Partitions 144 ft² 1600 - 144 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 258 W 617 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 258 W 881 - 0 0 -
People 5 2362 4163 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 594 416 5% 20 0
>> Total Zone Loads - 6536 4579 - 421 0
Zone Conditioning - 6394 4579 - -228 0
Plenum Wall Load 30% 105 - 0 0 -
Plenum Roof Load 70% 265 - 0 0 -
Plenum Lighting Load 30% 264 - 0 0 -
Exhaust Fan Load 0 CFM 0 - 21 CFM 0 -
Ventilation Load 0 CFM 0 0 21 CFM 276 0
Ventilation Fan Load 0 CFM 0 - 21 CFM -2 -
Space Fan Coil Fans - 33 - - -33 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 7061 4579 - 13 0
Cooling Coil - 0 0 - 0 0
Terminal Unit Cooling - 6427 4567 - 0 0
Terminal Unit Heating - 0 - - 0 -
>> Total Conditioning - 6427 4567 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program v4.90 Page 3 of 42


Air System Sizing Summary for IMAM-02-BED ROOM
Project Name: CIV-003 FINAL 10-02-2018 02/11/2018
Prepared by: HTCO 10:51Õ

Air System Information


Air System Name IMAM-02-BED ROOM Number of zones 1
Equipment Class TERM Floor Area 172.2 ft²
Air System Type 2P-FC Location Doha, Qatar

Sizing Calculation Information


Calculation Months Jan to Dec Zone CFM Sizing Sum of space airflow rates
Sizing Data Calculated Space CFM Sizing Individual peak space loads

Cooling Coil Sizing Data


No cooling coil loads occurred during this calculation.

Ventilation Fan Sizing Data


Actual max CFM 21 CFM Fan motor BHP 0.00 BHP
Standard CFM 21 CFM Fan motor kW 0.00 kW
Actual max CFM/ft² 0.12 CFM/ft² Fan static 0.12 in wg

Outdoor Ventilation Air Data


Design airflow CFM 21 CFM CFM/person 4.20 CFM/person
CFM/ft² 0.12 CFM/ft²

Hourly Analysis Program v4.90 Page 4 of 42


Zone Sizing Summary for IMAM-02-BED ROOM
Project Name: CIV-003 FINAL 10-02-2018 02/11/2018
Prepared by: HTCO 10:51Õ

Air System Information


Air System Name IMAM-02-BED ROOM Number of zones 1
Equipment Class TERM Floor Area 172.2 ft²
Air System Type 2P-FC Location Doha, Qatar

Sizing Calculation Information


Calculation Months Jan to Dec Zone CFM Sizing Sum of space airflow rates
Sizing Data Calculated Space CFM Sizing Individual peak space loads

Zone Sizing Data

Maximum Maximum Zone


Cooling Design Minimum Heating Floor
Sensible Airflow Airflow Time of Load Area Zone
Zone Name (MBH) (CFM) (CFM) Peak Load (MBH) (ft²) CFM/ft²
Zone 1 5.6 296 296 Aug 1600 0.4 172.2 1.72

Terminal Unit Sizing Data - Cooling

Total Sens Coil Coil Water Time


Coil Coil Entering Leaving Flow of
Load Load DB / WB DB / WB @ 16.2 °F Peak
Zone Name (MBH) (MBH) (°F) (°F) (gpm) Load
Zone 1 10.7 5.6 73.3 / 67.1 55.6 / 55.2 1.32 Aug 1600

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Heating Htg Coil


Heating Coil Water Fan OA Vent
Coil Ent/Lvg Flow Design Fan Fan Design
Load DB @20.0 °F Airflow Motor Motor Airflow
Zone Name (MBH) (°F) (gpm) (CFM) (BHP) (kW) (CFM)
Zone 1 0.0 -1.0 / -1.0 0.00 296 0.010 0.008 21

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (MBH) Load (CFM) (MBH) (ft²) CFM/ft²
Zone 1
IMAM-02-BED ROOM 1 5.6 Aug 1600 296 0.4 172.2 1.72

Hourly Analysis Program v4.90 Page 5 of 42


Air System Design Load Summary for IMAM-02-BED ROOM
Project Name: CIV-003 FINAL 10-02-2018 02/11/2018
Prepared by: HTCO 10:51Õ

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Aug 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 114.4 °F / 85.9 °F HEATING OA DB / WB 51.0 °F / 42.8 °F
Sensible Latent Sensible Latent
ZONE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 4 ft² 83 - 4 ft² - -
Wall Transmission 140 ft² 235 - 140 ft² 141 -
Roof Transmission 172 ft² 114 - 172 ft² 144 -
Window Transmission 4 ft² 49 - 4 ft² 23 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 0 ft² 0 - 0 ft² 0 -
Floor Transmission 172 ft² 0 - 172 ft² 92 -
Partitions 0 ft² 0 - 0 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 344 W 823 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 344 W 1175 - 0 0 -
People 5 2625 4625 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 510 463 5% 20 0
>> Total Zone Loads - 5614 5088 - 421 0
Zone Conditioning - 5590 5088 - -62 0
Plenum Wall Load 30% 105 - 0 0 -
Plenum Roof Load 70% 265 - 0 0 -
Plenum Lighting Load 30% 353 - 0 0 -
Exhaust Fan Load 0 CFM 0 - 21 CFM 0 -
Ventilation Load 0 CFM 0 0 21 CFM 101 0
Ventilation Fan Load 0 CFM 0 - 21 CFM -2 -
Space Fan Coil Fans - 28 - - -28 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 6341 5088 - 10 0
Cooling Coil - 0 0 - 0 0
Terminal Unit Cooling - 5619 5085 - 0 0
Terminal Unit Heating - 0 - - 0 -
>> Total Conditioning - 5619 5085 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program v4.90 Page 6 of 42


Air System Sizing Summary for IMAM-03-SITTING
Project Name: CIV-003 FINAL 10-02-2018 02/11/2018
Prepared by: HTCO 10:51Õ

Air System Information


Air System Name IMAM-03-SITTING Number of zones 1
Equipment Class TERM Floor Area 258.3 ft²
Air System Type 2P-FC Location Doha, Qatar

Sizing Calculation Information


Calculation Months Jan to Dec Zone CFM Sizing Sum of space airflow rates
Sizing Data Calculated Space CFM Sizing Individual peak space loads

Cooling Coil Sizing Data


No cooling coil loads occurred during this calculation.

Ventilation Fan Sizing Data


Actual max CFM 47 CFM Fan motor BHP 0.00 BHP
Standard CFM 47 CFM Fan motor kW 0.00 kW
Actual max CFM/ft² 0.18 CFM/ft² Fan static 0.12 in wg

Outdoor Ventilation Air Data


Design airflow CFM 47 CFM CFM/person 6.71 CFM/person
CFM/ft² 0.18 CFM/ft²

Hourly Analysis Program v4.90 Page 7 of 42


Zone Sizing Summary for IMAM-03-SITTING
Project Name: CIV-003 FINAL 10-02-2018 02/11/2018
Prepared by: HTCO 10:51Õ

Air System Information


Air System Name IMAM-03-SITTING Number of zones 1
Equipment Class TERM Floor Area 258.3 ft²
Air System Type 2P-FC Location Doha, Qatar

Sizing Calculation Information


Calculation Months Jan to Dec Zone CFM Sizing Sum of space airflow rates
Sizing Data Calculated Space CFM Sizing Individual peak space loads

Zone Sizing Data

Maximum Maximum Zone


Cooling Design Minimum Heating Floor
Sensible Airflow Airflow Time of Load Area Zone
Zone Name (MBH) (CFM) (CFM) Peak Load (MBH) (ft²) CFM/ft²
Zone 1 9.6 508 508 Jul 1600 0.8 258.3 1.97

Terminal Unit Sizing Data - Cooling

Total Sens Coil Coil Water Time


Coil Coil Entering Leaving Flow of
Load Load DB / WB DB / WB @ 16.2 °F Peak
Zone Name (MBH) (MBH) (°F) (°F) (gpm) Load
Zone 1 16.7 9.6 73.3 / 66.1 55.8 / 55.2 2.06 Jul 1600

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Heating Htg Coil


Heating Coil Water Fan OA Vent
Coil Ent/Lvg Flow Design Fan Fan Design
Load DB @20.0 °F Airflow Motor Motor Airflow
Zone Name (MBH) (°F) (gpm) (CFM) (BHP) (kW) (CFM)
Zone 1 0.0 -1.0 / -1.0 0.00 508 0.018 0.014 47

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (MBH) Load (CFM) (MBH) (ft²) CFM/ft²
Zone 1
IMAM-03-SITTING 1 9.6 Jul 1600 508 0.8 258.3 1.97

Hourly Analysis Program v4.90 Page 8 of 42


Air System Design Load Summary for IMAM-03-SITTING
Project Name: CIV-003 FINAL 10-02-2018 02/11/2018
Prepared by: HTCO 10:51Õ

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 114.4 °F / 85.9 °F HEATING OA DB / WB 51.0 °F / 42.8 °F
Sensible Latent Sensible Latent
ZONE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 8 ft² 129 - 8 ft² - -
Wall Transmission 353 ft² 566 - 353 ft² 354 -
Roof Transmission 258 ft² 176 - 258 ft² 216 -
Window Transmission 8 ft² 98 - 8 ft² 47 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 0 ft² 0 - 0 ft² 0 -
Floor Transmission 258 ft² 0 - 258 ft² 172 -
Partitions 101 ft² 1123 - 101 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 517 W 1234 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 517 W 1763 - 0 0 -
People 7 3675 6475 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 876 648 5% 39 0
>> Total Zone Loads - 9638 7123 - 829 0
Zone Conditioning - 9514 7123 - -298 0
Plenum Wall Load 30% 250 - 0 0 -
Plenum Roof Load 70% 410 - 0 0 -
Plenum Lighting Load 30% 529 - 0 0 -
Exhaust Fan Load 0 CFM 0 - 47 CFM 0 -
Ventilation Load 0 CFM 0 0 47 CFM 371 0
Ventilation Fan Load 0 CFM 0 - 47 CFM -4 -
Space Fan Coil Fans - 49 - - -49 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 10752 7123 - 20 0
Cooling Coil - 0 0 - 0 0
Terminal Unit Cooling - 9563 7115 - 0 0
Terminal Unit Heating - 0 - - 0 -
>> Total Conditioning - 9563 7115 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program v4.90 Page 9 of 42


Air System Sizing Summary for IMAM-04-BED ROOM
Project Name: CIV-003 FINAL 10-02-2018 02/11/2018
Prepared by: HTCO 10:51Õ

Air System Information


Air System Name IMAM-04-BED ROOM Number of zones 1
Equipment Class TERM Floor Area 193.8 ft²
Air System Type 2P-FC Location Doha, Qatar

Sizing Calculation Information


Calculation Months Jan to Dec Zone CFM Sizing Sum of space airflow rates
Sizing Data Calculated Space CFM Sizing Individual peak space loads

Cooling Coil Sizing Data


No cooling coil loads occurred during this calculation.

Ventilation Fan Sizing Data


Actual max CFM 25 CFM Fan motor BHP 0.00 BHP
Standard CFM 25 CFM Fan motor kW 0.00 kW
Actual max CFM/ft² 0.13 CFM/ft² Fan static 0.12 in wg

Outdoor Ventilation Air Data


Design airflow CFM 25 CFM CFM/person 5.00 CFM/person
CFM/ft² 0.13 CFM/ft²

Hourly Analysis Program v4.90 Page 10 of 42


Zone Sizing Summary for IMAM-04-BED ROOM
Project Name: CIV-003 FINAL 10-02-2018 02/11/2018
Prepared by: HTCO 10:51Õ

Air System Information


Air System Name IMAM-04-BED ROOM Number of zones 1
Equipment Class TERM Floor Area 193.8 ft²
Air System Type 2P-FC Location Doha, Qatar

Sizing Calculation Information


Calculation Months Jan to Dec Zone CFM Sizing Sum of space airflow rates
Sizing Data Calculated Space CFM Sizing Individual peak space loads

Zone Sizing Data

Maximum Maximum Zone


Cooling Design Minimum Heating Floor
Sensible Airflow Airflow Time of Load Area Zone
Zone Name (MBH) (CFM) (CFM) Peak Load (MBH) (ft²) CFM/ft²
Zone 1 7.2 378 378 Jul 1500 0.7 193.8 1.95

Terminal Unit Sizing Data - Cooling

Total Sens Coil Coil Water Time


Coil Coil Entering Leaving Flow of
Load Load DB / WB DB / WB @ 16.2 °F Peak
Zone Name (MBH) (MBH) (°F) (°F) (gpm) Load
Zone 1 12.2 7.1 73.3 / 66.0 55.8 / 55.2 1.51 Jul 1500

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Heating Htg Coil


Heating Coil Water Fan OA Vent
Coil Ent/Lvg Flow Design Fan Fan Design
Load DB @20.0 °F Airflow Motor Motor Airflow
Zone Name (MBH) (°F) (gpm) (CFM) (BHP) (kW) (CFM)
Zone 1 0.0 -1.0 / -1.0 0.00 378 0.014 0.011 25

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (MBH) Load (CFM) (MBH) (ft²) CFM/ft²
Zone 1
IMAM-04-BED ROOM 1 7.2 Jul 1500 378 0.7 193.8 1.95

Hourly Analysis Program v4.90 Page 11 of 42


Air System Design Load Summary for IMAM-04-BED ROOM
Project Name: CIV-003 FINAL 10-02-2018 02/11/2018
Prepared by: HTCO 10:51Õ

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 115.0 °F / 86.0 °F HEATING OA DB / WB 51.0 °F / 42.8 °F
Sensible Latent Sensible Latent
ZONE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 4 ft² 50 - 4 ft² - -
Wall Transmission 303 ft² 503 - 303 ft² 304 -
Roof Transmission 194 ft² 132 - 194 ft² 162 -
Window Transmission 4 ft² 49 - 4 ft² 23 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 0 ft² 0 - 0 ft² 0 -
Floor Transmission 194 ft² 0 - 194 ft² 135 -
Partitions 83 ft² 922 - 83 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 388 W 925 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 388 W 1322 - 0 0 -
People 5 2625 4625 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 653 463 5% 31 0
>> Total Zone Loads - 7181 5088 - 656 0
Zone Conditioning - 7079 5088 - -175 0
Plenum Wall Load 30% 220 - 0 0 -
Plenum Roof Load 70% 308 - 0 0 -
Plenum Lighting Load 30% 397 - 0 0 -
Exhaust Fan Load 0 CFM 0 - 25 CFM 0 -
Ventilation Load 0 CFM 0 0 25 CFM 225 0
Ventilation Fan Load 0 CFM 0 - 25 CFM -2 -
Space Fan Coil Fans - 37 - - -37 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 8040 5088 - 12 0
Cooling Coil - 0 0 - 0 0
Terminal Unit Cooling - 7116 5077 - 0 0
Terminal Unit Heating - 0 - - 0 -
>> Total Conditioning - 7116 5077 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program v4.90 Page 12 of 42


Air System Sizing Summary for IMAM-05- CORRIDOR
Project Name: CIV-003 FINAL 10-02-2018 02/11/2018
Prepared by: HTCO 10:51Õ

Air System Information


Air System Name IMAM-05- CORRIDOR Number of zones 1
Equipment Class TERM Floor Area 232.5 ft²
Air System Type 2P-FC Location Doha, Qatar

Sizing Calculation Information


Calculation Months Jan to Dec Zone CFM Sizing Sum of space airflow rates
Sizing Data Calculated Space CFM Sizing Individual peak space loads

Cooling Coil Sizing Data


No cooling coil loads occurred during this calculation.

Ventilation Fan Sizing Data


Actual max CFM 75 CFM Fan motor BHP 0.00 BHP
Standard CFM 75 CFM Fan motor kW 0.00 kW
Actual max CFM/ft² 0.32 CFM/ft² Fan static 0.12 in wg

Outdoor Ventilation Air Data


Design airflow CFM 75 CFM CFM/person 12.50 CFM/person
CFM/ft² 0.32 CFM/ft²

Hourly Analysis Program v4.90 Page 13 of 42


Zone Sizing Summary for IMAM-05- CORRIDOR
Project Name: CIV-003 FINAL 10-02-2018 02/11/2018
Prepared by: HTCO 10:51Õ

Air System Information


Air System Name IMAM-05- CORRIDOR Number of zones 1
Equipment Class TERM Floor Area 232.5 ft²
Air System Type 2P-FC Location Doha, Qatar

Sizing Calculation Information


Calculation Months Jan to Dec Zone CFM Sizing Sum of space airflow rates
Sizing Data Calculated Space CFM Sizing Individual peak space loads

Zone Sizing Data

Maximum Maximum Zone


Cooling Design Minimum Heating Floor
Sensible Airflow Airflow Time of Load Area Zone
Zone Name (MBH) (CFM) (CFM) Peak Load (MBH) (ft²) CFM/ft²
Zone 1 9.4 493 493 Jul 1500 0.5 232.5 2.12

Terminal Unit Sizing Data - Cooling

Total Sens Coil Coil Water Time


Coil Coil Entering Leaving Flow of
Load Load DB / WB DB / WB @ 16.2 °F Peak
Zone Name (MBH) (MBH) (°F) (°F) (gpm) Load
Zone 1 15.4 9.3 73.3 / 65.5 55.7 / 55.1 1.90 Jul 1500

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Heating Htg Coil


Heating Coil Water Fan OA Vent
Coil Ent/Lvg Flow Design Fan Fan Design
Load DB @20.0 °F Airflow Motor Motor Airflow
Zone Name (MBH) (°F) (gpm) (CFM) (BHP) (kW) (CFM)
Zone 1 0.0 -1.0 / -1.0 0.00 493 0.018 0.014 75

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (MBH) Load (CFM) (MBH) (ft²) CFM/ft²
Zone 1
IMAM-05- CORRIDOR 1 9.4 Jul 1500 493 0.5 232.5 2.12

Hourly Analysis Program v4.90 Page 14 of 42


Air System Design Load Summary for IMAM-05- CORRIDOR
Project Name: CIV-003 FINAL 10-02-2018 02/11/2018
Prepared by: HTCO 10:51Õ

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 115.0 °F / 86.0 °F HEATING OA DB / WB 51.0 °F / 42.8 °F
Sensible Latent Sensible Latent
ZONE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 0 ft² 0 - 0 ft² - -
Wall Transmission 45 ft² 46 - 45 ft² 45 -
Roof Transmission 233 ft² 158 - 233 ft² 195 -
Window Transmission 0 ft² 0 - 0 ft² 0 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 34 ft² 315 - 34 ft² 150 -
Floor Transmission 233 ft² 0 - 233 ft² 77 -
Partitions 72 ft² 802 - 72 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 698 W 1666 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 698 W 2380 - 0 0 -
People 6 3150 5550 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 852 555 5% 23 0
>> Total Zone Loads - 9369 6105 - 490 0
Zone Conditioning - 9285 6105 - -390 0
Plenum Wall Load 30% 52 - 0 0 -
Plenum Roof Load 70% 370 - 0 0 -
Plenum Lighting Load 30% 714 - 0 0 -
Exhaust Fan Load 0 CFM 0 - 75 CFM 0 -
Ventilation Load 0 CFM 0 0 75 CFM 470 0
Ventilation Fan Load 0 CFM 0 - 75 CFM -7 -
Space Fan Coil Fans - 48 - - -48 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 10468 6105 - 25 0
Cooling Coil - 0 0 - 0 0
Terminal Unit Cooling - 9333 6079 - 0 0
Terminal Unit Heating - 0 - - 0 -
>> Total Conditioning - 9333 6079 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program v4.90 Page 15 of 42


Air System Sizing Summary for IMAM-06- MAJLAS
Project Name: CIV-003 FINAL 10-02-2018 02/11/2018
Prepared by: HTCO 10:51Õ

Air System Information


Air System Name IMAM-06- MAJLAS Number of zones 1
Equipment Class TERM Floor Area 297.1 ft²
Air System Type 2P-FC Location Doha, Qatar

Sizing Calculation Information


Calculation Months Jan to Dec Zone CFM Sizing Sum of space airflow rates
Sizing Data Calculated Space CFM Sizing Individual peak space loads

Cooling Coil Sizing Data


No cooling coil loads occurred during this calculation.

Ventilation Fan Sizing Data


Actual max CFM 50 CFM Fan motor BHP 0.00 BHP
Standard CFM 50 CFM Fan motor kW 0.00 kW
Actual max CFM/ft² 0.17 CFM/ft² Fan static 0.12 in wg

Outdoor Ventilation Air Data


Design airflow CFM 50 CFM CFM/person 6.25 CFM/person
CFM/ft² 0.17 CFM/ft²

Hourly Analysis Program v4.90 Page 16 of 42


Zone Sizing Summary for IMAM-06- MAJLAS
Project Name: CIV-003 FINAL 10-02-2018 02/11/2018
Prepared by: HTCO 10:51Õ

Air System Information


Air System Name IMAM-06- MAJLAS Number of zones 1
Equipment Class TERM Floor Area 297.1 ft²
Air System Type 2P-FC Location Doha, Qatar

Sizing Calculation Information


Calculation Months Jan to Dec Zone CFM Sizing Sum of space airflow rates
Sizing Data Calculated Space CFM Sizing Individual peak space loads

Zone Sizing Data

Maximum Maximum Zone


Cooling Design Minimum Heating Floor
Sensible Airflow Airflow Time of Load Area Zone
Zone Name (MBH) (CFM) (CFM) Peak Load (MBH) (ft²) CFM/ft²
Zone 1 11.0 581 581 Jul 1600 0.6 297.1 1.96

Terminal Unit Sizing Data - Cooling

Total Sens Coil Coil Water Time


Coil Coil Entering Leaving Flow of
Load Load DB / WB DB / WB @ 16.2 °F Peak
Zone Name (MBH) (MBH) (°F) (°F) (gpm) Load
Zone 1 19.1 10.9 73.3 / 66.1 55.8 / 55.3 2.35 Jul 1600

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Heating Htg Coil


Heating Coil Water Fan OA Vent
Coil Ent/Lvg Flow Design Fan Fan Design
Load DB @20.0 °F Airflow Motor Motor Airflow
Zone Name (MBH) (°F) (gpm) (CFM) (BHP) (kW) (CFM)
Zone 1 0.0 -1.0 / -1.0 0.00 581 0.021 0.016 50

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (MBH) Load (CFM) (MBH) (ft²) CFM/ft²
Zone 1
IMAM-06- MAJLAS 1 11.0 Jul 1600 581 0.6 297.1 1.96

Hourly Analysis Program v4.90 Page 17 of 42


Air System Design Load Summary for IMAM-06- MAJLAS
Project Name: CIV-003 FINAL 10-02-2018 02/11/2018
Prepared by: HTCO 10:51Õ

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 114.4 °F / 85.9 °F HEATING OA DB / WB 51.0 °F / 42.8 °F
Sensible Latent Sensible Latent
ZONE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 4 ft² 51 - 4 ft² - -
Wall Transmission 162 ft² 246 - 162 ft² 163 -
Roof Transmission 297 ft² 202 - 297 ft² 249 -
Window Transmission 4 ft² 49 - 4 ft² 23 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 0 ft² 0 - 0 ft² 0 -
Floor Transmission 297 ft² 0 - 297 ft² 130 -
Partitions 166 ft² 1839 - 166 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 594 W 1419 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 594 W 2027 - 0 0 -
People 8 4200 7400 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 1003 740 5% 28 0
>> Total Zone Loads - 11036 8140 - 593 0
Zone Conditioning - 10877 8140 - -463 0
Plenum Wall Load 30% 109 - 0 0 -
Plenum Roof Load 70% 471 - 0 0 -
Plenum Lighting Load 30% 608 - 0 0 -
Exhaust Fan Load 0 CFM 0 - 50 CFM 0 -
Ventilation Load 0 CFM 0 0 50 CFM 552 0
Ventilation Fan Load 0 CFM 0 - 50 CFM -4 -
Space Fan Coil Fans - 56 - - -56 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 12121 8140 - 28 0
Cooling Coil - 0 0 - 0 0
Terminal Unit Cooling - 10933 8132 - 0 0
Terminal Unit Heating - 0 - - 0 -
>> Total Conditioning - 10933 8132 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program v4.90 Page 18 of 42


Air System Sizing Summary for IMAM-07- MAJLAS
Project Name: CIV-003 FINAL 10-02-2018 02/11/2018
Prepared by: HTCO 10:51Õ

Air System Information


Air System Name IMAM-07- MAJLAS Number of zones 1
Equipment Class TERM Floor Area 297.1 ft²
Air System Type 2P-FC Location Doha, Qatar

Sizing Calculation Information


Calculation Months Jan to Dec Zone CFM Sizing Sum of space airflow rates
Sizing Data Calculated Space CFM Sizing Individual peak space loads

Cooling Coil Sizing Data


No cooling coil loads occurred during this calculation.

Ventilation Fan Sizing Data


Actual max CFM 50 CFM Fan motor BHP 0.00 BHP
Standard CFM 50 CFM Fan motor kW 0.00 kW
Actual max CFM/ft² 0.17 CFM/ft² Fan static 0.12 in wg

Outdoor Ventilation Air Data


Design airflow CFM 50 CFM CFM/person 6.25 CFM/person
CFM/ft² 0.17 CFM/ft²

Hourly Analysis Program v4.90 Page 19 of 42


Zone Sizing Summary for IMAM-07- MAJLAS
Project Name: CIV-003 FINAL 10-02-2018 02/11/2018
Prepared by: HTCO 10:51Õ

Air System Information


Air System Name IMAM-07- MAJLAS Number of zones 1
Equipment Class TERM Floor Area 297.1 ft²
Air System Type 2P-FC Location Doha, Qatar

Sizing Calculation Information


Calculation Months Jan to Dec Zone CFM Sizing Sum of space airflow rates
Sizing Data Calculated Space CFM Sizing Individual peak space loads

Zone Sizing Data

Maximum Maximum Zone


Cooling Design Minimum Heating Floor
Sensible Airflow Airflow Time of Load Area Zone
Zone Name (MBH) (CFM) (CFM) Peak Load (MBH) (ft²) CFM/ft²
Zone 1 11.0 581 581 Jul 1600 0.6 297.1 1.96

Terminal Unit Sizing Data - Cooling

Total Sens Coil Coil Water Time


Coil Coil Entering Leaving Flow of
Load Load DB / WB DB / WB @ 16.2 °F Peak
Zone Name (MBH) (MBH) (°F) (°F) (gpm) Load
Zone 1 19.1 10.9 73.3 / 66.1 55.8 / 55.3 2.35 Jul 1600

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Heating Htg Coil


Heating Coil Water Fan OA Vent
Coil Ent/Lvg Flow Design Fan Fan Design
Load DB @20.0 °F Airflow Motor Motor Airflow
Zone Name (MBH) (°F) (gpm) (CFM) (BHP) (kW) (CFM)
Zone 1 0.0 -1.0 / -1.0 0.00 581 0.021 0.016 50

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (MBH) Load (CFM) (MBH) (ft²) CFM/ft²
Zone 1
IMAM-07- MAJLAS 1 11.0 Jul 1600 581 0.6 297.1 1.96

Hourly Analysis Program v4.90 Page 20 of 42


Air System Design Load Summary for IMAM-07- MAJLAS
Project Name: CIV-003 FINAL 10-02-2018 02/11/2018
Prepared by: HTCO 10:51Õ

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 114.4 °F / 85.9 °F HEATING OA DB / WB 51.0 °F / 42.8 °F
Sensible Latent Sensible Latent
ZONE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 4 ft² 51 - 4 ft² - -
Wall Transmission 162 ft² 246 - 162 ft² 163 -
Roof Transmission 297 ft² 202 - 297 ft² 249 -
Window Transmission 4 ft² 49 - 4 ft² 23 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 0 ft² 0 - 0 ft² 0 -
Floor Transmission 297 ft² 0 - 297 ft² 130 -
Partitions 166 ft² 1839 - 166 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 594 W 1419 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 594 W 2027 - 0 0 -
People 8 4200 7400 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 1003 740 5% 28 0
>> Total Zone Loads - 11036 8140 - 593 0
Zone Conditioning - 10877 8140 - -464 0
Plenum Wall Load 30% 109 - 0 0 -
Plenum Roof Load 70% 471 - 0 0 -
Plenum Lighting Load 30% 608 - 0 0 -
Exhaust Fan Load 0 CFM 0 - 50 CFM 0 -
Ventilation Load 0 CFM 0 0 50 CFM 552 0
Ventilation Fan Load 0 CFM 0 - 50 CFM -4 -
Space Fan Coil Fans - 56 - - -56 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 12121 8140 - 28 0
Cooling Coil - 0 0 - 0 0
Terminal Unit Cooling - 10933 8132 - 0 0
Terminal Unit Heating - 0 - - 0 -
>> Total Conditioning - 10933 8132 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program v4.90 Page 21 of 42


Air System Sizing Summary for IMAM-08- KITCHEN
Project Name: CIV-003 FINAL 10-02-2018 02/11/2018
Prepared by: HTCO 10:51Õ

Air System Information


Air System Name IMAM-08- KITCHEN Number of zones 1
Equipment Class TERM Floor Area 142.1 ft²
Air System Type 2P-FC Location Doha, Qatar

Sizing Calculation Information


Calculation Months Jan to Dec Zone CFM Sizing Sum of space airflow rates
Sizing Data Calculated Space CFM Sizing Individual peak space loads

Cooling Coil Sizing Data


No cooling coil loads occurred during this calculation.

Ventilation Fan Sizing Data


Actual max CFM 50 CFM Fan motor BHP 0.00 BHP
Standard CFM 50 CFM Fan motor kW 0.00 kW
Actual max CFM/ft² 0.35 CFM/ft² Fan static 0.12 in wg

Outdoor Ventilation Air Data


Design airflow CFM 50 CFM CFM/person 12.50 CFM/person
CFM/ft² 0.35 CFM/ft²

Hourly Analysis Program v4.90 Page 22 of 42


Zone Sizing Summary for IMAM-08- KITCHEN
Project Name: CIV-003 FINAL 10-02-2018 02/11/2018
Prepared by: HTCO 10:51Õ

Air System Information


Air System Name IMAM-08- KITCHEN Number of zones 1
Equipment Class TERM Floor Area 142.1 ft²
Air System Type 2P-FC Location Doha, Qatar

Sizing Calculation Information


Calculation Months Jan to Dec Zone CFM Sizing Sum of space airflow rates
Sizing Data Calculated Space CFM Sizing Individual peak space loads

Zone Sizing Data

Maximum Maximum Zone


Cooling Design Minimum Heating Floor
Sensible Airflow Airflow Time of Load Area Zone
Zone Name (MBH) (CFM) (CFM) Peak Load (MBH) (ft²) CFM/ft²
Zone 1 5.0 261 261 Aug 1500 0.2 142.1 1.84

Terminal Unit Sizing Data - Cooling

Total Sens Coil Coil Water Time


Coil Coil Entering Leaving Flow of
Load Load DB / WB DB / WB @ 16.2 °F Peak
Zone Name (MBH) (MBH) (°F) (°F) (gpm) Load
Zone 1 8.9 4.9 72.9 / 66.5 55.7 / 55.2 1.10 Jul 1600

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Heating Htg Coil


Heating Coil Water Fan OA Vent
Coil Ent/Lvg Flow Design Fan Fan Design
Load DB @20.0 °F Airflow Motor Motor Airflow
Zone Name (MBH) (°F) (gpm) (CFM) (BHP) (kW) (CFM)
Zone 1 0.0 -1.0 / -1.0 0.00 261 0.009 0.007 50

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (MBH) Load (CFM) (MBH) (ft²) CFM/ft²
Zone 1
IMAM-08- KITCHEN 1 5.0 Aug 1500 261 0.2 142.1 1.84

Hourly Analysis Program v4.90 Page 23 of 42


Air System Design Load Summary for IMAM-08- KITCHEN
Project Name: CIV-003 FINAL 10-02-2018 02/11/2018
Prepared by: HTCO 10:51Õ

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 114.4 °F / 85.9 °F HEATING OA DB / WB 51.0 °F / 42.8 °F
Sensible Latent Sensible Latent
ZONE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 4 ft² 26 - 4 ft² - -
Wall Transmission 21 ft² 30 - 21 ft² 21 -
Roof Transmission 142 ft² 97 - 142 ft² 119 -
Window Transmission 4 ft² 49 - 4 ft² 23 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 0 ft² 0 - 0 ft² 0 -
Floor Transmission 142 ft² 0 - 142 ft² 31 -
Partitions 267 ft² 1366 - 267 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 142 W 339 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 142 W 485 - 0 0 -
People 4 2100 3700 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 449 370 5% 10 0
>> Total Zone Loads - 4940 4070 - 204 0
Zone Conditioning - 4825 4070 - -614 0
Plenum Wall Load 30% 16 - 0 0 -
Plenum Roof Load 70% 225 - 0 0 -
Plenum Lighting Load 30% 145 - 0 0 -
Exhaust Fan Load 0 CFM 0 - 50 CFM 0 -
Ventilation Load 0 CFM 0 0 50 CFM 650 0
Ventilation Fan Load 0 CFM 0 - 50 CFM -4 -
Space Fan Coil Fans - 25 - - -25 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 5237 4070 - 6 0
Cooling Coil - 0 0 - 0 0
Terminal Unit Cooling - 4850 4067 - 0 0
Terminal Unit Heating - 0 - - 0 -
>> Total Conditioning - 4850 4067 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program v4.90 Page 24 of 42


Air System Sizing Summary for IMAM-09- KITCHEN
Project Name: CIV-003 FINAL 10-02-2018 02/11/2018
Prepared by: HTCO 10:51Õ

Air System Information


Air System Name IMAM-09- KITCHEN Number of zones 1
Equipment Class TERM Floor Area 142.1 ft²
Air System Type 2P-FC Location Doha, Qatar

Sizing Calculation Information


Calculation Months Jan to Dec Zone CFM Sizing Sum of space airflow rates
Sizing Data Calculated Space CFM Sizing Individual peak space loads

Cooling Coil Sizing Data


No cooling coil loads occurred during this calculation.

Ventilation Fan Sizing Data


Actual max CFM 50 CFM Fan motor BHP 0.00 BHP
Standard CFM 50 CFM Fan motor kW 0.00 kW
Actual max CFM/ft² 0.35 CFM/ft² Fan static 0.12 in wg

Outdoor Ventilation Air Data


Design airflow CFM 50 CFM CFM/person 12.50 CFM/person
CFM/ft² 0.35 CFM/ft²

Hourly Analysis Program v4.90 Page 25 of 42


Zone Sizing Summary for IMAM-09- KITCHEN
Project Name: CIV-003 FINAL 10-02-2018 02/11/2018
Prepared by: HTCO 10:51Õ

Air System Information


Air System Name IMAM-09- KITCHEN Number of zones 1
Equipment Class TERM Floor Area 142.1 ft²
Air System Type 2P-FC Location Doha, Qatar

Sizing Calculation Information


Calculation Months Jan to Dec Zone CFM Sizing Sum of space airflow rates
Sizing Data Calculated Space CFM Sizing Individual peak space loads

Zone Sizing Data

Maximum Maximum Zone


Cooling Design Minimum Heating Floor
Sensible Airflow Airflow Time of Load Area Zone
Zone Name (MBH) (CFM) (CFM) Peak Load (MBH) (ft²) CFM/ft²
Zone 1 5.0 261 261 Aug 1500 0.2 142.1 1.84

Terminal Unit Sizing Data - Cooling

Total Sens Coil Coil Water Time


Coil Coil Entering Leaving Flow of
Load Load DB / WB DB / WB @ 16.2 °F Peak
Zone Name (MBH) (MBH) (°F) (°F) (gpm) Load
Zone 1 8.9 4.9 72.9 / 66.5 55.7 / 55.2 1.10 Jul 1600

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Heating Htg Coil


Heating Coil Water Fan OA Vent
Coil Ent/Lvg Flow Design Fan Fan Design
Load DB @20.0 °F Airflow Motor Motor Airflow
Zone Name (MBH) (°F) (gpm) (CFM) (BHP) (kW) (CFM)
Zone 1 0.0 -1.0 / -1.0 0.00 261 0.009 0.007 50

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (MBH) Load (CFM) (MBH) (ft²) CFM/ft²
Zone 1
IMAM-09- KITCHEN 1 5.0 Aug 1500 261 0.2 142.1 1.84

Hourly Analysis Program v4.90 Page 26 of 42


Air System Design Load Summary for IMAM-09- KITCHEN
Project Name: CIV-003 FINAL 10-02-2018 02/11/2018
Prepared by: HTCO 10:51Õ

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 114.4 °F / 85.9 °F HEATING OA DB / WB 51.0 °F / 42.8 °F
Sensible Latent Sensible Latent
ZONE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 4 ft² 26 - 4 ft² - -
Wall Transmission 21 ft² 30 - 21 ft² 21 -
Roof Transmission 142 ft² 97 - 142 ft² 119 -
Window Transmission 4 ft² 49 - 4 ft² 23 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 0 ft² 0 - 0 ft² 0 -
Floor Transmission 142 ft² 0 - 142 ft² 31 -
Partitions 267 ft² 1366 - 267 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 142 W 339 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 142 W 485 - 0 0 -
People 4 2100 3700 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 449 370 5% 10 0
>> Total Zone Loads - 4940 4070 - 204 0
Zone Conditioning - 4825 4070 - -614 0
Plenum Wall Load 30% 16 - 0 0 -
Plenum Roof Load 70% 225 - 0 0 -
Plenum Lighting Load 30% 145 - 0 0 -
Exhaust Fan Load 0 CFM 0 - 50 CFM 0 -
Ventilation Load 0 CFM 0 0 50 CFM 650 0
Ventilation Fan Load 0 CFM 0 - 50 CFM -4 -
Space Fan Coil Fans - 25 - - -25 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 5237 4070 - 6 0
Cooling Coil - 0 0 - 0 0
Terminal Unit Cooling - 4850 4067 - 0 0
Terminal Unit Heating - 0 - - 0 -
>> Total Conditioning - 4850 4067 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program v4.90 Page 27 of 42


Air System Sizing Summary for IMAM-10- CORRIDOR
Project Name: CIV-003 FINAL 10-02-2018 02/11/2018
Prepared by: HTCO 10:51Õ

Air System Information


Air System Name IMAM-10- CORRIDOR Number of zones 1
Equipment Class TERM Floor Area 232.5 ft²
Air System Type 2P-FC Location Doha, Qatar

Sizing Calculation Information


Calculation Months Jan to Dec Zone CFM Sizing Sum of space airflow rates
Sizing Data Calculated Space CFM Sizing Individual peak space loads

Cooling Coil Sizing Data


No cooling coil loads occurred during this calculation.

Ventilation Fan Sizing Data


Actual max CFM 75 CFM Fan motor BHP 0.00 BHP
Standard CFM 75 CFM Fan motor kW 0.00 kW
Actual max CFM/ft² 0.32 CFM/ft² Fan static 0.12 in wg

Outdoor Ventilation Air Data


Design airflow CFM 75 CFM CFM/person 12.50 CFM/person
CFM/ft² 0.32 CFM/ft²

Hourly Analysis Program v4.90 Page 28 of 42


Zone Sizing Summary for IMAM-10- CORRIDOR
Project Name: CIV-003 FINAL 10-02-2018 02/11/2018
Prepared by: HTCO 10:51Õ

Air System Information


Air System Name IMAM-10- CORRIDOR Number of zones 1
Equipment Class TERM Floor Area 232.5 ft²
Air System Type 2P-FC Location Doha, Qatar

Sizing Calculation Information


Calculation Months Jan to Dec Zone CFM Sizing Sum of space airflow rates
Sizing Data Calculated Space CFM Sizing Individual peak space loads

Zone Sizing Data

Maximum Maximum Zone


Cooling Design Minimum Heating Floor
Sensible Airflow Airflow Time of Load Area Zone
Zone Name (MBH) (CFM) (CFM) Peak Load (MBH) (ft²) CFM/ft²
Zone 1 9.4 493 493 Jul 1500 0.5 232.5 2.12

Terminal Unit Sizing Data - Cooling

Total Sens Coil Coil Water Time


Coil Coil Entering Leaving Flow of
Load Load DB / WB DB / WB @ 16.2 °F Peak
Zone Name (MBH) (MBH) (°F) (°F) (gpm) Load
Zone 1 15.4 9.3 73.3 / 65.5 55.7 / 55.1 1.90 Jul 1500

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Heating Htg Coil


Heating Coil Water Fan OA Vent
Coil Ent/Lvg Flow Design Fan Fan Design
Load DB @20.0 °F Airflow Motor Motor Airflow
Zone Name (MBH) (°F) (gpm) (CFM) (BHP) (kW) (CFM)
Zone 1 0.0 -1.0 / -1.0 0.00 493 0.018 0.014 75

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (MBH) Load (CFM) (MBH) (ft²) CFM/ft²
Zone 1
IMAM-10- CORRIDOR 1 9.4 Jul 1500 493 0.5 232.5 2.12

Hourly Analysis Program v4.90 Page 29 of 42


Air System Design Load Summary for IMAM-10- CORRIDOR
Project Name: CIV-003 FINAL 10-02-2018 02/11/2018
Prepared by: HTCO 10:51Õ

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 115.0 °F / 86.0 °F HEATING OA DB / WB 51.0 °F / 42.8 °F
Sensible Latent Sensible Latent
ZONE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 0 ft² 0 - 0 ft² - -
Wall Transmission 45 ft² 46 - 45 ft² 45 -
Roof Transmission 233 ft² 158 - 233 ft² 195 -
Window Transmission 0 ft² 0 - 0 ft² 0 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 34 ft² 315 - 34 ft² 150 -
Floor Transmission 233 ft² 0 - 233 ft² 77 -
Partitions 72 ft² 802 - 72 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 698 W 1666 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 698 W 2380 - 0 0 -
People 6 3150 5550 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 852 555 5% 23 0
>> Total Zone Loads - 9369 6105 - 490 0
Zone Conditioning - 9285 6105 - -391 0
Plenum Wall Load 30% 52 - 0 0 -
Plenum Roof Load 70% 370 - 0 0 -
Plenum Lighting Load 30% 714 - 0 0 -
Exhaust Fan Load 0 CFM 0 - 75 CFM 0 -
Ventilation Load 0 CFM 0 0 75 CFM 470 0
Ventilation Fan Load 0 CFM 0 - 75 CFM -7 -
Space Fan Coil Fans - 47 - - -47 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 10468 6105 - 25 0
Cooling Coil - 0 0 - 0 0
Terminal Unit Cooling - 9332 6079 - 0 0
Terminal Unit Heating - 0 - - 0 -
>> Total Conditioning - 9332 6079 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program v4.90 Page 30 of 42


Air System Sizing Summary for IMAM-11-BED ROOM
Project Name: CIV-003 FINAL 10-02-2018 02/11/2018
Prepared by: HTCO 10:51Õ

Air System Information


Air System Name IMAM-11-BED ROOM Number of zones 1
Equipment Class TERM Floor Area 193.8 ft²
Air System Type 2P-FC Location Doha, Qatar

Sizing Calculation Information


Calculation Months Jan to Dec Zone CFM Sizing Sum of space airflow rates
Sizing Data Calculated Space CFM Sizing Individual peak space loads

Cooling Coil Sizing Data


No cooling coil loads occurred during this calculation.

Ventilation Fan Sizing Data


Actual max CFM 25 CFM Fan motor BHP 0.00 BHP
Standard CFM 25 CFM Fan motor kW 0.00 kW
Actual max CFM/ft² 0.13 CFM/ft² Fan static 0.12 in wg

Outdoor Ventilation Air Data


Design airflow CFM 25 CFM CFM/person 5.00 CFM/person
CFM/ft² 0.13 CFM/ft²

Hourly Analysis Program v4.90 Page 31 of 42


Zone Sizing Summary for IMAM-11-BED ROOM
Project Name: CIV-003 FINAL 10-02-2018 02/11/2018
Prepared by: HTCO 10:51Õ

Air System Information


Air System Name IMAM-11-BED ROOM Number of zones 1
Equipment Class TERM Floor Area 193.8 ft²
Air System Type 2P-FC Location Doha, Qatar

Sizing Calculation Information


Calculation Months Jan to Dec Zone CFM Sizing Sum of space airflow rates
Sizing Data Calculated Space CFM Sizing Individual peak space loads

Zone Sizing Data

Maximum Maximum Zone


Cooling Design Minimum Heating Floor
Sensible Airflow Airflow Time of Load Area Zone
Zone Name (MBH) (CFM) (CFM) Peak Load (MBH) (ft²) CFM/ft²
Zone 1 7.8 412 412 Aug 1600 0.7 193.8 2.13

Terminal Unit Sizing Data - Cooling

Total Sens Coil Coil Water Time


Coil Coil Entering Leaving Flow of
Load Load DB / WB DB / WB @ 16.2 °F Peak
Zone Name (MBH) (MBH) (°F) (°F) (gpm) Load
Zone 1 12.9 7.8 73.3 / 65.6 55.8 / 55.2 1.59 Aug 1600

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Heating Htg Coil


Heating Coil Water Fan OA Vent
Coil Ent/Lvg Flow Design Fan Fan Design
Load DB @20.0 °F Airflow Motor Motor Airflow
Zone Name (MBH) (°F) (gpm) (CFM) (BHP) (kW) (CFM)
Zone 1 0.0 -1.0 / -1.0 0.00 412 0.015 0.012 25

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (MBH) Load (CFM) (MBH) (ft²) CFM/ft²
Zone 1
IMAM-11-BED ROOM 1 7.8 Aug 1600 412 0.7 193.8 2.13

Hourly Analysis Program v4.90 Page 32 of 42


Air System Design Load Summary for IMAM-11-BED ROOM
Project Name: CIV-003 FINAL 10-02-2018 02/11/2018
Prepared by: HTCO 10:51Õ

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Aug 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 114.4 °F / 85.9 °F HEATING OA DB / WB 51.0 °F / 42.8 °F
Sensible Latent Sensible Latent
ZONE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 4 ft² 83 - 4 ft² - -
Wall Transmission 303 ft² 505 - 303 ft² 304 -
Roof Transmission 194 ft² 128 - 194 ft² 162 -
Window Transmission 4 ft² 49 - 4 ft² 23 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 0 ft² 0 - 0 ft² 0 -
Floor Transmission 194 ft² 0 - 194 ft² 135 -
Partitions 83 ft² 920 - 83 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 484 W 1157 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 484 W 1653 - 0 0 -
People 5 2625 4625 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 712 463 5% 31 0
>> Total Zone Loads - 7831 5088 - 656 0
Zone Conditioning - 7730 5088 - -171 0
Plenum Wall Load 30% 221 - 0 0 -
Plenum Roof Load 70% 298 - 0 0 -
Plenum Lighting Load 30% 496 - 0 0 -
Exhaust Fan Load 0 CFM 0 - 25 CFM 0 -
Ventilation Load 0 CFM 0 0 25 CFM 226 0
Ventilation Fan Load 0 CFM 0 - 25 CFM -2 -
Space Fan Coil Fans - 40 - - -40 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 8784 5088 - 13 0
Cooling Coil - 0 0 - 0 0
Terminal Unit Cooling - 7769 5085 - 0 0
Terminal Unit Heating - 0 - - 0 -
>> Total Conditioning - 7769 5085 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program v4.90 Page 33 of 42


Air System Sizing Summary for IMAM-12-BED ROOM
Project Name: CIV-003 FINAL 10-02-2018 02/11/2018
Prepared by: HTCO 10:51Õ

Air System Information


Air System Name IMAM-12-BED ROOM Number of zones 1
Equipment Class TERM Floor Area 172.2 ft²
Air System Type 2P-FC Location Doha, Qatar

Sizing Calculation Information


Calculation Months Jan to Dec Zone CFM Sizing Sum of space airflow rates
Sizing Data Calculated Space CFM Sizing Individual peak space loads

Cooling Coil Sizing Data


No cooling coil loads occurred during this calculation.

Ventilation Fan Sizing Data


Actual max CFM 21 CFM Fan motor BHP 0.00 BHP
Standard CFM 21 CFM Fan motor kW 0.00 kW
Actual max CFM/ft² 0.12 CFM/ft² Fan static 0.12 in wg

Outdoor Ventilation Air Data


Design airflow CFM 21 CFM CFM/person 4.67 CFM/person
CFM/ft² 0.12 CFM/ft²

Hourly Analysis Program v4.90 Page 34 of 42


Zone Sizing Summary for IMAM-12-BED ROOM
Project Name: CIV-003 FINAL 10-02-2018 02/11/2018
Prepared by: HTCO 10:51Õ

Air System Information


Air System Name IMAM-12-BED ROOM Number of zones 1
Equipment Class TERM Floor Area 172.2 ft²
Air System Type 2P-FC Location Doha, Qatar

Sizing Calculation Information


Calculation Months Jan to Dec Zone CFM Sizing Sum of space airflow rates
Sizing Data Calculated Space CFM Sizing Individual peak space loads

Zone Sizing Data

Maximum Maximum Zone


Cooling Design Minimum Heating Floor
Sensible Airflow Airflow Time of Load Area Zone
Zone Name (MBH) (CFM) (CFM) Peak Load (MBH) (ft²) CFM/ft²
Zone 1 6.5 344 344 Jul 1500 0.4 172.2 2.00

Terminal Unit Sizing Data - Cooling

Total Sens Coil Coil Water Time


Coil Coil Entering Leaving Flow of
Load Load DB / WB DB / WB @ 16.2 °F Peak
Zone Name (MBH) (MBH) (°F) (°F) (gpm) Load
Zone 1 11.0 6.4 73.2 / 66.0 55.9 / 55.3 1.36 Jul 1500

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Heating Htg Coil


Heating Coil Water Fan OA Vent
Coil Ent/Lvg Flow Design Fan Fan Design
Load DB @20.0 °F Airflow Motor Motor Airflow
Zone Name (MBH) (°F) (gpm) (CFM) (BHP) (kW) (CFM)
Zone 1 0.0 -1.0 / -1.0 0.00 344 0.012 0.010 21

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (MBH) Load (CFM) (MBH) (ft²) CFM/ft²
Zone 1
IMAM-12-BED ROOM 1 6.5 Jul 1500 344 0.4 172.2 2.00

Hourly Analysis Program v4.90 Page 35 of 42


Air System Design Load Summary for IMAM-12-BED ROOM
Project Name: CIV-003 FINAL 10-02-2018 02/11/2018
Prepared by: HTCO 10:51Õ

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 115.0 °F / 86.0 °F HEATING OA DB / WB 51.0 °F / 42.8 °F
Sensible Latent Sensible Latent
ZONE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 4 ft² 50 - 4 ft² - -
Wall Transmission 140 ft² 255 - 140 ft² 141 -
Roof Transmission 172 ft² 117 - 172 ft² 144 -
Window Transmission 4 ft² 49 - 4 ft² 23 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 0 ft² 0 - 0 ft² 0 -
Floor Transmission 172 ft² 0 - 172 ft² 92 -
Partitions 144 ft² 1604 - 144 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 258 W 617 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 258 W 881 - 0 0 -
People 5 2362 4163 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 594 416 5% 20 0
>> Total Zone Loads - 6530 4579 - 421 0
Zone Conditioning - 6393 4579 - -228 0
Plenum Wall Load 30% 114 - 0 0 -
Plenum Roof Load 70% 274 - 0 0 -
Plenum Lighting Load 30% 264 - 0 0 -
Exhaust Fan Load 0 CFM 0 - 21 CFM 0 -
Ventilation Load 0 CFM 0 0 21 CFM 276 0
Ventilation Fan Load 0 CFM 0 - 21 CFM -2 -
Space Fan Coil Fans - 33 - - -33 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 7078 4579 - 13 0
Cooling Coil - 0 0 - 0 0
Terminal Unit Cooling - 6426 4568 - 0 0
Terminal Unit Heating - 0 - - 0 -
>> Total Conditioning - 6426 4568 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program v4.90 Page 36 of 42


Air System Sizing Summary for IMAM-13-BED ROOM
Project Name: CIV-003 FINAL 10-02-2018 02/11/2018
Prepared by: HTCO 10:51Õ

Air System Information


Air System Name IMAM-13-BED ROOM Number of zones 1
Equipment Class TERM Floor Area 172.2 ft²
Air System Type 2P-FC Location Doha, Qatar

Sizing Calculation Information


Calculation Months Jan to Dec Zone CFM Sizing Sum of space airflow rates
Sizing Data Calculated Space CFM Sizing Individual peak space loads

Cooling Coil Sizing Data


No cooling coil loads occurred during this calculation.

Ventilation Fan Sizing Data


Actual max CFM 21 CFM Fan motor BHP 0.00 BHP
Standard CFM 21 CFM Fan motor kW 0.00 kW
Actual max CFM/ft² 0.12 CFM/ft² Fan static 0.12 in wg

Outdoor Ventilation Air Data


Design airflow CFM 21 CFM CFM/person 2.10 CFM/person
CFM/ft² 0.12 CFM/ft²

Hourly Analysis Program v4.90 Page 37 of 42


Zone Sizing Summary for IMAM-13-BED ROOM
Project Name: CIV-003 FINAL 10-02-2018 02/11/2018
Prepared by: HTCO 10:51Õ

Air System Information


Air System Name IMAM-13-BED ROOM Number of zones 1
Equipment Class TERM Floor Area 172.2 ft²
Air System Type 2P-FC Location Doha, Qatar

Sizing Calculation Information


Calculation Months Jan to Dec Zone CFM Sizing Sum of space airflow rates
Sizing Data Calculated Space CFM Sizing Individual peak space loads

Zone Sizing Data

Maximum Maximum Zone


Cooling Design Minimum Heating Floor
Sensible Airflow Airflow Time of Load Area Zone
Zone Name (MBH) (CFM) (CFM) Peak Load (MBH) (ft²) CFM/ft²
Zone 1 6.5 343 343 Jul 1500 0.4 172.2 1.99

Terminal Unit Sizing Data - Cooling

Total Sens Coil Coil Water Time


Coil Coil Entering Leaving Flow of
Load Load DB / WB DB / WB @ 16.2 °F Peak
Zone Name (MBH) (MBH) (°F) (°F) (gpm) Load
Zone 1 11.5 6.5 73.5 / 66.4 55.8 / 55.3 1.42 Jul 1500

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Heating Htg Coil


Heating Coil Water Fan OA Vent
Coil Ent/Lvg Flow Design Fan Fan Design
Load DB @20.0 °F Airflow Motor Motor Airflow
Zone Name (MBH) (°F) (gpm) (CFM) (BHP) (kW) (CFM)
Zone 1 0.0 -1.0 / -1.0 0.00 343 0.012 0.010 21

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (MBH) Load (CFM) (MBH) (ft²) CFM/ft²
Zone 1
IMAM-13-BED ROOM 1 6.5 Jul 1500 343 0.4 172.2 1.99

Hourly Analysis Program v4.90 Page 38 of 42


Air System Design Load Summary for IMAM-13-BED ROOM
Project Name: CIV-003 FINAL 10-02-2018 02/11/2018
Prepared by: HTCO 10:51Õ

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 115.0 °F / 86.0 °F HEATING OA DB / WB 51.0 °F / 42.8 °F
Sensible Latent Sensible Latent
ZONE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 4 ft² 50 - 4 ft² - -
Wall Transmission 140 ft² 255 - 140 ft² 141 -
Roof Transmission 172 ft² 117 - 172 ft² 144 -
Window Transmission 4 ft² 49 - 4 ft² 23 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 0 ft² 0 - 0 ft² 0 -
Floor Transmission 172 ft² 0 - 172 ft² 92 -
Partitions 0 ft² 0 - 0 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 431 W 1028 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 431 W 1469 - 0 0 -
People 10 2950 4550 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 592 455 5% 20 0
>> Total Zone Loads - 6511 5005 - 421 0
Zone Conditioning - 6484 5005 - -59 0
Plenum Wall Load 30% 114 - 0 0 -
Plenum Roof Load 70% 274 - 0 0 -
Plenum Lighting Load 30% 441 - 0 0 -
Exhaust Fan Load 0 CFM 0 - 21 CFM 0 -
Ventilation Load 0 CFM 0 0 21 CFM 104 0
Ventilation Fan Load 0 CFM 0 - 21 CFM -2 -
Space Fan Coil Fans - 33 - - -33 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 7345 5005 - 11 0
Cooling Coil - 0 0 - 0 0
Terminal Unit Cooling - 6517 5001 - 0 0
Terminal Unit Heating - 0 - - 0 -
>> Total Conditioning - 6517 5001 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program v4.90 Page 39 of 42


Air System Sizing Summary for IMAM-14-SITTING
Project Name: CIV-003 FINAL 10-02-2018 02/11/2018
Prepared by: HTCO 10:51Õ

Air System Information


Air System Name IMAM-14-SITTING Number of zones 1
Equipment Class TERM Floor Area 258.3 ft²
Air System Type 2P-FC Location Doha, Qatar

Sizing Calculation Information


Calculation Months Jan to Dec Zone CFM Sizing Sum of space airflow rates
Sizing Data Calculated Space CFM Sizing Individual peak space loads

Cooling Coil Sizing Data


No cooling coil loads occurred during this calculation.

Ventilation Fan Sizing Data


Actual max CFM 47 CFM Fan motor BHP 0.00 BHP
Standard CFM 47 CFM Fan motor kW 0.00 kW
Actual max CFM/ft² 0.18 CFM/ft² Fan static 0.12 in wg

Outdoor Ventilation Air Data


Design airflow CFM 47 CFM CFM/person 5.88 CFM/person
CFM/ft² 0.18 CFM/ft²

Hourly Analysis Program v4.90 Page 40 of 42


Zone Sizing Summary for IMAM-14-SITTING
Project Name: CIV-003 FINAL 10-02-2018 02/11/2018
Prepared by: HTCO 10:51Õ

Air System Information


Air System Name IMAM-14-SITTING Number of zones 1
Equipment Class TERM Floor Area 258.3 ft²
Air System Type 2P-FC Location Doha, Qatar

Sizing Calculation Information


Calculation Months Jan to Dec Zone CFM Sizing Sum of space airflow rates
Sizing Data Calculated Space CFM Sizing Individual peak space loads

Zone Sizing Data

Maximum Maximum Zone


Cooling Design Minimum Heating Floor
Sensible Airflow Airflow Time of Load Area Zone
Zone Name (MBH) (CFM) (CFM) Peak Load (MBH) (ft²) CFM/ft²
Zone 1 10.2 538 538 Jul 1600 0.8 258.3 2.08

Terminal Unit Sizing Data - Cooling

Total Sens Coil Coil Water Time


Coil Coil Entering Leaving Flow of
Load Load DB / WB DB / WB @ 16.2 °F Peak
Zone Name (MBH) (MBH) (°F) (°F) (gpm) Load
Zone 1 18.3 10.1 73.3 / 66.5 55.8 / 55.3 2.26 Jul 1600

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Heating Htg Coil


Heating Coil Water Fan OA Vent
Coil Ent/Lvg Flow Design Fan Fan Design
Load DB @20.0 °F Airflow Motor Motor Airflow
Zone Name (MBH) (°F) (gpm) (CFM) (BHP) (kW) (CFM)
Zone 1 0.0 -1.0 / -1.0 0.00 538 0.019 0.015 47

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (MBH) Load (CFM) (MBH) (ft²) CFM/ft²
Zone 1
IMAM-14-SITTING 1 10.2 Jul 1600 538 0.8 258.3 2.08

Hourly Analysis Program v4.90 Page 41 of 42


Air System Design Load Summary for IMAM-14-SITTING
Project Name: CIV-003 FINAL 10-02-2018 02/11/2018
Prepared by: HTCO 10:51Õ

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 114.4 °F / 85.9 °F HEATING OA DB / WB 51.0 °F / 42.8 °F
Sensible Latent Sensible Latent
ZONE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 8 ft² 98 - 8 ft² - -
Wall Transmission 353 ft² 604 - 353 ft² 354 -
Roof Transmission 258 ft² 176 - 258 ft² 216 -
Window Transmission 8 ft² 98 - 8 ft² 47 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 0 ft² 0 - 0 ft² 0 -
Floor Transmission 258 ft² 0 - 258 ft² 172 -
Partitions 101 ft² 1123 - 101 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 517 W 1234 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 517 W 1763 - 0 0 -
People 8 4200 7400 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 929 740 5% 39 0
>> Total Zone Loads - 10224 8140 - 829 0
Zone Conditioning - 10098 8140 - -296 0
Plenum Wall Load 30% 267 - 0 0 -
Plenum Roof Load 70% 410 - 0 0 -
Plenum Lighting Load 30% 529 - 0 0 -
Exhaust Fan Load 0 CFM 0 - 47 CFM 0 -
Ventilation Load 0 CFM 0 0 47 CFM 373 0
Ventilation Fan Load 0 CFM 0 - 47 CFM -4 -
Space Fan Coil Fans - 52 - - -52 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 11355 8140 - 21 0
Cooling Coil - 0 0 - 0 0
Terminal Unit Cooling - 10150 8134 - 0 0
Terminal Unit Heating - 0 - - 0 -
>> Total Conditioning - 10150 8134 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program v4.90 Page 42 of 42