The Bus Connection Unit 560BCU05 is designed The Bus Connection Unit 560BCU05 is used in
to make the RTU560s TSI, TSO, Alarm and Warn- the racks 23ET24 and 560SFR02. It is mounted
ing signals accessible to the outside. on the back-side of the rack, and fixed by four
snap-in holders (see figure 2)
By using the bus connection unit 560BCU05, up
to eight communication units (CMUs) can be used The connection to the RTU560 communication
in a configuration. units is made via up to eight connectors to slots
occupied by CMUx Modules. Two connector ca-
To expand the RTU560 system bus to another
bles are delivered with the 560BCU05 R0001.
rack (23ET24, 560SFR02), an 8 pole RJ45 con-
Additional connector cables are available as
nector is available. For cabling, a shielded 8 pole
560BCU05 R0002.
RJ45 patch cable can be used.
All supply voltages and control signals are inter-
faced by a direct Board-to-Board connection. To
enable operation using a 23ET24 rack, +24V
needs to be connected to a screw terminal con-
nector.
The two system signals ALARM and WARNING
can be accessed via relay contacts and are su-
pervised by a watchdog function. If the trigger
from the communication unit is missing for more
than 30 seconds, both relay contacts are acti-
vated.
The external minute interrupt of a real time clock
560RTCxx is connected to the system via an in-
ternal isolated opto-coupler (TSI) and routed to
the time master of the RTU560 system. The min-
ute pulse output (TSO) is available for other appli-
cations.
Board-to-Board connection
BCU05
Mounting
stand-off´s
560SFR02
backplane
Technical Data
In addition to the general technical data of the
RTU560, the following applies:
Voltage Supply
Minute Pulse Input (TSI)
Supply 5 V DC / approx. 80 mA
TSI Plug-in terminal strip 2-pole, 24 V DC / approx. 60 mA
24 VDC input, isolated
Signal Outputs
Connection Type
ALARM Plug-in terminal strips 2-pole
WARNING each Connectors 2 - 8 sub-connectors with flat
cable, 18-pole each
Relay contact Active closed, WARNING is
set also in case of ALARM.
≤ 1 A / ≤ 60 V DC / ≤ 30 W Environmental Conditions
ABB AG