0% found this document useful (0 votes)
28 views59 pages

Toaz - Info Smacna Leakage 2020 PR

Uploaded by

ahmed.el-sherif
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
28 views59 pages

Toaz - Info Smacna Leakage 2020 PR

Uploaded by

ahmed.el-sherif
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 59

HVAC System Air Leakage

2019
Presented By:
Mark Terzigni
Director of Engineering
Technical Services
SMACNA
Learning Objectives

• Understand the difference between “System” leakage


and “Duct” leakage
• Understand what information is required to properly
specify system leakage tests
• Understand what various codes and standards require
for duct air leakage testing
• Understand misconceptions related to leakage testing
What is “Duct Leakage”

• Duct leakage is the leakage of air from DUCT

• Equipment leakage is the leakage of air from


EQUIPMENT

• Accessory leakage is the leakage of air from


ACCESSORIES
System Leakage

• HVAC Air System Leakage is the combination of duct, equipment


and accessory leakage.

• DUCT leakage is not SYSTEM leakage


Energy Impacts

• Not all air leaks have the same impact on energy


• Leaks on the return can introduce “raw” air
• Supply leaks, especially into unconditioned space reduce the
amount conditioned air impacting indoor environmental
comfort
• Supply leaks into conditioned space do deliver the “energy” but
not to the intended area
• Because the impacts are different it is impossible to directly
relate a CFM of leakage to a specific energy loss.
Is Testing Justified?

• Many people agree that testing at least a portion of the


ductwork is justified.

• How much should you test?

• What sections of duct should you test?


How much to test?

• The majority of energy codes/standards require 25% of the “high‐pressure”


duct to be tested…

• ASHRAE 90.1 2010/13/16


• 6.4.4.2.2 Duct Leakage Tests. Ductwork that is designed to operate at static pressures
in excess of 3 in. w.c. and all ductwork located outdoors shall be leak‐tested
according to industry‐accepted test procedures (see Informative Appendix E).
Representative sections totaling no less than 25% of the total installed duct area for
the designated pressure class shall be tested. All sections shall be selected by the
building owner or the designated representative of the building owner. Positive
pressure leakage testing is acceptable for negative pressure ductwork.
How much to test?

• IECC 2012/2015/2018:
• 503.2.7.1.3 High‐pressure duct systems. …shall be leak
tested in accordance with the SMACNA HVAC Air Duct
Leakage Test Manual… Documentation shall be furnished by
the designer demonstrating that representative sections
totaling at least 25 percent of the duct area have been
tested…
How much to test?

• Some believe that 100% testing is required, and it is the


only way “to be sure”…

• Perhaps a more practical approach is the 25‐50‐100


approach…
How much to test?

• Currently proposed language would require duct (not system)


leakage testing in the base mechanical code for California.
• The latest proposal requires at least 10% of the duct (by surface
area) be tested.
• Additional testing is required if initial testing indicates issues
with performance.
What about “low‐pressure” duct?

• This is where discretion must be used.

• “…low pressure duct leaks more than high pressure


duct…”
• This statement is true if the duct is tested at the same
pressure, especially in older buildings where the seal class
varied by pressure class.
What about “low‐pressure” duct?

• As seal class “A” becomes the norm the difference in


leakage (at the same pressure) will likely decrease or
perhaps disappear altogether. So under operating
conditions the potential leakage for the low pressure
side would be lower because the operating pressure
would be lower
What about “low‐pressure” duct?

• Leakage is also a function of the “size of the hole” which


means it is a function of the amount of duct used.

• If the majority of duct is low pressure it may be justified


to test some of it.

• USE 25‐50‐100 (10‐20‐100)


Code Update

• IAPMO Green Plumbing and Mechanical Code Supplement


• Duct Leakage Tests. Ductwork that is designed to operate at static pressures in excess of 3 inches
Water Column (0.75 kPa) and all ductwork located outdoors shall be leak‐tested according to the
ANSI/SMACNA HVAC Air Duct Leakage Test Manual. Representative sections totaling no less than 25
20% percent of the total installed duct area for that designated pressure class shall be tested.
Should the tested 20% fail to meet the requirements of this section, then 40% of the total installed
duct area shall be tested. Should the tested 40% fail to meet the requirements of this section, then
100% of the total installed duct area shall be tested. All sections shall be selected by the building
owner or the designated representative of the building owner. Positive pressure leakage testing is
acceptable for negative pressure ductwork. The maximum permitted duct leakage shall be:
Code Update

• IAPMO Uniform Mechanical Code


• Duct Leakage Tests. Ductwork that is designed to operate at static pressures in excess of 3 inches
Water Column (0.75 kPa) and all ductwork located outdoors shall be leak‐tested according to the
ANSI/SMACNA HVAC Air Duct Leakage Test Manual. Representative sections totaling no less than 25
10% percent of the total installed duct area for that designated pressure class shall be tested.
Should the tested 20% fail to meet the requirements of this section, then 40% of the total installed
duct area shall be tested. Should the tested 40% fail to meet the requirements of this section, then
100% of the total installed duct area shall be tested. All sections shall be selected by the building
owner or the designated representative of the building owner. Positive pressure leakage testing is
acceptable for negative pressure ductwork. The maximum permitted duct leakage shall be:
Other standards

• Traditionally duct operating “in excess” of 3 in. wg was


tested.
• Current proposals include 3 in. wg
• Some make all duct fair game.
• CMC no limit on pressure
• 10% minimum proposed
• CEC no limit on pressure
• 25% minimum proposed
Duct or System Testing?

• To this point all of the codes and “used” energy standards only
require duct testing
• None specifically require true system testing
• Some residential address the “system” but still call it “duct” leakage
• The pass/fail criteria used are arbitrary
• All Commercial versions use SMACNA’s approach for duct
leakage pass/fail for commercial duct.
• Concept works for residential as well
Why not use a % to fan flow?

• Leakage is a function of pressure


• And the “size of the hole”

F  CL P N
Why not use a % to fan flow?

• As mentioned earlier Leakage is a function of pressure, and it is


a function of “the size of the hole”

• Leakage is not a function of the volume of air


• Leakage is not a function conditioned floor space
Why not use a % to fan flow?

• ASHRAE RP 1292
Why not use a % to fan flow?

Figure 5‐10 shows a plot of the percentage leakage as a


function of the supply airflow from the eight inch
terminal units. In general, the percent of leakage
(Qleakage divided by Qprimary) increased as the
primary airflow decreased.
Why not use a % to fan flow?

• Put simply as the “fan flow” decreased the percentage


of leakage increased…

• This is likely because the leakage itself stayed nearly


constant because the test pressure was the same.
Why not use a % to fan flow

Cl = 80
N = 0.5
Why not use a % to fan flow?

Cl = 80
N = 0.5
Why not use % to fan flow?

• Originally we (SMACNA) could not get nice curves for VAV boxes
• We tried to get leakage for the whole box to fit a curve
• Turned out the data worked once we treated a VAV box as a “box” and
a “damper”
• Damper leakage was a constant at a given pressure
• Not a function of surface area
• The “box” does leak as a function of surface area and pressure
Why not use a % to fan flow?

Cl = 3
N = 0.5
Per “rod” not area
Why not use a % to fan flow?

Cl = 5
N = 0.5
Per “rod” not area
Control Rod for Fire Damper

Do NOT apply
sealant at these
locations
Real Issue to Avoid

• When arbitrary requirements for pass/fail are used and are also
misapplied the contractor is forced to decide what to comply
with.
• What happens when a spec differs from
codes/standards/warranties/listings (UL)?
• The SMACNA standard will require designers to “prove” a
system was designed to meet the performance specs.
Why not use a % to fan flow?

• ALL of the codes/standards mentioned earlier use a


leakage class for duct, not a percent.
• 90.1 class 4 all duct
• IECC class 4 all duct
• IAPMO GPMCS class 4 all duct
Why not use a % to fan flow?

• ASHRAE RP 1292
Active Tests vs Static Tests

• Active test – test performed on a completed functioning system


• This method would measure the actual leakage at a given point
in time for the system under the operating conditions at that
time.
• This method is good for research studies and for attempts to
correlate energy use to leakage
• Remember though that not all leaks have the same impact
Active Tests vs Static Tests

• Static Test – current approach used for duct testing


• Allows for testing of incomplete systems
• Is a consistent basis of comparison
• Test conditions (pressure) are defined and not system dependent – test
pressure not to exceed capacity
Where can we get info on equipment or
accessories?

• The industry currently has several sources for


designers to use to get info on leakage for
equipment and accessories. There are still gaps,
and the industry is working to close them.
Equipment Leakage Test

• ASHRAE Standard 193 authorized September 30, 2006.


Method of Testing for Determining the Air‐Leakage Rate of
HVAC Equipment
• Published mid‐summer 2010.
• 1. PURPOSE:
• This standard prescribes a method of testing to determine the air‐
leakage rate of forced‐air heating, and cooling HVAC equipment, prior
to field installation.
Equipment Leakage Test

• 2. SCOPE:
• 2.1 This standard applies to the following:
a) Equipment intended for installation in ducted systems, including
furnaces, heat pumps, air conditioners, coil boxes, filter boxes, and
associated components.
b) Equipment that moves less than 3000 cfm (1400 L/S) of air.
• 2.2 It does not apply to field installed components, such as plenums
or ducts.
• NOTE no PASS/FAIL criteria and does not apply to VAV boxes
Equipment Leakage Data

• ASHRAE RP 1292
• Was not the intent to evaluate leakage
• Turned out that leakage was considerable

• Leakage rates for boxes were 5%‐30%...That’s right, the best


boxes still hit 5% and those rates are at non‐typical operating
conditions ie 1200 cfm for and 8 in.box (v~3400 fpm)
Equipment Leakage

• AHRI Standard 1350


• Provides for casing leakage data
• Uses surface area
• Uses leakage class
• Uses N of 0.65
Accessory Leakage

• Data virtually non‐existent except for single duct VAV boxes


• Some data that exists is not applicable
• Most data on dampers – Volume/Smoke etc. measure the
leakage across the damper when the damper is closed.
• Does not measure leakage from “inside” the system to “outside”
the system
Fill the Gaps

• What to do if data does not exist


• Skip testing unknown items
• The SMACNA System Air Leakage Test Standard allows for field
evaluation of items to determine leakage rates.
• Basically you isolate the item, verify the installation, test it for leakage.
Isolated test

• Not required but encouraged to test item at 3 pressures to


develop a curve
• Must be able to determine leakage at the desired test pressure
• This method can also be used to challenge leakage allowances
of “known” items
• Any party can use this approach to either raise or lower
allowable leakage
Issues to Avoid

• Items are to be installed per manufacturer’s instructions/listing


requirements
• Do not modify portions of the system for testing, the system
should be as close to “as installed” as possible
• Testing equipment may not be finite enough to measure
difference in low leakage items – may need to test multiple
items at once and average
Issues to Avoid

• Be careful to account for every component.


• VAV box is a good example
• Also has a damper
• May have coils, filters, electric reheat, etc.
• Each of those items impact leakage rates
Quote from Manufacturer

“It is extremely important to specify and order the


correct product. Field repairs or modifications
almost always result in a loss of UL certification.
If repairs or modifications are required, the AHJ
must be consulted.”
Why not use a “system” value

• If we are going to test a “system” we need to verify that


“specification” meets “expectation”
• If the system fails a test we need to be able to determine where
the deficiency is
• We need to stop assuming a value and then forcing contractors
to make those assumptions correct – we can do better than that
• Why go through the expense to test a temporarily modified
system?
“CHAIN of RESPONSIBILITY”

• The first link in the chain is the DESIGNER


• How a system performs is dependent on how it was designed
• MANUFACTURERS
• They must provide equipment that performs as “advertised”
• FABRICATOR/INSTALLERS/CONTRACTORS
• They must fabricate and install items correctly
• Code Bodies
• Must enforce codes consistently and correctly
Misconceptions

• The cost associated with testing the duct system is basically the
time and material to perform the test.

• Not true…Often the largest expense associated with testing is


the disruption to workflow or job schedule in addition to the
time and materials to perform the test.
Misconceptions

• The leakage rate determined through testing (SMACNA,


ASHRAE) is the actual leakage under operating
conditions

• Test pressures do not typically match operating pressures

• Conditions vary in modern systems


Misconceptions
Air Leakage Misconceptions

• Mean pressure:
• Standards in Europe utilize the concept of mean pressure for duct
testing.
• Example: The “high pressure” portion of a duct system requires 4 in. w.g. at the
fan but only 2 in. w.g. at the VAV boxes. The test pressure would be 3 in. w.g.
[(4+2)/2 = 3]
• The goal is to make test conditions closer to operating conditions.
Air Leakage Misconceptions

• Real life example…


• Down Stream of VAV box
• Spec’s required duct fabricated to 2 in. w.g.
• Engineer wanted leakage testing done at 4 in. w.g.
• Engineer wanted testing through flex to diffuser
• Max 2% leakage allowed (9.2 CFM)
• Typical downstream section
• 10’ o f 12 x 10 rect. Duct 12’of 9” round duct
• 1 lo‐loss tap, and 1 90° elbow
• 2 outlets (230 CFM each), 5’ flex on each
Air Leakage Misconceptions

• Let’s assume all leakage is from the rigid duct


• Total rigid duct surface area 65 ft2
• 9.2 CFM/65 ft2 x 100 = 14 cfm/100 ft2 = F
• CL = F/P0.65 = 14/40.65 =5.7 ~6
• Is this attainable? Yes and No…
• Yes, for the rigid duct in this example an average leakage class of 6 is
attainable, but not expected using the code compliant practices at the
time.
• Seal Class A and other construction options can achieve this leakage class, but
there is a cost associated with this…
Air Leakage Misconceptions

• What happens if we tested this at 2 in. w.g.?


• Per the first edition of the leakage manual the “average” leakage class for
the rigid duct is 19.
• This would permit a pass if the rigid duct leaked 19 CFM or less at 2 in. w.g.
S.P.
• Does that mean the rigid duct would leak 4%?
• Yes and No
• Yes, under these test conditions it would leak about 4%
• No, this leakage is not the same as leakage under operating conditions.
Air Leakage Misconceptions

• Reality check…
• Analysis of the system shows that it would operate 0.1 to 0.13 in.
w.g.(From VAV to diffuser)
• Includes rigid duct loss, fitting loss, flex duct loss (@15% compression), and max
static pressure for diffusers)
• Even at a leakage class of 48 (unsealed duct) at the maximum expected
operating pressure (.13 in. w.g.) the rigid duct would leak about 8 CFM
or 1.8%
This is less than the 2% or 9.2 CFM allowed by spec.
• Remember the mean pressure theory?
Air Leakage Misconceptions

• Reality check…
• Now, if we use the actual leakage class for the rigid duct (round and rect.
combined) CL = 19 @ the expected average operating pressure 0.065 in wg
• The actual leakage would be closer to 2 CFM or 0.4% leakage under operating
conditions.
• What else does this illustrate?
• Leakage testing for low pressure systems is not a good use of
time/money/effort.
• Looking at actual operating conditions your maximum benefit for this example
is 3 CFM (0.65%). That is assuming the duct goes from unsealed to sealed
Good Practices

• Test some of the system early on in the construction


process
• It will make sure that all parties involved understand
what is expected

• It will identify any potential issues early which makes


them easier and less expensive to fix
Good Practices

• Write a good specification


• Detail how much duct/system is to be tested
• 25‐50‐100
• Provide a “correct” pass/fail criterion
• AVOID arbitrary values such as X%
• Use available data from research
• Specify seal class “A” for duct
• NEVER SPECIFY TEST PRESSURES GREATER THAN THE
CONSTRUCTION CLASS
Summary

• Testing 100% of the system is rarely justified


• Testing ductwork does not reduce leakage
• Sealing ductwork reduces leakage
• Account for all items being tested
• Make sure data applies to test conditions

• There is no consensus based method to determine a correct


pass/fail criteria for the system – yet…

You might also like