Toaz - Info Smacna Leakage 2020 PR
Toaz - Info Smacna Leakage 2020 PR
2019
Presented By:
Mark Terzigni
Director of Engineering
Technical Services
SMACNA
Learning Objectives
• IECC 2012/2015/2018:
• 503.2.7.1.3 High‐pressure duct systems. …shall be leak
tested in accordance with the SMACNA HVAC Air Duct
Leakage Test Manual… Documentation shall be furnished by
the designer demonstrating that representative sections
totaling at least 25 percent of the duct area have been
tested…
How much to test?
• To this point all of the codes and “used” energy standards only
require duct testing
• None specifically require true system testing
• Some residential address the “system” but still call it “duct” leakage
• The pass/fail criteria used are arbitrary
• All Commercial versions use SMACNA’s approach for duct
leakage pass/fail for commercial duct.
• Concept works for residential as well
Why not use a % to fan flow?
F CL P N
Why not use a % to fan flow?
• ASHRAE RP 1292
Why not use a % to fan flow?
Cl = 80
N = 0.5
Why not use a % to fan flow?
Cl = 80
N = 0.5
Why not use % to fan flow?
• Originally we (SMACNA) could not get nice curves for VAV boxes
• We tried to get leakage for the whole box to fit a curve
• Turned out the data worked once we treated a VAV box as a “box” and
a “damper”
• Damper leakage was a constant at a given pressure
• Not a function of surface area
• The “box” does leak as a function of surface area and pressure
Why not use a % to fan flow?
Cl = 3
N = 0.5
Per “rod” not area
Why not use a % to fan flow?
Cl = 5
N = 0.5
Per “rod” not area
Control Rod for Fire Damper
Do NOT apply
sealant at these
locations
Real Issue to Avoid
• When arbitrary requirements for pass/fail are used and are also
misapplied the contractor is forced to decide what to comply
with.
• What happens when a spec differs from
codes/standards/warranties/listings (UL)?
• The SMACNA standard will require designers to “prove” a
system was designed to meet the performance specs.
Why not use a % to fan flow?
• ASHRAE RP 1292
Active Tests vs Static Tests
• 2. SCOPE:
• 2.1 This standard applies to the following:
a) Equipment intended for installation in ducted systems, including
furnaces, heat pumps, air conditioners, coil boxes, filter boxes, and
associated components.
b) Equipment that moves less than 3000 cfm (1400 L/S) of air.
• 2.2 It does not apply to field installed components, such as plenums
or ducts.
• NOTE no PASS/FAIL criteria and does not apply to VAV boxes
Equipment Leakage Data
• ASHRAE RP 1292
• Was not the intent to evaluate leakage
• Turned out that leakage was considerable
• The cost associated with testing the duct system is basically the
time and material to perform the test.
• Mean pressure:
• Standards in Europe utilize the concept of mean pressure for duct
testing.
• Example: The “high pressure” portion of a duct system requires 4 in. w.g. at the
fan but only 2 in. w.g. at the VAV boxes. The test pressure would be 3 in. w.g.
[(4+2)/2 = 3]
• The goal is to make test conditions closer to operating conditions.
Air Leakage Misconceptions
• Reality check…
• Analysis of the system shows that it would operate 0.1 to 0.13 in.
w.g.(From VAV to diffuser)
• Includes rigid duct loss, fitting loss, flex duct loss (@15% compression), and max
static pressure for diffusers)
• Even at a leakage class of 48 (unsealed duct) at the maximum expected
operating pressure (.13 in. w.g.) the rigid duct would leak about 8 CFM
or 1.8%
This is less than the 2% or 9.2 CFM allowed by spec.
• Remember the mean pressure theory?
Air Leakage Misconceptions
• Reality check…
• Now, if we use the actual leakage class for the rigid duct (round and rect.
combined) CL = 19 @ the expected average operating pressure 0.065 in wg
• The actual leakage would be closer to 2 CFM or 0.4% leakage under operating
conditions.
• What else does this illustrate?
• Leakage testing for low pressure systems is not a good use of
time/money/effort.
• Looking at actual operating conditions your maximum benefit for this example
is 3 CFM (0.65%). That is assuming the duct goes from unsealed to sealed
Good Practices