100 BED DISTRICT HOSPITAL, AZARA, ASSAM
INDEX
S.NO DESCRIPTION
01. SCOPE
Page 2 of 8
100 BED DISTRICT HOSPITAL, AZARA, ASSAM
1. SCOPE
This criterion covers the structural design basis for Proposed “100 BED DISTRICT HOSPITAL, AZARA,
ASSAM". The buildings will be made with RCC framed structure with cast-in-situ columns, beams and
slabs to suit the approved/ finalised architectural drawings. The buildings are multi-storey buildings with
floors at different levels, as per various architectural drawings.
The buildings shall be as per the Architectural requirement for civil and structural works, standard
specifications, relevant I.S. codes and local regulations.
All the design shall be based on Indian standard & codes as specified here.
• IS-875 (Part 1,2,4, & 5)-1987 - Code of Practice for Design Loads (Other Than Earthquake) For
Buildings and Structures
• IS-875 (Part 3)-2015 - Code of Practice for Design Loads (Other Than Earthquake) For Buildings and
Structures
• Code IS 1786 -2008 - Specification for high strength deformed steel bars and wires for concrete
reinforcement
• IS 1904 - Indian Standard Code of Practice for Design and Construction of Foundation in Soils:
General requirements.
• In addition to above any additional code wherever applicable to be followed. In absence of Indian
codes, international codes to be followed. In case of revisions in code, latest codes to be followed.
Page 3 of 8
3. LOADS AND FORCES
Loads and forces used for design shall be as defined in IS875, and is specified below.
Sunk load shall be taken considering the density of filling above 150mm as 8kN/ m3 and filling below 150mm
as 20 kN/ m3, wherever required.
Live load for building and structure shall be in accordance with IS875 part 2 unless otherwise specified or
required by the user or equipment requirement for areas not covered underneath.
Live Load
a) Ward 3 kN/m2
b) Laboratory 3 kN/m2
c) Staff room 3 kN/m2
d) Passage, Balcony, Stairs 4 kN/m2
e) Toilet 2 kN/m2
f) Bedrooms/ 2 kN/m2
Dorms
h) Lift M/C Room (Impact Loading) 10 kN/m2
i) Terrace 1.5 kN/m2 (Accessible Roof)
j) Resident doctor 3 kN/m 2
Wind load to be applied for structures shall be in accordance with IS875 part 3, and noted below.
• Basic wind speed, Vb, shall be 50m/sec
• Risk coefficient ‘K1’ shall be equal to 1.0. (Design Life considered is 50 years.)
Page 4 of 8
• Terrain Height & Structure Height factor ‘K2’ shall be obtained from Table 2 IS 875 part 3.
Terrain Category – 3 (Considering scattered buildings around the project structure).
• Topographic factor K3 = 1.0
• Importance factor for the cyclonic region,K4 = 1.0
• Wind Directionality Factor, Kd= 0.9 (for buildings, solid signs, open signs, lattice frameworks, and
trussed towers (triangular, square, rectangular)
• Wind Directionality Factor, Kd= 1.0 (for circular or near-circular forms)
• Area averaging Factor, Ka (as per Cl. 7.2.2, IS 875 Part 3:2016)
• Combination Factor, Kc (as per Cl. 7.3.3.13, IS 875 Part 3:2016)
Seismic loads to be applied for structures shall be in accordance with the applicable
E = AhX W
The approximate fundamental natural period of vibration (Ta) in seconds, of buildings, shall be estimated
T = 0.09 x h / (d)0.5 (For moment-resisting frame buildings with brick infill panels)
Where
d = length of the building the considered direction of earthquake
h= height of the building
4. COMBINATION OF LOADS
Page 5 of 8
Concrete structural members shall be designed to have, at all sections, a calculated strength necessary to
carry the following factored loads and forces as per table 18 of IS 456.
Wind load & earthquake load will not act in tandem & each one to be checked with provisions of
combinations as per design/loading codes. In the above combinations, wind to be substituted for
earthquake & checked in additional combinations.
All concrete design shall conform to IS456-2000, unless noted otherwise. The detailing of concrete
RCC retaining walls will be provided in accordance with Architectural drawings in the basement periphery
considering cracked section. Water proofing lining/layer for wall area under water and active earth pressure
6. DESIGN PARAMETERS
RCC structures shall be designed based on limit state method of design as given in IS: 456-2000 & ductility
provision in detailing of RCC structures shall be considered judiciously based on IS: 13920-2016 for Lateral
force resisting elements or the structure. The following parameters shall be used:
RCC grade shall be as per drawings in accordance with clause 6.0 (Table 5) of IS 456-2000 for all. Minimum
Environmental Exposure condition for all structure shall be considered as Moderate as per Clause 8.2.2.1 of
7. BUILDING MOVEMENT
Vertical Deflection
The deflection shall generally be limited to the following:
Page 6 of 8
a) The final deflection due to all loads including the effects of temperature, creep and shrinkage and
measured from the as-cast level of the supports of floors, roofs and all other horizontal members, should
partitions and the application of finishes should not normally exceed span/350 or 20 mm whichever is less.
8. HORIZONTAL DEFLECTION
Horizontal movement will occur due to creep shrinkage, temperature effect and Drift due to
These movements will occur throughout construction and during the life of the building.
Drift:
The storey drifts in any storey due to the minimum specified design lateral force, with partial load factor of
1.0shall not exceed 0.004 times the storey height.
Lateral sway:
Under transient wind load the lateral sway at the top should not exceed H/500, where H is the total height
of the building.
9. SOFTWARE USED
ETABS & SAFE, a Product of Computers and Structures Inc. & STAAD Pro a product of Bentley Engineers,
along with MS Excel shall be used for the analysis & design of the structure.
Allowable bearing pressures and/or pile capacities shall be in accordance with soil report.
Page 7 of 8