Presentation - Slides PATTILLO Fire Resistant Design and Detailing 9.24.20
Presentation - Slides PATTILLO Fire Resistant Design and Detailing 9.24.20
OR…..
Fire Resistance Ratings – IBC 703.3
Fire Partition:
• Dwelling Unit
Separation;
Corridors
• Openings are
protected
• May terminate at a Fire Barrier Fire walls
FRT Wood
Thinner framing
with dropped
Joist hanger if joists ceiling allows
perpendicular to main mechanical
wall lines to run in
corridor
Interior Fire-Rated Walls: Differences
Fire Barrier
• Shafts, Occupancy
Separation
• Openings are
protected and
limited
Fire Partition: • Continuous from Fire walls
• Fire Barriers:
§ May be constructed with any
materials permitted by the
construction type
§ Fire Resistance Ratings:
• Shaft Enclosures: IBC 713.4
• 2 Hr when connecting 4
stories or more, 1 hr if
less
• Separated Occupancies: IBC
Table 508.4
• Fire Areas: IBC Table
707.3.10
Fire Barriers – IBC 707
• 707.5: Continuity: Fire barriers shall extend from the top of the
foundation or floor/ceiling assembly below to the underside of the floor
or roof sheathing, slab or deck above and shall be securely attached
thereto. Such fire barriers shall be continuous through concealed space,
such as the space above a suspended ceiling
Fire walls
• Building
Separation
• Openings are
protected and
limited
Fire Partition: Fire Barrier • Continuous from
• Dwelling Unit • Shafts, foundation
Separation;
Corridors
Occupancy
Separation to/through roof
• Openings are
protected
• Openings are
protected and and exterior wall
• May terminate
at a fire rated •
limited
Continuous to/through
floor/ceiling/r
oof assembly
from floor
through exterior wall
concealed
space at each
level
• Structural stability
Fire Walls – IBC 706
Building 1 Building 2
Fire Walls - Horizontal Continuity
EXTERIOR WALL
FIRE WALL EXTENDS
MIN. 18" BEYOND EXT.
SURFACE OF EXT. WALL
• V
AIR GAP
0' " 1"
RESILIENT DRAFT STOPS AT
MAX. 10' O.C. HORIZONTAL
Construction
Type:
• V
2 Hour Fire Wall Assembly
WOOD STRUCTURAL PANELS WHERE REQUIRED FOR SHEAR
Types:
• III
AIR GAP
• IV
AIR GAP
0' " 1"
2 1/2" METAL STUDS AT 24" O.C.
BATT INSULATION (OPTIONAL)
INTERIOR OR EXTERIOR FINISH AS REQUIRED
GA WP 1548 2 LAYERS 5/8" TYPE 'X' GYP. BD. ON EACH SIDE OF METAL STUDS
Construction
Types:
• III
• IV
• V
Also see UL
U336
Fire Walls – Ratings & Materials
Opportunity for Wood Framed Fire Walls:
• Permitted in type V Construction
• Fire Walls in type V Construction of
A, B, E, R and several other
occupancies may be 2 hour
Fire Walls in type III and IV construction
are required to be constructed of non-
combustible materials
• Opportunity for wood frame bearing
walls on each side of fire wall to meet
structural stability requirements
3 Hour Fire Wall Assembly
Construction
Types:
• III
• IV
• V • (2) 1” Type X Gypsum
• 2” H Studs
• 2” mineral fiber insulation
each side
Types:
• III
• IV
AIR GAP
0' " 1"
• V
AIR GAP
0' " 1"
1 5/8" METAL STUDS AT 24" O.C. MAX.
BATT INSULATION (OPTIONAL)
INTERIOR OR EXTERIOR FINISH AS REQUIRED
3 LAYERS 1/2" TYPE 'X' GYP. BD. ON EACH SIDE OF METAL STUDS
RESILIENT CHANNELS
RESILIENT CHANNELS
Yes!
PARTITION WALL
RATED FLOOR
ASSEMBLY
to match horizontal
assembly
• IBC 2015 714.4.2, Except. 7:
Permitted if wall is covered
DOUBLE TOP PLATE OF WALL
with type X gypsum each PARTITION WALL INTERRUPTS CEILING GYPSUM
side
INTERIOR WALL TO FLOOR INTERSECTION
Joint vs. Assembly Intersection
SECTION 202
DEFINITIONS
http://www.woodworks.org/ask-an-expert/
Light Frame Bearing Walls – 2018 IBC