Error Analysis of CVT in The Operation Environment
Error Analysis of CVT in The Operation Environment
Abstract—The capacitor voltage transformer (CVT) is a potential transformers fail to power off in fact, otherwise
potential transformer (PT) composed of capacitive voltage production and living power will be impacted [8]. In addition,
divider and electromagnetic unit. In high voltage classes, the error characteristics of the CVT are easily interrupted by
capacitor voltage transformer has the advantage of simpler surroundings, CVT environment is different from actual
structure and lower cost in comparison with electromagnetic operating environment when off-line error detection is made
potential transformer (PT), so potential transformers with according to the verification regulation, which will result in
voltage class of 220kV and above are CVT basically. certain deviations between off-line detection data and actual
Transformer acts as an important link of power trade measuring operation conditions, and the off-line error data fail to
system, and its accuracy is directly related to the justness and
completely reflect error characteristics of potential transformer
fairness of power trade. CVT at transformer substation is usually
installed outdoor and often runs in different natural
during actual operation.
environments, while periodic detection is adopted for CVT, but An online monitoring system for capacitor voltage
there is no relevant research on the impacts of CVT error transformer error is developed in this paper, and it is applied to
characteristics from the natural environment during actual 500kV Xinduqiao Transformer Substation for real-time
operation. In this paper, online monitoring system is used to monitoring of CVT error characteristics.
compare a good-stability bus with line CVT, taking PT as
standard, so as to research the CVT error characteristics in
actual operation cases. As the result indicated, ratio error and II. SYSTEM DESIGNE
angle error of the CVT present regular changes within 24h, two
extreme inflection points of the ratio error respectively occur at A. Selecting a Template (Heading 2)
6:00 a.m. and 4:00 p.m., representing shifting towards negative Online monitoring system for capacitor voltage transformer
values, similar phase errors, but no out-of-tolerance. error developed in this paper is referred to Fig.1. This online
monitoring system consists of voltage monitoring device ADU-
Keywords—Capacitor voltage transformer; Online monitoring; 100, data processing device DPU-100, clock synchronization
Error; Accuracy; Inflection point
device TDU-200, exchanger, server and remote receiving end.
The integral accuracy of the system is grade 0.05, with
I. INTRODUCTION synchronous error less than 2us.
In comparison with an electromagnetic potential PT A phase PT B phase PT C phase CVT A phase CVT B phase CVT C phase
transformer (PT), the capacitor voltage transformer (CVT) has
such advantages as high insulating strength, generation of no
ferromagnetic resonance, cheaper price and so on. As for ADUˉ100 ˄1˅
Voltage monitoring device
ADUˉ100 ˄2˅
Voltage monitoring device
gateway measuring at transformer substation with voltage class
of 220kV and above, voltages are mostly measured by CVT [1- Synchronous
optical fiber
DPUˉ100
Synchronous
optical fiber
4]. CVT is mainly composed of capacitive voltage divider, Synchronous
optical fiber
Data processing device
Fig.2 Scene drawing of ADU-100