Simocode Pro 2017 Katalog (En)
Simocode Pro 2017 Katalog (En)
SIRIUS
Industrial Controls
SIMOCODE pro 3UF7 Motor
Management and Control Devices
Catalog Edition
Abridged April
IC 10 A 2017 siemens.com/simocode
© Siemens AG 2017
Related catalogs
Related catalogs Miscellaneous
E86060-K1010-A101-A7-7600 E86060-D4001-A510-D7-7600
E86060-K7010-A101-A3-7600 www.siemens.com/tst
E86060-K6710-A101-B8-7600 www.siemens.com/sirius/catalogs
[email protected]
E86060-K4670-A101-B5-7600 (include the catalog name in the subject field)
SITOP KT 10.1
Power supply Technical Assistance
SITOP
Industrial Controls
SIRIUS 1 Introduction
2 Industrial Communication
3 Switching Devices –
Contactors and Contactor Assemblies –
for Switching Motors
4 Switching Devices –
Contactors and Contactor Assemblies –
Special Applications
5 Switching Devices –
Contactors and Contactor Assemblies –
Contactor Relays and Relays
Catalog Abridged IC 10 A · 04/2017 6 Switching Devices –
Soft Starters and Solid-State Switching
Catalog Abridged IC 10 A · 04/2017 is an abridged version Devices
of Catalog IC 10 · 2017 with updated content.
This content replaces the corresponding sections of 7 Protection Equipment
Catalog IC 10 · 2017.
Refer to the Industry Mall for current updates of
Catalog IC 10: 8 Load Feeders and Motor Starters
www.siemens.com/industrymall for Use in the Control Cabinet
Please contact your local Siemens branch.
11 Safety Technology
Industrial Controls
Ordering notes
3SU1900-0AB71-0AB0
SD: 5 working days
PG: 41J
Order quantity 10 units or a multiple thereof
Dimensions
All dimensions in mm.
10
© Siemens AG 2017
10
information. 10/134 General data
Timing relays
Article No. 10/35 General data 10/138 Relays, analogically adjustable for
10/36 SIRIUS 3RP25 timing relays 1 sensor
3RA1943-2C
3RA1943-2B 17.5 mm and 22.5 mm 10/141 Relays, digitally adjustable for 1 sensor
3RA1953-2B 10/48 SIRIUS 3RP20 timing relays, 45 mm 10/142 Relays, digitally adjustable for up to
IC01_00413
3RA1953-2N 3 sensors
10/54 7PV15 timing relays, 17.5 mm
3/100 SIRIUS 3RA28 solid-state time-delay 10/144 Accessories
Or directly in the Internet, e. g.
www.siemens.com/ auxiliary switch blocks for mounting SIRIUS 3RS14, 3RS15 temperature
product?3RA1943-2C onto 3RT2 contactors and monitoring relays for IO-Link
3RH2 contactor relays 10/145 General data
Notes: 3/105 SIRIUS 3RA28 function modules for 10/151 Relays, digitally adjustable for 1 sensor
mounting onto 3RT2 contactors and 10/154 Relays, digitally adjustable for up to
3RT191. function modules can be found 3RH2 contactor relays 3 sensors
- in the Catalog Add-On IC 10 AO · 2016 10/59 SIRIUS 3RT19 timing relays for 10/156 Accessories
in the Information and Download Center mounting onto 3RT1 contactors 10/157 SIRIUS 3RN2 thermistor motor
- in the interactive Catalog CA 01 SIRIUS 3RR21, 3RR22 monitoring relays protection
for mounting onto 3RT2 contactors Coupling relays and signal converters/
- in the Industry Mall
10/62 Current and active current monitoring interface converters
SIRIUS 3RR24 monitoring relays 5/33 Coupling relays
Conversion tool, e.g. from 3UG3 to 3UG4 for mounting onto 3RT2 contactors for
3/151 3TG10 power relays/miniature
or from 3RS17 to 3RS70 see IO-Link
www.siemens.com/sirius/conversion-tool 10/70 contactors
Current and active current monitoring
10/166 SIRIUS 3RS70 signal converters
Siemens IC 10 A · 04/2017
© Siemens AG 2017
© Siemens AG 2017
■ Overview
Expansion SIMOCODE
possibilities pro C pro S pro V1)
PROFIBUS PROFIBUS PROFIBUS2) PROFINET
Modbus RTU2) EtherNet/IP
Operator panels ✓ ✓ ✓ ✓
Operator panels -- -- ✓ ✓
with display
Current measuring ✓ ✓ ✓ ✓
modules
Current/voltage -- -- ✓ ✓
measuring
modules
Decoupling -- -- ✓ ✓
modules
Expansion
modules:
• Digital modules -- -- 2 2
• Fail-safe digital -- -- 1 1
SIMOCODE pro S for efficient entry into motor management and modules3)
SIMOCODE pro V for maximum functionality
• Analog modules -- -- 1 2
More information • Ground-fault -- -- 1 1
modules
Home page, see www.siemens.com/simocode
• Temperature -- -- 1 2
Industry Mall, see www.siemens.com/product?3UF7 modules
SIMOCODE pro is a flexible, modular motor management • Multifunction -- 1 -- --
system for motors with constant speeds in the low-voltage modules
performance range. It optimizes the connection between I&C ✓ Available
and motor feeder, increases plant availability and allows signifi- -- Not available
cant savings to be made for installation, commissioning, 1)
Maximum of five expansion modules.
operation and maintenance of a system. 2)
When an operator panel with display and/or a decoupling module are
SIMOCODE pro offers, for example: used, more restrictions on the number of expansion modules connectable
per basic unit must be observed, see page 10/14.
• Multifunctional, solid-state full motor protection that is 3)
The fail-safe digital module can be used instead of one of the two digital
independent of the automation system modules.
• Integrated control functions instead of hardware for the motor
control
Per feeder each system always comprises one basic unit and
• Detailed operational, service and diagnostics data one separate current measuring module. The two modules are
• Open communication via PROFIBUS DP, PROFINET/OPC UA, connected together electrically through the system interface
10
Modbus RTU or EtherNet/IP with a connection cable and can be mounted mechanically
connected as a unit (one behind the other) or separately (side
• Safety relay function for the fail-safe disconnection of motors
by side). The motor current to be monitored is decisive only for
up to SIL 3 (IEC 61508, IEC 62061) or PL e with Category 4
the choice of the current measuring module.
(EN ISO 13849-1)
• SIMOCODE ES is the software package for SIMOCODE pro An operator panel for mounting in the control cabinet door is
parameterization, start up and diagnostics. optionally connectable through a second system interface on
the basic unit. Both the current measuring module and the
Device series operator panel are electrically supplied by the basic unit through
the connection cable. More inputs, outputs and functions can be
SIMOCODE pro C
added to the SIMOCODE pro V and SIMOCODE pro S by means
The compact system for direct-on-line starters and reversing of optional expansion modules, thus supplementing the inputs
starters or for controlling a motor starter protector. and outputs already existing on the basic unit. With the
DM-F Local and DM-F PROFIsafe fail-safe digital modules it is
SIMOCODE pro S also possible to integrate the fail-safe disconnection of motors in
The smart system for direct-on-line, reversing, and wye-delta the SIMOCODE pro V motor management system.
starters or for controlling a motor starter protector or soft starter. All modules are connected by connection cables. The connec-
Its expandability with a multifunction module provides compre- tion cables are available in various lengths. The maximum
hensive input/output project data volume, precise ground-fault distance between the modules (e.g. between the basic unit and
detection via the 3UL23 residual-current transformers and the current measuring module) must not exceed 2.5 m. The total
temperature measurement. length of all the connection cables per system interface of the
SIMOCODE pro V basic unit may be up to 3 m.
The variable system with all control functions and with the possi- Note:
bility of expanding the inputs, outputs and functions of the SIMOCODE pro can also be found in the TIA Selection Tool. The
system at will using expansion modules various system components can therefore be conveniently
selected; see www.siemens.com/tia-selection-tool.
Communication
Functions
Communication at basic unit via:
PROFIBUS
Optional expansions
Current/voltage Basic unit Operator Earth-fault Temperature Digital modules Analog
measuring module panel module module Standard Fail-safe module
SIMOCODE pro V
Communication
Functions
10
IC01_00532
■ Benefits
General customer benefits Recording of measuring curves
• Integrating the whole motor feeder into the process control by SIMOCODE pro can record measuring curves and therefore is
means of PROFIBUS DP, PROFINET/OPC UA, Modbus RTU or able, for example, to present the progression of motor current
EtherNet/IP significantly reduces the wiring between the motor during motor start up.
feeder and the PLC.
• Decentralization of the automated processes by means of Flexible motor control implemented with integrated control
configurable control and monitoring functions in the feeder functions (instead of comprehensive hardware interlocks)
saves resources in the automation system and ensures full Many predefined motor control functions have already been
functionality and protection of the feeder even if the I&C or bus integrated into SIMOCODE pro, including all necessary logic
system fails operations and interlocks:
• The acquisition and monitoring of operating, service and • Overload relays
diagnostics data in the feeder and process control system • Direct-on-line and reversing starters
increases plant availability as well as maintenance and
service-friendliness • Wye/delta starters (also with direction reversal)
• The high degree of modularity allows users to perfectly imple- • Two speeds, motors with separate windings
ment their plant-specific requirements for each motor feeder (pole-changing starter); also with direction reversal
• The SIMOCODE pro system offers functionally graded and • Two speeds, motors with separate Dahlander windings
space-saving solutions for each customer application (also with direction reversal)
• The replacement of the control circuit hardware with inte- • Positioner actuation
grated control functions decreases the number of hardware • Solenoid valve actuation
components and wiring required and in this way limits stock • Actuation of a motor starter protector
keeping costs and potential wiring errors
• Soft starter actuation (also with direction reversal)
• The use of electronic full motor protection permits better
utilization of the motors and ensures long-term stability of the These control functions are predefined in SIMOCODE pro and
tripping characteristic and reliable tripping even after years of can be freely assigned to the inputs and outputs of the device
service (including the PROFIBUS/PROFINET process image).
• Thanks to the precision of the current, voltage, power and These predefined control functions can also be flexibly adapted
energy measurements (especially those acquired by the to each customized configuration of a motor feeder by means of
2nd-generation current/voltage measuring modules), costs freely configurable logic modules (truth tables, counters, timers,
can be internally allocated with a high degree of accuracy. edge evaluation, etc.) and with the help of standard functions
• By virtue of its wide frequency range of 20 to 400 Hz, (power failure monitoring, emergency start, external faults, etc.),
SIMOCODE can be used in combination with the 2nd-genera- without additional auxiliary relays being necessary in the control
tion current/voltage measuring modules in a a wide range of circuit.
motor applications. SIMOCODE pro makes a lot of additional hardware and wiring in
Multifunctional, electronic full motor protection the control circuit unnecessary, which results in a high level of
for rated motor currents up to 820 A standardization of the motor feeder in terms of its design and
circuit diagrams.
10
SIMOCODE pro offers comprehensive protection of the motor
feeder by means of a combination of different, multi-step and de-
layable protection and monitoring functions:
• Inverse-time delayed electronic overload protection
(CLASS 5E to 40E)
• Thermistor motor protection
• Phase failure / unbalance protection
• Stall protection
• Monitoring of adjustable limit values for the motor current
• Voltage and power monitoring
• Monitoring of the power factor (motor idling/load shedding)
• Ground-fault monitoring
• Temperature monitoring, e.g. over PT100/PT1000
• Monitoring of operating hours, downtime and number of starts
etc.
The operator panel is used to control the motor feeder and can redundancy are priorities.
replace all conventional pushbuttons and indicator lights to save SIMOCODE pro Modbus RTU
space. It makes SIMOCODE pro or the feeder directly operable
in the control cabinet. It features all the status LEDs available on SIMOCODE pro Modbus RTU supports, for example:
the basic unit and externalizes the system interface for simple • Communication at 1 200/2 400/4 800/9 600/19 200 or
parameterization or diagnosis on a PC/PG. 57 600 baud
Operator panel with display • Access to freely parameterizable process image via
Modbus RTU
As an alternative to the 3UF720 standard operator panel for
SIMOCODE pro V, a 3UF721 operator panel with display is also • Access to all operating, service and diagnostics data via
available. This can additionally indicate current measured Modbus RTU
values, operational and diagnostics data or status information of SIMOCODE pro EtherNet/IP
the motor feeder at the control cabinet. The pushbuttons of the
operator panel can be used to control the motor. Furthermore, it SIMOCODE pro EtherNet/IP supports, for example:
is possible to set parameters such as rated motor current, limit • Line and ring bus topology thanks to an integrated switch
values, etc. directly via the operator panel with display (with
SIMOCODE pro V PROFIBUS as of E15, SIMOCODE pro V • Ring structures via Device Level Ring (DLR) protocol
Modbus RTU as of E02 and with all SIMOCODE pro V PROFINET • Operating, service and diagnostics data via standard web
and EtherNet/IP). browser
• NTP-synchronized time
• Parameter assignment via SIMOCODE ES V14 – via local
device interface and Ethernet
10
Overview of the energy management process • Automatic generation of energy management data
We offer you a unique portfolio for efficient energy management • Integration into TIA Portal and into automation
in the industry – a process that is used to optimize the energy • Simple configuration
requirements. We split up our industrial energy management into
three phases – identify, evaluate, and realize – and we support For more information, see www.siemens.com/energysuite.
you with the appropriate hardware and software solutions in
every process phase.
The innovative SIRIUS industrial controls products can also
make a major contribution to the energy efficiency of a plant
(www.siemens.com/sirius/energysaving).
■ Application
SIMOCODE pro is often used for automated processes where Safety technology for SIMOCODE pro
plant downtimes are very expensive (e.g. chemical, oil/gas,
water/wastewater, steel or cement industries) and where it is The safe disconnection of motors in the process industry is
important to prevent plant downtimes through detailed opera- becoming increasingly important as the result of new and
tional, service and diagnostics data or to locate faults very revised standards and requirements in the safety technology
quickly when they occur. field.
SIMOCODE pro is modular and space-saving and suited With the DM-F Local and DM-F PROFIsafe fail-safe expansion
especially for operation in motor control centers (MCCs) in the modules it is easy to integrate functions for fail-safe disconnec-
process industry and for power plant technology. tion into the SIMOCODE pro V motor management system while
retaining service-proven concepts. The strict separation of
Applications safety functions and operational functions proves particularly
advantageous for planning, configuring and construction.
Protection and control of motors in hazardous areas for types of Seamless integration in the motor management system leads to
protection EEx e/d according to ATEX guideline 94/9/EC greater transparency for diagnostics and during operation of the
• With heavy starting (paper, cement, metal and water system.
industries)
Suitable components for this purpose are the DM-F Local and
• In high-availability plants (chemical, oil, raw material DM-F PROFIsafe fail-safe expansion modules, depending on the
processing industries, power plants) requirements:
Use of SIMOCODE pro 3UF7 with IE3/IE4 motors • The DM-F Local fail-safe digital module for when direct
assignment between a fail-safe hardware shutdown signal
Note: and a motor feeder is required, or
When using the SIMOCODE pro 3UF7 in conjunction with highly • The DM-F PROFIsafe fail-safe digital module for when a
energy-efficient IE3/IE4 motors, please observe the information fail-safe controller (F-CPU) creates the signal for disconnec-
on dimensioning and configuring; see Application Manual tion and transmits it in a fail-safe manner through
"SIRIUS Controls with IE3/IE4 motors", PROFIBUS/PROFIsafe or PROFINET/PROFIsafe to the motor
https://support.industry.siemens.com/cs/ww/en/view/94770820. management system
For more information, see Catalog IC 10, Preface.
■ Technical specifications
More information
Technical specifications, see "SIRIUS Controls with IE3/IE4 motors" Application Manual, see
https://support.industry.siemens.com/cs/ww/en/ps/16337/td https://support.industry.siemens.com/cs/ww/en/view/94770820
SIMOCODE pro - Manual Collection see Selection data for type-tested assemblies/load feeders
https://support.industry.siemens.com/cs/ww/en/view/109743951 • Manual "Configuring SIRIUS", see
"SIMOCODE pro Safety Fail-Safe Digital Modules" System Manual, see https://support.industry.siemens.com/cs/ww/en/view/40625241
https://support.industry.siemens.com/cs/ww/en/view/50564852 • Manual "Configuring SIRIUS Innovations", see
10
https://support.industry.siemens.com/cs/ww/en/view/39714188
General data
Type 3UF7
Permissible ambient temperature
• During operation °C -25 ... +60; 3UF721: 0 …+60
• During storage and transport °C -40 ... +80; 3UF721: -20 ... +70
Degree of protection (acc. to IEC 60529)
• Measuring modules with busbar connection IP00
• Operator panel (front) and door adapter (front) with cover IP54
• Other components IP20
Shock resistance (sine pulse) g/ms 15/11
Mounting position Any
Frequency Hz 50/60 5 %
EMC interference immunity (according to IEC 60947-1) Corresponds to degree of severity 3
• Conducted interference, burst acc. to IEC 61000-4-4 kV 2 (power ports)
kV 1 (signal ports)
• Conducted interference, high frequency acc. to V 10
IEC 61000-4-6
• Conducted interference, surge acc. to IEC 61000-4-5 kV 2 (line to ground); 3UF7320-1AB, 3UF7330-1AB: 1 (line to ground)
kV 1 (line to line); 3UF7320-1AB, 3UF7330-1AB: 0.5 (line to line)
• Electrostatic discharge, ESD acc. to IEC 61000-4-2 kV 8 (air discharge); 3UF7020: operator input during operation only on the front
kV 6 (contact discharge); 3UF721: 4 (contact discharge)
• Field-related interference acc. to IEC 61000-4-3 V/m 10
EMC emitted interference (according to IEC 60947-1)
• Conducted and radiated interference emission EN 55011/EN 55022 (CISPR 11/CISPR 22)
(Corresponds to degree of severity A)
Protective separation (acc. to IEC 60947-1) All circuits in SIMOCODE pro are safely separated from each other according to
IEC 60947-1, i.e. they are designed with doubled creepage paths and
clearances. In this context, compliance with the instructions in the test report
"Safe Isolation" No. 2668 is required.
Basic units
Type 3UF7000-1AU00-0, 3UF7010-1AU00-0, 3UF7000-1AB00-0, 3UF7010-1AB00-0,
3UF7011-1AU00-0, 3UF7020-1AU01-0, 3UF7011-1AB00-0, 3UF7020-1AB01-0,
3UF7012-1AU00-0, 3UF7013-1AU00-0 3UF7012-1AB00-0, 3UF7013-1AB00-0
Control circuit
Rated control supply voltage Us (acc. to IEC 61131-2) 110 ... 240 AC/DC; 50/60 Hz 24 V DC
Operating range
• SIMOCODE pro C (3UF7000) and SIMOCODE pro V PROFIBUS 0.85 ... 1.1 x Us 0.80 ... 1.2 × Us
(3UF7010) SIMOCODE pro V Modbus RTU (3UF7012)
• SIMOCODE pro V PROFINET (3UF7011), SIMOCODE pro V
EtherNet/IP (3UF7013) and SIMOCODE pro S (3UF7020)
- Operation 0.85 ... 1.1 x Us 0.80 ... 1.2 × Us
- Start up 0.85 ... 1.1 x Us 0.85 ... 1.2 × Us
Power consumption
• SIMOCODE pro C (3UF7000) and SIMOCODE pro S (3UF7020) 7 VA/5 W 5W
• SIMOCODE pro V PROFIBUS (3UF7010) and SIMOCODE pro V 10 VA/7 W 7W
Modbus RTU (3UF7012) including two connected expansion
modules
• SIMOCODE pro V PROFIBUS E15/V 4.0 7 VA/5 W 4W
(3UF7010-1A.00-0 -Z B01), incl. two connected expansion
modules
• SIMOCODE pro V PROFINET (3UF7011) and SIMOCODE pro V 11 VA/8 W 8W
EtherNet/IP (3UF7013), including two connected expansion
modules
Rated insulation voltage Ui V 300 (at pollution degree 3)
Rated impulse withstand voltage Uimp kV 4
Relay outputs
• Number
- SIMOCODE pro C, SIMOCODE pro V 3 monostable relay outputs
- SIMOCODE pro S 2 monostable relay outputs
• Specified short-circuit protection for auxiliary contacts
(relay outputs)
- Fuse links 6 A operational class gG; 10 A quick-response (IEC 60947-5-1)
- Miniature circuit breaker 1.6 A, C characteristic (IEC 60947-5-1); 6 A, C characteristic (Ik < 500 A)
• Rated uninterrupted current A 6
• Rated switching capacity
- AC-15 6 A/24 V AC 6 A/120 V AC 3 A/230 V AC
- DC-13 2 A/DC 24 V 0.55 A/DC 60 V 0.25 A/DC 125 V
Inputs (binary) 4 inputs supplied internally by the device electronics (with 24 V DC) and
connected to a common potential
Thermistor motor protection (binary PTC)
• Summation cold resistance k 1.5
• Response value k 3.4 ... 3.8
• Return value k 1.5 ... 1.65
10
Type 3UF7110- 3UF7111- 3UF7112- 3UF7113- 3UF7114-
1AA01-0 1AA01-0 1AA01-0 1.A01-0 1BA01-0
Main circuit
Set current Ie A 0.3 ... 4 3 ... +40 10 ... 115 20 ... 200 63 ... 630
Rated insulation voltage Ui V 690
Rated operational voltage Ue V 690
Rated impulse withstand voltage Uimp kV 6
Rated frequency Hz 50/60
Type of current Three-phase current
Short circuit Additional short-circuit protection is required in the main circuit
Typical voltage measuring range
• Phase-to-phase voltage/line-to-line voltage (e.g. UL1 L2) V 110 ... 690
• Phase voltage (e.g. UL1 N) V 65 ... 400
Accuracy at 25 °C, 50/60 Hz
Valid for current range A 0.25 ... 8 7.5 ... 230 15 ... 400 15 ... 400 47 ... 1260
and for voltage range • Phase-to-phase voltage VL in the range 0.85 x 110 V - 1.1 x 690 V
• Phase voltage VL in the range 0.85 x 65 V - 1.1 x 400 V
• Current measurement % 1.5
• Voltage measurement % 1.5
• Power factor measurement (p.f. 0.5) % 1.5
• Apparent power measurement (p.f. 0.5) % 3
• Active power measurement (p.f. 0.5) % 5
• Energy measurement (p.f. 0.5) % 5
• Frequency measurement (p.f. 0.5) % 1.5
Notes on voltage measurement
• Supply lines for voltage measurement In the supply lines from the main circuit for voltage measurement of
SIMOCODE pro it may be necessary to provide additional line protection!
Analog module
Type 3UF74
Control circuit
Inputs
• Channels 2 (passive)
• Parameterizable measuring ranges mA 0/4 ... 20
• Shielding Up to 30 m shield recommended, from 30 m shield required
• Max. input current (destruction limit) mA 40
• Accuracy % 1
• Input resistance 50
• Conversion time ms 150
• Resolution Bit 12
• Open-circuit detection With measuring range 4 ... 20 mA
Outputs
• Channels 1
• Parameterizable output range mA 0/4 ... 20
• Shielding Up to 30 m shield recommended, from 30 m shield required
• Max. voltage at output V DC 30
• Accuracy % 1
• Max. output load 500
• Conversion time ms 25
• Resolution Bit 12
• Short-circuit proof Yes
Connection type Two-wire connection
Electrical separation of inputs/output to the device electronics No
Fail-safe digital modules
Type 3UF7320-1AB00-0 3UF7320-1AU00-0 3UF7330-1AB00-0 3UF7330-1AU00-0
Control circuit
Rated control supply voltage Us V 24 DC 110 ... 240 AC/DC; 24 DC 110 ... 240 AC/DC;
50/60 Hz 50/60 Hz
Power consumption 3 CO 9.5 VA/4.5 W 4W 11 VA/5.5 W
Rated insulation voltage V 300
Rated impulse withstand voltage Uimp kV 4
Relay outputs
• Number 2 relay enabling circuits, 2 relay outputs
Version of the fuse link A 4, operational class gG
For short-circuit protection of the relay enabling circuit
Rated uninterrupted current A 5
Rated switching capacity
• AC-15 3 A/AC 24 V; 3 A/AC 120 V; 1.5 A/AC 230 V
• DC-13 4 A/24 V DC; 0.55 A/60 V DC; 0.22 A/125 V DC
Inputs (binary) 5 (with internal power supply from the device electronics)
10
Cable length
• Between sensor/start signal and evaluation electronics m 1500
• For further digital signals m 300
Safety data 1)
SIL level max. according to IEC 61508 3
Performance level PL according to EN ISO 13849-1 e
Category according to EN ISO 13849-1 4
Stop category according to EN 60204-1 0
Probability of a dangerous failure
(at 40 °C) for SIL 3 applications
• Per hour (PFHd) at a high demand rate 1/h 4.5 x 10-9 4.6 x 10-9 4.4 x 10-9 4.4 x 10-9
according to IEC 62061
• On demand (PFDavg) at a low demand rate 5.4 x 10-6 5.5 x 10-6 5.1 x 10-6 5.2 x 10-6
according to IEC 61508
T1 value for proof-test interval or a 20
service life according to IEC 61508
1)
More safety data, see system manual
"SIMOCODE pro Safety Fail-Safe Digital Modules",
https://support.industry.siemens.com/cs/ww/en/view/50564852.
■ More information
Configuration instructions when using an operator panel Use of a decoupling module (voltage measurement in insulated
with display and/or a decoupling module with networks) in combination with an operator panel with display
SIMOCODE pro V with PROFIBUS or Modbus RTU
Digital Digital Analog Temperature Ground-fault
If you want to use an operator panel with display and/or a decou- module 1 module 2 module module module
pling module in the SIMOCODE pro V system with PROFIBUS SIMOCODE pro V (24 V DC)
(product version earlier than E15) or Modbus RTU (product ver- ✓ -- ✓ ✓ ✓
sion earlier than E02), configuration instructions concerning the
✓ ✓ -- ✓ ✓
type and number of connectable expansion modules must be
observed. SIMOCODE pro V (110 ... 240 V AC/DC)
✓1) -- ✓ ✓ ✓
The following tables show the maximum possible configuration ✓ ✓ -- -- --
of the expansion modules for the various combinations. These
✓2) ✓2) ✓3) -- --
are also conveniently stored in the TIA Selection Tool. See
www.siemens.com/tia-selection-tool. ✓ -- -- ✓ ✓
3UF7000-1A.00-0
SIMOCODE pro S1)
PROFIBUS DP interface, 1.5 Mbps, RS 485
4 I/2 O freely assignable, input for thermistor connection,
monostable relay outputs, can be expanded by a
multifunction module
Rated control supply voltage Us:
• 24 V DC } 3UF7020-1AB01-0 1 1 unit 42J
• 110 ... 240 V AC/DC } 3UF7020-1AU01-0 1 1 unit 42J
3UF7020-1A.01-0
SIMOCODE pro V2)
PROFIBUS DP interface, 12 Mbps, RS 485
4 I/3 O freely assignable, input for thermistor connection,
monostable relay outputs, can be expanded by
expansion modules
Rated control supply voltage Us:
• 24 V DC } 3UF7010-1AB00-0 1 1 unit 42J
• 110 ... 240 V AC/DC } 3UF7010-1AU00-0 1 1 unit 42J
3UF7010-1A.00-0
SIMOCODE pro PROFINET
SIMOCODE pro V PROFINET
ETHERNET/PROFINET IO,
OPC UA server and web server, 100 Mbps,
2 x connection to bus through RJ45, PROFINET system
10
redundancy, media redundancy protocol,
4 I/3 O freely assignable, input for thermistor connection,
monostable relay outputs, can be expanded by expansion
modules, web server in German/English/Chinese/Russian
Rated control supply voltage Us:
• 24 V DC } 3UF7011-1AB00-0 1 1 unit 42J
3UF7011-1A.00-0
• 110 ... 240 V AC/DC } 3UF7011-1AU00-0 1 1 unit 42J
1)
The connection cable to the current measuring module must be at least
30 cm.
2)
For the use of 2nd-generation current/voltage measuring modules,
SIMOCODE pro V PROFIBUS with product version E15 (V 4.0) must be
ordered. This version does not have marine certification or CCC approval
and can be ordered at no extra charge. The article number must be
supplemented by "-Z" and the order code "B01",
e.g. 3UF7010-1A.00-0 -Z B01.
3UF7150-1AA00-0
SIMOCODE pro operator panels
Operator panels
Installation in control cabinet door or front plate,
for plugging into all SIMOCODE pro basic units,
ten LEDs for status indication and user-assignable
buttons for controlling the motor
• Titanium gray } 3UF7200-1AA01-0 1 1 unit 42J
3UF7200-1AA01-0
• Light gray } 3UF7200-1AA00-0 1 1 unit 42J
3UF7200-1AA00-0
Operator panels for SIMOCODE pro V
Installation in control cabinet door or front plate, for
plugging into SIMOCODE pro V and SIMOCODE pro V PN,
seven LEDs for status indication and user-assignable
buttons for controlling the motor, multilingual display, e.g.
for indication of measured values, status information or
fault messages
• Titanium gray
- English/German/French/Spanish/Portuguese/ } 3UF7210-1AA01-0 1 1 unit 42J
Italian/Polish/Finnish
10
- English/Chinese/Russian/Korean } 3UF7210-1BA01-0 1 1 unit 42J
3UF7210-1.A01-0
• Light gray
- English/German/French/Spanish/Portuguese/ } 3UF7210-1AA00-0 1 1 unit 42J
Italian/Polish/Finnish
- English/Chinese/Russian/Korean } 3UF7210-1BA00-0 1 1 unit 42J
3UF7210-1.A00-0
Digital modules
Up to two digital modules can be used to add additional
binary inputs and relay outputs to the basic unit. The input
circuits of the digital modules are supplied from an external
power supply.
Four binary inputs and two relay outputs
Up to two digital modules can be connected
Relay outputs Input voltage
Monostable 24 V DC } 3UF7300-1AB00-0 1 1 unit 42J
3UF7300-1AU00-0 110 ... 240 V AC/DC } 3UF7300-1AU00-0 1 1 unit 42J
Bistable 24 V DC } 3UF7310-1AB00-0 1 1 unit 42J
110 ... 240 V AC/DC } 3UF7310-1AU00-0 1 1 unit 42J
Analog module
By means of the analog module, the basic unit can be } 3UF7400-1AA00-0 1 1 unit 42J
optionally expanded with analog inputs and outputs
(0/4 ... 20 mA).
Two inputs (passive) for input and one output for output of
0/4 ... 20 mA signals, max. one analog module can be
connected per pro V basic unit and max. two analog
modules per pro V PN basic unit
3UF7400-1AA00-0
10
Ground-fault modules1)
Ground-fault monitoring using 3UL23 residual-current } 3UF7510-1AA00-0 1 1 unit 42J
transformers and ground-fault modules is used in cases
where precise detection of the ground-fault current is
required or power systems with high impedance are
grounded.
With the ground-fault module, it is possible to determine
the precise fault current as a measured value, and to
define freely selectable warning and trip limits in a wide
range from 30 mA ... 40 A.
3UF7510-1AA00-0 One input for connecting a 3UL23 residual-current
transformer, up to one ground-fault module can be
connected
Note:
For corresponding residual-current transformers, see
Catalog IC 10, Chapter 10 or Industry Mall.
Temperature modules
Irrespective of the thermistor motor protection of the basic } 3UF7700-1AA00-0 1 1 unit 42J
units, an additional max. three analog temperature sensors
can be evaluated using a temperature module.
Sensor types: PT100/PT1000, KTY83/KTY84 or NTC
Three inputs for connecting up to three analog temperature
sensors, up to one temperature module can be connected
per pro V basic unit and up to two temperature modules
per pro V PN basic unit
3UF7700-1AA00-0
1)
Possible with pro V PROFIBUS basic unit from product version E10, pro V
PROFINET basic unit from product version E04, all pro V Modbus RTU or
EtherNet/IP basic units.
Multifunction modules
The multifunction module is the expansion module of the
SIMOCODE pro S device series with the following
functions:
• Digital module function with four digital inputs and two
monostable relay outputs
• Ground-fault module function with an input for the
connection of a 3UL23 residual-current transformer with
freely selectable warning and trip limits in a wide zone of
30 mA ... 40 A
3UF7600-1AU01-0 • Temperature module function with an input for connecting
an analog temperature sensor PT100, PT1000, KTY83,
KTY84, or NTC
Max. one multifunction module can be connected per
pro S basic unit
Input voltage of the digital inputs:
• 24 V DC } 3UF7600-1AB01-0 1 1 unit 42J
• 110 ... 240 V AC/DC } 3UF7600-1AU01-0 1 1 unit 42J
10
Memory modules
Enable transmission to a new system,
e.g. when a device is replaced, without the need for
additional aids or detailed knowledge of the device.
Memory module for SIMOCODE pro C } 3UF7900-0AA00-0 1 1 unit 42J
For saving the complete parameterization of a
SIMOCODE pro C system
Memory module for SIMOCODE pro S and
SIMOCODE pro V
For saving the complete parameterization of a
SIMOCODE pro system
10
• Titanium gray } 3UF7901-0AA01-0 1 1 unit 42J
3UF7901-0AA01-0
• Light gray } 3UF7901-0AA00-0 1 1 unit 42J
3UF7901-0AA00-0
Interface covers
For system interface
• Titanium gray 10 3RA6936-0B 1 5 units 42F
3RA6936-0B
• Light gray } 3UF7950-0AA00-0 1 5 units 42J
3UF7950-0AA00-0
Addressing plugs
For assigning the PROFIBUS or Modbus RTU address } 3UF7910-0AA00-0 1 1 unit 42J
without using a PC/PG to SIMOCODE pro through the
system interface
3UF7910-0AA00-0
3UF7902-0AA00-0
Y connection cable
For use in conjunction with the initialization module;
connects the basic unit, current measuring module or
current/voltage measuring module, and initialization
module
System interface length Open cable end
0.1 m 1.0 m } 3UF7931-0CA00-0 1 1 unit 42J
0.5 m 1.0 m } 3UF7932-0CA00-0 1 1 unit 42J
1.0 m 1.0 m } 3UF7937-0CA00-0 1 1 unit 42J
Bus connection terminals
For shield support and strain relief of the PROFIBUS cable } 3UF7960-0AA00-0 1 1 unit 42J
on a SIMOCODE pro S
3UF7960-0AA00-0
Door adapters
For external connection of the system interface, } 3UF7920-0AA00-0 1 1 unit 42J
e.g. outside a control cabinet
10
3UF7920-0AA00-0
Adapters for operator panel
The adapter enables the smaller 3UF7200 operator panel } 3UF7922-0AA00-0 1 1 unit 42J
from SIMOCODE pro to be used in a front panel cutout in
which previously, e.g. after a change of system, a larger
3UF52 operator panel from SIMOCODE-DP had been
used, degree of protection IP54
3UF7922-0AA00-0
Labeling strips
• For pushbuttons of the 3UF720 operator panel } 3UF7925-0AA00-0 100 400 units 42J
• For pushbuttons of the 3UF721 operator panel with } 3UF7925-0AA01-0 100 600 units 42J
display
• For LEDs of the 3UF720 operator panel } 3UF7925-0AA02-0 100 1200 units 42J
3UF7925-0AA02-0
Push-in lugs
For screw fixing, e.g. on mounting plate,
two units required per device
• Can be used for 3UF71.0, 3UF71.1 and 3UF71.2 2 3RV2928-0B 100 10 units 41E
• Can be used for 3UF700, 3UF701, 3UF73, 3UF74, 3UF75 5 3RP1903 1 10 units 41H
and 3UF77
3RV2928-0B • Can be used for 3UF7020, 3UF7600 2 3ZY1311-0AA00 1 10 units 41L
3RT195.-4G
Bus termination modules
With separate control supply voltage for bus termination following
the last unit on the bus line
Supply voltage:
• 115/230 V AC 5 3UF1900-1KA00 1 1 unit 42J
• 24 V DC 5 3UF1900-1KB00 1 1 unit 42J
3UF1900-1KA00
Software
SIMOCODE ES (TIA Portal)
10
Software for configuring, commissioning, operating and
diagnosing SIMOCODE pro based on the TIA Portal,
see page 14/20.
3ZS1322-.C.12-0Y.5
SIMOCODE ES
Software for configuring, commissioning, operating and
diagnosing SIMOCODE pro in Version 2007,
see Catalog IC 10, Chapter 14 or Industry Mall.
3ZS1312-.C.10-0Y.5
SIMOCODE pro block library for SIMATIC PCS 7
The PCS 7 block library can be used for simple and
convenient integration of SIMOCODE pro into the
SIMATIC PCS 7 process control system, see page 14/24.
3ZS1632-.XX02-0Y.0
■ Overview
The 3UF18 current transformers are protection transformers and
More information are used for actuating overload relays. Protection transformers
Home page, see www.siemens.com/sirius are designed to ensure proportional current transfer up to a
Industry Mall, see www.siemens.com/product?3UF18 multiple of the primary rated current. The 3UF18 current trans-
formers convert the maximum current of the corresponding
operating range into the standard value of 1 A secondary.
3UF1843
1) The following setting ranges for the protection of EEx e motors are
applicable:
- 3UF1843-1BA00: 0.25 ... 1.25 A
- 3UF1843-2AA00. 1.25 ... 6.3 A
- 3UF1843-2BA00: 2.5 ... 12.5 A.
■ Accessories
10
Price groups
PG 2AP, 346, 42B, 42C, 42D, 42H,
42J
14/2 Introduction
SIMOCODE ES
3RA1943-2C
3RA1943-2B
3RA1953-2B
IC01_00413
3RA1953-2N
Siemens IC 10 A · 04/2017
© Siemens AG 2017
■ Overview
SIMOCODE ES V14 Basic Standard Premium
Access through the local interface ✓ ✓ ✓
on the device
Parameter assignment in list form ✓ ✓ ✓
Parameter printing in list form ✓ ✓ ✓
Operating ✓ ✓ ✓
Diagnostics ✓ ✓ ✓
Test ✓ ✓ ✓
Service data ✓ ✓ ✓
Analog value recording1) ✓ ✓ ✓
Trend display of measured values -- ✓ ✓
Parameterizing with convenient -- ✓ ✓
graphical display
Parameterizing with the integrated -- ✓ ✓
graphics editor (CFC-based)
Printing of diagrams -- ✓ ✓
Selecting the SIMOCODE pro device configuration in SIMOCODE ES Parameter comparison -- ✓ ✓
(TIA Portal)
Access through -- -- ✓
More information PROFIBUS/PROFINET/EtherNet2)
Teleservice through MPI -- -- ✓
Home page, see www.siemens.com/sirius
Routing3) -- -- ✓
Industry Mall, see www.siemens.com/product?3ZS1
✓ Function available
Technical specifications, see
https://support.industry.siemens.com/cs/ww/en/ps/16716/td -- Function not available
To download the SIMOCODE ES (TIA Portal) software see
https://support.industry.siemens.com/cs/ww/en/view/109738034 1) For SIMOCODE pro V.
To download the SIMOCODE ES 2007 software see 2)
In combination with Modbus devices, SIMOCODE ES Premium does not
https://support.industry.siemens.com/cs/ww/en/view/109480470 offer any additional functions compared with SIMOCODE ES Standard.
3)
See http://support.automation.siemens.com/WW/view/en/109738745.
SIMOCODE ES is the central software for configuration, startup,
operation and diagnostics of SIMOCODE pro. Working with libraries
Version 14, which is based on the central engineering framework Users can create copy templates for SIMOCODE pro device
Totally Integrated Automation Portal (TIA Portal), is available in configuration and can manage them in global or project
addition to SIMOCODE ES Version 2007. libraries.
This way, individual modules, diagrams and complete device
SIMOCODE ES V14 is integrated seamlessly when further
configurations can be saved as reusable elements for frequently
TIA Portal-based software such as STEP 7 or WinCC is available,
occurring tasks.
thus enabling users to achieve a consistent, efficient and
intuitive solution for all automation tasks. Integrated graphics editor
However, use of SIMOCODE ES V14 as stand-alone software The graphics editor is a part of SIMOCODE ES Standard and
also provides these advantages. SIMOCODE ES Premium. It is based on the Continuous Function
Chart (CFC) and adds a powerful tool to the parameterizing
Three program versions interface that enables easy parameterization of devices by
The user can choose between three different versions of drag & drop. Extremely compact documentation of all config-
SIMOCODE ES: SIMOCODE ES Basic, SIMOCODE ES Standard ured parameters is possible, as is the graphic online presenta-
and SIMOCODE ES Premium. While SIMOCODE ES Basic is a tion of the configured device functions including all signal states
powerful tool for startup or maintenance personnel, during operation.
SIMOCODE ES Standard and Premium are the perfect tools for
engineers or configuration engineers on account of their larger
scope of functions and integrated graphics editor. Unlike the
Standard version, SIMOCODE ES Premium also permits
parameterization and diagnostics through PROFIBUS.
PROFINET/EtherNet. Indication of all operating, service and
diagnostics data supplies important information about the
current state of the motor and plant at all times – everywhere on
PROFIBUS/PROFINET/EtherNet.
14
■ Benefits
• Easy parameterization with the graphics editor based on the • Universally applicable through stand-alone version or
Continuous Function Chart (CFC) reduces engineering work seamless integration into the central engineering framework
and shortens start up times when other TIA Portal-based software such as STEP 7 or
• Clear plant documentation by means of graphic presentation WinCC are available
• Detailed information, also when there are faults, is a help for • Parameter changes are also possible during normal operation
maintenance personnel and shortens downtimes • Users can create copy templates for device configurations
and can manage them in global libraries
14
Notes:
SIMOCODE ES V13 licenses can also be used for
SIMOCODE ES V14.
Please order PC cable separately, see page 14/23.
For description of the software versions, see page 14/20.
■ Accessories
Version SD Article No. Price PU PS* PG
14
per PU (UNIT,
SET, M)
d
Optional accessories
USB PC cables } 3UF7941-0AA00-0 1 1 unit 42J
For connecting to the USB interface of a PC/PG,
for communication with SIMOCODE ES through the system
interface
3UF7941-0AA00-0 USB/serial adapters 5 3UF7946-0AA00-0 1 1 unit 42J
For connecting an RS 232 PC cable to the USB interface of
a PC, recommended for use in conjunction with
SIMOCODE ES
■ Overview
More information
Home page, see www.siemens.com/sirius
Industry Mall, see www.siemens.com/product?3ZS1
Technical specifications, see
https://support.industry.siemens.com/cs/ww/en/ps/16718/td
Programming and Operating Manual for the "SIMOCODE pro PCS 7 Library":
• Version V8.2, see
https://support.industry.siemens.com/cs/ww/en/view/103954289
• Version V8.0 + SP3, see
https://support.industry.siemens.com/cs/ww/en/view/84626047
The PCS 7 block library can be used for simple and easy
integration of SIMOCODE pro into the SIMATIC PCS 7 process
control system. One focus here is on easy configuration, Advanced Process Library (APL) - faceplates and function blocks for
because the number of required configuration steps is reduced control and measured data of the SIMOCODE pro library for PCS 7
crucially. The configuration of the modules is based on the
PCS 7 standard configuration processes and is optimally harmo-
nized with the functions of SIMOCODE pro. Users who have
previously integrated conventional motor feeders into PCS 7 will
therefore find it easy to switch to SIMOCODE pro.
■ Benefits
• Uniform and continuous integration into SIMATIC PCS 7 • Greater process transparency due to greater information
• Standardized blocks for simple integration and optimal density in the process control system
operation
14
14
Industrial Controls
Siemens AG
In order to protect plants, systems, machines and networks
Digital Factory against cyber threats, it is necessary to implement – and
Control Products continuously maintain – a holistic, state-of-the-art indus-
Postfach 23 55 trial security concept. Siemens’ products and solutions only
90713 FÜRTH
form one element of such a concept.
GERMANY
Customer is responsible to prevent unauthorized access to
its plants, systems, machines and networks. Systems,
© Siemens AG 2017
Subject to change without prior notice
machines and components should only be connected to the
PDF (E86060-K1010-A291-A1-7600) enterprise network or the internet if and to the extent
KG 0417 32 En necessary and with appropriate security measures (e.g. use
Produced in Germany of firewalls and network segmentation) in place.
Additionally, Siemens’ guidance on appropriate security
The information provided in this catalog contains merely general measures should be taken into account. For more informa-
descriptions or characteristics of performance which in case of actual
tion about industrial security, please visit
use do not always apply as described or which may change as a result
of further development of the products. An obligation to provide the
http://www.siemens.com/industrialsecurity.
respective characteristics shall only exist if expressly agreed in the
Siemens’ products and solutions undergo continuous
terms of contract. Availability and technical specifications are subject
to change without notice.
development to make them more secure. Siemens strongly
recommends to apply product updates as soon as available
All product designations may be trademarks or product names
and to always use the latest product versions. Use of
of Siemens AG or supplier companies whose use by third parties
for their own purposes could violate the rights of the owners. product versions that are no longer supported, and failure
to apply latest updates may increase customer’s exposure
to cyber threats.
To stay informed about product updates, subscribe to the
Siemens Industrial Security RSS Feed under
http://www.siemens.com/industrialsecurity.