© Siemens AG 2017

SIRIUS

Industrial Controls
SIMOCODE pro 3UF7 Motor
Management and Control Devices
Catalog Edition
Abridged April
IC 10 A 2017 siemens.com/simocode
© Siemens AG 2017

Related catalogs
Related catalogs Miscellaneous

Industrial Controls IC 10 Products for Automation and Drives CA 01


SIRIUS Interactive Catalog
DVD

E86060-K1010-A101-A7-7600 E86060-D4001-A510-D7-7600

Industrial Controls IC 10 AO Industry Mall


SIRIUS Classic Information and Ordering Platform
on the Internet:

PDF (E86060-K1010-A191-A5-7600) www.siemens.com/industrymall

Safety Integrated SI 10 Siemens TIA Selection Tool


Safety Technology for for the selection, configuration and ordering of
Factory Automation TIA products and devices

E86060-K7010-A101-A3-7600 www.siemens.com/tst

Industrial Communication IK PI Information and Download Center


SIMATIC NET Digital versions of the catalogs are available
in the Internet

E86060-K6710-A101-B8-7600 www.siemens.com/sirius/catalogs

SIMATIC ST 70 Response E-mail


Products for Please send your comments and suggestions
Totally Integrated Automation for improvement to

[email protected]
E86060-K4670-A101-B5-7600 (include the catalog name in the subject field)

Low-Voltage Power Distribution and LV 10


Electrical Installation Technology
SENTRON • SIVACON • ALPHA Trademarks
Protection, Switching, Measuring and Monitoring
Devices, Switchboards and Distribution Systems
All product designations may be registered trademarks or
PDF (E86060-K8280-A101-A4-7600) product names of Siemens AG or other supplying companies.
Print (E86060-K8280-A101-A3-7600) Third parties using these trademarks or product names for their
own purposes may infringe upon the rights of the trademark
SIMOTICS GP, SD, XP, DP D 81.1 owners.
Low-Voltage Motors
Type series 1FP1, 1LE1, 1MB1 and 1PC1 Further information about industrial controls:
Frame sizes 71 to 315 www.siemens.com/sirius
Power range 0.09 to 200 kW
E86060-K5581-A111-A9-7600

SITOP KT 10.1
Power supply Technical Assistance
SITOP

Expert technical assistance


E86060-K2410-A101-B2-7600 for Industrial controls:
Tel.: +49 (911) 895-5900
Fax: +49 (911) 895-5907
SITRAIN ITC
Training for Industry E-Mail: technical-
[email protected]
Only available in German
E86060-K6850-A101-C5
© Siemens AG 2017

Industrial Controls
SIRIUS 1 Introduction

2 Industrial Communication

3 Switching Devices –
Contactors and Contactor Assemblies –
for Switching Motors

4 Switching Devices –
Contactors and Contactor Assemblies –
Special Applications

5 Switching Devices –
Contactors and Contactor Assemblies –
Contactor Relays and Relays
Catalog Abridged IC 10 A · 04/2017 6 Switching Devices –
Soft Starters and Solid-State Switching
Catalog Abridged IC 10 A · 04/2017 is an abridged version Devices
of Catalog IC 10 · 2017 with updated content.
This content replaces the corresponding sections of 7 Protection Equipment
Catalog IC 10 · 2017.
Refer to the Industry Mall for current updates of
Catalog IC 10: 8 Load Feeders and Motor Starters
www.siemens.com/industrymall for Use in the Control Cabinet
Please contact your local Siemens branch.

© Siemens AG 2017 9 Motor Starters for Use in the Field,


High Degree of Protection

10 Monitoring and Control Devices

11 Safety Technology

12 Position and Safety Switches

13 Commanding and Signaling Devices

14 Parametrization, Configuration and


Visualization with SIRIUS

The products and systems described in this


catalog are manufactured/distributed under 15 Power Supply
application of a certified quality manage-
ment system in accordance with
EN ISO 9001
(for the Certified Registration No. see 16 Appendix
www.siemens.com/system-certificates/cp).
The certificate is recognized by all IQNet
countries.
© Siemens AG 2017

Industrial Controls

Ordering notes

■ Things you should know about Catalog Abridged IC 10 A


Catalog Abridged IC 10 A contains all selection and
order-relevant data.
Standard delivery time (SD)
SD in days (d) Preferred types are available immediately from The delivery times apply up to the ramp at Siemens AG (products ready
} Preferred type stock, i.e. are dispatched within 24 hours. for dispatch). The transport times depend on the destination and type of
Normal quantities of the products are usually shipping. The standard transport time for Germany is one day.
X On request
delivered within the specified time following receipt The delivery times specified here represent the situation in April 2017.
of your order at our branch. They are continuously optimized. For more up-to-the-minute information,
In exceptional cases, the actual delivery time may please visit www.siemens.com/sirius/mall.
differ from that specified.
Price units (PU)
The price unit defines the number of units, sets or
meters to which the specified price applies.
Packaging sizes (PS)
The packaging size defines the number, e.g. of For multi-unit packing and reusable packaging. see Catalog IC 10,
units, sets or meters, contained in an outer Chapter 16 "Appendix" "Ordering notes".
packaging.
Only the quantity defined by the packaging size or
a multiple thereof can be ordered.
Price groups (PG)
Each product is assigned to a price group.
Example
3RA2110-0FA15-1AP0
SD: 2 working days SD Article No. Price PU PS* PG
PG: 41D per PU (UNIT,
Order quantity 1 unit or a multiple thereof d SET, M)
2 3RA2110-0FA15-1AP0 1 1 ST 41D
3RV1901-0H } 3RV1901-0H 1 10 ST 41E
SD: Preferred type 5 3SU1900-0AB71-0AB0 100 10 ST 41J
PG: 41E
Order quantity 10 units or a multiple thereof

3SU1900-0AB71-0AB0
SD: 5 working days
PG: 41J
Order quantity 10 units or a multiple thereof
Dimensions
All dimensions in mm.
10
© Siemens AG 2017

Monitoring and Control Devices

Price groups SIRIUS 3UG45, 3UG46 monitoring


PG 200, 2SP, 470, 41B, 41E, 41F, 41H, relays for stand-alone installation
41L, 42F, 42J, 5K1, 5M2, 5P1, 5T1, 5W3 10/77 General data
10/80 Line monitoring
10/2 Introduction
10/85 Voltage monitoring
SIMOCODE 3UF motor management 10/88 Current monitoring
and control devices 10/90 Power factor and active current
SIMOCODE pro 3UF7 motor monitoring
management and control devices Residual current monitoring
10/5 General data 10/93 - Residual-current monitoring relays
10/15 Basic units 10/95 - 3UL23 residual-current transformers
10/18 Expansion modules Insulation monitoring
10/20 Fail-safe expansion modules 10/96 - General data
10/21 Accessories 10/98 - For ungrounded AC networks
10/24 3UF18 current transformers for overload 10/100 - For ungrounded DC and AC networks
protection Level monitoring
10/103 - Level monitoring relays
ST 70 LOGO! logic modules1) 10/106 - Level monitoring sensors
10/23 General data 10/107 Speed monitoring
10/24 LOGO! Modular basic versions 10/110 Accessories
10/25 LOGO! Modular pure versions SIRIUS 3UG48 monitoring relays
10/26 LOGO! Modular expansion modules for stand-alone installation for IO-Link
LOGO! Modular communication 10/111 General data
modules 10/114 Line monitoring
10/27 - LOGO! CMK2000 communication 10/117 Voltage monitoring
modules
10/120 Current monitoring
10/28 - LOGO! CSM unmanaged
10/123 Power factor and active current
10/29 - LOGO! CMR
monitoring
(mobile wireless communication)
Residual current monitoring
10/31 Accessories
10/127 - Residual-current monitoring relays
15/4 LOGO!Power
10/130 Speed monitoring
10/33 LOGO!Contact
Click on the Article No. in the 10/133 Accessories
10/34 LOGO! Software
catalog PDF to access it in the SIRIUS 3RS10, 3RS11, 3RS20, 3RS21
Industry Mall and get all related Relays temperature monitoring relays

10
information. 10/134 General data
Timing relays
Article No. 10/35 General data 10/138 Relays, analogically adjustable for
10/36 SIRIUS 3RP25 timing relays 1 sensor
3RA1943-2C
3RA1943-2B 17.5 mm and 22.5 mm 10/141 Relays, digitally adjustable for 1 sensor
3RA1953-2B 10/48 SIRIUS 3RP20 timing relays, 45 mm 10/142 Relays, digitally adjustable for up to
IC01_00413

3RA1953-2N 3 sensors
10/54 7PV15 timing relays, 17.5 mm
3/100 SIRIUS 3RA28 solid-state time-delay 10/144 Accessories
Or directly in the Internet, e. g.
www.siemens.com/ auxiliary switch blocks for mounting SIRIUS 3RS14, 3RS15 temperature
product?3RA1943-2C onto 3RT2 contactors and monitoring relays for IO-Link
3RH2 contactor relays 10/145 General data
Notes: 3/105 SIRIUS 3RA28 function modules for 10/151 Relays, digitally adjustable for 1 sensor
mounting onto 3RT2 contactors and 10/154 Relays, digitally adjustable for up to
3RT191. function modules can be found 3RH2 contactor relays 3 sensors
- in the Catalog Add-On IC 10 AO · 2016 10/59 SIRIUS 3RT19 timing relays for 10/156 Accessories
in the Information and Download Center mounting onto 3RT1 contactors 10/157 SIRIUS 3RN2 thermistor motor
- in the interactive Catalog CA 01 SIRIUS 3RR21, 3RR22 monitoring relays protection
for mounting onto 3RT2 contactors Coupling relays and signal converters/
- in the Industry Mall
10/62 Current and active current monitoring interface converters
SIRIUS 3RR24 monitoring relays 5/33 Coupling relays
Conversion tool, e.g. from 3UG3 to 3UG4 for mounting onto 3RT2 contactors for
3/151 3TG10 power relays/miniature
or from 3RS17 to 3RS70 see IO-Link
www.siemens.com/sirius/conversion-tool 10/70 contactors
Current and active current monitoring
10/166 SIRIUS 3RS70 signal converters

1) See Catalog ST 70 "Products for


Totally Integrated Automation".

Siemens IC 10 A · 04/2017
© Siemens AG 2017
© Siemens AG 2017

SIMOCODE 3UF Motor Management and Control Devices


SIMOCODE pro 3UF7 Motor Management and Control Devices
General data

■ Overview
Expansion SIMOCODE
possibilities pro C pro S pro V1)
PROFIBUS PROFIBUS PROFIBUS2) PROFINET
Modbus RTU2) EtherNet/IP
Operator panels ✓ ✓ ✓ ✓
Operator panels -- -- ✓ ✓
with display
Current measuring ✓ ✓ ✓ ✓
modules
Current/voltage -- -- ✓ ✓
measuring
modules
Decoupling -- -- ✓ ✓
modules
Expansion
modules:
• Digital modules -- -- 2 2
• Fail-safe digital -- -- 1 1
SIMOCODE pro S for efficient entry into motor management and modules3)
SIMOCODE pro V for maximum functionality
• Analog modules -- -- 1 2
More information • Ground-fault -- -- 1 1
modules
Home page, see www.siemens.com/simocode
• Temperature -- -- 1 2
Industry Mall, see www.siemens.com/product?3UF7 modules
SIMOCODE pro is a flexible, modular motor management • Multifunction -- 1 -- --
system for motors with constant speeds in the low-voltage modules
performance range. It optimizes the connection between I&C ✓ Available
and motor feeder, increases plant availability and allows signifi- -- Not available
cant savings to be made for installation, commissioning, 1)
Maximum of five expansion modules.
operation and maintenance of a system. 2)
When an operator panel with display and/or a decoupling module are
SIMOCODE pro offers, for example: used, more restrictions on the number of expansion modules connectable
per basic unit must be observed, see page 10/14.
• Multifunctional, solid-state full motor protection that is 3)
The fail-safe digital module can be used instead of one of the two digital
independent of the automation system modules.
• Integrated control functions instead of hardware for the motor
control
Per feeder each system always comprises one basic unit and
• Detailed operational, service and diagnostics data one separate current measuring module. The two modules are
• Open communication via PROFIBUS DP, PROFINET/OPC UA, connected together electrically through the system interface

10
Modbus RTU or EtherNet/IP with a connection cable and can be mounted mechanically
connected as a unit (one behind the other) or separately (side
• Safety relay function for the fail-safe disconnection of motors
by side). The motor current to be monitored is decisive only for
up to SIL 3 (IEC 61508, IEC 62061) or PL e with Category 4
the choice of the current measuring module.
(EN ISO 13849-1)
• SIMOCODE ES is the software package for SIMOCODE pro An operator panel for mounting in the control cabinet door is
parameterization, start up and diagnostics. optionally connectable through a second system interface on
the basic unit. Both the current measuring module and the
Device series operator panel are electrically supplied by the basic unit through
the connection cable. More inputs, outputs and functions can be
SIMOCODE pro C
added to the SIMOCODE pro V and SIMOCODE pro S by means
The compact system for direct-on-line starters and reversing of optional expansion modules, thus supplementing the inputs
starters or for controlling a motor starter protector. and outputs already existing on the basic unit. With the
DM-F Local and DM-F PROFIsafe fail-safe digital modules it is
SIMOCODE pro S also possible to integrate the fail-safe disconnection of motors in
The smart system for direct-on-line, reversing, and wye-delta the SIMOCODE pro V motor management system.
starters or for controlling a motor starter protector or soft starter. All modules are connected by connection cables. The connec-
Its expandability with a multifunction module provides compre- tion cables are available in various lengths. The maximum
hensive input/output project data volume, precise ground-fault distance between the modules (e.g. between the basic unit and
detection via the 3UL23 residual-current transformers and the current measuring module) must not exceed 2.5 m. The total
temperature measurement. length of all the connection cables per system interface of the
SIMOCODE pro V basic unit may be up to 3 m.

The variable system with all control functions and with the possi- Note:
bility of expanding the inputs, outputs and functions of the SIMOCODE pro can also be found in the TIA Selection Tool. The
system at will using expansion modules various system components can therefore be conveniently
selected; see www.siemens.com/tia-selection-tool.

Siemens IC 10 A · 04/2017 10/5


© Siemens AG 2017

SIMOCODE 3UF Motor Management and Control Devices


SIMOCODE pro 3UF7 Motor Management and Control Devices
General data

Basic Optional expansions


Current Basic unit Operator Multifunction module
measuring module panel
SIMOCODE pro S

Communication

Functions
Communication at basic unit via:
PROFIBUS

Optional expansions
Current/voltage Basic unit Operator Earth-fault Temperature Digital modules Analog
measuring module panel module module Standard Fail-safe module
SIMOCODE pro V

Communication

Functions
10

IC01_00532

Communication at basic unit via:


PROFIBUS/PROFIsafe
PROFINET/PROFIsafe
OPC UA
Modbus RTU
EtherNet/IP

SIMOCODE pro S and SIMOCODE pro V: system structure


Article No. scheme
Product versions Article number
SIMOCODE pro motor management system 3UF7 @@@– 1 @@0 @– 0
Type of unit/module e.g. 0 = basic unit @
Functional version of the module e.g. 20 = SIMOCODE pro S @@
Connection type of the current transformer @
Voltage version e.g. B = 24 V DC @
Enclosure color e.g. 1 = titanium gray @
Example 3UF7 0 2 0 – 1 A B 0 1 – 0
Note:
The Article No. scheme shows an overview of product versions For your orders please use the article numbers quoted in the
for better understanding of the logic behind the article numbers. selection and ordering data.

10/6 Siemens IC 10 A · 04/2017


© Siemens AG 2017

SIMOCODE 3UF Motor Management and Control Devices


SIMOCODE pro 3UF7 Motor Management and Control Devices
General data

■ Benefits
General customer benefits Recording of measuring curves
• Integrating the whole motor feeder into the process control by SIMOCODE pro can record measuring curves and therefore is
means of PROFIBUS DP, PROFINET/OPC UA, Modbus RTU or able, for example, to present the progression of motor current
EtherNet/IP significantly reduces the wiring between the motor during motor start up.
feeder and the PLC.
• Decentralization of the automated processes by means of Flexible motor control implemented with integrated control
configurable control and monitoring functions in the feeder functions (instead of comprehensive hardware interlocks)
saves resources in the automation system and ensures full Many predefined motor control functions have already been
functionality and protection of the feeder even if the I&C or bus integrated into SIMOCODE pro, including all necessary logic
system fails operations and interlocks:
• The acquisition and monitoring of operating, service and • Overload relays
diagnostics data in the feeder and process control system • Direct-on-line and reversing starters
increases plant availability as well as maintenance and
service-friendliness • Wye/delta starters (also with direction reversal)
• The high degree of modularity allows users to perfectly imple- • Two speeds, motors with separate windings
ment their plant-specific requirements for each motor feeder (pole-changing starter); also with direction reversal
• The SIMOCODE pro system offers functionally graded and • Two speeds, motors with separate Dahlander windings
space-saving solutions for each customer application (also with direction reversal)
• The replacement of the control circuit hardware with inte- • Positioner actuation
grated control functions decreases the number of hardware • Solenoid valve actuation
components and wiring required and in this way limits stock • Actuation of a motor starter protector
keeping costs and potential wiring errors
• Soft starter actuation (also with direction reversal)
• The use of electronic full motor protection permits better
utilization of the motors and ensures long-term stability of the These control functions are predefined in SIMOCODE pro and
tripping characteristic and reliable tripping even after years of can be freely assigned to the inputs and outputs of the device
service (including the PROFIBUS/PROFINET process image).
• Thanks to the precision of the current, voltage, power and These predefined control functions can also be flexibly adapted
energy measurements (especially those acquired by the to each customized configuration of a motor feeder by means of
2nd-generation current/voltage measuring modules), costs freely configurable logic modules (truth tables, counters, timers,
can be internally allocated with a high degree of accuracy. edge evaluation, etc.) and with the help of standard functions
• By virtue of its wide frequency range of 20 to 400 Hz, (power failure monitoring, emergency start, external faults, etc.),
SIMOCODE can be used in combination with the 2nd-genera- without additional auxiliary relays being necessary in the control
tion current/voltage measuring modules in a a wide range of circuit.
motor applications. SIMOCODE pro makes a lot of additional hardware and wiring in
Multifunctional, electronic full motor protection the control circuit unnecessary, which results in a high level of
for rated motor currents up to 820 A standardization of the motor feeder in terms of its design and
circuit diagrams.

10
SIMOCODE pro offers comprehensive protection of the motor
feeder by means of a combination of different, multi-step and de-
layable protection and monitoring functions:
• Inverse-time delayed electronic overload protection
(CLASS 5E to 40E)
• Thermistor motor protection
• Phase failure / unbalance protection
• Stall protection
• Monitoring of adjustable limit values for the motor current
• Voltage and power monitoring
• Monitoring of the power factor (motor idling/load shedding)
• Ground-fault monitoring
• Temperature monitoring, e.g. over PT100/PT1000
• Monitoring of operating hours, downtime and number of starts
etc.

Siemens IC 10 A · 04/2017 10/7


© Siemens AG 2017

SIMOCODE 3UF Motor Management and Control Devices


SIMOCODE pro 3UF7 Motor Management and Control Devices
General data
Detailed operational, service and diagnostics data Communication
SIMOCODE pro makes different operational, service and diag- SIMOCODE pro has either an integrated PROFIBUS DP or
nostics data available and helps to detect potential faults in time Modbus RTU interface (SUB-D or terminal connection) or a
and to prevent them by means of preventative measures. In the PROFINET or EtherNet/IP interface (2 x RJ45).
event of a malfunction, a fault can be diagnosed, localized and
rectified very quickly - there are no or very short downtimes. Fail-safe disconnection through PROFIBUS or PROFINET with
the PROFIsafe profile is also possible in conjunction with a fail-
Operating data safe controller (F-CPU) and the DM-F PROFIsafe fail-safe digital
• Motor switching state derived from the current flow in the main module.
circuit SIMOCODE pro PROFIBUS
• All phase currents SIMOCODE pro PROFIBUS supports, for example:
• All phase voltages and phase-to-phase voltages • Cyclic services (DPV0) and acyclic services (DPV1)
• Active power, apparent power and power factor • Extensive diagnostics and hardware interrupts
• Phase unbalance and phase sequence • Time stamp with high timing precision (SIMATIC S7) for
• Ground-fault current SIMOCODE pro V
• Frequency • DPV1 communication after the Y-Link
• Time to trip SIMOCODE pro PROFINET
• Motor temperature
SIMOCODE pro PROFINET supports, for example:
• Remaining cooling time etc.
• Line and ring bus topology thanks to an integrated switch
Service data • Media redundancy via MRP protocol
• Motor operating hours • Operating, service and diagnostics data via standard web
• Motor stop times browser
• Number of motor starts • OPC UA server for open communication with visualization and
• Number of overload trips control system
• Interval for compulsory testing of the enabling circuits • NTP-synchronized time
• Energy consumed • Interval function and measured values for energy
management via PROFIenergy
• Internal comments stored in the device etc.
• Module exchange without PC memory module through
Diagnostics data proximity detection
• Numerous detailed early warning and fault messages • Extensive diagnostics and maintenance alarms
• Internal device fault logging with time stamp System redundancy with SIMOCODE pro PROFINET
• Time stamping of freely selectable status, alarm or fault
messages etc. The device supports the system redundancy mechanisms of
PROFINET IO and therefore can be operated directly on
Easy operation and diagnostics fault-tolerant systems such as SIMATIC S7-400 H. As such,
SIMOCODE pro can provide decisive added value also for the
Operator panel field level of plants in which plant availability and control system
10

The operator panel is used to control the motor feeder and can redundancy are priorities.
replace all conventional pushbuttons and indicator lights to save SIMOCODE pro Modbus RTU
space. It makes SIMOCODE pro or the feeder directly operable
in the control cabinet. It features all the status LEDs available on SIMOCODE pro Modbus RTU supports, for example:
the basic unit and externalizes the system interface for simple • Communication at 1 200/2 400/4 800/9 600/19 200 or
parameterization or diagnosis on a PC/PG. 57 600 baud
Operator panel with display • Access to freely parameterizable process image via
Modbus RTU
As an alternative to the 3UF720 standard operator panel for
SIMOCODE pro V, a 3UF721 operator panel with display is also • Access to all operating, service and diagnostics data via
available. This can additionally indicate current measured Modbus RTU
values, operational and diagnostics data or status information of SIMOCODE pro EtherNet/IP
the motor feeder at the control cabinet. The pushbuttons of the
operator panel can be used to control the motor. Furthermore, it SIMOCODE pro EtherNet/IP supports, for example:
is possible to set parameters such as rated motor current, limit • Line and ring bus topology thanks to an integrated switch
values, etc. directly via the operator panel with display (with
SIMOCODE pro V PROFIBUS as of E15, SIMOCODE pro V • Ring structures via Device Level Ring (DLR) protocol
Modbus RTU as of E02 and with all SIMOCODE pro V PROFINET • Operating, service and diagnostics data via standard web
and EtherNet/IP). browser
• NTP-synchronized time
• Parameter assignment via SIMOCODE ES V14 – via local
device interface and Ethernet

10/8 Siemens IC 10 A · 04/2017


© Siemens AG 2017

SIMOCODE 3UF Motor Management and Control Devices


SIMOCODE pro 3UF7 Motor Management and Control Devices
General data
Notes on safety The SIMOCODE pro 3UF7 motor management system makes
the following contribution to the energy efficiency of the plant as
In order to protect plants, systems, machines and networks a whole:
against cyber threats, it is necessary to implement (and contin-
uously maintain) a holistic, state-of-the-art industrial security • Energy consumption:
concept. Siemens products and solutions represent only one Clear display of the energy consumption of a motor feeder or
component of such a concept. process element by means of the acquisition and transmission
of all operating and consumption data, such as current,
For more information on industrial security, see voltage, active and reactive power, energy consumption,
www.siemens.com/industrialsecurity. motor temperature, etc.
SIMOCODE pro motor management and control devices with • Energy management:
communication function, see from page 10/15. Evaluation of measured energy values (e.g. limit value
monitoring) with exporting of local or central actions
Accessories, see from page 10/21. (= forwarding to higher-level)
For more information, e.g. on software, see pages 14/20 and • PROFIenergy:
14/24. SIMOCODE pro V PROFINET supports the PROFIenergy
Autonomous operation functions. Reduced energy consumption thanks to automatic
disconnection in the intervals and forwarding of the measured
An essential feature of SIMOCODE pro is the autonomous values for higher-level energy management systems.
execution of all protection and control functions, even when
communication to the I&C system is interrupted. This means that Advantages from integrated energy management
even in the event of bus system or automation system failure, full
functionality of the feeder is ensured or a specific behavior can
be parameterized in case of such a fault, e.g. targeted shutdown
of the feeder or execution of particular parameterized control
mechanisms (such as reversal of the direction of rotation). Ready for Ready for
SIMATIC
siemens.com/ SIMATIC
Advantages through energy efficiency
Energy Suite
energysuite Energy Suite

As an integrated option for the TIA Portal, the SIMATIC Energy


Suite couples energy management with automation efficiently,
making energy consumption at your production facility
transparent.
Thanks to the simplified configuration of energy-measuring
components, e.g. SIMOCODE pro V, configuration effort is also
clearly reduced.
Thanks to the end-to-end connection with higher-level energy
management systems or cloud-based services, you can seam-
4

lessly expand the recorded energy data to create a cross-site


0 24
1_ 0

energy management system.


IC0

The advantages at a glance:

10
Overview of the energy management process • Automatic generation of energy management data
We offer you a unique portfolio for efficient energy management • Integration into TIA Portal and into automation
in the industry – a process that is used to optimize the energy • Simple configuration
requirements. We split up our industrial energy management into
three phases – identify, evaluate, and realize – and we support For more information, see www.siemens.com/energysuite.
you with the appropriate hardware and software solutions in
every process phase.
The innovative SIRIUS industrial controls products can also
make a major contribution to the energy efficiency of a plant
(www.siemens.com/sirius/energysaving).

Siemens IC 10 A · 04/2017 10/9


© Siemens AG 2017

SIMOCODE 3UF Motor Management and Control Devices


SIMOCODE pro 3UF7 Motor Management and Control Devices
General data

■ Application
SIMOCODE pro is often used for automated processes where Safety technology for SIMOCODE pro
plant downtimes are very expensive (e.g. chemical, oil/gas,
water/wastewater, steel or cement industries) and where it is The safe disconnection of motors in the process industry is
important to prevent plant downtimes through detailed opera- becoming increasingly important as the result of new and
tional, service and diagnostics data or to locate faults very revised standards and requirements in the safety technology
quickly when they occur. field.

SIMOCODE pro is modular and space-saving and suited With the DM-F Local and DM-F PROFIsafe fail-safe expansion
especially for operation in motor control centers (MCCs) in the modules it is easy to integrate functions for fail-safe disconnec-
process industry and for power plant technology. tion into the SIMOCODE pro V motor management system while
retaining service-proven concepts. The strict separation of
Applications safety functions and operational functions proves particularly
advantageous for planning, configuring and construction.
Protection and control of motors in hazardous areas for types of Seamless integration in the motor management system leads to
protection EEx e/d according to ATEX guideline 94/9/EC greater transparency for diagnostics and during operation of the
• With heavy starting (paper, cement, metal and water system.
industries)
Suitable components for this purpose are the DM-F Local and
• In high-availability plants (chemical, oil, raw material DM-F PROFIsafe fail-safe expansion modules, depending on the
processing industries, power plants) requirements:
Use of SIMOCODE pro 3UF7 with IE3/IE4 motors • The DM-F Local fail-safe digital module for when direct
assignment between a fail-safe hardware shutdown signal
Note: and a motor feeder is required, or
When using the SIMOCODE pro 3UF7 in conjunction with highly • The DM-F PROFIsafe fail-safe digital module for when a
energy-efficient IE3/IE4 motors, please observe the information fail-safe controller (F-CPU) creates the signal for disconnec-
on dimensioning and configuring; see Application Manual tion and transmits it in a fail-safe manner through
"SIRIUS Controls with IE3/IE4 motors", PROFIBUS/PROFIsafe or PROFINET/PROFIsafe to the motor
https://support.industry.siemens.com/cs/ww/en/view/94770820. management system
For more information, see Catalog IC 10, Preface.

■ Technical specifications
More information
Technical specifications, see "SIRIUS Controls with IE3/IE4 motors" Application Manual, see
https://support.industry.siemens.com/cs/ww/en/ps/16337/td https://support.industry.siemens.com/cs/ww/en/view/94770820
SIMOCODE pro - Manual Collection see Selection data for type-tested assemblies/load feeders
https://support.industry.siemens.com/cs/ww/en/view/109743951 • Manual "Configuring SIRIUS", see
"SIMOCODE pro Safety Fail-Safe Digital Modules" System Manual, see https://support.industry.siemens.com/cs/ww/en/view/40625241
https://support.industry.siemens.com/cs/ww/en/view/50564852 • Manual "Configuring SIRIUS Innovations", see
10

https://support.industry.siemens.com/cs/ww/en/view/39714188

General data
Type 3UF7
Permissible ambient temperature
• During operation °C -25 ... +60; 3UF721: 0 …+60
• During storage and transport °C -40 ... +80; 3UF721: -20 ... +70
Degree of protection (acc. to IEC 60529)
• Measuring modules with busbar connection IP00
• Operator panel (front) and door adapter (front) with cover IP54
• Other components IP20
Shock resistance (sine pulse) g/ms 15/11
Mounting position Any
Frequency Hz 50/60 5 %
EMC interference immunity (according to IEC 60947-1) Corresponds to degree of severity 3
• Conducted interference, burst acc. to IEC 61000-4-4 kV 2 (power ports)
kV 1 (signal ports)
• Conducted interference, high frequency acc. to V 10
IEC 61000-4-6
• Conducted interference, surge acc. to IEC 61000-4-5 kV 2 (line to ground); 3UF7320-1AB, 3UF7330-1AB: 1 (line to ground)
kV 1 (line to line); 3UF7320-1AB, 3UF7330-1AB: 0.5 (line to line)
• Electrostatic discharge, ESD acc. to IEC 61000-4-2 kV 8 (air discharge); 3UF7020: operator input during operation only on the front
kV 6 (contact discharge); 3UF721: 4 (contact discharge)
• Field-related interference acc. to IEC 61000-4-3 V/m 10
EMC emitted interference (according to IEC 60947-1)
• Conducted and radiated interference emission EN 55011/EN 55022 (CISPR 11/CISPR 22)
(Corresponds to degree of severity A)
Protective separation (acc. to IEC 60947-1) All circuits in SIMOCODE pro are safely separated from each other according to
IEC 60947-1, i.e. they are designed with doubled creepage paths and
clearances. In this context, compliance with the instructions in the test report
"Safe Isolation" No. 2668 is required.

10/10 Siemens IC 10 A · 04/2017


© Siemens AG 2017

SIMOCODE 3UF Motor Management and Control Devices


SIMOCODE pro 3UF7 Motor Management and Control Devices
General data

Basic units
Type 3UF7000-1AU00-0, 3UF7010-1AU00-0, 3UF7000-1AB00-0, 3UF7010-1AB00-0,
3UF7011-1AU00-0, 3UF7020-1AU01-0, 3UF7011-1AB00-0, 3UF7020-1AB01-0,
3UF7012-1AU00-0, 3UF7013-1AU00-0 3UF7012-1AB00-0, 3UF7013-1AB00-0
Control circuit
Rated control supply voltage Us (acc. to IEC 61131-2) 110 ... 240 AC/DC; 50/60 Hz 24 V DC
Operating range
• SIMOCODE pro C (3UF7000) and SIMOCODE pro V PROFIBUS 0.85 ... 1.1 x Us 0.80 ... 1.2 × Us
(3UF7010) SIMOCODE pro V Modbus RTU (3UF7012)
• SIMOCODE pro V PROFINET (3UF7011), SIMOCODE pro V
EtherNet/IP (3UF7013) and SIMOCODE pro S (3UF7020)
- Operation 0.85 ... 1.1 x Us 0.80 ... 1.2 × Us
- Start up 0.85 ... 1.1 x Us 0.85 ... 1.2 × Us
Power consumption
• SIMOCODE pro C (3UF7000) and SIMOCODE pro S (3UF7020) 7 VA/5 W 5W
• SIMOCODE pro V PROFIBUS (3UF7010) and SIMOCODE pro V 10 VA/7 W 7W
Modbus RTU (3UF7012) including two connected expansion
modules
• SIMOCODE pro V PROFIBUS E15/V 4.0 7 VA/5 W 4W
(3UF7010-1A.00-0 -Z B01), incl. two connected expansion
modules
• SIMOCODE pro V PROFINET (3UF7011) and SIMOCODE pro V 11 VA/8 W 8W
EtherNet/IP (3UF7013), including two connected expansion
modules
Rated insulation voltage Ui V 300 (at pollution degree 3)
Rated impulse withstand voltage Uimp kV 4
Relay outputs
• Number
- SIMOCODE pro C, SIMOCODE pro V 3 monostable relay outputs
- SIMOCODE pro S 2 monostable relay outputs
• Specified short-circuit protection for auxiliary contacts
(relay outputs)
- Fuse links 6 A operational class gG; 10 A quick-response (IEC 60947-5-1)
- Miniature circuit breaker 1.6 A, C characteristic (IEC 60947-5-1); 6 A, C characteristic (Ik < 500 A)
• Rated uninterrupted current A 6
• Rated switching capacity
- AC-15 6 A/24 V AC 6 A/120 V AC 3 A/230 V AC
- DC-13 2 A/DC 24 V 0.55 A/DC 60 V 0.25 A/DC 125 V
Inputs (binary) 4 inputs supplied internally by the device electronics (with 24 V DC) and
connected to a common potential
Thermistor motor protection (binary PTC)
• Summation cold resistance k  1.5
• Response value k 3.4 ... 3.8
• Return value k 1.5 ... 1.65

2nd generation current/voltage measuring modules

10
Type 3UF7110- 3UF7111- 3UF7112- 3UF7113- 3UF7114-
1AA01-0 1AA01-0 1AA01-0 1.A01-0 1BA01-0
Main circuit
Set current Ie A 0.3 ... 4 3 ... +40 10 ... 115 20 ... 200 63 ... 630
Rated insulation voltage Ui V 690
Rated operational voltage Ue V 690
Rated impulse withstand voltage Uimp kV 6
Rated frequency Hz 50/60
Type of current Three-phase current
Short circuit Additional short-circuit protection is required in the main circuit
Typical voltage measuring range
• Phase-to-phase voltage/line-to-line voltage (e.g. UL1 L2) V 110 ... 690
• Phase voltage (e.g. UL1 N) V 65 ... 400
Accuracy at 25 °C, 50/60 Hz
Valid for current range A 0.25 ... 8 7.5 ... 230 15 ... 400 15 ... 400 47 ... 1260
and for voltage range • Phase-to-phase voltage VL in the range 0.85 x 110 V - 1.1 x 690 V
• Phase voltage VL in the range 0.85 x 65 V - 1.1 x 400 V
• Current measurement % 1.5
• Voltage measurement % 1.5
• Power factor measurement (p.f. 0.5) % 1.5
• Apparent power measurement (p.f. 0.5) % 3
• Active power measurement (p.f. 0.5) % 5
• Energy measurement (p.f. 0.5) % 5
• Frequency measurement (p.f. 0.5) % 1.5
Notes on voltage measurement
• Supply lines for voltage measurement In the supply lines from the main circuit for voltage measurement of
SIMOCODE pro it may be necessary to provide additional line protection!

Siemens IC 10 A · 04/2017 10/11


© Siemens AG 2017

SIMOCODE 3UF Motor Management and Control Devices


SIMOCODE pro 3UF7 Motor Management and Control Devices
General data

Current measuring modules or current/voltage measuring


modules
Type 3UF7110- 3UF7111- 3UF7112- 3UF7113- 3UF7114-
1AA00-0 1AA00-0 1AA00-0 1.A00-0 1BA00-0
Main circuit
Set current Ie A 0.3 ... 3 2.4 … 25 10 ... 100 20 ... 200 63 ... 630
Rated insulation voltage Ui V 690; 3UF7103 and 3UF7104: 1 000 (at pollution degree 3)
Rated operational voltage Ue V 690
Rated impulse withstand voltage Uimp kV 6; 3UF7103 and 3UF7104: 8
Rated frequency Hz 50/60
Type of current Three-phase current
Short circuit Additional short-circuit protection is required in the main circuit
Accuracy of current measurement (in the range of 1 x minimum % 3
current setting Iu to 8 x max. current setting Io)
Typical voltage measuring range
• Phase-to-phase voltage/line-to-line voltage (e.g. UL1 L2) V 110 ... 690
• Phase voltage (e.g. UL1 N) V 65 ... 400
Accuracy
• Voltage measurement (phase voltage UL in the range 230 ... 400 V) % 3 (typical)
• Power factor measurement % 5 (typical)
(in the rated load range PF (cos )= 0.4 ... 0.8)
• Apparent power measurement (in the rated load range) % 5 (typical)
Notes on voltage measurement
• In insulated, high-resistance or asymmetrically grounded forms of In these networks the current/voltage measuring module can be used only with an
power supply system and for single-phase systems upstream decoupling module on the system interface.
• Supply lines for voltage measurement In the supply lines from the main circuit for voltage measurement of
SIMOCODE pro it may be necessary to provide additional line protection!
Digital modules or multifunction modules
Type 3UF7300, 3UF7310, 3UF7600
Control circuit
Rated insulation voltage Ui V 300 (at pollution degree 3)
Rated impulse withstand voltage Uimp kV 4
Relay outputs
• Number 2 monostable or bistable relay outputs (depending on the version)
• Specified short-circuit protection for auxiliary contacts
(relay outputs)
- Fuse links 6 A operational class gG; 10 A quick-response (IEC 60947-5-1)
- Miniature circuit breaker 1.6 A, C characteristic (IEC 60947-5-1); 6 A, C characteristic (Ik < 500 A)
• Rated uninterrupted current A 6
• Rated switching capacity
- AC-15 6 A/24 V AC 6 A/120 V AC 3 A/230 V AC
- DC-13 2 A/24 V DC 0.55 A/60 V DC 0.25 A/125 V DC
10

Inputs (binary) 4 inputs, electrically isolated, supplied externally with 24 V DC or


110 ... 240 V AC/DC depending on the version, connected to a common potential
Ground-fault modules or multifunction modules
Type 3UF7510, 3UF7600
Control circuit
Connectable residual-current transformer 3UL23
Type of current for monitoring Type A (AC and pulsating DC residual currents)
Adjustable response value 30 mA ... 40 A
Relative measurement error % 7.5
Temperature modules or multifunction modules
Type 3UF7600, 3UF7700
Sensor circuit
Number of temperature sensors
• 3UF7700 3 temperature sensors
• 3UF7600 1 temperature sensor
Typical sensor current
• PT100 mA 1 (typical)
• PT1000/KTY83/KTY84/NTC mA 0.2 (typical)
Open-circuit/short-circuit detection
• Sensor type PT100/PT1000 KTY83-110 KTY84 NTC
- Open circuit ✓ ✓ ✓ --
- Short circuit ✓ ✓ ✓ ✓
- Measuring range °C -50 ... +500 -50 ... +175 -40 ... +300 80 ... 160
Measuring accuracy at 20 °C ambient temperature (T20) K <2
Deviations due to ambient temperature % 0.05 per K deviation from T20
(in % of the measuring range)
Conversion time ms 500
Connection type Two- or three-wire connection
✓ Detection possible -- Detection not possible

10/12 Siemens IC 10 A · 04/2017


© Siemens AG 2017

SIMOCODE 3UF Motor Management and Control Devices


SIMOCODE pro 3UF7 Motor Management and Control Devices
General data

Analog module
Type 3UF74
Control circuit
Inputs
• Channels 2 (passive)
• Parameterizable measuring ranges mA 0/4 ... 20
• Shielding Up to 30 m shield recommended, from 30 m shield required
• Max. input current (destruction limit) mA 40
• Accuracy % 1
• Input resistance  50
• Conversion time ms 150
• Resolution Bit 12
• Open-circuit detection With measuring range 4 ... 20 mA
Outputs
• Channels 1
• Parameterizable output range mA 0/4 ... 20
• Shielding Up to 30 m shield recommended, from 30 m shield required
• Max. voltage at output V DC 30
• Accuracy % 1
• Max. output load  500
• Conversion time ms 25
• Resolution Bit 12
• Short-circuit proof Yes
Connection type Two-wire connection
Electrical separation of inputs/output to the device electronics No
Fail-safe digital modules
Type 3UF7320-1AB00-0 3UF7320-1AU00-0 3UF7330-1AB00-0 3UF7330-1AU00-0
Control circuit
Rated control supply voltage Us V 24 DC 110 ... 240 AC/DC; 24 DC 110 ... 240 AC/DC;
50/60 Hz 50/60 Hz
Power consumption 3 CO 9.5 VA/4.5 W 4W 11 VA/5.5 W
Rated insulation voltage V 300
Rated impulse withstand voltage Uimp kV 4
Relay outputs
• Number 2 relay enabling circuits, 2 relay outputs
Version of the fuse link A 4, operational class gG
For short-circuit protection of the relay enabling circuit
Rated uninterrupted current A 5
Rated switching capacity
• AC-15 3 A/AC 24 V; 3 A/AC 120 V; 1.5 A/AC 230 V
• DC-13 4 A/24 V DC; 0.55 A/60 V DC; 0.22 A/125 V DC
Inputs (binary) 5 (with internal power supply from the device electronics)

10
Cable length
• Between sensor/start signal and evaluation electronics m 1500
• For further digital signals m 300
Safety data 1)
SIL level max. according to IEC 61508 3
Performance level PL according to EN ISO 13849-1 e
Category according to EN ISO 13849-1 4
Stop category according to EN 60204-1 0
Probability of a dangerous failure
(at 40 °C) for SIL 3 applications
• Per hour (PFHd) at a high demand rate 1/h 4.5 x 10-9 4.6 x 10-9 4.4 x 10-9 4.4 x 10-9
according to IEC 62061
• On demand (PFDavg) at a low demand rate 5.4 x 10-6 5.5 x 10-6 5.1 x 10-6 5.2 x 10-6
according to IEC 61508
T1 value for proof-test interval or a 20
service life according to IEC 61508
1)
More safety data, see system manual
"SIMOCODE pro Safety Fail-Safe Digital Modules",
https://support.industry.siemens.com/cs/ww/en/view/50564852.

Siemens IC 10 A · 04/2017 10/13


© Siemens AG 2017

SIMOCODE 3UF Motor Management and Control Devices


SIMOCODE pro 3UF7 Motor Management and Control Devices
General data

■ More information
Configuration instructions when using an operator panel Use of a decoupling module (voltage measurement in insulated
with display and/or a decoupling module with networks) in combination with an operator panel with display
SIMOCODE pro V with PROFIBUS or Modbus RTU
Digital Digital Analog Temperature Ground-fault
If you want to use an operator panel with display and/or a decou- module 1 module 2 module module module
pling module in the SIMOCODE pro V system with PROFIBUS SIMOCODE pro V (24 V DC)
(product version earlier than E15) or Modbus RTU (product ver- ✓ -- ✓ ✓ ✓
sion earlier than E02), configuration instructions concerning the
✓ ✓ -- ✓ ✓
type and number of connectable expansion modules must be
observed. SIMOCODE pro V (110 ... 240 V AC/DC)
✓1) -- ✓ ✓ ✓
The following tables show the maximum possible configuration ✓ ✓ -- -- --
of the expansion modules for the various combinations. These
✓2) ✓2) ✓3) -- --
are also conveniently stored in the TIA Selection Tool. See
www.siemens.com/tia-selection-tool. ✓ -- -- ✓ ✓

The DM-F Local and DM-F PROFIsafe fail-safe expansion ✓ Available


modules behave in this connection like digital modules for -- Not available
1)
standard applications. No bistable relay outputs and no more than three of five relay outputs
active simultaneously (> 3 s).
Use of an operator panel with display 2)
No bistable relay outputs and no more than five of seven relay outputs
active simultaneously (> 3 s).
Digital Digital Analog Temperature Ground-fault 3)
Analog module output is not used.
module 1 module 2 module module module
Only operator panel with display for SIMOCODE pro V Configuration instructions for the use of a fail-safe
(24 V DC or 110 ... 240 V AC/DC) expansion module
Max. four expansion modules can be used
Operator panel with display and current/voltage measurement Fail-safe Digital Analog Temperature Ground-fault
with SIMOCODE pro V (110 ... 240 V AC/DC) digital module 2 module module module
module
Max. three expansion modules can be used or:
DM-F Local
-- -- ✓ ✓ --
Max. four expansion modules can be used
✓ Available DM-F PROFIsafe
-- Not available Max. three expansion modules can be used or:
Use of a decoupling module (voltage measurement in insulated ✓ ✓ ✓ ✓ --
networks) ✓ Available
-- Not available
Digital Digital Analog Temperature Ground-fault
module 1 module 2 module module module Protective separation
SIMOCODE pro V (24 V DC)
All circuits in SIMOCODE pro are safely isolated from each other
✓1) ✓1) ✓ ✓ ✓
in accordance with IEC 60947-1. That is, they are designed with
SIMOCODE pro V (110 ... 240 V AC/DC)
10

double creepages and clearances. In the event of a fault, there-


✓ ✓ -- ✓ ✓ fore, no parasitic voltages can be formed in neighboring circuits.
✓1) ✓1) ✓ ✓ -- The instructions of Test log No. 2668 must be complied with.
✓ -- ✓ ✓ --
Types of protection EEx e and EEx d
✓ -- ✓ -- ✓
The overload protection and the thermistor motor protection of
✓ Available
the SIMOCODE pro system comply with the requirements for
-- Not available overload protection of explosion-proof motors to the type of
1)
No bistable relay outputs and no more than five of seven relay outputs protection:
active simultaneously (> 3 s).
• EEx d "flameproof enclosure" e.g. according to IEC 60079-1
• EEx e "increased safety" e.g. according to IEC 60079-7
When using SIMOCODE pro devices with a 24 V DC control
voltage, electrical separation must be ensured using a battery or
a safety transformer according to IEC 61558-2-6.
EC type-examination certificate BVS 06 ATEX F 001
Test report: BVS PP 05.2029 EG.

10/14 Siemens IC 10 A · 04/2017


© Siemens AG 2017

SIMOCODE 3UF Motor Management and Control Devices


SIMOCODE pro 3UF7 Motor Management and Control Devices
Basic units

■ Selection and ordering data


Version SD Screw terminals PU PS* PG
(UNIT,
Article No. Price SET, M)
d per PU
SIMOCODE pro PROFIBUS
SIMOCODE pro C
PROFIBUS DP interface, 12 Mbps, RS 485
4 I/3 O freely assignable, input for thermistor connection,
monostable relay outputs
Rated control supply voltage Us:
• 24 V DC } 3UF7000-1AB00-0 1 1 unit 42J
• 110 ... 240 V AC/DC } 3UF7000-1AU00-0 1 1 unit 42J

3UF7000-1A.00-0
SIMOCODE pro S1)
PROFIBUS DP interface, 1.5 Mbps, RS 485
4 I/2 O freely assignable, input for thermistor connection,
monostable relay outputs, can be expanded by a
multifunction module
Rated control supply voltage Us:
• 24 V DC } 3UF7020-1AB01-0 1 1 unit 42J
• 110 ... 240 V AC/DC } 3UF7020-1AU01-0 1 1 unit 42J

3UF7020-1A.01-0
SIMOCODE pro V2)
PROFIBUS DP interface, 12 Mbps, RS 485
4 I/3 O freely assignable, input for thermistor connection,
monostable relay outputs, can be expanded by
expansion modules
Rated control supply voltage Us:
• 24 V DC } 3UF7010-1AB00-0 1 1 unit 42J
• 110 ... 240 V AC/DC } 3UF7010-1AU00-0 1 1 unit 42J

3UF7010-1A.00-0
SIMOCODE pro PROFINET
SIMOCODE pro V PROFINET
ETHERNET/PROFINET IO,
OPC UA server and web server, 100 Mbps,
2 x connection to bus through RJ45, PROFINET system

10
redundancy, media redundancy protocol,
4 I/3 O freely assignable, input for thermistor connection,
monostable relay outputs, can be expanded by expansion
modules, web server in German/English/Chinese/Russian
Rated control supply voltage Us:
• 24 V DC } 3UF7011-1AB00-0 1 1 unit 42J
3UF7011-1A.00-0
• 110 ... 240 V AC/DC } 3UF7011-1AU00-0 1 1 unit 42J
1)
The connection cable to the current measuring module must be at least
30 cm.
2)
For the use of 2nd-generation current/voltage measuring modules,
SIMOCODE pro V PROFIBUS with product version E15 (V 4.0) must be
ordered. This version does not have marine certification or CCC approval
and can be ordered at no extra charge. The article number must be
supplemented by "-Z" and the order code "B01",
e.g. 3UF7010-1A.00-0 -Z B01.

* You can order this quantity or a multiple thereof.


Illustrations are approximate Siemens IC 10 A · 04/2017 10/15
© Siemens AG 2017

SIMOCODE 3UF Motor Management and Control Devices


SIMOCODE pro 3UF7 Motor Management and Control Devices
Basic units

Version SD Screw terminals PU PS* PG


(UNIT,
Article No. Price SET, M)
d per PU
SIMOCODE pro Modbus RTU
SIMOCODE pro V Modbus RTU1)
Modbus RTU interface, 57.6 kbp, RS485,
4 I/3 O freely parameterizable,
input for thermistor connection,
monostable relay outputs,
can be expanded using expansion modules
Rated control supply voltage Us:
• 24 V DC } 3UF7012-1AB00-0 1 1 unit 42J
• 110 ... 240 V AC/DC } 3UF7012-1AU00-0 1 1 unit 42J
3UF7012-1A.00-0
SIMOCODE pro EtherNet/IP
SIMOCODE pro V EtherNet/IP1)
EtherNet/IP interface, web server, 100 Mbps,
2 x connection to bus through RJ45,
media redundancy DLR,
4 I/3 O freely parameterizable,
input for thermistor connection,
monostable relay outputs,
can be expanded using expansion modules,
web server in German/English/Chinese/Russian
Rated control supply voltage Us:
3UF7013-1A.00-0 • 24 V DC } 3UF7013-1AB00-0 1 1 unit 42J
• 110 ... 240 V AC/DC } 3UF7013-1AU00-0 1 1 unit 42J
SIMOCODE pro current or current/voltage measuring modules
Current measuring modules
• Straight-through 0.3 ... 3 45 } 3UF7100-1AA00-0 1 1 unit 42J
transformers 2.4 … 25 45 } 3UF7101-1AA00-0 1 1 unit 42J
10 ... 100 55 } 3UF7102-1AA00-0 1 1 unit 42J
20 ... 200 120 } 3UF7103-1AA00-0 1 1 unit 42J
• Bus connections 20 ... 200 120 } 3UF7103-1BA00-0 1 1 unit 42J
63 ... 630 145 } 3UF7104-1BA00-0 1 1 unit 42J
3UF7100-1AA00-0
2nd generation current/voltage measuring modules
for SIMOCODE pro V1)
Voltage measurement up to 690 V,
measured values with increased accuracy,
10

power, power factor and active current monitoring


• Straight-through 0.3 ... 4 45 } 3UF7110-1AA01-0 1 1 unit 42J
transformers 3 ... +40 45 } 3UF7111-1AA01-0 1 1 unit 42J
10 ... 115 55 } 3UF7112-1AA01-0 1 1 unit 42J
3UF7110-1AA01-0 20 ... 200 120 } 3UF7113-1AA01-0 1 1 unit 42J
• Bus connections 20 ... 200 120 } 3UF7113-1BA01-0 1 1 unit 42J
63 ... 630 145 } 3UF7114-1BA01-0 1 1 unit 42J
Note:
The 2nd-generation current/voltage measuring modules require
SIMOCODE pro V PROFIBUS basic units as of product version
E15 (Z version), SIMOCODE pro V PROFINET as of product
version E10 or SIMOCODE pro V EtherNet/IP as of product
version E01, see page 10/15 and above.
3UF7113-1AA01-0
Current/voltage measuring modules
for SIMOCODE pro V
Voltage measurement up to 690 V
If required in connection with a decoupling module
• Straight-through 0.3 ... 3 45 } 3UF7110-1AA00-0 1 1 unit 42J
transformers 2.4 … 25 45 } 3UF7111-1AA00-0 1 1 unit 42J
10 ... 100 55 } 3UF7112-1AA00-0 1 1 unit 42J
20 ... 200 120 } 3UF7113-1AA00-0 1 1 unit 42J
3UF7110-1AA00-0
• Bus connections 20 ... 200 120 } 3UF7113-1BA00-0 1 1 unit 42J
63 ... 630 145 } 3UF7114-1BA00-0 1 1 unit 42J
1) The SIMOCODE ES (TIA Portal) V14 software is necessary for Note:
parameterization, see page 14/20.
SIMOCODE pro V basic unit in a hardened version via
SIPLUS extreme upon request.

* You can order this quantity or a multiple thereof.


10/16 Siemens IC 10 A · 04/2017 Illustrations are approximate
© Siemens AG 2017

SIMOCODE 3UF Motor Management and Control Devices


SIMOCODE pro 3UF7 Motor Management and Control Devices
Basic units

Version Current setting Width SD Screw terminals PU PS* PG


(UNIT,
Article No. Price SET, M)
A mm d per PU
SIMOCODE pro decoupling modules
Decoupling module
For connecting upstream from a current/voltage 2 3UF7150-1AA00-0 1 1 unit 42J
measuring module on the system interface when using
voltage detection in insulated, high-resistance or
asymmetrically grounded systems and in single-phase
systems

3UF7150-1AA00-0
SIMOCODE pro operator panels
Operator panels
Installation in control cabinet door or front plate,
for plugging into all SIMOCODE pro basic units,
ten LEDs for status indication and user-assignable
buttons for controlling the motor
• Titanium gray } 3UF7200-1AA01-0 1 1 unit 42J

3UF7200-1AA01-0
• Light gray } 3UF7200-1AA00-0 1 1 unit 42J

3UF7200-1AA00-0
Operator panels for SIMOCODE pro V
Installation in control cabinet door or front plate, for
plugging into SIMOCODE pro V and SIMOCODE pro V PN,
seven LEDs for status indication and user-assignable
buttons for controlling the motor, multilingual display, e.g.
for indication of measured values, status information or
fault messages
• Titanium gray
- English/German/French/Spanish/Portuguese/ } 3UF7210-1AA01-0 1 1 unit 42J
Italian/Polish/Finnish

10
- English/Chinese/Russian/Korean } 3UF7210-1BA01-0 1 1 unit 42J

3UF7210-1.A01-0
• Light gray
- English/German/French/Spanish/Portuguese/ } 3UF7210-1AA00-0 1 1 unit 42J
Italian/Polish/Finnish
- English/Chinese/Russian/Korean } 3UF7210-1BA00-0 1 1 unit 42J

3UF7210-1.A00-0

* You can order this quantity or a multiple thereof.


Illustrations are approximate Siemens IC 10 A · 04/2017 10/17
© Siemens AG 2017

SIMOCODE 3UF Motor Management and Control Devices


SIMOCODE pro 3UF7 Motor Management and Control Devices
Expansion modules

■ Selection and ordering data


Version SD Screw terminals PU PS* PG
(UNIT,
Article No. Price SET, M)
d per PU
Expansion modules for SIMOCODE pro V
With SIMOCODE pro V, it is possible to expand the type
and number of inputs and outputs in steps. Each expansion
module has two system interfaces on the front. Through the
one system interface the expansion module is connected to
the system interface of the SIMOCODE pro V using a
connection cable; through the second system interface,
further expansion modules or the operator panel can be
connected. The power supply for the expansion modules is
provided by the connection cable through the basic unit.
Note:
Please order connection cable separately, see page 10/21.

Digital modules
Up to two digital modules can be used to add additional
binary inputs and relay outputs to the basic unit. The input
circuits of the digital modules are supplied from an external
power supply.
Four binary inputs and two relay outputs
Up to two digital modules can be connected
Relay outputs Input voltage
Monostable 24 V DC } 3UF7300-1AB00-0 1 1 unit 42J
3UF7300-1AU00-0 110 ... 240 V AC/DC } 3UF7300-1AU00-0 1 1 unit 42J
Bistable 24 V DC } 3UF7310-1AB00-0 1 1 unit 42J
110 ... 240 V AC/DC } 3UF7310-1AU00-0 1 1 unit 42J

Analog module
By means of the analog module, the basic unit can be } 3UF7400-1AA00-0 1 1 unit 42J
optionally expanded with analog inputs and outputs
(0/4 ... 20 mA).
Two inputs (passive) for input and one output for output of
0/4 ... 20 mA signals, max. one analog module can be
connected per pro V basic unit and max. two analog
modules per pro V PN basic unit

3UF7400-1AA00-0
10

Ground-fault modules1)
Ground-fault monitoring using 3UL23 residual-current } 3UF7510-1AA00-0 1 1 unit 42J
transformers and ground-fault modules is used in cases
where precise detection of the ground-fault current is
required or power systems with high impedance are
grounded.
With the ground-fault module, it is possible to determine
the precise fault current as a measured value, and to
define freely selectable warning and trip limits in a wide
range from 30 mA ... 40 A.
3UF7510-1AA00-0 One input for connecting a 3UL23 residual-current
transformer, up to one ground-fault module can be
connected
Note:
For corresponding residual-current transformers, see
Catalog IC 10, Chapter 10 or Industry Mall.
Temperature modules
Irrespective of the thermistor motor protection of the basic } 3UF7700-1AA00-0 1 1 unit 42J
units, an additional max. three analog temperature sensors
can be evaluated using a temperature module.
Sensor types: PT100/PT1000, KTY83/KTY84 or NTC
Three inputs for connecting up to three analog temperature
sensors, up to one temperature module can be connected
per pro V basic unit and up to two temperature modules
per pro V PN basic unit
3UF7700-1AA00-0
1)
Possible with pro V PROFIBUS basic unit from product version E10, pro V
PROFINET basic unit from product version E04, all pro V Modbus RTU or
EtherNet/IP basic units.

* You can order this quantity or a multiple thereof.


10/18 Siemens IC 10 A · 04/2017 Illustrations are approximate
© Siemens AG 2017

SIMOCODE 3UF Motor Management and Control Devices


SIMOCODE pro 3UF7 Motor Management and Control Devices
Expansion modules

Version SD Screw terminals PU PS* PG


(UNIT,
Article No. Price SET, M)
d per PU
Expansion modules for SIMOCODE pro S
With SIMOCODE pro S, it is possible to expand the type
and number of inputs and outputs. The expansion module
has two system interfaces on the front. Through the one
system interface the expansion module is connected to the
system interface of the SIMOCODE pro S using a connec-
tion cable; through the second system interface, the opera-
tor panel can be connected. The power supply for the
expansion module is provided by the connection cable
through the basic unit.
Note:
Please order connection cable separately, see page 10/21.

Multifunction modules
The multifunction module is the expansion module of the
SIMOCODE pro S device series with the following
functions:
• Digital module function with four digital inputs and two
monostable relay outputs
• Ground-fault module function with an input for the
connection of a 3UL23 residual-current transformer with
freely selectable warning and trip limits in a wide zone of
30 mA ... 40 A
3UF7600-1AU01-0 • Temperature module function with an input for connecting
an analog temperature sensor PT100, PT1000, KTY83,
KTY84, or NTC
Max. one multifunction module can be connected per
pro S basic unit
Input voltage of the digital inputs:
• 24 V DC } 3UF7600-1AB01-0 1 1 unit 42J
• 110 ... 240 V AC/DC } 3UF7600-1AU01-0 1 1 unit 42J

10

* You can order this quantity or a multiple thereof.


Illustrations are approximate Siemens IC 10 A · 04/2017 10/19
© Siemens AG 2017

SIMOCODE 3UF Motor Management and Control Devices


SIMOCODE pro 3UF7 Motor Management and Control Devices
Fail-safe expansion modules

■ Selection and ordering data


Version SD Screw terminals PU PS* PG
(UNIT,
Article No. Price SET, M)
d per PU
Fail-safe expansion modules for SIMOCODE pro V
Thanks to the fail-safe expansion modules,
SIMOCODE pro V can be expanded with the function of a
safety relay for the fail-safe disconnection of motors.
A maximum of one fail-safe digital module can be
connected; it can be used instead of a digital module.
The fail-safe expansion modules are equipped likewise with
two system interfaces at the front for making the connection
to other system components. Unlike other expansion
modules, power is supplied to the modules through a
separate terminal connection.
Note:
Please order connection cable separately, see page 10/21.

DM-F Local fail-safe digital modules


For fail-safe disconnection using a hardware signal
Two relay enabling circuits, joint switching; two relay
outputs, common potential disconnected fail-safe; inputs
for sensor circuit, start signal, cascading and feedback
circuit, safety function adjustable using DIP switches
Rated control supply voltage Us:
• 24 V DC } 3UF7320-1AB00-0 1 1 unit 42J
• 110 ... 240 V AC/DC } 3UF7320-1AU00-0 1 1 unit 42J
3UF7320-1AB00-0
DM-F PROFIsafe fail-safe digital modules1)
For fail-safe disconnection using PROFIBUS/PROFIsafe or
PROFINET/PROFIsafe
Two relay enabling circuits, joint switching; two relay
outputs, common potential disconnected fail-safe; one
input for feedback circuit; three binary standard inputs
Rated control supply voltage Us:
• 24 V DC } 3UF7330-1AB00-0 1 1 unit 42J
• 110 ... 240 V AC/DC } 3UF7330-1AU00-0 1 1 unit 42J
3UF7330-1AB00-0
1)
Cannot be used in conjunction with SIMOCODE pro V for Modbus RTU or
EtherNet/IP communication.
10

* You can order this quantity or a multiple thereof.


10/20 Siemens IC 10 A · 04/2017 Illustrations are approximate
© Siemens AG 2017

SIMOCODE 3UF Motor Management and Control Devices


SIMOCODE pro 3UF7 Motor Management and Control Devices
Accessories

■ Selection and ordering data


Version SD Article No. Price PU PS* PG
per PU (UNIT,
SET, M)
d
Connection cables (essential accessory)
In different lengths for connecting basic unit, current
measuring module, current/voltage measuring module,
operator panel or expansion modules or decoupling
module
Version Length
Flat 0.025 m } 3UF7930-0AA00-0 1 1 unit 42J
Flat 0.1 m } 3UF7931-0AA00-0 1 1 unit 42J
3UF7932-0AA00-0 Flat 0.3 m } 3UF7935-0AA00-0 1 1 unit 42J
Flat 0.5 m } 3UF7932-0AA00-0 1 1 unit 42J
Round 0.5 m } 3UF7932-0BA00-0 1 1 unit 42J
Round 1.0 m } 3UF7937-0BA00-0 1 1 unit 42J
Round 2.5 m } 3UF7933-0BA00-0 1 1 unit 42J
PC cables and adapters
USB PC cables } 3UF7941-0AA00-0 1 1 unit 42J
For connecting to the USB interface of a PC/PG,
for communication with SIMOCODE pro through the
system interface
3UF7941-0AA00-0

USB/serial adapters 5 3UF7946-0AA00-0 1 1 unit 42J


To connect an RS 232 PC cable to to the USB interface of
a PC, recommended for use in conjunction with
SIMOCODE pro 3UF7

Memory modules
Enable transmission to a new system,
e.g. when a device is replaced, without the need for
additional aids or detailed knowledge of the device.
Memory module for SIMOCODE pro C } 3UF7900-0AA00-0 1 1 unit 42J
For saving the complete parameterization of a
SIMOCODE pro C system
Memory module for SIMOCODE pro S and
SIMOCODE pro V
For saving the complete parameterization of a
SIMOCODE pro system

10
• Titanium gray } 3UF7901-0AA01-0 1 1 unit 42J

3UF7901-0AA01-0
• Light gray } 3UF7901-0AA00-0 1 1 unit 42J

3UF7901-0AA00-0
Interface covers
For system interface
• Titanium gray 10 3RA6936-0B 1 5 units 42F

3RA6936-0B
• Light gray } 3UF7950-0AA00-0 1 5 units 42J

3UF7950-0AA00-0
Addressing plugs
For assigning the PROFIBUS or Modbus RTU address } 3UF7910-0AA00-0 1 1 unit 42J
without using a PC/PG to SIMOCODE pro through the
system interface

3UF7910-0AA00-0

* You can order this quantity or a multiple thereof.


Illustrations are approximate Siemens IC 10 A · 04/2017 10/21
© Siemens AG 2017

SIMOCODE 3UF Motor Management and Control Devices


SIMOCODE pro 3UF7 Motor Management and Control Devices
Accessories

Version SD Article No. Price PU PS* PG


per PU (UNIT,
SET, M)
d
Accessories for motor control centers
With the draw-out technology often used in motor control
centers it is possible to integrate a SIMOCODE pro
initialization module in the switchboard on a permanent
basis. Feeder-related parameter and address data can
then be permanently assigned to this feeder.
Initialization module } 3UF7902-0AA00-0 1 1 unit 42J
For automatic parameterization of SIMOCODE pro S and
SIMOCODE pro V basic units (pro V PROFIBUS basic
units from product version E09)

3UF7902-0AA00-0
Y connection cable
For use in conjunction with the initialization module;
connects the basic unit, current measuring module or
current/voltage measuring module, and initialization
module
System interface length Open cable end
0.1 m 1.0 m } 3UF7931-0CA00-0 1 1 unit 42J
0.5 m 1.0 m } 3UF7932-0CA00-0 1 1 unit 42J
1.0 m 1.0 m } 3UF7937-0CA00-0 1 1 unit 42J
Bus connection terminals
For shield support and strain relief of the PROFIBUS cable } 3UF7960-0AA00-0 1 1 unit 42J
on a SIMOCODE pro S

3UF7960-0AA00-0
Door adapters
For external connection of the system interface, } 3UF7920-0AA00-0 1 1 unit 42J
e.g. outside a control cabinet
10

3UF7920-0AA00-0
Adapters for operator panel
The adapter enables the smaller 3UF7200 operator panel } 3UF7922-0AA00-0 1 1 unit 42J
from SIMOCODE pro to be used in a front panel cutout in
which previously, e.g. after a change of system, a larger
3UF52 operator panel from SIMOCODE-DP had been
used, degree of protection IP54

3UF7922-0AA00-0
Labeling strips
• For pushbuttons of the 3UF720 operator panel } 3UF7925-0AA00-0 100 400 units 42J
• For pushbuttons of the 3UF721 operator panel with } 3UF7925-0AA01-0 100 600 units 42J
display
• For LEDs of the 3UF720 operator panel } 3UF7925-0AA02-0 100 1200 units 42J

3UF7925-0AA02-0
Push-in lugs
For screw fixing, e.g. on mounting plate,
two units required per device
• Can be used for 3UF71.0, 3UF71.1 and 3UF71.2 2 3RV2928-0B 100 10 units 41E
• Can be used for 3UF700, 3UF701, 3UF73, 3UF74, 3UF75 5 3RP1903 1 10 units 41H
and 3UF77
3RV2928-0B • Can be used for 3UF7020, 3UF7600 2 3ZY1311-0AA00 1 10 units 41L

* You can order this quantity or a multiple thereof.


10/22 Siemens IC 10 A · 04/2017 Illustrations are approximate
© Siemens AG 2017

SIMOCODE 3UF Motor Management and Control Devices


SIMOCODE pro 3UF7 Motor Management and Control Devices
Accessories

Version SD Article No. Price PU PS* PG


per PU (UNIT,
SET, M)
d
Terminal covers
Covers for cable lugs and busbar connections
• Length 100 mm, can be used for 3UF71.3-1BA0.-0 } 3RT1956-4EA1 1 1 unit 41B
• Length 120 mm, can be used for 3UF71.4-1BA0.-0 } 3RT1966-4EA1 1 1 unit 41B
Covers for box terminals
• Length 25 mm, can be used for 3UF71.3-1BA0.-0 } 3RT1956-4EA2 1 1 unit 41B
• Length 30 mm, can be used for 3UF71.4-1BA0.-0 } 3RT1966-4EA2 1 1 unit 41B
3RT1956-4EA1 Covers for screw terminals
Between contactor and current measuring module or
current/voltage measuring module for direct mounting
• Can be used for 3UF71.3-1BA0.-0 } 3RT1956-4EA3 1 1 unit 41B
3RT1956-4EA2 • Can be used for 3UF71.4-1BA0.-0 } 3RT1966-4EA3 1 1 unit 41B
Box terminal blocks
For round and ribbon cables
• Up to 70 mm2, can be used for 3UF71.3-1BA0.-0 } 3RT1955-4G 1 1 unit 41B
• Up to 120 mm2, can be used for 3UF71.3-1BA0.-0 } 3RT1956-4G 1 1 unit 41B
• Up to 240 mm2, can be used for 3UF71.4-1BA0.-0 } 3RT1966-4G 1 1 unit 41B

3RT195.-4G
Bus termination modules
With separate control supply voltage for bus termination following
the last unit on the bus line
Supply voltage:
• 115/230 V AC 5 3UF1900-1KA00 1 1 unit 42J
• 24 V DC 5 3UF1900-1KB00 1 1 unit 42J

3UF1900-1KA00
Software
SIMOCODE ES (TIA Portal)

10
Software for configuring, commissioning, operating and
diagnosing SIMOCODE pro based on the TIA Portal,
see page 14/20.

3ZS1322-.C.12-0Y.5
SIMOCODE ES
Software for configuring, commissioning, operating and
diagnosing SIMOCODE pro in Version 2007,
see Catalog IC 10, Chapter 14 or Industry Mall.

3ZS1312-.C.10-0Y.5
SIMOCODE pro block library for SIMATIC PCS 7
The PCS 7 block library can be used for simple and
convenient integration of SIMOCODE pro into the
SIMATIC PCS 7 process control system, see page 14/24.

3ZS1632-.XX02-0Y.0

* You can order this quantity or a multiple thereof.


Illustrations are approximate Siemens IC 10 A · 04/2017 10/23
© Siemens AG 2017

SIMOCODE 3UF Motor Management and Control Devices

3UF18 current transformers for overload protection

■ Overview
The 3UF18 current transformers are protection transformers and
More information are used for actuating overload relays. Protection transformers
Home page, see www.siemens.com/sirius are designed to ensure proportional current transfer up to a
Industry Mall, see www.siemens.com/product?3UF18 multiple of the primary rated current. The 3UF18 current trans-
formers convert the maximum current of the corresponding
operating range into the standard value of 1 A secondary.

■ Selection and ordering data


Type of mounting Operating range SD Screw terminals PU PS* PG
(UNIT,
Article No. Price SET, M)
A d per PU
For stand-alone installation
Screw fixing and snap-on 0.25 … 2.51) 20 3UF1843-1BA00 1 1 unit 42J
mounting onto TH 35 standard 1.25 … 12.51) 20 3UF1843-2AA00 1 1 unit 42J
mounting rail according to 2.5 … 251) 20 3UF1843-2BA00 1 1 unit 42J
IEC 60715 12.5 ... 50 20 3UF1845-2CA00 1 1 unit 42J
16 … 65 20 3UF1847-2DA00 1 1 unit 42J
25 … 100 20 3UF1848-2EA00 1 1 unit 42J

3UF1843

For mounting onto contactors and stand-alone installation


Screw fixing 32 … 130 20 3UF1850-3AA00 1 1 unit 42J
50 … 200 20 3UF1852-3BA00 1 1 unit 42J
63 … 250 20 3UF1854-3CA00 1 1 unit 42J
100 … 400 20 3UF1856-3DA00 1 1 unit 42J
125 … 500 20 3UF1857-3EA00 1 1 unit 42J
160 … 630 20 3UF1868-3FA00 1 1 unit 42J
205 … 820 20 3UF1868-3GA00 1 1 unit 42J
3UF1868

1) The following setting ranges for the protection of EEx e motors are
applicable:
- 3UF1843-1BA00: 0.25 ... 1.25 A
- 3UF1843-2AA00. 1.25 ... 6.3 A
- 3UF1843-2BA00: 2.5 ... 12.5 A.

■ Accessories
10

For contactor type SD Article No. Price PU PS* PG


per PU (UNIT,
SET, M)
d
Terminal covers
For transformer/contactor combinations and stand-alone
installation for transformer (cover required per connection
side)
3UF1845 20 3TX7446-0A 1 1 unit 41B
3UF1848 20 3TX7466-0A 1 1 unit 41B
3UF1850, 3UF1852 5 3TX7506-0A 1 1 unit 41B
3UF1854 to 3UF1857 5 3TX7536-0A 1 2 units 41B
3UF1868-3FA00 5 3TX7686-0A 1 1 unit 41B
3UF1868-3GA00 5 3TX7696-0A 1 1 unit 41B
3TX7466-0A
For covering the screw terminal for direct mounting on
contactor (cover required per contactor/transformer
combination)
3UF1848 20 3TX7466-0B 1 1 unit 41B
3UF1850, 3UF1852 20 3TX7506-0B 1 1 unit 41B
3UF1854 to 3UF1857 20 3TX7536-0B 1 1 unit 41B
3UF1868-3FA00 15 3TX7686-0B 1 1 unit 41B

* You can order this quantity or a multiple thereof.


10/24 Siemens IC 10 A · 04/2017 Illustrations are approximate
14
© Siemens AG 2017

Parameterization, Configuration and Visualization with SIRIUS

Price groups
PG 2AP, 346, 42B, 42C, 42D, 42H,
42J

14/2 Introduction

14/5 Simulation Tool for Soft Starters


(STS)

14/6 SIRIUS Soft Starter ES


(TIA Portal)

14/9 Soft Starter ES

14/12 SIRIUS 3RW44 Soft Starter


block library for SIMATIC PCS 7

14/15 Motor Starter ES

14/18 SIRIUS Motor Starter block library


for SIMATIC PCS 7

14/20 SIMOCODE ES (TIA Portal)

SIMOCODE ES

14/24 SIMOCODE pro block library


for SIMATIC PCS 7

14/31 AS-Interface block library


for SIMATIC PCS 7

14/34 SIRIUS Safety ES

Click on the Article No. in the


catalog PDF to access it in the
14

Industry Mall and get all related


information.
Article No.

3RA1943-2C
3RA1943-2B
3RA1953-2B
IC01_00413

3RA1953-2N

Or directly in the Internet, e. g.


www.siemens.com/
product?3RA1943-2C

Siemens IC 10 A · 04/2017
© Siemens AG 2017

Parameterization, Configuration and Visualization with SIRIUS

SIMOCODE ES (TIA Portal)

■ Overview
SIMOCODE ES V14 Basic Standard Premium
Access through the local interface ✓ ✓ ✓
on the device
Parameter assignment in list form ✓ ✓ ✓
Parameter printing in list form ✓ ✓ ✓
Operating ✓ ✓ ✓
Diagnostics ✓ ✓ ✓
Test ✓ ✓ ✓
Service data ✓ ✓ ✓
Analog value recording1) ✓ ✓ ✓
Trend display of measured values -- ✓ ✓
Parameterizing with convenient -- ✓ ✓
graphical display
Parameterizing with the integrated -- ✓ ✓
graphics editor (CFC-based)
Printing of diagrams -- ✓ ✓
Selecting the SIMOCODE pro device configuration in SIMOCODE ES Parameter comparison -- ✓ ✓
(TIA Portal)
Access through -- -- ✓
More information PROFIBUS/PROFINET/EtherNet2)
Teleservice through MPI -- -- ✓
Home page, see www.siemens.com/sirius
Routing3) -- -- ✓
Industry Mall, see www.siemens.com/product?3ZS1
✓ Function available
Technical specifications, see
https://support.industry.siemens.com/cs/ww/en/ps/16716/td -- Function not available
To download the SIMOCODE ES (TIA Portal) software see
https://support.industry.siemens.com/cs/ww/en/view/109738034 1) For SIMOCODE pro V.
To download the SIMOCODE ES 2007 software see 2)
In combination with Modbus devices, SIMOCODE ES Premium does not
https://support.industry.siemens.com/cs/ww/en/view/109480470 offer any additional functions compared with SIMOCODE ES Standard.
3)
See http://support.automation.siemens.com/WW/view/en/109738745.
SIMOCODE ES is the central software for configuration, startup,
operation and diagnostics of SIMOCODE pro. Working with libraries
Version 14, which is based on the central engineering framework Users can create copy templates for SIMOCODE pro device
Totally Integrated Automation Portal (TIA Portal), is available in configuration and can manage them in global or project
addition to SIMOCODE ES Version 2007. libraries.
This way, individual modules, diagrams and complete device
SIMOCODE ES V14 is integrated seamlessly when further
configurations can be saved as reusable elements for frequently
TIA Portal-based software such as STEP 7 or WinCC is available,
occurring tasks.
thus enabling users to achieve a consistent, efficient and
intuitive solution for all automation tasks. Integrated graphics editor
However, use of SIMOCODE ES V14 as stand-alone software The graphics editor is a part of SIMOCODE ES Standard and
also provides these advantages. SIMOCODE ES Premium. It is based on the Continuous Function
Chart (CFC) and adds a powerful tool to the parameterizing
Three program versions interface that enables easy parameterization of devices by
The user can choose between three different versions of drag & drop. Extremely compact documentation of all config-
SIMOCODE ES: SIMOCODE ES Basic, SIMOCODE ES Standard ured parameters is possible, as is the graphic online presenta-
and SIMOCODE ES Premium. While SIMOCODE ES Basic is a tion of the configured device functions including all signal states
powerful tool for startup or maintenance personnel, during operation.
SIMOCODE ES Standard and Premium are the perfect tools for
engineers or configuration engineers on account of their larger
scope of functions and integrated graphics editor. Unlike the
Standard version, SIMOCODE ES Premium also permits
parameterization and diagnostics through PROFIBUS.
PROFINET/EtherNet. Indication of all operating, service and
diagnostics data supplies important information about the
current state of the motor and plant at all times – everywhere on
PROFIBUS/PROFINET/EtherNet.
14

Parameterize easily and ergonomically with the CFC-based graphics


editor of SIMOCODE ES V14

14/20 Siemens IC 10 A · 04/2017


© Siemens AG 2017

Parameterization, Configuration and Visualization with SIRIUS

SIMOCODE ES (TIA Portal)


Online functions for startup and diagnosis
To this end, SIMOCODE ES provides powerful functions for
startup and diagnosis of motor feeders. Besides a detailed dis-
play of status information and the causes of faults, all available
measurement and statistics data can be retrieved online.
Access to the fault and event memory and also to analog values
recorded on the device, e.g. current or voltage, is also possible.

Live trend display of SIMOCODE ES V14


Additional functions
SIMOCODE ES V14 offers numerous advantages of the
TIA Portal that can be used in an integrated working
environment.
Seamless integration
Commissioning functions of SIMOCODE ES V14 When using other TIA Portal-based software such as STEP 7 or
Trend display of measured values WinCC, for example, the configuration for devices and networks
for all components used is created in a standardized environ-
With this online function, SIMOCODE ES Standard or Premium ment.
can present the trends of different measured values. It is thus
possible for example to record and evaluate the startup charac-
teristic of a motor or its behavior under different load conditions.

■ Benefits
• Easy parameterization with the graphics editor based on the • Universally applicable through stand-alone version or
Continuous Function Chart (CFC) reduces engineering work seamless integration into the central engineering framework
and shortens start up times when other TIA Portal-based software such as STEP 7 or
• Clear plant documentation by means of graphic presentation WinCC are available
• Detailed information, also when there are faults, is a help for • Parameter changes are also possible during normal operation
maintenance personnel and shortens downtimes • Users can create copy templates for device configurations
and can manage them in global libraries

14

Siemens IC 10 A · 04/2017 14/21


© Siemens AG 2017

Parameterization, Configuration and Visualization with SIRIUS

SIMOCODE ES (TIA Portal)

■ Selection and ordering data


Parameterization and service software for SIMOCODE pro 3UF7
• Delivered without PC cable
Version SD Article No. Price PU PS* PG
per PU (UNIT,
SET, M)
d
SIMOCODE ES V14 Basic
Floating license for one user
Engineering software,
software and documentation on DVD,
6 languages (English/German/French/Italian/
Spanish/Chinese),
combo license for parallel use of versions 2007 and
V14 of SIRIUS ES,
for all SIMOCODE pro,
online functions via system interface
• License key on USB flash drive, Class A } 3ZS1322-4CC12-0YA5 1 1 unit 42J
3ZS1322-4CC12-0YA5 • License key download, Class A } 3ZS1322-4CE12-0YB5 1 1 unit 42J
SIMOCODE ES V14 Standard
Floating license for one user
Engineering software,
software and documentation on DVD,
6 languages (English/German/French/Italian/
Spanish/Chinese),
combo license for parallel use of versions 2007 and
V14 of SIRIUS ES,
for all SIMOCODE pro,
online functions via system interface,
parameterizing with the integrated graphics editor
(CFC-based)
3ZS1322-5CC12-0YA5
• License key on USB flash drive, Class A } 3ZS1322-5CC12-0YA5 1 1 unit 42J
• License key download, Class A } 3ZS1322-5CE12-0YB5 1 1 unit 42J
Upgrade for SIMOCODE ES 2007 2 3ZS1322-5CC12-0YE5 1 1 unit 42J
Floating license for one user,
engineering software,
software and documentation on DVD,
license key on USB flash drive, Class A
6 languages (English/German/French/Italian/
Spanish/Chinese),
combo license for parallel use of versions 2007 and
V14 of SIRIUS ES,
for all SIMOCODE pro,
online functions via system interface,
parameterizing with the integrated graphics editor
(CFC-based)
Powerpack for SIMOCODE ES V14 Basic 2 3ZS1322-5CC12-0YD5 1 1 unit 42J
Floating license for one user,
engineering software,
license key on USB flash drive, Class A
6 languages (English/German/French/Italian/
Spanish/Chinese),
for all SIMOCODE pro,
online functions via system interface,
parameterizing with the integrated graphics editor
(CFC-based)
Software Update Service } 3ZS1322-5CC12-0YL5 1 1 unit 42J
For 1 year with automatic extension,
requires software version of SIMOCODE ES (TIA Portal),
engineering software,
software and documentation on DVD,
online functions via system interface,
parameterizing with the integrated graphics editor
(CFC-based)
14

Notes:
SIMOCODE ES V13 licenses can also be used for
SIMOCODE ES V14.
Please order PC cable separately, see page 14/23.
For description of the software versions, see page 14/20.

* You can order this quantity or a multiple thereof.


14/22 Siemens IC 10 A · 04/2017 Illustrations are approximate
© Siemens AG 2017

Parameterization, Configuration and Visualization with SIRIUS

SIMOCODE ES (TIA Portal)

Version SD Article No. Price PU PS* PG


per PU (UNIT,
SET, M)
d
SIMOCODE ES V14 Premium
Floating license for one user
Engineering software,
software and documentation on DVD,
6 languages (English/German/French/Italian/
Spanish/Chinese),
combo license for parallel use of versions 2007 and
V14 of SIRIUS ES, for all SIMOCODE pro,
online functions via system interface and
PROFIBUS/PROFINET/Ethernet/IP,
parameterizing with the integrated graphics editor
(CFC-based)
3ZS1322-6CC12-0YA5
• License key on USB flash drive, Class A } 3ZS1322-6CC12-0YA5 1 1 unit 42J
• License key download, Class A } 3ZS1322-6CE12-0YB5 1 1 unit 42J
Upgrade for SIMOCODE ES 2007 2 3ZS1322-6CC12-0YE5 1 1 unit 42J
Floating license for one user, engineering software,
software and documentation on DVD,
license key on USB flash drive, Class A
6 languages (English/German/French/Italian/
Spanish/Chinese),
combo license for parallel use of versions 2007 and
V14 of SIRIUS ES, for all SIMOCODE pro,
online functions via system interface and
PROFIBUS/PROFINET/EtherNet/IP,
parameterizing with the integrated graphics editor
(CFC-based)
Powerpack for SIMOCODE ES V14 Standard 2 3ZS1322-6CC12-0YD5 1 1 unit 42J
Floating license for one user, engineering software,
license key on USB flash drive, Class A
6 languages (English/German/French/Italian/
Spanish/Chinese),
for all SIMOCODE pro,
online functions via system interface and
PROFIBUS/PROFINET/EtherNet/IP,
parameterizing with the integrated graphics editor
(CFC-based)
Software Update Service } 3ZS1322-6CC12-0YL5 1 1 unit 42J
For 1 year with automatic extension,
requires software version of SIMOCODE ES (TIA Portal),
engineering software,
software and documentation on DVD,
online functions via system interface and
PROFIBUS/PROFINET/EtherNet/IP,
parameterizing with the integrated graphics editor
(CFC-based)
SIMOCODE ES V14 software download
Trial license, Class A } 3ZS1322-6CE12-0YG8 1 1 unit 42J
Engineering software,
6 languages (English/German/French/Italian/
Spanish/Chinese),
for all SIMOCODE pro,
online functions via system interface and
PROFIBUS/PROFINET/EtherNet/IP,
parameterizing with the integrated graphics editor
(CFC-based)
Notes:
Please order PC cable separately, see Accessories. For description of the software versions, see page 14/20.

■ Accessories
Version SD Article No. Price PU PS* PG
14

per PU (UNIT,
SET, M)
d
Optional accessories
USB PC cables } 3UF7941-0AA00-0 1 1 unit 42J
For connecting to the USB interface of a PC/PG,
for communication with SIMOCODE ES through the system
interface
3UF7941-0AA00-0 USB/serial adapters 5 3UF7946-0AA00-0 1 1 unit 42J
For connecting an RS 232 PC cable to the USB interface of
a PC, recommended for use in conjunction with
SIMOCODE ES

* You can order this quantity or a multiple thereof.


Illustrations are approximate Siemens IC 10 A · 04/2017 14/23
© Siemens AG 2017

Parameterization, Configuration and Visualization with SIRIUS

SIMOCODE pro block library for SIMATIC PCS 7

■ Overview

Advanced Process Library (APL) - faceplates and blocks for statistical


data of the SIMOCODE pro library for PCS 7

More information
Home page, see www.siemens.com/sirius
Industry Mall, see www.siemens.com/product?3ZS1
Technical specifications, see
https://support.industry.siemens.com/cs/ww/en/ps/16718/td
Programming and Operating Manual for the "SIMOCODE pro PCS 7 Library":
• Version V8.2, see
https://support.industry.siemens.com/cs/ww/en/view/103954289
• Version V8.0 + SP3, see
https://support.industry.siemens.com/cs/ww/en/view/84626047

The PCS 7 block library can be used for simple and easy
integration of SIMOCODE pro into the SIMATIC PCS 7 process
control system. One focus here is on easy configuration, Advanced Process Library (APL) - faceplates and function blocks for
because the number of required configuration steps is reduced control and measured data of the SIMOCODE pro library for PCS 7
crucially. The configuration of the modules is based on the
PCS 7 standard configuration processes and is optimally harmo-
nized with the functions of SIMOCODE pro. Users who have
previously integrated conventional motor feeders into PCS 7 will
therefore find it easy to switch to SIMOCODE pro.

■ Benefits
• Uniform and continuous integration into SIMATIC PCS 7 • Greater process transparency due to greater information
• Standardized blocks for simple integration and optimal density in the process control system
operation
14

14/24 Siemens IC 10 A · 04/2017


© Siemens AG 2017

Parameterization, Configuration and Visualization with SIRIUS

SIMOCODE pro block library for SIMATIC PCS 7

■ Selection and ordering data


Version SD Article No. Price PU PS* PG
per PU (UNIT,
SET, M)
d
SIMOCODE pro block library for SIMATIC PCS 7
Version V8 with Advanced Process Library (APL)
Engineering software V8 } 3ZS1632-1XX02-0YA0 1 1 unit 42J
For one engineering station (single license)
including runtime software for execution of the
AS modules in an automation system
(single license), English/German
Scope of supply:
AS blocks and faceplates for integrating SIMOCODE pro
into the PCS 7 process control system
with Advanced Process Library,
for PCS 7 version V8.0, V8.1 and V8.2
3ZS1632-1XX02-0YA0 Type of delivery:
software and documentation on CD,
one license for one engineering station
one license for one automation station
Runtime license V8 } 3ZS1632-2XX02-0YB0 1 1 unit 42J
For execution of the AS modules in an
automation system (single license)
Required for using the AS modules of the engineering
software V8 within a plant
Type of delivery:
one license for one automation station,
without software and documentation

14

* You can order this quantity or a multiple thereof.


Illustrations are approximate Siemens IC 10 A · 04/2017 14/25
© Siemens AG 2017

Parameterization, Configuration and Visualization with SIRIUS

SIMOCODE pro block library for SIMATIC PCS 7

Version SD Article No. Price PU PS* PG


per PU (UNIT,
SET, M)
d
SIMOCODE pro block library for SIMATIC PCS 7 version V7
without Advanced Process Library (APL)
Engineering software V7 } 3UF7982-0AA10-0 1 1 unit 42J
For one engineering station (single license)
including runtime software for execution of the
AS modules in an automation system
(single license), English/German/French
Scope of supply:
AS modules and faceplates for integrating
SIMOCODE pro into the PCS 7 process control system,
for PCS 7 version V7.0/V7.1
Type of delivery:
3UF7982-0AA10-0 software and documentation on CD,
one license for one engineering station
one license for one automation station
Runtime license V7 } 3UF7982-0AA11-0 1 1 unit 42J
For execution of the AS modules in an
automation system (single license)
Required for using the AS modules of the engineering
software V7 or the engineering software migration V7-V8 on
an additional automation system within a plant
Type of delivery:
one license for one automation station,
without software and documentation
Upgrade for PCS 7 block library 2 3UF7982-0AA13-0 1 1 unit 42J
SIMOCODE pro, V6.0 or V6.1
to version SIMOCODE pro V7.0/V7.1
For one engineering station (single license)
including runtime software for execution of the
AS modules in an automation system
(single license), English/German/French
Scope of supply:
AS modules and faceplates for integrating
SIMOCODE pro into the PCS 7 process control system,
for PCS 7 version V7.0 or V7.1
Type of delivery:
software and documentation on CD,
one license for one engineering station
one license for one automation station
Engineering software migration V7-V8 } 3UF7982-0AA20-0 1 1 unit 42J
For upgrading (migrating) an existing engineering software
V7 of the SIMOCODE pro block library for PCS 7
Conditions of use:
availability of the engineering software V7 (license) of the
SIMOCODE pro block library for PCS 7 for the PCS 7
version V7.0 or V7.1
Engineering software migration V7-V8 can be installed
directly onto a system with PCS 7 version V8; installation of
the previous version is unnecessary.
For one engineering station (single license)
including runtime software for execution of the AS modules
in an automation system (single license),
English/German/French
Scope of supply:
AS blocks and faceplates for integrating SIMOCODE pro
into the PCS 7 process control system,
for PCS 7 version V8.0 and higher
Type of delivery:
software and documentation on CD,
license for upgrading an existing license
for one engineering station and the associated
14

runtime licenses of a plant

* You can order this quantity or a multiple thereof.


14/26 Siemens IC 10 A · 04/2017 Illustrations are approximate
© Siemens AG 2017

Industrial Controls

Conditions of sale and delivery

■ 1. General Provisions ■ 3. Additional Terms and Conditions


By using this catalog you can acquire hardware and software The dimensions are in mm. In Germany, according to the
products described therein from Siemens AG subject to the German law on units in measuring technology, data in inches
following Terms and Conditions of Sale and Delivery (hereinafter apply only to devices for export.
referred to as "T&C"). Please note that the scope, the quality and Illustrations are not binding.
the conditions for supplies and services, including software
products, by any Siemens entity having a registered office Insofar as there are no remarks on the individual pages of this
outside Germany, shall be subject exclusively to the General catalog - especially with regard to data, dimensions and weights
Terms and Conditions of the respective Siemens entity. The given - these are subject to change without prior notice.
following T&C apply exclusively for orders placed with Siemens
Aktiengesellschaft, Germany. ■ 4. Export regulations
1.1 For customers with a seat or registered office in We shall not be obligated to fulfill any agreement if such
Germany fulfillment is prevented by any impediments arising out of
national or international foreign trade or customs requirements
For customers with a seat or registered office in Germany, the
or any embargoes and/or other sanctions.
following applies subordinate to the T&C:
Export of goods listed in this catalog may be subject to licensing
• the "General Terms of Payment"1) and,
requirements. We will indicate in the delivery details whether
• for software products, the "General License Conditions for licenses are required under German, European and US export
Software Products for Automation and Drives for Customers lists. Goods labeled with "AL" not equal to "N" are subject to
with a Seat or Registered Office in Germany"1) and, European or German export authorization when being exported
• for other supplies and services, the "General Conditions for out of the EU. Goods labeled with "ECCN" not equal to "N" are
the Supply of Products and Services of the Electrical and subject to US re-export authorization.
Electronics Industry"1). The export indications can be viewed in advance in the
description of the respective goods on the Industry Mall, our
1.2 For customers with a seat or registered office outside
online catalog system. Only the export labels "AL" and "ECCN"
Germany
indicated on order confirmations, delivery notes and invoices
For customers with a seat or registered office outside Germany, are authoritative.
the following applies subordinate to the T&C:
Even without a label, or with label "AL:N" or "ECCN:N", authori-
• the "General Terms of Payment"1) and, zation may be required i .a. due to the final disposition and
• for software products, the "General License Conditions for intended use of goods.
Software Products for Automation and Drives for Customers If you transfer goods (hardware and/or software and/or
with a Seat or Registered Office outside of Germany"1) and technology as well as corresponding documentation, regardless
• for other supplies and/or services, the "General Conditions for of the mode of provision) delivered by us or works and services
Supplies of Siemens Industry for Customers with a Seat or (including all kinds of technical support) performed by us to a
Registered Office outside of Germany"1). third party worldwide, you must comply with all applicable
national and international (re-)export control regulations.
■ 2. Prices If required for the purpose of conducting export control checks,
you (upon request by us) shall promptly provide us with all infor-
The prices are in € (Euro) ex point of delivery, exclusive of mation pertaining to the particular end customer, final dispo-
packaging. sition and intended use of goods delivered by us respectively
The sales tax (value added tax) is not included in the prices. It works and services provided by us, as well as to any export
shall be charged separately at the respective rate according to control restrictions existing in this relation.
the applicable statutory legal regulations. The products listed in this catalog may be subject to
Prices are subject to change without prior notice. We will charget European/German and/or US export regulations. Any export
the prices valid at the time of delivery. requiring approval is therefore subject to authorization by the
To compensate for variations in the price of raw materials (e.g. relevant authorities.
silver, copper, aluminum, lead, gold, dysprosium and neodym), Errors excepted and subject to change without prior notice.
surcharges are calculated on a daily basis using the so-called
metal factor for products containing these raw materials. A
surcharge for the respective raw material is calculated as a 1) The text of the Terms and Conditions of Siemens AG can be
supplement to the price of a product if the basic official price of downloaded at
the raw material in question is exceeded. www.siemens.com/automation/salesmaterial-
The metal factor of a product indicates the basic official price as/catalog/en/terms_of_trade_en.pdf
(for those raw materials concerned) as of which the surcharges
on the price of the product are applied, and with what method of
calculation.
An exact explanation of the metal factor can be downloaded at:
www.siemens.com/automation/salesmaterial-
as/catalog/en/terms_of_trade_en.pdf
To calculate the surcharge (except in the cases of dysprosium
and neodym), the official price from the day prior to that on which
the order was received or the release order was effected is used.
To calculate the surcharge applicable to dysprosium and
neodym ("rare earths"), the corresponding three-month basic
average price in the quarter prior to that in which the order was
received or the release order was effected is used with a one-
month buffer (details on the calculation can be found in the
explanation of the metal factor).
© Siemens AG 2017

Get more information Security information


Control Products: Siemens provides products and solutions with industrial
www.siemens.com/sirius security functions that support the secure operation of
plants, systems, machines and networks.

Siemens AG
In order to protect plants, systems, machines and networks
Digital Factory against cyber threats, it is necessary to implement – and
Control Products continuously maintain – a holistic, state-of-the-art indus-
Postfach 23 55 trial security concept. Siemens’ products and solutions only
90713 FÜRTH
form one element of such a concept.
GERMANY
Customer is responsible to prevent unauthorized access to
its plants, systems, machines and networks. Systems,
© Siemens AG 2017
Subject to change without prior notice
machines and components should only be connected to the
PDF (E86060-K1010-A291-A1-7600) enterprise network or the internet if and to the extent
KG 0417 32 En necessary and with appropriate security measures (e.g. use
Produced in Germany of firewalls and network segmentation) in place.
Additionally, Siemens’ guidance on appropriate security
The information provided in this catalog contains merely general measures should be taken into account. For more informa-
descriptions or characteristics of performance which in case of actual
tion about industrial security, please visit
use do not always apply as described or which may change as a result
of further development of the products. An obligation to provide the
http://www.siemens.com/industrialsecurity.
respective characteristics shall only exist if expressly agreed in the
Siemens’ products and solutions undergo continuous
terms of contract. Availability and technical specifications are subject
to change without notice.
development to make them more secure. Siemens strongly
recommends to apply product updates as soon as available
All product designations may be trademarks or product names
and to always use the latest product versions. Use of
of Siemens AG or supplier companies whose use by third parties
for their own purposes could violate the rights of the owners. product versions that are no longer supported, and failure
to apply latest updates may increase customer’s exposure
to cyber threats.
To stay informed about product updates, subscribe to the
Siemens Industrial Security RSS Feed under
http://www.siemens.com/industrialsecurity.