0% found this document useful (0 votes)
19 views

Study Material

Uploaded by

jexada5774
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
19 views

Study Material

Uploaded by

jexada5774
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 4

SF6 working - The SF₆ circuit breaker works by using sulfur hexafluoride (SF₆) gas to Protective Relay: The

e Relay: The circuitry introduced for protection through automatic operation in


extinguish an arc when a fault occurs. When a fault is detected, the breaker trips and the event of abnormal conditions or faults in the machine or system is called a
separates its contacts, which causes an arc to form. The SF₆ gas, which is sealed in a protective relaying system. Relay Time: The minimum time required for the relay to
high-pressure chamber, is then directed toward the arc. As the contacts separate, the operate and disconnect the circuit during an abnormal or fault condition is called the
puffer mechanism compresses and forces the SF₆ gas over the arc. The gas has high relay time. Pick-up current: It is the minimum current in the relay coil at which the relay
dielectric strength, which helps absorb the arc’s energy and quickly cools it down, starts to operate. As long as the current in the relay is less than the pick-up value, the
effectively quenching the arc. The SF₆ gas restores the insulation between the contacts, relay does not operate . Reset Current: The current value below which the relay stops
stopping the flow of current and ensuring the system remains safe. operating after it has been activated. If the current drops below this level, the relay
Construction -The construction of an SF₆ circuit breaker consists of several key "resets" and returns to its normal state. Current Setting: A parameter set on the relay
components. The most important part is the SF₆ gas chamber, which is a sealed that defines the threshold current at which the relay will trigger an alarm or trip action.
enclosure containing sulfur hexafluoride gas under high pressure. Inside this chamber It is used to set the sensitivity of the relay Plug Setting Multiplier (PSM): A factor used
are fixed and moving contacts, which separate during a fault to create an arc. A puffer to adjust the current setting of a relay based on the plug setting. It allows for scaling the
mechanism is also integrated into the breaker; it compresses the SF₆ gas and directs it relay's protection function to match the system's requirements. Time Setting
over the arc to extinguish it. The breaker also includes a nozzle that channels the gas Multiplier (TSM): A multiplier that adjusts the time delay of the relay. By altering the
across the arc, helping to cool and quench it. Additionally, the operating mechanism, time setting, the relay's reaction time can be fine-tuned to either speed up or slow down
often spring or hydraulic-based, drives the movement of the contacts to initiate the the trip action depending on the system's needs.
separation. The entire assembly is housed in a metal or insulating casing to ensure safety
and contain the gas under pressure. The construction is designed to handle high Air Circuit Breaker (ACB): Air Circuit Breakers (ACBs) are designed to handle high fault
voltages and fault currents while providing fast and reliable arc quenching. currents, and they use air as the medium to extinguish the electric arc when the
Specification:Voltage Rating: 33 kV to 800 kV;Current Rating: Interrupts fault currents up contacts open. When a fault occurs, the breaker’s contacts separate, and an electric arc
to 63 kA or higher;Dielectric Strength: Three times that of air;Interruption Time: 40-60 is formed between them. The intense heat of the arc can cause significant damage if not
milliseconds (2-3 cycles) Applications -High Voltage: Substations, transmission systems extinguished promptly. In an ACB, the air is forced through the arc to cool it and reduce
(above 33 kV),Power,Plants/Industry: High power handling environments,Gas-Insulated the ionization of the air, thereby quenching the arc. This can be done using air blast
Switchgear (GIS): Compact, indoor setups where space and safety are priorities. systems or by utilizing natural air currents in the breaker. The arc is elongated and
cooled until it is extinguished, and the circuit is disconnected. ACBs are mainly used in
VCB Construction: It consists of an enclosure made of insulating material, such as glass. industrial and commercial installations, where the need to handle high current ratings,
The vacuum retained inside the container is about 10⁻⁷ torr. The enclosure is supported often hundreds or thousands of amps, is essential. Applications: ACBs are commonly
by end flanges made of non-magnetic material. The contacts are disc-shaped, and the used in industrial and commercial applications where large currents need to be
contact tips are made of copper-chromium or copper-bismuth alloy. The contact region controlled, such as in electrical distribution boards, transformers, and generators.
is surrounded by a vapor-condensing shield, which prevents the condensed vapor from
reaching the glass enclosure. Metallic bellows are used to allow the movement of the Miniature Circuit Breaker (MCB): MCBs are designed to protect electrical circuits from
moving contact without disturbing the vacuum. Metal-ceramic seals are used at overcurrent or short circuit conditions. They consist of a bimetallic strip and an
respective points to ensure sealing. Working: Under normal working conditions, the electromagnetic trip mechanism. When an overload occurs, the current flowing through
contacts are closed. Upon the occurrence of a fault, the moving contact moves upwards, the circuit increases, and the bimetallic strip inside the MCB heats up. As the strip bends
and an arc is produced between the contacts due to ionization of metal vapors. The arc due to the heat, it activates a trip mechanism, opening the circuit. For short circuit
is then extinguished. The arc extinction process is explained in the principle of working protection, the MCB has an electromagnetic coil that instantly detects the high surge of
of the vacuum circuit breaker. Applications: Outdoor application where maintenance current. When a short circuit occurs, the sudden increase in current creates a magnetic
required is minimum. In the high voltage system from 22 kV to 66 kV power circuits. This field that pulls a plunger, triggering the opening of the contacts to disconnect the power.
breaker is also useful in rural area with limited rating 60 to 100 MVA MCBs are typically used in low-power circuits, such as those found in homes and offices,
Specifications- A Vacuum Circuit Breaker (VCB) operates at 11 kV to 66 kV, with a current to protect appliances and devices from damage caused by overloads or short circuits.
rating up to 40 kA. It has fast interruption times (20-30 ms), high dielectric strength, and Applications: MCBs are widely used in residential and commercial buildings for
durable copper-chrome alloy contacts. VCBs are rated for over 30,000 operations and protection of low-power circuits. They are used in lighting, power distribution, and
work in temperatures from -10°C to +50°C. appliance circuits where the current is lower.

Gas Insulated Switchgear (GIS) Moulded Case Circuit Breaker (MCCB): MCCBs are similar to MCBs but are designed to
handle much higher currents, typically from 100 A to 2500 A or more. MCCBs provide
In this type of switchgear, sulfur hexafluoride (SF₆) gas is used as insulation due to its overload and short circuit protection through a combination of thermal and magnetic
excellent dielectric and arc-quenching properties. The properties of SF₆ gas include mechanisms. The thermal protection works using a bimetallic strip, just like in MCBs, but
being colorless, odorless, non-toxic, non-inflammable, inert, and stable up to 500°C. SF₆ with a wider range of current handling capabilities. The magnetic protection works
gas-insulated metal-clad switchgear is referred to as Gas Insulated Switchgear (GIS). GIS through an electromagnetic coil, which triggers a trip when a short circuit or rapid fault
is used for voltage levels such as 12 kV, 36 kV, 72 kV, 145 kV, 245 kV, 420 kV, and higher. current is detected. One key feature of MCCBs is that the trip settings can be adjusted to
In such GIS substations, various equipment, including circuit breakers (CB), bus bars, suit the specific needs of the circuit, making them more flexible for industrial and
isolators, load break switches, current transformers (CT), potential transformers (PT), commercial applications. These circuit breakers are typically used in large electrical
and earthing switches, are housed in separate metal-enclosed modules filled with SF₆ panels, industrial machinery, and buildings with high-power requirements. Applications:
gas. This gas provides phase-to-ground insulation.SF₆ has a higher dielectric strength MCCBs are used in industrial applications where higher current ratings (up to 2500 A)
than air, so the clearance required is smaller, which results in a more compact overall are required. They protect electrical installations in factories, commercial buildings.
size.GIS is widely used in areas where land is costly, such as in cities, industrial
townships, hydro stations, and densely populated areas. Earth Leakage Circuit Breaker (ELCB): The ELCB is designed to detect earth leakage
Gas Insulated Switchgear (GIS) offers the advantage of a compact design, thanks to the currents, which could pose a risk of electric shock. An ELCB works by constantly
high dielectric strength of SF₆ gas, which reduces clearance requirements and makes it monitoring the current flowing through the live and neutral conductors. Under normal
ideal for areas where land is scarce, such as cities and industrial zones. It is reliable, low- conditions, the current entering the live conductor should be equal to the current
maintenance, and can handle high voltage applications efficiently. However, its returning through the neutral conductor. If there is any leakage of current to earth—
disadvantages include high initial costs, environmental concerns due to the use of SF₆ such as when a person touches a live part or when current flows through the ground—
gas (a potent greenhouse gas), and the need for careful handling and maintenance of the balance is disturbed. The ELCB detects this imbalance and trips the circuit,
the gas. Additionally, GIS is more suitable for medium to high voltage applications, disconnecting the power supply and preventing the risk of electric shock. This type of
limiting its use in lower voltage systems. circuit breaker is essential for safety in areas where humans are at risk of electric shock,
such as bathrooms or kitchens, or in places where electrical installations are exposed to
Buchholz relay moisture. Modern ELCBs are often replaced by Residual Current Devices (RCDs) or
Construction - It consists of a domed vessel with two mercury switches. The upper Residual Current Circuit Breakers (RCCBs), which are more sensitive and provide better
mercury switch is attached to a float, which is hinged as shown. The lower mercury protection. Applications: ELCBs are used in residential and commercial installations to
switch is attached to a flap, and the mechanism is also hinged . Alarm circuit contacts protect users from electric shock. They are particularly important in wet or damp
are connected to the upper mercury switch, and trip circuit contacts are connected to environments, such as bathrooms, kitchens, or areas with water-related appliances,
the lower mercury switch. The upper mercury switch operates during incipient faults, where leakage currents pose a high risk.
while the lower mercury switch operates in the case of severe faults.
Working-Under normal working conditions, the position of the mercury switches is as A thermal relay is a type of protective relay commonly used to protect electrical circuits
shown. It can be observed that the alarm circuit contacts and trip circuit contacts are from overheating and excessive current. It operates based on the principle of thermal
not bridged by liquid mercury in the switch. In the case of incipient faults, the oil heats expansion, where an overcurrent causes a temperature rise in the relay. The thermal
up, decomposes, and gases are formed. The majority of the gas is hydrogen (70%), relay consists of a bimetallic strip or coil that bends or deflects when exposed to heat
which accumulates at the top near the dome. Due to the gas pressure, the float moves generated by excessive current. The relay is designed to trip and disconnect the circuit if
down, and the mercury level shifts, closing the alarm circuit contacts. Thus, the alarm the temperature rises beyond a preset threshold, thereby preventing damage to
circuit is completed, and the alarm sounds . Merits 1. Simple. 2. Fault detection is faster. equipment like motors, transformers, and other electrical devices. Thermal relays are
3. Operation is reliable. Demerits 1. Only applicable for oil immersed transformer. 2. widely used for motor protection and in situations where a delay is necessary for
Only the faults below oil level can be detected. handling brief overcurrent conditions, as they provide a time-delay characteristic based
on the amount of overcurrent. They are simple, reliable, and inexpensive, but are less
sensitive and slower compared to other types of relays
Alternators require protection from several faults and abnormal conditions: 1.Normal Condition:The system operates with normal or below-normal current, and
1.Prime Mover Failure: If the prime mover stops, the alternator may start drawing voltage and frequency remain within acceptable limits. The current flows through the
power, causing overheating. Reverse power protection detects this and disconnects the intended paths without disturbance. All three-phase voltages are balanced with a 120°
alternator. phase displacement. Protective systems provide efficient and economical protection.
. 2 .Field Failure (Loss of Excitation): Without excitation, the alternator loses Voltage at the consumer's end remains within ±5% limits. Standby generators are
synchronism. Field failure protection trips it to prevent instability. available for peak load hours.
3.Overcurrent: Excessive current from overloads or short circuits can damage windings. 2. Abnormal Condition:A defect in any part of the system causes abnormalities like
Overcurrent relays trip the alternator when currents exceed safe limits overcurrent, overvoltage, frequency disturbances, and equipment damage.The system
.4 .Overspeed: Caused by load loss or governor issues, overspeeding can damage the experiences unbalanced voltages and currents, power reversal, underfrequency, power
rotor. Overspeed protection trips the alternator if speed is too high. swinging, temperature rise, and instability.
5 .Overvoltage: Excess voltage from load rejection stresses insulation. Overvoltage
relays prevent damage by disconnecting the alternator. Working, Construction, and Operation of Electromagnetic Attraction Relay
6. Unbalanced Loading: Unequal loading causes overheating and rotor vibration. Working: An electromagnetic attraction relay works by generating a magnetic field when
Negative sequence relays detect imbalance and protect the alternator. current flows through its coil, attracting the armature. This movement of the armature
7. Stator Winding Fault: Internal faults in the stator windings can lead to severe damage. opens or closes contacts, triggering protective actions. The relay operates when current
Differential and earth fault protection detect these and trip the alternator. exceeds a set value (pickup current). If the current is below the set value, the armature
remains stationary, and the contacts stay in their default position.
Different Faults in Transformers Construction: The relay consists of an electromagnet, an armature, a spring for
1.Internal Faults: These include phase-to-phase faults, phase-to-ground faults, and resetting, and contacts. The electromagnet generates a magnetic field when current
inter-turn faults within the windings. They can be caused by insulation failure, passes through the coil, and the armature moves towards the electromagnet when the
overheating, or mechanical stress. current reaches the set value.
2.External Faults: These occur outside the transformer, such as faults on connected lines Operation: In the event of a fault, such as overcurrent, the current energizes the
or equipment, causing overloads or abnormal currents in the transformer. electromagnet, attracting the armature and changing the contact positions. This triggers
3.Overloading: Excessive current demand can lead to overheating, damaging insulation protective devices, like circuit breakers, to isolate the fault. The spring resets the
and windings armature once the fault is cleared, restoring the relay to its original state.

Protection Mechanisms for Transformers Working Principle of Induction Type Overcurrent Relay:
1.Differential Protection: This is the primary protection for internal faults. It compares An overcurrent relay works on the principle of electromagnetic induction. When the
the currents at the transformer's primary and secondary windings. Under normal current in the circuit exceeds a predetermined value, it generates a magnetic field that
conditions, the currents are balanced. In case of an internal fault, a difference arises, induces current in a secondary winding. This induced current produces a torque on an
which triggers the differential relay to trip the transformer. It is sensitive and effective aluminium disk, causing it to rotate.
for detecting internal faults. Construction of Induction Type Overcurrent Relay:
2.Overcurrent Protection: Overcurrent relays protect against excessive current caused Electromagnet: Consists of primary and secondary windings.
by overloads or external faults. When the current exceeds a preset level, the overcurrent Driving Disk: An aluminium disk is placed between the electromagnets. The torque
relay trips, disconnecting the transformer to prevent overheating. generated by the induced current causes the disk to rotate.
3.Earth Fault Protection: Earth (ground) fault relays detect leakage current that flows to Spring: Provides a restraining torque that opposes the driving torque.
the ground, which could indicate insulation failure or a phase-to-ground fault. This Operation of Induction Type Overcurrent Relay: When current flows through the
protection trips the transformer to avoid severe insulation damage. primary winding, it induces current in the secondary winding, creating a rotating
4.Overheating Protection: Overheating protection monitors transformer temperature magnetic field. This field interacts with the aluminium disk, causing it to rotate. The
through sensors (thermistors or RTDs). If the temperature exceeds safe levels, the relay rotation of the disk is opposed by the restraining torque from the spring. If the current
trips to prevent insulation breakdown and winding damage. This protection is crucial, as exceeds a preset value (the overcurrent setting), the driving torque overcomes the
overheating is one of the main causes of transformer failure. restraining torque, causing the disk to rotate sufficiently. This movement triggers the
relay, which opens the circuit breaker and isolates the faulty section of the system.
Limitations of Differential Protection
1.Sensitivity to Inrush Current: When a transformer is energized, a high inrush current Static Relay : A static relay is a type of relay that has no moving parts. The comparison or
flows, which can falsely trigger differential protection. Special techniques, such as measurement of electrical quantities is done by a stationary network. The relay gives a
harmonic restraint, are used to prevent nuisance tripping . tripping signal when the threshold condition is reached. The rectified output is fed to
2.External Fault Disturbance: External faults with high currents may cause momentary the relay measuring circuit, and when the threshold condition is met, an output is
unbalance in differential current, leading to possible misoperation . produced. This output is then amplified by an amplifier. The amplified signal is sent to
3.CT Saturation: Saturation of current transformers (CTs) during faults can cause the output device, which energises the trip coil to operate the circuit breaker.
incorrect readings, potentially affecting differential protection accuracy. Advantages: 1. Consume very less power. 2. Have a long life. 3. High accuracy and
Shock proof. 5. Reset time is very less. 5. Very sensitive since they use amplifiers.
Arc Voltage: The voltage that maintains the arc between the circuit breaker contacts Disadvantages : 1. Affected by high voltage. 2. Electrostatic discharge. 3.More costly.
during the interruption process. It arises due to ionization of the medium and helps 4. Affected by surrounding conditions.
sustain the arc until it is extinguished.
Restriking Voltage: The transient voltage that appears across the circuit breaker contacts Directional relay: Need and operation
immediately after arc extinction or at current zero. This voltage can cause the arc to Need of directional relays : In a power system, electrical power flows from the source to
restrike if it occurs during the transient period; if not, the arc will not restrike later. the load under normal conditions. However, in the event of faults or abnormal
Recovery Voltage: The voltage that appears across the circuit breaker contacts after the conditions, power may flow in the reverse direction in some parts of the system. In such
arc is fully extinguished and all transients have dissipated. It is a steady-state voltage at cases, it is essential to detect the reverse power flow and quickly isolate the faulty
the system’s nominal frequency, typically equal to the supply voltage. section of the system. Reverse power flow is detected by directional relays.
RRRV : RRRV (Rate of Rise of Restriking Voltage): RRRV is the speed at which the Operation of a Directional Relay : A directional relay detects the direction of power
restriking voltage increases after the circuit breaker opens. It determines if the arc will flow by comparing the phase angle between the voltage and current. It uses a polarising
restrike: if RRRV exceeds the dielectric strength rise between contacts, the arc will voltage and a measuring current to determine if the power is flowing in the correct
restrike. RRRV depends on the recovery voltage and the natural frequency of the L-C direction. Normal Flow: When the current and voltage are in phase, the relay detects
circuit formed by the system’s inductance and capacitance. normal power flow. Reverse Flow: If the current and voltage are out of phase (reverse
power flow), the relay trips and isolates the faulty section of the system.
Faults: 1. Symmetrical Faults: A symmetrical fault, also known as a balanced fault,
involves all three phases equally and occurs when all phases experience the same fault Isolators are devices used in electrical systems to isolate a section of the circuit for
conditions. This type of fault is less common but more severe.A fault where all three maintenance or fault isolation, ensuring safety. They operate when the circuit is de-
phases are shorted together, or to the ground, with equal impedance. This fault is rare energized and do not carry current during normal operation.
but can cause severe damage if not cleared quickly. Cause: Typically caused by severe
external events, such as lightning strikes or equipment failure that affects all three Vertical Break Type Isolator:
phases simultaneously. Vertical break isolators are outdoor air-break disconnecting switches rated 7 kV and
above. They are gang operated and designed for outdoor applications, isolating circuit
2. Unsymmetrical Faults: It involve unequal fault conditions between phases. These are
breakers, transformer banks, surge arresters, and for line sectioning. The contacts break
more common and less severe than symmetrical faults: Single Line-to-Ground Fault:
vertically, providing adequate clearance for high-voltage applications.
One phase is in contact with the ground, and the other two phases are unaffected.
Line-to-Line Fault: Two phases come into contact with each other. Horizontal Break Type Isolator:
Double Line-to-Ground Fault: Two phases are in contact with the ground. This isolator has three stacks of insulators per phase mounted on a galvanized steel
Cause: These faults are typically caused by external factors like tree branches, animals, frame. The two outer stacks are fixed, while the central stack rotates around its vertical
or insulation breakdown. axis through about 90°. It is used for voltages above 245 kV, offering flexibility in high-
voltage installations.
Protection Zones : Protection zones are specific areas or sections of a power system Pantograph Type Isolator:
where protective measures are applied to detect and isolate faults. Each zone is The pantograph isolator uses a pantograph mechanism, where the insulator column
designed to monitor the health of particular equipment or sections, such as generators, rotates to close the upper arms on the overhead bus bar. The current flows through the
transformers, transmission lines, and feeders. The idea is to isolate faults within the conducting arms. Upon opening, the pantograph blades collapse vertically, providing
smallest possible area to minimize the impact on the rest of the system.
isolation between the line and the upper terminal. This design is suitable for overhead
Backup Protection: Backup protection is a secondary level of protection that provides
line systems.
redundancy in case the primary protection fails to detect or isolate a fault. Backup
protection systems are typically set to operate with a time delay to avoid interfering with
the faster-acting primary protection.
Need for energy conservation in induction motor : The need for energy conservation in Need for Energy Conservation in Transformers
induction motors arises from their widespread use and the high amount of energy they
consume. Transformers are vital power equipment in a power system, playing a significant role in
1.High Operating Costs: Induction motors are used extensively in industrial and the generation, transmission, and distribution of electrical energy. The operating
commercial applications, which leads to significant electricity costs. Energy conservation efficiency of a transformer directly affects the costs and benefits of the entire power
can help reduce these costs substantially, improving profitability. system. In a typical power distribution grid, electric transformer power loss contributes
2.Energy Demand and Grid Load: Induction motors contribute to a large portion of to about 40-50% of the total transmission and distribution loss. The demand for
energy demand on electrical grids. Conserving energy helps to reduce peak demand, distribution transformers is ever-increasing. The power loss generated by transformers
easing the burden on power generation and distribution infrastructure. can be considerable due to their large transportation energy requirements and long
3.Environmental Impact: Lowering energy consumption in induction motors reduces the operating times. According to statistics, the total power loss generated by transformers
need for additional power generation, which often relies on fossil fuels. This leads to can account for about 10% of the total generation capacity. Therefore, the study of
lower greenhouse gas emissions and supports environmental sustainability goals. transformer energy conservation is essential.
4.Longer Motor Lifespan: By using energy conservation practices like matching motor
size to the load, regular maintenance, and avoiding excessive rewinding, motors operate Causes of technical losses : I²R Losses (Resistance in Conductors): Energy is lost as
more efficiently and experience less strain. This leads to a longer lifespan, reducing the heat when current flows through resistive materials. Minimising conductor length and
frequency of replacements and maintenance costs. using high-conductivity materials can reduce these losses. Core Losses in
5.Improved Efficiency and Performance: Energy-efficient motors can operate at higher Transformers: Losses due to hysteresis and eddy currents in transformer cores. Using
efficiency levels, resulting in more stable and reliable performance, which can enhance high-quality core materials reduces these losses. Losses in Electrical Machines:
productivity in industrial settings. Motors and generators experience losses from friction and resistance in windings. Using
6.Compliance with Efficiency Standards: Many countries have regulations and efficiency efficient machines with proper maintenance reduces these losses.
standards for motors. Energy conservation measures ensure that businesses comply Inductive Losses: Reactive power in inductive components causes losses. Power factor
with these standards, avoiding potential fines and supporting national energy correction devices help reduce these. Leakage Currents: Energy
conservation goals. lost due to electrical leakage through degraded insulation. Regular maintenance can
prevent leakage. Corona Losses: Losses in high-voltage transmission due to ionization
Energy conservation techniques for induction motors of air around conductors. Improved insulation can mitigate these losses.
Motor Survey: Conducting a motor survey helps identify inefficient motors or those Transformer Load Losses: Losses from resistance in transformer windings under load.
running under unsuitable conditions. This allows for targeted interventions, like Proper transformer sizing reduces these losses.
replacing or resizing motors, to optimise energy use. Reduce technical losses : Controlling I²R losses- It involves using high-conductivity
Matching Motor to Load: Ensuring that the motor size is appropriate for the load materials like copper or aluminum for conductors, reducing the transmission distance to
requirements prevents energy wastage. Motors operating under light loads are lower resistance, and ensuring proper sizing of conductors to match the load. Regular
inefficient, so selecting a motor that closely matches the load improves energy maintenance of cables and equipment is also crucial to avoid any increase in resistance
efficiency. due to damage or corrosion.
Operating in Star Mode: For motors running at partial load, operating in star mode
reduces the voltage and, consequently, the energy consumption. This technique is Optimizing distribution- Optimizing distribution voltage helps reduce losses by
effective when motors are running at lower than full load. maintaining voltage at optimal levels. Higher voltage levels are more efficient, as they
Rewinding of Motor: When motors fail, rewinding them can restore functionality, but reduce I²R losses. Voltage regulation equipment, such as voltage regulators or tap-
inefficient rewinding may reduce energy efficiency. Proper rewinding techniques can changing transformers, can be used to stabilize voltage levels within permissible limits,
minimise energy losses and maintain motor efficiency close to the original. while high-voltage lines are beneficial in long-distance transmission to minimize losses.
Replacement by Energy-Efficient Motor: Upgrading to energy-efficient motors (e.g., IE3
or IE4 motors) reduces energy consumption, as these motors are designed to operate at Balancing phase currents- It is another effective way to reduce losses. Ensuring an even
higher efficiency levels compared to standard motors. load distribution across all three phases prevents overloading one phase, which could
Periodic Maintenance: Regular maintenance, such as cleaning, lubrication, and lead to higher losses. Phase-balancing devices or automatic controllers can detect and
inspection of electrical connections, ensures that motors run smoothly and efficiently. correct imbalances in real-time, while regular monitoring ensures the system operates
This helps in reducing losses due to friction, wear, and electrical issues. efficiently.

Significant Features of Energy-Efficient Motors Energy conservation in lighting source


Optimised Design: Energy-efficient motors have improved core materials, such as high- Replacing Lamp Sources: Swap traditional incandescent or halogen lamps with energy-
quality steel, and use advanced manufacturing processes that minimise energy losses. efficient options like LEDs or CFLs, which consume up to 80% less energy and have
Higher Efficiency Rating: These motors are typically rated as IE3 or IE4 according to longer lifespans. These lamps generate less heat, reducing the need for air conditioning
international efficiency standards, with better performance than standard motors. and further lowering energy costs. Their increased efficiency also contributes to fewer
Reduced Losses: They are designed to have lower iron, copper, and stray losses, which replacements, leading to cost savings over time. This shift also supports environmental
improves overall efficiency. sustainability by reducing the overall energy demand.
Improved Cooling System: Better cooling reduces overheating and wear, helping the
motor maintain efficiency over time Using Energy-Efficient Luminaires: Install luminaires with optimized light distribution
.Enhanced Insulation and Bearings: High-quality insulation materials and bearings and smart controls (e.g., motion or daylight sensors), which automatically adjust the
minimise wear, increasing the lifespan and reducing maintenance needs. lighting based on occupancy or ambient light. This ensures that lighting is used only
when needed, reducing waste and energy consumption. Additionally, energy-efficient
Advantages of Energy-Efficient Motors luminaires provide better light quality and improved performance, resulting in a more
Lower Energy Costs: Their high efficiency reduces electricity consumption, leading to sustainable and cost-effective lighting system. This also enhances user comfort and
significant cost savings, especially in continuous or high-duty applications.Environmental productivity by providing consistent lighting levels.
Benefits: Reduced energy consumption means lower greenhouse gas emissions,
supporting sustainability and environmental goals. Longer Lifespan: Enhanced design Tariff and Types of Tariff Structures
and materials reduce wear and tear, extending the motor's service life.
Reduced Heat Generation: Energy-efficient motors generate less heat, which benefits An electricity tariff is the price charged by electricity suppliers for the use of electrical
surrounding equipment and further reduces energy needed for cooling . energy. Tariffs are designed to cover the total cost of providing electricity services,
Regulatory Compliance: These motors meet global energy efficiency standards, helping including operational expenses, maintenance, and capital investments
industries comply with regulations and avoid penalties. Different types of tariffs: Special Tariffs: These tariffs are designed for
specific types of consumers or particular applications. They may include discounts,
Applications of Energy-Efficient Motors : Industrial Manufacturing: Used in machines, incentives, or rates tailored to encourage energy conservation, support particular
compressors, conveyors, and pumps to reduce energy costs in industrial processes. industries, or provide financial relief to certain groups.
HVAC Systems: Common in heating, ventilation, and air conditioning applications where Time-of-Day Tariff (TOD): In this tariff structure, electricity prices vary depending on the
motors run continuously, providing substantial energy savings. time of day. Prices are typically lower during off-peak hours (e.g., at night) and higher
Agriculture: Used in irrigation pumps, fans, and dryers where efficiency directly impacts during peak demand periods (e.g., during the day). This encourages consumers to shift
operational costs. their usage to periods when the demand is lower, helping to balance grid load.
Peak-off-Day Tariff: This type of tariff applies higher charges during peak hours and
Limitations of Energy-Efficient Motors : offers lower rates during non-peak times. It's designed to discourage excessive energy
Higher Initial Cost: Energy-efficient motors are more expensive to purchase compared to use during periods of high demand, helping to prevent grid overload and ensure stable
standard motors due to advanced materials and design. energy supply.
Compatibility with Existing Systems: They may require modifications to existing systems Power Factor Tariff: This tariff is based on the power factor of the consumer's electrical
or controls, which can add to initial installation costs. installation. If the power factor (the ratio of real power to apparent power) is low, the
Diminished Returns for Low Duty Cycles: In applications with low operating hours, the consumer is charged a higher tariff. Improving the power factor through the use of
energy savings may not justify the higher upfront cost. capacitors or power factor correction equipment can reduce these additional charges.
Maintenance Expertise: Due to advanced features, maintenance may require specialised Maximum Demand Tariff: This tariff charges consumers based on their peak demand,
knowledge or training, adding to operational complexity. i.e., the maximum amount of electricity they draw at any point in time during a billing
period. It encourages consumers to manage their load effectively to avoid excessive
charges for high demand, typically with a fixed charge based on the highest demand
recorded.
Load Factor Tariff: The load factor is the ratio of average demand to peak demand over a
specific period. Consumers with a high load factor (steady and consistent usage) are
charged a lower tariff, as their consumption pattern is more predictable and less likely to
stress the grid. A low load factor results in higher charges due to inefficient usage
patterns.
Application of tariff system to reduce energy bill: Aggregated Technical and Commercial losses (ATC) refer to the combined losses in the
1.Time-of-Use (TOU): Higher prices during peak hours and lower prices during off-peak electricity supply chain due to both technical factors and commercial factors. These
hours, encouraging users to shift usage to cheaper times.2. Tiered Pricing: Higher rates losses impact the efficiency of energy distribution and contribute to financial losses in
for higher energy usage, incentivising conservation. 3.Demand Charges: Charges based the system.
on peak demand, encouraging users to limit high-energy use. 4.Incentives for 1.Technical Losses: These are losses that occur naturally in the electrical system as a
Efficiency: Discounts or rebates for using energy-efficient appliances result of resistance in conductors and equipment such as transformers and cables. The
5. Critical Peak Pricing (CPP): Higher prices during grid stress periods, motivating main technical loss is the I²R loss, which occurs due to the resistance in the conductors
reduced usage. 6. Smart Metering: Dynamic pricing based on real-time data, allowing and the flow of current.
for more control over consumption and costs. 2.Commercial Losses: These are losses that occur due to non-technical reasons, such as:
a) Theft of electricity: Illegal tapping or bypassing of meters.
Factors governing the selection of cogeneration system – b) Metering inaccuracies: Incorrect readings from meters or faulty meters.
Load Pattern: The cogeneration system should match the facility’s energy demand c) Billing issues: Problems related to inaccurate billing or under-billing.
profile. A steady or constant demand benefits from a system running at optimal capacity, d) Discrepancies in consumption data: Errors in recording or reporting consumption
while variable or peak loads require a flexible system capable of adjusting output. data.
Types of Fuel Available: The choice of fuel—natural gas, biomass, coal, or waste heat—
affects system efficiency, environmental impact, and operational costs. Renewable fuels Fundamental quality requirements :
like biomass may be preferred for sustainability, while natural gas is commonly used for Selectivity: It ensures that only the faulty section is isolated, while the rest of the system
its efficiency and lower emissions. continues to function.
Heat-to-Power Ratio: The system’s heat-to-power ratio should match the facility’s Speed: The relay should disconnect the faulty section as quickly as possible to prevent
needs. High heat-to-power ratios are ideal for facilities needing substantial heat, while damage and improve system stability.
low ratios are better for facilities prioritizing electricity over heat. Sensitivity: Sensitivity refers to the ability to detect faults even with low-level inputs.
Electricity Buyback: Systems should have the option to sell excess electricity back to the More sensitive relays operate with smaller fault currents.
grid through net metering or buyback programs, offering a financial incentive and Reliability: The relay system must operate correctly under fault conditions and avoid
reducing energy costs. unnecessary operation during normal conditions.
Grid-Dependent and Independent Systems: A grid-dependent system operates with the Simplicity: The system should be simple for easy maintenance, as simpler designs are
local electricity grid, allowing for backup power and excess energy export. An generally more reliable.
independent (off-grid) system operates without the grid, offering energy security but Economy: The protective system should balance cost and performance, ensuring
requiring additional storage for stability. adequate protection without excessive expense.
Capital Investment and Operating Costs: The initial installation cost and ongoing
operational costs must be balanced. Systems with lower operational and maintenance
costs are more cost-effective in the long term.

Energy Conservation and Auditing :


An energy audit is an inspection and analysis of energy flows in a building, process, or
system to identify ways to reduce energy consumption without affecting performance. It
involves providing a technical report with recommendations for improving energy
efficiency, a cost-benefit analysis, and an action plan. In commercial and industrial
settings, it is the first step to identify opportunities to reduce energy costs. The main
goal is to lower energy use per unit of output or reduce operating costs, while
establishing a benchmark for better energy management.
Energy conservation refers to reducing energy consumption while achieving the same
outcome. It involves eliminating unnecessary energy waste and using energy more
efficiently. This practice can lead to financial savings, environmental benefits, improved
national and personal security, and enhanced comfort.
Energy Demand : Energy demand refers to the amount of energy required by individuals,
businesses, and industries to perform various activities, such as heating, cooling, lighting,
manufacturing, and transportation. It fluctuates based on factors like population size,
economic growth, seasonal weather patterns, and technological advancements.
Energy Supply: Energy supply refers to the total amount of energy available to meet the
demand, sourced from both renewable and non-renewable resources. It includes energy
produced from fossil fuels (coal, oil, natural gas), nuclear power, and renewable sources
(solar, wind, hydroelectric, etc.), as well as energy imports and storage solutions.

Star Labelling: Definition, Need, and Benefits


Definition: Star labelling is a system that rates the energy efficiency of appliances or
equipment using a star rating, where more stars represent higher energy efficiency. It
helps consumers identify products that use less energy, leading to cost savings and
environmental benefits.

Need: 1. Energy Conservation : Reduces energy consumption and environmental


impact.
2. Consumer Awareness: Guides consumers to choose energy-efficient products.
3. Cost Savings : Helps reduce electricity bills by choosing more efficient appliances.
4. Sustainability: Promotes the use of products that have a smaller environmental
footprint.
5. Regulatory Compliance: Ensures products meet energy efficiency standards.
6. Government and Industry Support : Helps meet national energy-saving targets.

Benefits: 1. Informed Choices: Consumers can easily compare the energy efficiency of
products. 2. Lower Energy Costs : Energy-efficient products reduce operating expenses.
3.Environmental Impact: Reduces greenhouse gas emissions through energy savings.
4. Demand for Efficient Products: Encourages manufacturers to innovate in energy-
efficient design.
5.National Energy Savings: Contributes to significant reductions in national energy
consumption.
6.Improved Brand Image: Manufacturers gain positive public recognition for
sustainability efforts.

Current national scenario regarding energy demand and supply:


India’s energy scenario is heavily reliant on coal, which provides 55% of primary energy.
Although natural gas has seen slight growth, oil’s share has decreased, with India
meeting 70% of its oil demand through imports, mainly from the Gulf. The country’s
extensive coal reserves are estimated to last over 200 years, and India is the world’s
fourth-largest coal producer. Natural gas contributes nearly 9% of energy use, but
demand exceeds supply. Electricity generation capacity is diversified across thermal,
hydro, nuclear, and renewables, with hydro and nuclear each playing modest roles.
Industry is the largest energy consumer at 49%, followed by transport, residential, and
agriculture sectors. The nation’s energy policy focuses on reducing dependency on
imports, enhancing energy efficiency, and expanding renewable energy sources to meet
growing demand sustainably.

You might also like