LNT-ATS Solutions
LNT-ATS Solutions
Making Changeover
Safer, Smarter [
L&T Electrical & Automation, India's leading switchgear company, is dedicated to promoting excellence
in among the fraternity of electrical practitioners. Beginning with a single Switchgear Training Centre
(STC) in Pune in 1986, the initiative has grown to cover 6 state-of the-art facilities at strategic locations
across the country.
The STCs offer a wide range of courses with hands-on training for students, electricians, electrical
engineers, panel builders and consultants. A cutting-edge curriculum, refreshed regularly, helps
enhance on-site electrical safety, system reliability and cost efficiency.
MANUAL AUTOMATIC
SOURCE SOURCE
TRANSFER TRANSFER
MECHANICALLY INTERLOCK
ACBs
MANUAL
MECHANICALLY INTERLOCKED
CHANGEOVER MCCBs
SWITCHES
AUTOMATIC
TRANSFER
CONTROLLER
MECHANICALLY INTERLOCKED
CONTACTORS
MOTORISED CHANGEOVER
SWITCHES
CONTENT
Motorised Changeover 28
• Manual Source Transfer Solution (MSTS): These are generally toggle / knob operated switches or circuit
breakers which need to be manually switched on so that the load circuit gets transferred from one power
source to the other. The manual transfer switches can be used where power outage happens quite rarely and
loss of power does not cause any loss to the appliances or systems used with the electric power supply
• Automatic Source Transfer Solution (ASTS): These automatically transfer the power to the load circuit from
one power source to the other. Thus, these are more convenient to use as one does not have to manually
operate to switch the power source. During normal power interruption, these switching devices will
automatically transfer the load circuits to the emergency power source. Once normal power has been restored,
the process is automatically reversed. Automatic transfer systems are useful where even a small loss of power
can cause a lot of production losses. Automatic transfer systems have therefore found their popularity and
utility in several industrial and commercial applications where a constant source of power is necessary
Automatic Source Transfer Solutions: operate in two different methods i.e. open transition and close transition.
• Break before make switching action. In this, the connection to one power source is opened before the
connection to the other source is made and during this process of power transfer, the flow of electricity
is interrupted. This changeover time can be adjusted by using different time-settings available in any
voltage sensing controller
• This is the most popular method used in many installations for automatic power transfer. This system is
widely used in applications which can accept a small interruption of power from few msec to few
seconds
• It does not require alternate hot source (like a continuous running DG set or an UPS)
• Make before break switching action for uninterrupted power transfer. This facilitate a seamless transfer
of power supply from one source to other by momentarily paralleling both the sources (<100 msec)
during the transfer period. The transfer switch monitors the phase angle difference between the two
sources and when it approaches zero degree, the switch operates
• This system is used primarily in critical installations like Hospitals, Data Centres etc where even
momentary power interruption is not acceptable
• However, this system necessarily requires alternate hot source (like a continuous running DG set or an
UPS) all the time
While the closed transition method is the best to ensure no interruption of power at all, open transition method is more
popularly used due to following reasons:
1. Most power transfer applications accept a momentary interruption in the order of 60 msec to 5 seconds
2. Non-availability of hot sources in most applications
3. Very high prices of close transition auto transfer switches
4. Multiple choices available to the user for open transition power transfer & protection with a combination of
conventional switching, sensing & control devices
5. Ease of maintenance
1
Automatic Source Transfer Solutions in LV system
A typical open transition auto transfer system involves:
1. Two 4 pole, mechanically and/or electrically interlocked power switching devices which can be remotely
operated
2. Voltage and/or frequency sensing accessories or controller
3. Back up protection devices like circuit breakers or fuses in case the power switching devices have only
switching capability
As mentioned earlier, the key elements in any source transfer systems are:
For any ASTS, it is important to monitor the source voltage to decide on which source needs to be in service & a control
system to ensure the correct logic is in place to get the most optimized power. The different options used for this are:
• Use of Under voltage release in circuit breaker to monitor the source voltages & enable a control logic with
auxiliary & trip alarm contacts
• Simple controller with separate voltage sensor, contactors, timers, logic & interlocking control circuit power
• High end digital auto transfer controller with in-built voltage, frequency sensor & a complete logic controller for
all transfer control, interlocking features, multiple setting for voltage & time, digital display, communication etc.
ASTS necessarily needs two separate 4 pole switching devices suitable to offer complete isolation in OFF state. Depending
on the application & installation requirement, they must have on-load or off-load switching duty. In addition to the
switching device, it must have the necessary protections available against any abnormal condition. The switching &
protection functions can be combined into one device e.g. Air circuit breakers & Moulded Case circuit breakers. In case
the switching devices like contactors, changeover switches etc, separate upstream protection devices like circuit breakers
or HRC fuses must be provided.
Interlocking
One of the key and a must safety feature for any open transition ASTS is to ensure that under no circumstances, both the
sources will get switched on together even momentarily. Hence, reliable and failsafe mechanisms must be incorporated
to ensure that the two switching devices are fully interlocked so that only one device can be closed at any point of time.
1. Mechanical interlock - This is the most reliable method of interlocking. This can be done through suitable
interlocking mechanisms like base plate, clutch wire or see-saw toggle interlocks
2. Electrical Interlocking - This is generally used in addition to the mechanical interlocks. It electrically interlocks
the two switching devices like circuit breakers, contactors etc and can be logically programmed for operating
sequence and with time delay etc. This can be done by using:
a. A combination of under voltage release with Auxiliary contacts for circuit breakers
b. Using an external controller & suitably wiring it
c. Using the NO & NC contacts with the coil in case of contactors
2
Automatic Source Transfer Solutions in LV system
3.Self interlocked mechanism – This is generally adopted in the changeover SDs or Auto Transfer switches.
The basic mechanism of SDs will not permit closure of both switches together
Keeping all the above requirements of ASTS, there can be multiple combinations which can be selected. The
selection of transfer system for specific installations can be optimized by keeping following parameters in mind:
1. Feeder Ratings
2. Application need in terms of maximum acceptable change-over time
3. Desired features in terms of sensing & interlocking
4. Specific safety considerations
5. Panel space
6. Life expectancy
7. Cost
1. Two electrically operated ACB for higher ratings with mechanical & electrical interlocks along with a
sophisticated auto transfer controller
2. Two motorized MCCBs, mounted on a mechanical interlock base plate & electrically interlocked
through under voltage releases
3
Automatic Source Transfer Solutions in LV system
a. Simple & Easy to install, same circuit breakers for switching, protection & isolation
b. Voltage sensing & electrical interlocking through UV release
c. Optimum panel space utilized, no extra cut-out in door
d. Minimum change-over time – 100 msec.
e. Most economical MCCB based solution
3. Two motorized MCCBs, mounted on a mechanical interlock base plate & electrically interlocked
through a simple voltage controller
a. Easy to install, same circuit breakers for switching, protection & isolation
b. Voltage sensing & electrical interlocking, time delay setting through voltage controller
c. Optimum panel space utilized, Controller can be mounted inside panel or on the door
d. Full MCCB life available for change-over operations
e. Minimum change-over time – 100 msec.
f. Moderate increase in cost for MCCB based solution
4. Two motorized MCCBs, mounted on a mechanical interlock base plate & electrically interlocked
through sophisticated auto transfer controller
4
Automatic Source Transfer Solutions in LV system
5. One motorized Changeover switch disconnector with either a simple voltage controller or a
sophisticated auto transfer controller, backed up by suitable protective devices such as HRC
fuses/ACBs/MCCBs
AuXC-2000
a. Single motorized Change-over switch for power transfer with self interlocked mechanism - higher
reliability
b. Additional Fuse / Circuit breaker required for protection
c. Sensing, time setting option, multiple change-over logics etc, through either a simple or a
sophisticated Auto Transfer Controller AuXC-2000
d. Least panel space required with fuse back up
e. Higher mechanical life
f. Minimum change-over time - 1 sec.
g. Most economical Automatic Source Transfer Solution (with fuse back up and simple controller)
6. Two mechanically & electrically interlocked power contactors, backed up by suitable protective
devices such as ACBs/MCCBs/SDFs (also providing isolation). These can also have a simple voltage
controller or a sophisticated auto transfer controller for enhanced features
AuXC-2000
Mechanically Interlocked Contactors
5
Automatic Source Transfer Solutions in LV system
L&T today offers a comprehensive and effective solution for all your Power transfer needs, through the various
options discussed above.
In electrical Air Circuit Breakers and motorised MCCBs we offer the advantage of having an inbuilt short circuit
protection. This not only makes the solution compact but also provides the user with high end protection features
offered through our MATRIX releases. These kind of features are usually required in big industrial applications where
these solutions work out to be the best.
The contactor solution is ideal for applications where switching frequency is very high. Such applications may be
residential or commercial applications where switching frequency is high due to frequent power outages. The
contactors having a high mechanical life coupled with an SCPD device offer an economical and reliable solution.
We also offer the solution of changeover switches which have inbuilt interlocking features. Hence, no separate
interlocking accessories are required. Changeover switched having a good withstand capability. With changeover
switched one also has the flexibility of choosing a controller instead of having one single unit. Based on requirement
the user may go for simple voltage controller or advanced controller switches like
AuXC-2000
Thus as seen above, we provide the user a great flexibility through a plethora of changeover solutions. The user can
select the most optimum solution based on specific application requirement.
• For applications where the switching frequency is high, contactor solution is recommended. This is because
contactors have a high switching life. This solution works best in residential and commercial loads where
power outages are very common leading to frequent switching between EB and DG
• For applications above 800A, changeover solution through Air circuit breakers is the most optimum. This
solution works best in big industries as current levels are mostly above 800A
• In applications where the switching frequency is low, Motorized MCCB solution is recommended. This
solution also offers the advantage of having both switching and protection in a single unit. This solution
works best in residential and commercial applications, where both EB and DG supply are provided and
frequency of switching is low
• In applications where there is frequent maintenance on the load side, changeover switches are
recommended as they provide effective isolation. Also since changeover switches have inbuilt interlocking
mechanism, no separate interlocking devices are required. Changeover switches are also recommended in
applications involving changeover between drives and soft starters
6
Comparison of Automatic Source Transfer Solutions
A quick comparison of various Automatic Source Transfer Solution is tabulated below,
Parameters ACB with MCCB with MCCB with MCCB with Change-over Power
AuXC-2000 AuXC-2000 basic controller U/V release SD Contactor
Feeder Ratings 400 - 6300 A 63 - 630 A 63 - 630 A 63 - 630 A 125 - 1000 A 16 - 800 A
Minimum
150 msec 100 msec 100 msec 100 msec 1 second 20 to 50 msec
Changeover time
Through Motor With Electrical With Electrical With Electrical With Electrical Through
Remote Operating Operating Operating Operating Electro-magnet
Operation Mechanism Mechanism Mechanism Mechanism
on top on top on top on top
Life- Mechanical
no. of operating 5,000 to 20,000 8,000 to 15,000 8,000 to 15,000 8,000 to 15,000 10,000 to 20,000 Approx 10 x 106
cycles (no load)
Life-Electrical
no. of operating 2,000 to 10,000 4,000 to 10,000 4,000 to 10,000 2,000 to 5,000 2,000 to 3,000 Approx 10,00000
cycles (no load)
1. Extendable 1. Low panel space 1. Low panel space 1. Low panel space 1. Low panel space 1. Extendable
electrical life 2. In built 2. In built 2. In built protection 2. Fail proof self- life
Unique Feature 2. Robust & protection protection 3. External controller interlock 2. Ease of
maintainable not required mechanism maintenance
product
3. In built Protection
Cost
9 7 5 4 3 4
(Scale 1 to 10)
2 Omega 4 pole 2 DN3-630 TM, 2 DN3-630 TM, 2 DN3-630 TM, 1 C-Line Change- 2 MCX 46
EDO ACB (630A) 50 kA, 4 pole 50 kA, 4 pole 50 kA, 4 pole over SD (630A) Contactors
with MTX1.5G MCCBs (630A) MCCBs (630A) MCCBs (630A) + 1 EOM (700A)
+ 1 AuXC-1000 / + 2 SEOM + 2 SEOM + 2 SEOM + Option 1 : 6 + 1 MIL kit
1000H / 1000L + 1 AuXC-1000 / + 1 Basic + 2 sets of UV HN630 Fuses / + Option 1 : 2
controller 1000H / 1000L controller release & Fuse Bases 630A SDFs with
Typical 630 A +1 Clutch wire controller + 1 MIL kit aux contact Option 2: 2 fuses
Change-over MIL kit + 1 MIL kit + 1 MIL kit 630A SDFs Option 2 : 2
Scheme with fuses DN630 MCCBs
Option 3 : 2 + 1 basic
DN630 MCCBs controller or
+ 1 basic AuXC-1000 /
controller or 1000H / 1000L
AuXC-1000 /
1000H / 1000L
7
AuXC-2000 Controller
There are many electrical services which are required to be powered up always. Interruption of supply to these kinds
of services is not desired. These loads are part of any industry, hospital, school, commercial buildings, shopping malls,
name any place of importance. These loads can be firefighting system, emergency lighting, control stations, CCTV,
emergency pumps, security system etc. L&T’s micro-processor based Automatic Transfer Controller
AuXC-2000along with L&T switchgear is the answer to all auto source transfer requirements.
Changeover Conditions
All the conditions which can help establish whether a power source is or is not suitable are defined by the
user through setting following parameters
Parameter Description
Minimum voltage One or more phases too low
Maximum voltage One or more phases too high
Phase loss Threshold below which the unit intervention is quicker than with a normal decrease.
Asymmetry (unbalance) Phases within the Maximum-Minimum range but too different from each other
Minimum frequency Too low frequency
Maximum frequency Too high frequency
Phase sequence Reverse rotation of phases
8
AuXC-2000 Controller
AC Supply : terminals 13, 14 Measuring accuracy
Rated voltage Us 100 - 240V~ Mains and generator voltage ±0.25% f.s. ±1digit
Insulation type Single between OUT4-5 and OUT 6-7 OUT6 and OUT 7 outputs: terminals 28,29,30
Double toward the remaining groups Contact type 2 x 1 NO + contact common
Rated insulation voltage Ui 250V~ AC1 - 8A 250V~
Rated current DC1 - 8A 30V=
Single Double AC15 -1.5A 250V~
Rated impulse withstand voltage Uimp 4kV Uimp 6kV Max rated voltage 300V~
7 5
Power frequency withstand voltage 1.5kV 3kV Mechanical / electrical endurance 1x10 / 1x10 ops
Line 1 and Line 2 voltage inputs: terminals 1-4 and 5-8 Maximum current at contact common 10A
Maximum rated voltage Ue 100…480V~ L-L (277VAC L-N) Connections
Measuring range 50…576V~ L-L (333V~L-N) Terminal type Plug-in / removable
Frequency range 45-65Hz Cable cross section (min... max) 0.2-2.5 mm² (24... 12 AWG)
Measuring method True RMS Tightening torque 0.56 Nm (5 lbin)
Measuring input impedance > 0.5MW L-N > 1,0MW L-L Housing
Single-phase, two-phase, Version Flushmount
Wiring mode three-phase with or without
neutral or balanced Material Polycarbonate
three-phase system. Degree of protection IP40 on front / IP20 terminals
Ambient operating conditions Weight 680g
Operating temperature +70Oc -30..... *Notice: this product has been designed for environment A. Use of this product in
Vibration resistance -30... +80OC environment B may cause unwanted electromagnetic disturbances in which case the
user may be required to take adequate mitigation measures.
Climatic sequence <80% (IEC/EN 60068-2-78)
Shock resistance 2
Measurement category 3
Overvoltage category III
Maximum pollution degree Z/ABDM (IEC/EN 60068-2-61)
Relative humidity 15g (IEC/EN 60068-2-27)
Storage temperature 0.7g (IEC/EN 60068-2-6)
9
AuXC-2000 Controller
Front buttons functions
Selects the
OFF operating
mode
Selects the
automatic Select the manual
mode. Green operating mode
AUT LED lights
ؿand فkeys - Used to scroll through the display pages or to select the list of options
in a menu. Simultaneously pressing ف+ calls ؿup the Main menu with rotating icons
Front LED
Operational Modes
OFF Mode
In this mode the device is disabled, and does not take any action. All views, both of the measures of the status
LEDs remain active. If the control of the switching devices is impulsive, in OFF mode both open and close
commands are disabled. If instead it is in continuous mode, the behaviour can be selected by P05.10. To access
the programming menu is always necessary to enter in advance the OFF mode. Pressing the OFF-RESET button
resets the retentive alarms, provided that the conditions that generated the alarm has been removed
10
AuXC-2000 Controller
Manual Mode
In this mode, you can manually control the switches on the display by selecting the switch that you
want to control by pressing the MAN key, and pressing the ؿor فbutton to confirm the operation of closing or opening.
While the opening-closing of the breakers is enabled, the page scroll is locked. Pressing MAN several times it is possible to
unlock it and to move through other display pages. If is controlled manually closing a switch while the other is still closed,
the unit will proceed before the opening of the other switch and then to the closure of the commanded one, inserting the
interlock time programmed. When working with the generators, you can manually control the switching on and off of the
generator in a manner similar to that described for switches, but moving on the page start / stop groups.
Line 2 selected
Breaker 1 selected
Selectable function
Function selectable Page scroll locked with MAN
with MAN
Page scroll locked
Auto Mode
The AUT mode is highlighted by the lighting of the corresponding green LED. In automatic mode, the unit manages
automatically the opening and closing of the breakers and the starting and stopping of generator sets.When the priority
line voltage is out of bounds for a time longer than those set (line presence green LED turns off), the unit disconnects the
load from the priority line and connect it to the secondary line, managing both start- up of any generator and interlock time
delay. It is possible to program the unit to open the priority line breaker before or after the secondary line has been made
available, through parameter P05.05 in the M05 Changeover menu. When the priority line comes back within the limits, the
unit will switch back the load on it and decide the possible cooling cycle of the generator. It is possible also to lock the
automatic return to the priority line by means of parameter P05.12. The cycles of automatic operation vary according to the
type of application (utility-utility, utility-generator, generator-generator) and depending on the type of switching devices
used (motorized breakers, motorized changeovers, contactors).
Changeover switch
HRC Fuse
Circuit breaker
Contactor coil
NO contact
NC contact
11
Wiring Diagrams - AuXC-2000
Control of Motorised Control of Motorised
Moulded Case Circuit Breakers Changeover Switch
(Without Undervoltage Relay) Disconnector
K2 K1 K2 K1
K1 K2 K1 K2
K1 K1
K2 K2
K1 K1
K2 K2
OUT 1
OUT 2
OUT 1
OUT 2
OUT1 - OUT7 OUT1 - OUT7
B300 / 250V~ 8A AC1 / 1A 30V= PILOT DUTY B300 / 250V~ 8A AC1 / 1A 30V= PILOT DUTY
OUT 3
OUT 4
OUT 5
OUT 6
OUT 7
OUT 3
OUT 4
OUT 5
OUT 6
OUT 7
INP 1
INP 2
INP 3
INP 4
INP 5
INP 6
INP 1
INP 2
INP 3
INP 4
INP 5
INP 6
COM
COM
OUT 3
OUT 4
OUT 5
OUT 6
OUT 7
OUT 3
OUT 4
OUT 5
OUT 6
OUT 7
INP 1
INP 2
INP 3
INP 4
INP 5
INP 6
INP 1
INP 2
INP 3
INP 4
INP 5
INP 6
COM
COM
Programming Connection Parameter Setting (Description) Programming Connection Parameter Setting (Description)
Terminal code Terminal code
Others - P05.07 Breaker pulse or breaker continuous 15(INP1) P10.01.01 Line 1 breaker closed (Feedback 1)
Inputs
15(INP1) P10.01.01 Line 1 breaker closed (Feedback 1) 16(INP2) P10.02.01 Line 2 breaker closed (Feedback 2)
16(INP2) P10.02.01 Line 2 breaker closed (Feedback 2) 25(OUT4) P11.04.01 Close line 1 contactor/circuit breaker
Inputs
17(INP3) P10.03.01 Line 1 circuit breaker protection (Trip 1) Outputs 27(OUT5) P11.05.01 Open line 1 / line 2
18(INP4) P10.04.01 Line 2 circuit breaker protection (Trip 2) 30(OUT7) P11.07.01 Close line 2 contactor/circuit breaker
25(OUT4) P11.04.01 Open line 1 contactor/circuit breaker Others - P05.07 Changeover continuous
27(OUT5) P11.05.01 Close line 1 contactor/circuit breaker
Outputs
28(OUT6) P11.06.01 Open line 2 contactor/circuit breaker
30(OUT7) P11.07.01 Close line 2 contactor/circuit breaker
12
Wiring Diagrams - AuXC-2000
Control of Contactors Control of Omega ACBs
K2 K1 K2 K1
K1 K2 K1 K2
K1 K1
K2 K2
K1 K1
K2 K2
OUT 1
OUT 2
OUT 1
OUT 2
OUT1 - OUT7 OUT1 - OUT7
B300 / 250V~ 8A AC1 / 1A 30V= PILOT DUTY B300 / 250V~ 8A AC1 / 1A 30V= PILOT DUTY
OUT 3
OUT 4
OUT 5
OUT 6
OUT 7
OUT 3
OUT 4
OUT 5
OUT 6
OUT 7
INP 1
INP 2
INP 3
INP 4
INP 5
INP 6
INP 1
INP 2
INP 3
INP 4
INP 5
INP 6
COM
COM
OUT 3
OUT 4
OUT 5
OUT 6
OUT 7
OUT 3
OUT 4
OUT 5
OUT 6
OUT 7
INP 1
INP 2
INP 3
INP 4
INP 5
INP 6
INP 1
INP 2
INP 3
INP 4
INP 5
INP 6
COM
COM
K1 K2
K2 K1
13
Overall Dimensions - AuXC-2000
Rear Terminal Connections
OUT 1
OUT 2
OUT1 - OUT7
B300 / 250V~ 8A AC1 / 1A 30V= PILOT DUTY
OUT 3
OUT 4
OUT 5
OUT 6
OUT 7
INP 1
INP 2
INP 3
INP 4
INP 5
INP 6
COM
14
Air Circuit Breakers
Frame 1 2 3
0
Rated Uninterrupted Current (In) (A) at 50 C 400-2000 2500$ 400-3200 400-5000 6300#
Version N S H S H N* S H H V H V
Rated Impulse withstand Voltage Uimp 12kV (Main Circuit) & 4kV (Auxiliary Circuit)
Utilization Category B
660/690V AC 36 50 55 50 55 36 50 55 65 75 65 75
400/415V AC
Rated Service S.C.
Breaking Capacity Ics (kA) 500/550V AC 100% Icu
660/690V AC
3.0sec 26 36 44 36 44 26 44 50 65 75 65 75
400/415V AC 105 143 176 143 176 105 143 176 176 220 176 220
Rated S.C. Making
Icm (kA) 500/550V AC 88 121 143 121 143 88 121 154 154 187 154 187
Capacity
660/690V AC 76 105 121 105 121 76 105 121 143 165 143 165
15
Air Circuit Breakers
W D
H : Height
W : Width
D : Depth with flat terminals
16
Matrix Release Family
UW-MTX 4.5
UW-MTX 3.5EC
UW-MTX 1.5G
UW-MTX 4.5
UW-MTX 3.5/3.5EC
Advanced Version
UW-MTX 1.0/1G/1.5G
Basic Version
Accessories
17
Accessories - Air Circuit Breakers
Mechanical Interlock
Mechanical Interlock is used for interlocking breakers as per the desired control scheme. It can interlock up to three
Omega ACBs of Fixed/Draw-out/Mixed version. The breakers can be interlocked in Vertical or Horizontal
configuration.
Two Incomers A B
(2 I/C)
G
Three Incomers A B C
(3 I/C)
G
G
Two Incomers &
One Standby A B C
(2 I/C + 1 S/B)
18
Mounting Dimensions
400-1600A N & 400-2500A S/H Fr.1 4P (100% N)
Fixed Circuit Breaker
300 min
300 min
7
OFF ON
430
A A
6 435 6 Panel
447 A Door
25 112 25
324
45 mm
7
Panel
Door
433
OFF ON
16
Disconnected
35
Test
A A 25.5 A
49.5 100 250 47.5 250
62.4 280
447
421
Use this
mounting hole Use this
mounting hole
(250)
These 2 supports
(280)
are must
All Dimensions in mm
19
Mounting Dimensions
400-3200A S/H Fr.2 4P (100% N)
Fixed Circuit Breaker
300 min
300 min
7
430
A A Panel Door
(Outer surface)
A 142
6 569 6
25 112 25
581
324
45 mm
7
Panel
Door
433
16
Disconnected
35
A TEST
49.5 100 250 A 47.5 25.5 A
581 250
62.4 280
421
(49.5) (100) (250) (47.5)
(62.4)
(280)
These 3 supports
are must
All Dimensions in mm
20
Mounting Dimensions
400-6300A H/V Fr.3 4P (100% N)
Fixed Circuit Breaker
300 min
300 min
7
430
A A
Panel Door
(Outer surface)
6 835 6 A 142
25 112 25
847
334
45 mm
45 mm
7
Panel
Door
433
16
35
35.5 Test
A A A A
49.5 200 100 250 47.5
250
847 62.4 280
431
Use this
Use this
mounting hole
mounting hole
Use this
mounting holes
(280)
(250)
These 4 supports
are must
All Dimensions in mm
21
ACB Ordering Information
UW 1 08 N X D 1 2 9 0 0(5) OMEGA 800A Fr-1 50kA 3P EDO UW-MTX1.5G
(3)
Temperature Rise Monitoring
Not Required 0
Required 1
Current Ratings
Type
400A 04 Manually Operated 1
630A 06 Electrically Operated 2
800A 08
1000A 10 (2)
Selection for control voltage
1250A 12
For Manually Operated 0
1600A 16
240V AC ECD & CR & 240V AC SR 1
2000A 20
240V AC ECD & CR & 24V DC SR 2
2500A (4) 25
3200A 32
Version
4000A 40
Draw-out D
5000A 50
Fixed F
6300A 63
22
MCCB
Dsine MCCB can be used for ASTS ranging from 63A to 630A withfollowing different solutions
1. MCCB with AuXC-2000
2. MCCB with Basic controller (UV relay)
3. MCCB with UV release
Technical Data Sheet
Frame 250A 400A 630A
DN2-250 DN3-400 DN3-630
Type
D N S V D N S D N S V
Release TM/MP (MTX1.0/2.0/3.0) TM/MP (MTX1.0/2.0/3.0) TM/MP (MTX1.0/2.0/3.0)
Current Range (A) 32, 40, 63, 80, 100, 125, 320, 400,
320, 400 500, 630
160, 200, 250 500, 630
Poles 3/4 3/4 3/4
Impulse withstand Voltage Uimp (kV) 8 8 8
Rated Operational Voltage Ue (V) (MAX) 690 690 690
Rated Insulation Voltage Ui (V) 800 800 800
Utilization Category A A A
Standard IEC60947-2, EN60947-2 & IS/IEC60947-2
240 V AC 50 70 100 - 50 70 100 50 70 100 -
415 V AC 36 50 70 100 36 50 70 36 50 70 100
480 V AC 25 36 42 65 25 36 42 25 36 42 65
Icu(kA)
550 V AC 18 25 36 - 15 20 25 15 20 25 -
Rated 600 V AC 16 18 22 - 12 18 22 12 18 22 -
Short 690 V AC 10 15 20 8 15 20 8 10 15
36 50
Circuit
Breaking 240 V AC 100% 100% 100% - 100% 100% 100% 100% 100% 100% -
Capacity 415 V AC 100% 100% 100% 100% 100% 100% 100% 100% 100% 100% 100%
480 V AC 100% 100% 100% 100% 100% 100% 100% 100% 100% 100% 100%
Ics as % Icu
550 V AC 100% 100% 100% - 100% 100% 100% 100% 100% 100% -
600 V AC 100% 100% 100% - 100% 100% 100% 100% 100% 100% -
690 V AC 50% 50% 50% 50% 50% 50% 50% 50% 50% 50% 50%
Mechanical 25000 25000 15000 15000 15000
Life
Electrical @1.0 In 10000 10000* 4000 4000 4000*
Operating Frequency (Hz) 50/60
Total Opening Time <10 msec
Finger-proof Terminals Yes
Suitable for Isolation Yes
IP Class IP40
Pollution Degree III
Load Line Bias No
Ambient Temperature -5ºC to 55ºC
Storage Temperature -35º C to 70ºC
Mounting Position in vertical Plane Vertical and 90º in both directions
3-Pole 105 x 96 x 179 140 x 111.5 x 266 140 x 111.5 x 266
Dimensions (WxDxH) mm
4-Pole 140 x 96 x 179 183.5 x 111.5 x 266 183.5 x 111.5 x 266
Weight (kg) (3/4 Pole) 2.5 / 3.3 5.5 / 7.2 5.8 / 7.4 6 / 7.8 6.3 / 8
A Auxiliary Contact 1 C / O or 2 C / O
Trip Alarm Contact 1C/O
C
Internal Auxiliary & Trip Alarm Contact 1C/O+1C/O
C
Shunt Release 110 / 415 V AC 50 Hz, 24 / 110 / 220 V DC $
E 240 V AC 50 Hz
Under Voltage Release
S Rotary Operating Mechanism (Direct/Extended) P
S Electrical Operating Mechanism P
O Mechanical Interlock Kit P
Spreader Terminals P
R External
Key lock P
I
Neutral CT with Adaptor Kit Available for 3P MCCBs with MTX2.0 & MTX3.0 release only
E Current Metering Module Available for MTX2.0 release for current metering only @
S Display, Communication and Voltage Module Available for MTX3.0 release for Communication & Power metering
$ : ‘NO’ of control contactor to be connected in series for 220V DC, 24V DC Notes : • Any two internal accessories can be mounted at a time
@ : Contains display module & metering module, separate cable • Separate earth fault module required for earth fault protection
required for connection using TM releases
* : at 415V • lcu : Rated ultimate short-circuit breaking capacity
DN2 -1500 @ 690V DN3 -1000 @ 690V Ics : Rated service short-circuit breaking
O
capacity
• Reference Temperature 40ºC & 50 C
• V version MCCBs, to be used with extended Romanly
23
Trip Units & Accessories
Magnetic Releases
Motor Back up Protection Release MTX2.0 with LSING + Current Metering
(DN2, DN3 - Magnetic Protection only) (DN2, DN3)
DN3-M
Accessories
Internal
8
Auxiliary Contact
8
Trip Alarm Contact
8
Aux+Trip Alarm Contact
8
Shunt
8
UV Auxiliary Contact TAC Shunt Release UV Release
External
8
Stored Energy
Electrically Operated
Mechanism
8
External Neutral CT
8
ROMs
8
Key Locks
8
Spreaders
8
MIL Kit
8
GF Module SEEOM External ROM Spreaders
8
MTX Modules NCT
8
Terminal Shrouds
24
Technical Details of SEEOM
Product Architecture
DN3-SEEOM DN2-SEEOM
CONNECTION WIRES
FUSE
PADLOCK LEVER
PADLOCK SLIDER
ON PUSH BUTTON
CHARGING HANDLE
INDICATOR WINDOWS
25
Motorised MCCB Product Features
Padlock Slider ON and TRIP Push Buttons
The Padlock Slider can be set in ON and TRIP push buttons provided on the
AUTO mode for electrical operation fascia assists in manual operation of SEEOM.
or MANUAL mode for onsite manual
operation by human personnel.
As a safety feature the control supply ON TRIP
of SEEOM is automatically cut off in
manual operation. DISCHARGED I ON
Indicator Windows
EMERGENCY TRIP
The Charge/Discharge and ON/OFF window
helps to ascertain the state of SEEOM and
MCCB respectively.
TRIP
ON
Fuse Protection
The SEEOM is provided with a Cartridge type fuse to ensure healthiness of the
control supply. It protects the internal components from damage due to faulty
control supply.
Padlocking
It can also be used for Lock out and Tag out procedure used while undertaking
maintenance of the system.
26
Overall Dimensions
MCCB with Stored Energy Electrically
Operated Mechanism (SE-EOM)
DN2
245.5
35 Door
237.5
18.7
= =
Door
Cut-out
94
N
157
ON TRIP
156
DN3
264
= =
94 Mounting 43.5
256
holes for MCCB = =
Door
45 49
62.1
94
Door
Cut-out
94
224
N ON TRIP
DN2
372
Ø10 Mounting Holes
41.5 141 141
35
10
149
209
239
177
152.5
316
346
266
161 161
Holes for Breaker All dimensions are in mm
Mounting
Mounting Details
27
Motorised Changeover Product Features
4 1
3
7
6
5 2
1. Site Mountable
Motorised kit (EOM) can be mounted over the manual
changeover switch directly at site without any change in
the panel area.
3. Manual Override
Manual operation of motorised changeover switch is also feasible
through the manual override feature.
As a safety feature, the control supply of motorised kit (EOM) is
automatically cut off during the insertion of handle.
28
Motorised Changeover Product Features
5. Auxiliary Contacts
It consists two sets of changeover contacts one for each S-D. It is
prewired and prefitted in motorised changeover switch.
6. Pad Locking
Provision for padlocking in OFF position with three padlocks
of Ø5 to Ø7. Padlocking possible in both auto and manual
mode.
7. Fuse Protection
Inbuilt glass fuse of 5 x 20 size protects the motorised kit (EOM)
during abnormalities. Also, spare fuse holder has been provided
for storage of fuse.
Compact Design
No change in H x W x D of motorised changeover switch and manual changeover switch.
29
Changeover Switches
Frame 2
Reference Standards
30
Frame 3 Frame 4 Frame 5 Frame 6
250 A 315 A 400 A 630 A 630 A 800 A 1000 A 1250 A 1600 A 2000 A
CO3-250 CO3-315 CO4-400 CO4-630 CO5-630 CO5-800 CO5-1000 CO6-1250 CO6-1600 CO6-2000
4 Pole 4 Pole 4 Pole 4 Pole 4 Pole 4 Pole 4 Pole 4 Pole 4 Pole 4 Pole
415 415 415 415 415 415 415 415 415 415
50 / 60 50 / 60 50 / 60 50 / 60 50 / 60 50 / 60 50 / 60 50 / 60 50 / 60 50 / 60
12 12 12 12 12 12 12 12 12 12
3 3 3 3 3 3 3 3 3 3
250 315 400 630 630 800 1000 1250 1600 2000
250 315 400 630 630 800 1000 1250 1600 2000
250 315 400 630 630 800 1000 1250 1600#/1250 2000#/1250
132 160 225 315 315 400 450 710 710 710
2000 2520 3200 5040 5040 6400 8000 10000 10000 10000
2500 3150 4000 6300 6300 8000 10000 12500 12500 12500
16 18 22 26 35 50 50 50 50 50
28 28 35 35 70 85 85 85 85 85
32 36 46 55 73.5 105 105 105 105 105
16000 16000 10000 10000 10000 10000 10000 10000 10000 10000
2000 2000 2000 2000 2000 1000 1000 1000 1000 500
1 1 2 3 3
NA NA NA NA NA
100 100 100 100 100
50 50 50 50
240 V ac 240 V ac 240 V ac 240 V ac
85% - 110% 85% - 110% 85% - 110% 85% - 110%
3 3 3 3
-5 to + 55 -5 to + 55 -5 to + 55 -5 to + 55
IP30 IP30 IP30 IP30
2 2 2 2
0.6 0.7 0.7 0.7
1.4 1.4 1.4 1.4
1.4 1.4 1.4 1.4
1 1.25 1.25 1.25
260 310 380 274
84 84 84 108
94 94 94 118
31
Overall Dimensions
CO2 to CO5 (125-1000A)
Motorised Changeover Switch
G
K (Mounting)
= =
J (Mounting)
=
NOII OFF
L
C
H
D
M
I NO
MANUAL
AUTO
=
R
A
N
P
Mounting Earthing
holes E F F F 10.1
Screws
(4 Nos.) (2 Nos.)
125 22 3 138 121 28 44 210 211 120 190 CO2 CX2 240.3 234.3 30 42 112 M6 M4
160 CO2 CX2 22 3 138 121 28 44 210 211 120 190 CO3 CX3 277.2 271.2 39 54 138 M8 M4
200 26 5 150 121 28 44 210 211 120 190 CO4 CX4 293.7 287.7 42 58 151 M8 M4
250 29 4.5 182 156 32 56 260 239 159 235.4 CO5 CX5 330.9 324.9 45 66.7 182 M8 M5
CO3 CX3
315 35 5 198 164 32 56 260 239 159 235.4
400 40 5 228 202 32.3 70 310 329 200 286
CO4 CX4
630 40 6 228 202 32.3 70 310 329 200 286
630 50 6 264 228 - 80 380 351.6 220 345
800 CO5 CX5 50 8 264 228 - 80 380 351.6 220 345
1000 50 8 264 228 - 80 380 351.6 220 345
CO6-1250/1600/2000
Motorised Changeover Switch
540
389
108
271 118
>PP-EPDM-FR<
>PP-EPDM-FR<
Ck50604
Ck50604
101
101
=
347
MANUAL AUTO
250.4
ON
274
OFF II
ON
=
= =
70
All dimensions are in mm
32
Overall Dimensions
Panel Cutout
Motorised Changeover Switch
Panel Cutout
B
=
AUTO
MANUAL
88
ON I
OFF II ON
=
Type A B
CO2 with CX2 95 60
52.5 CO3 with CX3 117.7 79.5
88 CO4 with CX4 143 100
CO5 with CX5 172.5 110
BEZEL ASSEMBLY
Ø3 x 4
100
Door
100
6 6
Panel Cutout
*Available with standard product.
33
MCX Four Pole Contactor
Conformance to standards
Power contacts
No. of poles 4 4 4 4
Conventional thermal current, lth/Utilisation category AC1 at 550C 16A 25A 32A 40A
Service temperature 0
-20 C to 55 C 0 0
-20 C to 55 C 0 0
-20 C to 55 C 0
-20 C to 550C
0
Link - - - -
Main terminal capacity
Solid conductor (sq mm) 2x4 2x4 2x4 2x4
Coil
Voltage available for 50Hz opn, Uc (V) 110, 220, 240, 415 110, 220, 240, 415 110, 220, 240, 415 110, 220, 240, 415
Pick-up VA 68 68 68 68
VA 11 11 11 11
Hold-on
Watts 4 4 4 4
Pick-up (%Uc) 55 - 120 55 - 120 55 - 120 55 - 120
Limits of operation
Drop-off (%Uc) 30 - 50 30 - 50 30 - 50 30 - 50
Overall dimensions H x W x D in mm 83 x 45 x 83.7 83 x 45 x 83.7 83 x 45 x 83.7 83 x 45 x 83.7
Mounting dimensions H x W in mm (60 - 65 - 70) x 35 (60 - 65 - 70) x 35 (60 - 65 - 70) x 35 (60 - 65 - 70) x 35
34
MCX 11 MCX 12 MCX 13 MCX 22 MCX 23
30 40 50 62.5 82.5
4 4 4 4 4
- - - - -
8 kV 8 kV 8 kV 8 kV 8 kV
1 x 16 1 x 16 1 x 16 1 x 35 1 x 35
2 x 10 2 x 10 2 x 10 - -
- - - - -
110, 220, 240, 415 110, 220, 240, 415 110, 220, 240, 415 240, 415 240, 415
22 22 22 22 22
5 5 5 5.5 5.5
25 - 45 25 - 45 25 - 45 40 - 60 40 - 60
80 x 83.5 x 91.8 80 x 83.5 x 91.8 80 x 83.5 x 91.8 109 x 103 x 120.5 109 x 103 x 120.5
35
MCX Four Pole Contactor
Conformance to standards
Power contacts
No. of poles 4 4 4
Conventional thermal current, lth / Utilisation category AC1 at 550C 160A 200A 255A
0 0
Service temperature 0
-20 C to 55 C 0
-20 C to 55 C -20 C to 550C
0
Coil
Voltage available for 50Hz opn, Uc (V) 110, 240, 415 110, 240, 415 110, 240, 415
VA 36 36 36
Hold-on
Watts 10 10 10
36
MCX 41 MCX 42 MCX 43 MCX 44 MCX 45 MCX 46 MCX 47
4 4 4 4 4 4 4
2 NO + 2 NC 2 NO + 2 NC 2 NO + 2 NC 2 NO + 2 NC 2 NO + 2 NC 2 NO + 2 NC 2 NO + 2 NC
8 kV 8 kV 8 kV 8 kV 8 kV 8 kV 8 kV
2 x (50 mm x 5 mm) 2 x (50 mm x 5 mm) 2 x (50 mm x 5 mm) 2 x (50 mm x 5 mm) 2 x (50 mm x 5 mm) 2 x (50 mm x 5 mm) 2 x (50 mm x 5 mm)
- - - - - - -
- - - - - - -
110, 240, 415 110, 240, 415 110, 240, 415 110, 240, 415 110, 240, 415 110, 240, 415 110, 240, 415
95 95 95 95 25 25 25
35 35 35 35 10 10 10
35 - 65 35 - 65 35 - 65 35 - 65 35 - 65 35 - 65 35 - 65
278 x 248 x 221 278 x 248 x 221 275 x 248 x 221 275 x 248 x 221 275 x 248 x 221 275 x 248 x 221 275 x 248 x 221
170 x 225 170 x 225 170 x 225 170 x 225 170 x 225 170 x 225 170 x 225
37
Four Pole Power Contactors for System Changeover
Why Four Pole contactors are selected as per AC-1 Utilization category
38
Ordering Information
Accessories for MCX
Add-on Blocks Mechanical Interlock Kit
Accessories Spares
MCX MCX MCX MCX MCX Spare Spare
01 - 04 11 - 13 21 - 23 31 - 34 41 - 47 Contactor
Kits Coil *
Mounting Configuration Cat. No. Cat. No. Cat No. Cat. No. Cat. No. MCX 01 - 04 - CS94105
4 NO CS94112 CS94112 CS94112 - - MCX 11 CS94077
3 NO + 1 NC CS94113 CS94113 CS94113 - - MCX 12 CS94078 CS94009
2 NO + 2 NC CS94114 CS94114 CS94114 - - MCX 13 CS90307
1 NO + 3 NC CS94115 CS94115 CS94115 - - MCX 21 CS94330
4 NC CS94116 CS94116 CS94116 - - MCX 22 CS94331 ST91291
Top
2 NO CS94117 CS94117 CS94117 - - MCX 23 CS90078
Add 1 NO + 1 NC CS94118 CS94118 CS94118 - - MCX 31 CS94081
on
2 NC CS94119 CS94119 CS94119 - - MCX 32 CS94082
Block CS94196
1 NO CS94120 CS94120 CS94120 - - MCX 33 CS94083
1 NC CS94121 CS94121 CS94121 - - MCX 34 CS94084
First Left 1 NO + 1 NC CS94220 CS94201 CS94201 CS94205 CS94205 MCX 41 CS94295
First Right 1 NO + 1 NC CS94221 CS94202 CS94202 CS94206 CS94206 MCX 42 CS94296
CS94195
Second Left 1 NO + 1 NC - CS94203 CS94203 CS94207 CS94207 MCX 43 CS94297
Second Right 1 NO + 1 NC - CS94204 CS94204 CS94208 CS94208 MCX 44 CS94298
Mechanical Interlock Kit CS94126 ST50540 CS93095 SS94992 CS94301 MCX 45 CS94299
Surge Suppressors* CS94166 CS94163 CS94163 CS94164 CS94165 MCX 46 CS94300 CS94193
39
Overall Dimensions
Four Pole Contactors - Type MCX
MCX 01-04
67.8
70
65
77
60
83.7
81.5
35 20 35
65
10
45 45
M4 Mounting Contactor B
Holes-10 Nos. 19
55
70
80
Contactor A
196
All Dimensions in mm
40
Overall Dimensions
Four Pole Contactors - Type MCX
MCX 22-23
131 131
CS93095
Mechanical
Interlock
Kit For
MCX 21, 22
149
140
124
MCX 23 MCX 23
108.5
2T1 4T2 6T3 8T4 2T1 4T2 6T3 8T4
25
297
MCX 32-34
Suitable Mounting
197 197 Screws M6 - (6 Nos)
240V 240V
50Hz 50Hz
1 L1 3 L2 5 L3 7 L4 1 L1 3 L2 5 L3 7 L4
A1 A1
177
164
180
MCX 34 MCX 34
A2 A2
2 T1 4 T2 6 T3 8 T4 2 T1 4 T2 6 T3 8 T4
240V 240V
50Hz 50Hz
Ø6.5
425
All Dimensions in mm
41
Overall Dimensions
Four Pole Contactors - Type MCX
MCX 41 / MCX 42 / MCX 43 / MCX 44 / MCX 45 / MCX 46 / MCX 47
Ø9 - Mounting Holes
MCX 41 - 45
Contactors
MCX-M5
Mechanical
Interlock
Kit
A1 A1
275
3 L2 5 L3 3 L2 5 L3
1 L1 7 L4 1 L1 7 L4
241
250
MCX 41 MCX 41
2 T1 4 T2 8 T4 2 T1 8 T4
6 T3 4 T2 6 T3
A2 A2
9 90
49.75 49.75
256
62.5 62.5 62.5 99.5
280 280
595
1 L1 3 L2 5 L3
7 L4
1 L1 3 L2 5 L3
7 L4
MCX 41
2 T1
MCX 41
4 T2
A2 6 T3 8 T4
2 T1
4 T2
A2 6 T3 8 T4
All Dimensions in mm
42
Notes:
Electrical Standard Products (ESP) Offices:
Product improvement is a continuous process. For the latest information and special applications, please contact any of our offices listed here.
Registered Office: L&T House, N. M. Marg, Ballard Estate, Mumbai 400 001, INDIA CIN: L99999MH1946PLC004768
SP 50717 R1 130417