6719 UnderstandingDynamic DF 20230911 Web
6719 UnderstandingDynamic DF 20230911 Web
Distance Characteristic
Donald D. Fentie
Schweitzer Engineering Laboratories, Inc.
© 2016 IEEE. Personal use of this material is permitted. Permission from IEEE must be obtained
for all other uses, in any current or future media, including reprinting/republishing this material
for advertising or promotional purposes, creating new collective works, for resale or
redistribution to servers or lists, or reuse of any copyrighted component of this work in other
works.
This paper was presented at the 69th Annual Conference for Protective Relay Engineers and can
be accessed at: https://doi.org/10.1109/CPRE.2016.7914922.
For the complete history of this paper, refer to the next page.
Revised edition released September 2023
1
I. INTRODUCTION m ∙ Zr Operating Restraining
Mho distance elements continue to be popular for
transmission protection worldwide. In the past, as relay R
X 3 dZ1
δ1
3 δ = 90°
dZ2 Zr
Zr δ2 2
dZ
Z1 dZ3
2 δ3
(b) Z2
Z 1 Z3
R
–2 –1 1 2
R
–2 –1 1 2
dZ ⋅ Z *= (
dZ ⋅ Z ⋅ cos (θ dZ − θ Z ) + j ⋅ sin (θ dZ − θ Z ) ) (7) Equations (16) and (17) show the circle-mapping technique
in terms of voltage:
Taking the real part of (7) yields the cosine comparator (8),
the result of which is positive if the impedance plots inside the Re ( Z r ⋅ I − V ) ⋅ V * =0 (16)
mho circle.
Re V ⋅ V *
Re dZ ⋅ Z * = dZ ⋅ Z ⋅ cos (θ dZ − θ Z ) > 0 (8) Zr = (17)
Re 1∠θ Zr ⋅ I ⋅ V *
Substituting (1) into (8) gives (9):
Renaming Zr as Zmapped in (15) yields (18):
Re ( Z r − Z ) ⋅ Z * > 0 (9)
Re Z ⋅ Z *
Equation (9) is often expressed in terms of voltage, as shown Z mapped = (18)
Re 1∠θ Zr ⋅ Z *
in (10), by multiplying each term by current, where V is the
measured voltage at the relay and I is the fault loop current, as Zmapped is the magnitude of the point of intersection between
described in Section III, Subsection A [1]. the dotted circle and the bolted fault locus, as shown in Fig. 5.
This impedance is analogous to the per unit quantity r that is
Re ( Z r ⋅ I − V ) ⋅ V * > 0 (10)
mapped on the M-line [1]. In Fig. 5(a), Zmapped is positive and
The mho element in Fig. 4 is represented in terms of voltage less than the reach point Zr, so the element operates. In Fig. 5(b),
on the complex plane. Zmapped exceeds the reach point Zr, so the element restrains.
I∙X δ X
Impedance
3
50 mapped to
dV line angle
Zr
40
I ∙ Zr 2 dZ
30
(a)
V Zmapped 1
20
Z
10
R
–2 –1 1 2
I∙R
–20 –10 10 20 30 Zmapped Zr
0 1 2 3
Fig. 4 Mho element in terms of voltage.
(
Re Z r ∠θ Zr − Z ⋅ Z * =
0 ) (12)
Re Z r ∠θ Zr ⋅ Z * − Re Z ⋅ Z * =
0 (13) R
–2 –1 1 2
Re Z ⋅ Z * Zr Zmapped
Zr = (14)
Re 1∠θ Zr ⋅ Z * 0 1 2 3 4
Zr can also be mapped as a negative number in (14) by Fig. 5 Mapping a measured impedance to the line angle and corresponding
removing the absolute value sign, as shown in (15). number line for (a) A fault within reach point, (b) An external fault.
4
Equation (18) benefits us by reducing the number of Extensive research of polarization has resulted in the
comparator calculations to just one per relay-processing examination of several solutions [1] [2] [6] [7]. Cross-
interval, regardless of the number of mho zones. The output of polarization uses the unfaulted phases during a fault. For
the equation Zmapped is a scalar quantity that we can compare example, a BC mho element might use a shifted voltage vector
with the scalar mho reach points of all other zones. This method of VA for polarization instead of VBC. Also, an AG mho element
is more computationally efficient than performing (9) for each might use a shifted voltage vector of VBC for polarization
mho element. instead of VA. Positive-sequence voltage is another polarization
type that produces excellent results by using all three phases.
III. POLARIZATION The polarization techniques previously discussed are
unreliable for three-phase faults close to the relay because the
A. Polarization Choices
voltage on each phase is zero. One solution to this problem is
The term Zr ∙ I − V in (16) is defined as the operating quantity to use a memory filter in the polarization algorithm so that the
dV that can change by 180 degrees, depending on fault location, voltage decays slowly over many cycles [2]. This technique
as shown in Fig. 6. We then compare the operating quantity dV provides a way of dealing with a bolted three-phase fault at the
to the polarizing quantity, which is defined as the measured relay location for a period of time, depending on the memory
voltage V in (16). decay.
The polarizing quantities for self-polarizing and positive-
I∙X
sequence memory polarizing are shown in Table 1 for the six
50 fault loops.
V
45 TABLE 1
OPERATING AND POLARIZING QUANTITIES
40
Self- Positive-Sequence
35 dV Relay
Polarizing Memory Polarizing Loop Current
Element
30 Quantity Quantity
(a) I ∙ Zr
25 AG VA VA1mem IA + k0 ∙ IRES
20 BG VB VB1mem IB + k0 ∙ IRES
15 CG VC VC1mem IC + k0 ∙ IRES
10 AB VAB VAB1mem IA − IB
5 BC VBC VBC1mem IB − IC
I∙R CA VCA VCA1mem IC − IA
–15 –10 –5 5 10 15 20
We can replace the self-polarizing voltage V in (17) with the
positive-sequence memory voltage V1mem, as shown in (19). The
I∙X numerator of (19) still contains the term V that was derived
60 from the operate quantity dV.
dV
50 I ∙ Zr Re V ⋅ V1mem*
Zr = (19)
40 Re 1∠θ Zr ⋅ I ⋅ V1mem*
(b) V
30 During a fault, the self-polarizing voltage at the relay
20 decreases on the faulted phases while the memory voltage
slowly decays from prefault levels. This causes the memory-
10 polarized mho circle to become larger than the self-polarized
I∙R circle because the angle comparison is now between Vp (V1mem)
–30 –20 –10 10 20 30 40 and dV, as shown in Fig. 7(b). The impedance equivalent of Vp
is the polarizing impedance Zp, as shown in Fig. 7(a). Even
Fig. 6 Operating quantity dV direction is determined by fault location for an
(a) External fault, (b) Internal fault.
without memory, positive-sequence voltage polarization causes
the mho to expand. An exception is in the case of a close-in,
The angle of the polarizing term should remain relatively three-phase fault because the voltage is zero on all three phase.
constant during a fault. We call the mho element in Section II The memory voltage decays over time, causing the dynamic
the self-polarized element because the relay uses the voltage of circle to shrink. The steady-state resting point of the dynamic
the faulted phase(s) for polarization. This polarization circle depends upon several system parameters and the fault
jeopardizes the security and dependability of the element during type, as discussed in Section III, Subsection B. One benefit of
close-in faults because the voltage is too small to be accurately the dynamic expansion is the initial increase in resistive
measured. Modern relays use other forms of polarization that coverage provided by this expansion, without changing the
perform reliably for all fault types and locations. reach point.
5
X X
3 3
Zr Zr
2 dZ 2 dZ
Zp
1 Z 1 Z
Zp
R R
–2 –1 1 2 3 –1 1 2
ZS1
Based on [3], the expansion is derived mathematically as a The expansion properties of the dynamic mho circle during
vector that begins at the origin and ends at the dynamic mho phase-to-phase faults are simple, for two reasons. First, the
circle. This vector is represented as b for the steady-state mho derivation does not involve the zero-sequence network and so
characteristic, and bmem for the full expansion. For a three-phase does not contain zero-sequence impedances. Second, negative-
fault, we have (20). sequence impedances are often assumed to equal corresponding
b=0 positive-sequence impedances.
(20)
bmem = − Z S1
X 3
Zr
3
2 dZ
Zr
1 Z
1
Zp
R
–2 –1 1 2
R
–2 –1 1 2 0.5 ∙ ZS1
b(mem) –1
3) Phase-to-Phase-to-Ground Fault 60
As with other faults we have examined up to this point, the
dynamic mho expansion during a phase-to-phase-to-ground VC1mem 40
Z S0 + m ⋅ Z L0
b = − Z S1
Z S1 + m ⋅ Z L1 + 2 ⋅ Z S0 + 2 ⋅ m ⋅ Z L0 (22) VB1mem –40
bmem = − Z S1 –60
–40 –20 20 40 60
Zr
VB 2 dZ
–40
Zp
R
–2 0.8 ∙ ZS1 1 2
–1
60 X
VC
40 4
VA
3
–60 –40 –20 20 40
Zr
IA (a)
–40 2
VB Zp ZL1 + ZR1
–60
X
VA1mem
3
–40 –20 20 40 60
Zr
–40 2
VB1mem (b)
–60 Zp 0.8 ∙ (ZL1 + ZR1)
P1,2 =
ES ⋅ ER sin δ S , R( ) (24)
Im(V)
X total 40
where
δ S , R arg ( ES ) − arg ( ER )
= (25)
(c)
Xtotal is the total reactance between sources ES and ER. Power 20
VA VA1mem
flows from the source with the leading voltage angle, and this
creates a positive-sequence voltage drop across the source
impedance; therefore, the positive-sequence memory voltage at
the relay is unequal to the source voltage at fault inception. The Re(V)
Re(V)
20 40 60
11
IV. TESTING
X
A. Justification for Testing
3 Dynamic mho expansion varies based on manufacturer
Zr
dZ implementation of the elements. In one implementation, the
time constant of the memory polarization is four cycles [2].
2 We advise testing the dynamic mho when assessing the
θ performance of the element on lines with series capacitors. The
Z dynamic mho expansion is necessary to detect forward faults
1
that are directly in front of a line-end capacitor with bus-side
Zp potential transformers (PTs) (see Section V, Subsection B).
R
Often, this type of testing employs a real-time simulator, where
–2 2 the relay is included in the playback loop.
In practice, the static or self-polarized mho is tested
extensively at steady state; for most applications, the reach
–1
point is the most important aspect of the element. We
recommend testing mho elements by using values from a
Fig. 24 Positive load flow reducing resistive fault coverage by shifting the constant-source impedance model.
dynamic mho to the left.
B. Testing Considerations
Vector VA1mem, and therefore Zp, increasingly lags the
Section III shows that the dynamic circle does not shrink
measured fault voltage VA for forward power flow as the
back to the self-mho circle except in the case of a three-phase
prefault current increases. This causes Zp to shift the dynamic
fault. This may be confusing to a relay tester using a common
mho circle to the left for forward load flow; reverse load flow
test procedure because the mho element appears to operate as if
has the opposite effect. Four impedance graphs in Fig. 25
the dynamic circle did not exist.
illustrate this effect for different levels of load flow.
The dynamic mho element does not usually interfere with
testing because of the test voltages that are typically used.
X X
Table 4 lists several test voltages and currents used to test a
3 3
Zr Zr
phase-to-ground mho circle by simulating an AG fault.
2 dZ 2 dZ TABLE 4
(a) (b) EXAMPLE TEST QUANTITIES
Z Z
1 1
Zp Zp
R R Test
Test 1 Test 2 Test 3 Test 4
–2 1 2 –2 1 2 Quantity
VA V (sec) 27∠0° 27∠0° 27∠20° 27∠−20°
VB V (sec) 67∠−120° 67∠−120° 67∠−120° 67∠−120°
X X VC V (sec) 67∠120° 67∠120° 67∠120° 67∠120°
3 3
Zr Zr
V1 V (sec) 53.67∠0° 53.67∠0° 53.21∠3.3° 53.21∠−3.3°
2 dZ 2 dZ IA A (sec) 3∠−20° 1.6∠−60° 2.64∠−20° 3.19∠−20°
(c) (d)
Z Z
1 1 Note: IB = IC = 0 A.
Zp Zp
R R
The voltage angles in Tests 1 and 2 for VA, VB, and VC are,
–2 1 2 –2 1 2
respectively, 0, −120, and 120 degrees. This means that voltage
VA is in phase with V1mem; therefore, the impedance vector Z is
Fig. 25 Dynamic mho during fault conditions with varying sending source in phase with Zp.
angle: (a) −40°, (b) −20°, (c) 0°, (d) 20°. For an AG fault,
Distance-element overreach for high-resistance faults during VA
Z= (28)
heavy forward/reverse load conditions is a concern when I A + k0 ⋅ I R
applying distance elements. The adaptability of the positive-
sequence memory-polarized distance element minimizes V1mem
Zp = (29)
overreaching concerns [11]. I A + k0 ⋅ I R
12
X –2
Zr
4 X
dZ
(a) 6
2 Zr
Zp
4
Z R
dZ
–6 –4 4 (b)
2
–2
Z R
–6 –4 –2 2 4
Zp
X
6 dZ
Zr Fig. 27 Uncommon test values for an AG fault; dynamic mho shifts
Z
4 (a) Test 3: Inside the static mho, (b) Test 4: Outside the static mho.
Zp
This same element behavior also applies to the phase
2 elements. From Table 2, we obtain the following:
(b)
R
VBC1mem =− j ⋅ VA1mem ⋅ 3
–6 –4 –2 2 4 6 VBC is calculated as
–2 VBC =VB − VC =− j ⋅ VA1 ⋅ 3
Both vectors are in phase using common test voltages;
–4
therefore, Vectors Z and Zp are also in phase, and the dynamic
mho circle does not affect testing. For a BC fault, we obtain the
–6 following:
VBC
Fig. 26 Common test values for an AG fault; the dynamic mho does not Z= (30)
interfere with testing when the angle of VA and V1mem are equal: (a) Test 1,
I B − IC
(b) Test 2.
VBC1mem
Test 3, shown in Fig. 27(a), shows an example of where
Zp = (31)
I B − IC
V1mem lags VA and the dynamic mho circle moves inside the
static mho. In this scenario, the element does not operate until C. Verification
the impedance enters the dynamic mho circle. Test 4, shown in Often, we can draw the dynamic and static mho elements on
Fig. 27(b), shows the opposite scenario, where V1mem leads VA, the same graph, but the dynamic mho element determines relay
causing a test impedance from the first quadrant to enter the operation. By performing a steady-state test, we can prove the
dynamic mho circle first and operate before reaching the static existence of the dynamic mho circle. We use the values shown
mho. in Table 5 to test a relay with positive-sequence memory
voltage. Settings are shown in Table 6.
13
2 | IA | = 4.93 A ES ER
B. Expansion and Security Relay R2 initially restrains for the three-phase reverse fault
Mho elements are inherently directional, as shown in Fig. 8 but may eventually operate as the dynamic mho shrinks back to
and Fig. 22. Forward faults expand the dynamic element back the self-polarized mho. A properly set directional element that
towards the source, and reverse faults shrink the element in the supervises the mho element prevents relay operation even if the
first quadrant. impedance plots inside the dynamic mho circle. The
As with the use of other elements, there are some instances progression of the dynamic characteristic is shown in
where using the mho element poses a security concern. An Fig. 32(a). If the fault is not three-phase, the dynamic mho will
example would be for ground-distance element overreach not completely shrink to the self-polarized mho, as described in
during phase-to-phase-to-ground faults [1]. We can largely Section III. In most cases, the reach point Zr exceeds the series
mitigate these security concerns by supervising the mho capacitor reactance Xc; however, if the opposite is true, then R2
characteristic with directional and fault-identification logic [4]. will operate during mho expansion and restrain during steady
In such a special case as a series capacitor application, we state, as shown in Fig. 32(b).
strongly recommend transient simulations to ensure proper
dynamic operation. The capacitive impedance in these X
scenarios can place more emphasis on dynamic expansion for
proper relay operation. For example, in Fig. 30 we apply a 4
dZ 80%
X
(b) 60%
3 Z
40%
Zr
20%
2 Zr
0%
0.2
1 dZ
R
–0.4 –0.2 0.2 0.4
R
–2 –1 1 2 Fig. 32 Impedance diagram for Relay R2 in response to a reverse three-
Z phase fault on the opposite side of the series capacitor: (a) Case I: | Zr | > | Xc |,
Zp (b) Case II: | Zr | < | Xc |.
VII. REFERENCES
[1] E. O. Schweitzer, III and J. Roberts, “Distance Relay Element Design,”
Proceedings of the 46th Annual Conference for Protective Relay
Engineers, College Station, TX, April 1993.
[2] E. O. Schweitzer, III, “New Developments in Distance Relay Polarization
and Fault Type Selection,” presented at the 16th Annual Western
Protective Relay Conference, Spokane, WA, October 1989.
[3] F. Calero, “Distance Elements: Linking Theory With Testing,” 62nd
Annual Conference for Protective Relay Engineers, Austin, TX,
April 2009, pp. 333–352.
[4] D. Costello, “Determining the Faulted Phase,” 63rd Annual Conference
for Protective Relay Engineers, College Station, TX, April 2010,
pp. 1–20.
[5] H. Altuve Ferrer and E. O. Schweitzer, III, “Modern Solutions for
Protection, Control, and Monitoring of Electric Power Systems,”
Schweitzer Engineering Laboratories, Inc., Pullman, WA, 2010.
[6] S. Zocholl, “Three-Phase Circuit Analysis and the Mysterious k0 Factor,”
22nd Annual Western Protective Relay Conference, Spokane, WA,
October 1995.
[7] L. M. Wedepohl, “Polarized Mho Distance Relay,” Proceedings of IEE,
Volume 112, No. 3, March 1965.
[8] H. Altuve, J. Mooney, G. Alexander, “Advances in Series-Compensated
Line Protection,” 35th Annual Western Protective Relay Conference,
Spokane, WA, October 2008.
[9] J. Zydanowicz, “Application of the Idea of Steady-State Impedance and
Admittance to the Construction of Diagrams Intended for the Analysis of
the Operation of Distance and Directional Relays and Protective
Schemes,” Conférence Internationale des Grands Reseaux Électriques à
Haute Tension, Paris, France, June 1960.
[10] L. P. Cavero, “Analysis of Complex Distance-Relay Characteristics
Taking Load Into Account,” IEE Conf. Publ. 185, 1980, pp. 192–194. Previously presented at the 2016 Texas A&M
[11] J. Roberts, A. Guzman, and E. O. Schweitzer III, “Z=V/I Does Not Make Conference for Protective Relay Engineers.
a Distance Relay,” presented at the 20th Annual Western Protective Relay © 2016, 2017, 2023 IEEE – All rights reserved.
Conference, Spokane, WA, October 1993. 20230911 • TP6719-01