Revision Date: 9 Feb 2023, REV 2

Setting interface—ONLY FOR REFERENCE ON INTERFACE


Name Plate of main motor and Back Drive motor

Parameters setting on VFD(centrifuge 1/2/3, dryer, cutting pump)


Parameter setting for VFD, VFD Model # SB70G11/SB70G15/SB70G30/SB70G37/SB70G55
No. Code Parameter Factory setting value Description

1 F0-01 Run the main given channel 2 Adjust by UP/DOWN

Run command channel


2 F0-02 1 External terminal input run command
selection

3 F0-06 Maximum frequency 60 According to the motor nameplate

4 F0-07 Top frequency 60 According to the motor nameplate

5 F1-00 Acceleration time 500 Time from 0Hz to the highest frequency

6 F1-01 Deceleration time 1000 Time from the highest frequency to 0Hz

7 F2-13 Maximum output voltage 480 according to the motor nameplate


X1 digital input terminal
8 F4-00 19 Speed adjustment
function
X2 digital input terminal
9 F4-01 20 Deceleration adjustment
function

10 F4-08 Running mode 0 Start&stop mode of frequency converter

11 F5-02 T1 relay output 5 fault output

12 F5-03 T2 relay output 3 Frequency level signal detection 1

13 F5-06 Frequency level detection 1 25

according to the motor


14 FA-01 Motor rated power according to the motor nameplate
nameplate
according to the motor
15 FA-03 Motor rated current according to the motor nameplate
nameplate

16 FA-04 Motor rated frequency 60 according to the motor nameplate

17 FA-06 Motor rated voltage 480 according to the motor nameplate

18 F0-10 Parameter write protection 2 Full protection

Alarm value setting for centrifuge 1/2/3


Proposed wording for changing the
No. Parameter Description (Explanation) Alarm value
Parameter name

1 Main motor current Bowl motor current 65A Bowl Motor Current

Bowl motor load torque 1(percentage of


2 Main motor torque Bowl motor load torque percentage
percentage torque)
3 Back current Back current (back drive motor) 30A Back drive Motor Current

Minimum Differential speed with Bowl


4 Lower differential limit Minimum differential speed 15rpm
Speed & Conveyor Speed
Maximum Differential speed with Bowl
5 Upper differential limit Maximum differential speed 45rpm
Speed & Conveyor Speed

6 Sprial bearing lubrication Conveyor bearing lubrication 800h Greasing at the Conveyor Bearing

7 Differential lubrication Differential gear box lubrication 800h Gearbox Greasing

Hourly Maintenance as per Manual


8 Level 1 maintenance Level 1 maintenance 1000h
instruction
Hourly Maintenance as per Manual
9 Level 2 maintenance Level 2 maintenance 2000h
instruction

Alarm value/Shutdown value setting for centrifuge 1/2/3


Proposed wording for changing the
No. Parameter Description (Explanation) Alarm value/Shutdown value
Parameter name
1 Small end temperature Conical end temperature 85℃/95℃ Solid End Temperature
2 Big end temperature Cylindrical end temperature 85℃/95℃ Liquid End Temperature
3 Equipment vibration Equipment vibration 11mm/s/15mm/s Excessive Vibration
4 Back motor torque Back drive motor torque 0.5 or (50%)/0.6 or (60%) Back drive Motor

Parameters setting on centrifuge


Proposed wording for changing the
No. Parameter Description (Explanation) Set value Parameter name

Bowl Motor and back drive motor


1 Differential ration Differential Speed Ratio 48
speed differential
When the back drive motor torque is
Back motor torque is high,and the feed
higher than the set alarm value, the feed
2 pump temporarily reduces the 0.3 or (30%) Load Operation of Back Drive Motor
frequency multiple pump operating frequency will be reduced
to (0.3) times of set operating frequency

After the torque value of the back drive


Back motor torque is high,and the motor exceeds the set alarm value for 3
3 permanent frequency reduction consecutive times, the pump will 0.9 or (90%) Load Operation of Back Drive Motor
multiple of feed pump automatically decelerate to (0.9) times of
the original set frequency

4 Main motor speed(50Hz) Main motor speed(50Hz) 2960rpm Bowl Motor Speed

5 Back motor speed(50Hz) Back motor speed(50Hz) 1480rpm Back Drive Motor Speed

6 Design valve of drum speed Set maximum running bowl speed 3000rpm Bowl Speed

7 Automatic delay downtime Automatic delay downtime 120s Auto Delay Downtime duration

Shutdown time in case of high auxiliary Shutdown time in case of high back drive
8 torque delay
120s ESD of back drive motor
motor torque delay

Primary Current input to Secondary


Transformation ratio of current
9 transformer
Current transformer ratio 400 current output at full load.

Delay shutdown of cleaning auxiliary Delay shutdown of the back drive motor on Shut down duration of cleaning mode
10 fan
600s
cleaning mode on
Back drive motor fan shutdown time
11 Delay shutdown of auxiliary fan Delay shutdown of the back drive motor 600s
duration

12 Drum speed limit Bowl speed limit 3000rpm Maximum Bowl Speed
Minimum frequency of feed pump in Set minimum frequency of feed pump in
13 automatic mode
3Hz Auto set up mode of Pump Frequency
automatic mode