0% found this document useful (0 votes)
13 views1 page

Ammonia Export Early Work For Berth No. 17 Pars Petrochemical Port 2nd Phase - Assalouyeh

Uploaded by

mo.hadidi
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
13 views1 page

Ammonia Export Early Work For Berth No. 17 Pars Petrochemical Port 2nd Phase - Assalouyeh

Uploaded by

mo.hadidi
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

Ammonia Export Early work for Berth No.

17 Pars Petrochemical Port 2nd Phase – Assalouyeh

F&G IO List

EWP2-SPI-DD-17-IN-LIS-0003-02
Sub System Function

Software/ Hardwire
Signal Type

IS Barrier

IO Type

Command
Indicator
Rev.

Control
Status
Alarm
ID Tag No. Description Refference Document Remark

From

To
1 00 90‐TGD‐17‐001 Toxic Gas Detector (Ammonia) F FGS 4‐20mA Hardwire ✓ AIR ✓ ✓ EWP2‐TIC‐DD‐17‐SF‐LAY‐0002 ‐
2 00 90‐TGD‐17‐002 Toxic Gas Detector (Ammonia) F FGS 4‐20mA Hardwire ✓ AIR ✓ ✓ EWP2‐TIC‐DD‐17‐SF‐LAY‐0002 ‐
3 00 90‐TGD‐17‐003 Toxic Gas Detector (Ammonia) F FGS 4‐20mA Hardwire ✓ AIR ✓ ✓ EWP2‐TIC‐DD‐17‐SF‐LAY‐0002 ‐
4 00 90‐TGD‐17‐004 Toxic Gas Detector (Ammonia) F FGS 4‐20mA Hardwire ✓ AIR ✓ ✓ EWP2‐SPI‐DD‐17‐SF‐LAY‐0002 ‐
5 00 90‐TGD‐17‐005 Toxic Gas Detector (Ammonia) F FGS 4‐20mA Hardwire ✓ AIR ✓ ✓ EWP2‐SPI‐DD‐17‐SF‐LAY‐0002 ‐
6 00 90‐TGD‐17‐006 Toxic Gas Detector (Ammonia) F FGS 4‐20mA Hardwire ✓ AIR ✓ ✓ EWP2‐SPI‐DD‐17‐SF‐LAY‐0002 ‐
7 00 90‐TGD‐17‐007 Toxic Gas Detector (Ammonia) F FGS 4‐20mA Hardwire ✓ AIR ✓ ✓ EWP2‐SPI‐DD‐17‐SF‐LAY‐0002 ‐
8 00 90‐FD‐17‐001 UV/IR Flame Detector F FGS 4‐20mA Hardwire ✓ AIR ✓ ✓ EWP2‐SPI‐DD‐17‐SF‐LAY‐0002 ‐
9 00 90‐FD‐17‐002 UV/IR Flame Detector F FGS 4‐20mA Hardwire ✓ AIR ✓ ✓ EWP2‐SPI‐DD‐17‐SF‐LAY‐0002 ‐
10 00 90‐FD‐17‐003 UV/IR Flame Detector F FGS 4‐20mA Hardwire ✓ AIR ✓ ✓ EWP2‐SPI‐DD‐17‐SF‐LAY‐0002 ‐
11 00 90‐FD‐17‐004 UV/IR Flame Detector F FGS 4‐20mA Hardwire ✓ AIR ✓ ✓ EWP2‐SPI‐DD‐17‐SF‐LAY‐0002 ‐
12 00 90‐FD‐17‐005 UV/IR Flame Detector F FGS 4‐20mA Hardwire ✓ AIR ✓ ✓ EWP2‐SPI‐DD‐17‐SF‐LAY‐0002 ‐
13 00 90‐FD‐17‐006 UV/IR Flame Detector F FGS 4‐20mA Hardwire ✓ AIR ✓ ✓ EWP2‐SPI‐DD‐17‐SF‐LAY‐0002 ‐
14 00 90‐MAC‐17‐001 Manual Alarm Call Point F FGS 24Vdc Hardwire DIR ✓ ✓ EWP2‐SPI‐DD‐17‐SF‐LAY‐0002 ‐
15 00 90‐MAC‐17‐002 Manual Alarm Call Point F FGS 24Vdc Hardwire DIR ✓ ✓ EWP2‐SPI‐DD‐17‐SF‐LAY‐0002 ‐
16 00 90‐MAC‐17‐003 Manual Alarm Call Point F FGS 24Vdc Hardwire DIR ✓ ✓ EWP2‐SPI‐DD‐17‐SF‐LAY‐0002 ‐
17 00 90‐MAC‐17‐004 Manual Alarm Call Point F FGS 24Vdc Hardwire DIR ✓ ✓ EWP2‐SPI‐DD‐17‐SF‐LAY‐0002 ‐
18 00 90‐HR‐17‐001 Fire Audible Alarm Horn FGS F 24Vdc Hardwire DOR ✓ ✓ EWP2‐SPI‐DD‐17‐SF‐LAY‐0002 ‐
19 00 90‐HR‐17‐002 Fire Audible Alarm Horn FGS F 24Vdc Hardwire DOR ✓ ✓ EWP2‐SPI‐DD‐17‐SF‐LAY‐0002 ‐
20 00 90‐RFB‐17‐001 Red Flash Light Beacon FGS F 24Vdc Hardwire DOR ✓ ✓ EWP2‐SPI‐DD‐17‐SF‐LAY‐0002 ‐
21 00 90‐RFB‐17‐002 Red Flash Light Beacon FGS F 24Vdc Hardwire DOR ✓ ✓ EWP2‐SPI‐DD‐17‐SF‐LAY‐0002 ‐
22 00 90‐BFB‐17‐001 BLue Flash Light Beacon FGS F 24Vdc Hardwire DOR ✓ ✓ EWP2‐SPI‐DD‐17‐SF‐LAY‐0002 ‐
23 00 90‐BFB‐17‐002 BLue Flash Light Beacon FGS F 24Vdc Hardwire DOR ✓ ✓ EWP2‐SPI‐DD‐17‐SF‐LAY‐0002 ‐

F&G Total IO Summery


REV Software/ Hardwire SUB System I/O Type Signal QTY Signal QTY + 20%
00 Hardwire PLC DI 0 0
00 Hardwire PLC DIR 4 5
00 Hardwire PLC DOR 6 7
00 Hardwire PLC AIR 13 16
00 Hardwire PLC TOTAL 23 28