INSTALLATION MANUAL

CEILING CONCEALED
CHILLED WATER FAN COIL UNIT
(C Series)

IM-CCCW-0308(5)-DAIKIN (ASEAN)
Part No.: R08019031562E

CVR-IM-CCCW 0308(5)DK(asean).ind1 1 11/29/13 8:34:18 AM


CVR-IM-CCCW 0308(5)DK(asean).ind2 2 11/29/13 8:34:19 AM
OUTLINE AND DIMENSIONS

English
Indoor Unit: Ceiling Concealed Fan Coil Unit C Series

All dimensions are in mm


LEFT PIPING
D

Original Instruction
H
150 31

10
K
51

I
L

J
M

I
10
150 31
N G
O 10
20
40
40

WATER OUTLET
131
Q

P
131

E
178

WATER INLET
133
39

36 40

10

F
63
C
B
A

All dimensions are in mm


RIGHT PIPING

D
H
31 150
10

51
I
J

L
I

31 150
10

G N
10 O
20

40
40

WATER OUTLET
131

Q
131
P
E

WATER INLET
133
178
40
36 40

10
F

C 63
B
A

Dimension
A B C D E F G H I J K L M N O P Q
Model
FWPMM3AV1 808 774 702 741 267 36 662 662 93 225 115 218 76 411 351 211 211

1-1

IM-CCCW 0308(5)DK(asean)-EN.indd1 1 11/29/13 8:37:28 AM


All dimensions are in mm
LEFT PIPING
D
H
DETAIL B FOR FWPMM6/7 DETAIL A FOR FWPMM4 R 31

10
WATER OUTLET WATER OUTLET 51

I
K
162

179
121

133
WATER INLET WATER INLET

J
61 60
84

I
M

10
R 31
SEE DETAIL A FOR FWPMM4 N G
SEE DETAIL B FOR FWPMM6/7 O
10
40

40
WATER INLET
131

131
Q

E
WATER OUTLET P
36 40
40

10

F
C
B
A

All dimensions are in mm


RIGHT PIPING
D
H
31 R
10

DETAIL A FOR FWPMM4 DETAIL B FOR FWPMM6/7


51
I

WATER OUTLET
WATER OUTLET
J

162
WATER INLET
179

WATER INLET 121


133
I

60 61
84
10

31 R
G

N SEE DETAIL A FOR FWPMM4


O SEE DETAIL B FOR FWPMM6/7
10
40
40

WATER INLET
P

Q
131

131
E

WATER OUTLET
36 40

40

10
F

C
B
A

Dimension
A B C D E F G H I J K L M N O P Q R
Model
FWPMM4AV1 939 914 842 881 267 36 802 802 93 225 114 222 76 412 351 211 211 185
FWPMM6AV1 1108 1075 1002 1041 267 36 962 962 93 225 64 272 76 412 351 211 211 179
FWPMM7AV1 1243 1209 1137 1176 267 36 1097 1097 93 225 64 272 76 412 351 211 211 206

1-2

IM-CCCW 0308(5)DK(asean)-EN.indd2 2 11/29/13 8:37:29 AM


All dimensions are in mm
LEFT PIPING

English
H
R 25

16
50

I
L

J
I
M
371 40

15
N G
O D
25
W

15
WATER OUTLET WATER INLET

P
S
160
Q

E
15
15
V
22

F
U C
T B
A

All dimensions are in mm


RIGHT PIPING
H
25 R
16

50
I

K
J

L
M
I

40 371
15

G N
D O
25
W
15

WATER INLET WATER OUTLET


P
S

160
Q
E

15

15
V
22
F

U
C T
B
A

Dimension
A B C D E F G H I J K L
Model
FWPMM8AV1 987 997 920 959 296 36 824 869 131 339 136 367
FWPMM11AV1 1292 1297 1225 1264 316 36 824 1174 119 401 147 394

Dimension
M N O P Q R S T U V W
Model
FWPMM8AV1 97 600 521 121 213 410 91 137 87 167 31
FWPMM11AV1 97 638 559 186 233 563 156 148 97 149 51

1-3

IM-CCCW 0308(5)DK(asean)-EN.indd3 3 11/29/13 8:37:29 AM


All dimensions are in mm
LEFT PIPING D
H
R 25

15
50

I
L

J
M

I
N S 40
O G
60

40
WATER OUTLET WATER INLET

P
93
Q
188

E
40
15
59

15

F
U C
T B
A

All dimensions are in mm


RIGHT PIPING
D
H
25 R
15

50
I

K
L
J

M
I

40 S N
G O
60
40

WATER INLET WATER OUTLET


P
93

188
Q
E

40

15
V
59

15
F

C U
B T
A

Dimension
Model A B C D E F G H I J K L

FWPMM9AV1 972 988 917 956 384 36 798 866 143 256 162 206
FWPMM12AV1 1088 1105 1033 1072 384 36 798 982 143 256 162 206
FWPMM14AV1 1342 1358 1287 1326 384 36 798 1236 143 256 159 209
FWPMM16AV1 1542 1558 1487 1526 384 36 798 1436 143 256 159 199

Dimension
Model M N O P Q R S T U V

FWPMM9AV1 173 541 462 173 307 409 359 159 109 196
FWPMM12AV1 173 541 462 173 307 467 359 159 109 196
FWPMM14AV1 173 541 462 173 307 594 359 156 106 196
FWPMM16AV1 183 541 462 173 307 694 359 154 104 196
1-4

IM-CCCW 0308(5)DK(asean)-EN.indd4 4 11/29/13 8:37:30 AM


INSTALLATION MANUAL

English
This manual provides the procedures of installation to ensure a safe and good standard of operation for the air
conditioner unit.
Special adjustment may be necessary to suit local requirement.
Before using your air conditioner, please read this instruction manual carefully and keep it for future reference.
This appliance is intended to be used by expert or trained users in shops, in light industry and on farms, or for
commercial use by lay persons.
This appliance is not intended for use by persons, including children, with reduced physical, sensory or mental
capabilities, or lack of experience and knowledge, unless they have been given supervision or instruction concerning
use of the appliance by a person responsible for their safety.
Children should be supervised to ensure that they do not play with the appliance.

SAFETY PRECAUTIONS

! WARNING ! CAUTION
• Installation and maintenance should be performed by Please take note of the following important points when
qualified persons who are familiar with local code and installing.
regulation, and experienced with this type of appliance. • Ensure that the drainage piping is connected properly.
• All field wiring must be installed in accordance with the If the drainage piping is not connected properly, it may
national wiring regulation. cause water leakage which will dampen the furniture.
• Ensure that the rated voltage of the unit corresponds to that • Ensure that the unit’s panel is closed after service or
of the name plate before commencing wiring work according installation.
to the wiring diagram. Unsecured panels will cause the unit to operate
• The unit must be GROUNDED to prevent possible hazard noisily.
due to insulation failure. • Sharp edges and coil surfaces are potential locations which
• All electrical wiring must not touch the water piping or any may cause injury hazards. Avoid from being in contact with
moving parts of the fan motors. these places.
• Confirm that the unit has been switched OFF before • Before turning off the power supply set the remote
installing or servicing the unit. controller’s ON/OFF switch to the “OFF” position to
• Risk of electric shock, can cause injury or death. Disconnect prevent the nuisance tripping of the unit. If this is not done,
all remain electric power supplies before servicing. the unit’s fans will start turning automatically when power
• DO NOT pull out the power cord when the power is ON. resumes, posing a hazard to service personnel or the user.
This may cause serious electrical shocks which may result • Do not install the units at or near doorway.
in the fire hazards. • Do not install the units at area like hot spring or oil refinery
• Keep the indoor and outdoor units, power cable and plant where sulphide gas exists.
transmission wiring, at least 1m from TVs and radios, to • Do not operate any heating apparatus too close to the air
prevent distorted pictures and static. {Depending on the type conditioner unit or use in room where mineral oil, oil vapour
and source of the electrical waves, static may be heard even or oil steam exist, this may cause platic part to melt or
when more than 1m away}. deform as a result of excessive heat or chemical reaction.
• When the unit is used in kitchen, keep flour away from going
into suction of the unit.
• This unit is not suitable for factory used where cutting oil
mist or iron powder exist or voltage fluctuates greatly.
• Ensure the color of wires of the outdoor unit and the
terminal markings are same to the indoors respectively.
• IMPORTANT : DO NOT INSTALL OR USE THE AIR
CONDITIONER UNIT IN A LAUNDRY ROOM.
• Don’t use joined and twisted wires for incoming power
supply.
• The equipment is not intended for use in a potentially
explosive atmosphere.

NOTICE
Disposal requirement
Your air conditioning product is marked with this symbol. This means that electrical and electronic products shall
not be mixed with unsorted household waste.
Do not try to dismantle the system yourself: the dismantling of the air conditioning system, treatment of the
refrigerant, of oil and of other parts must be done by a qualified installer in accordance with relevant local and
national legislation.
Air conditioners must be treated at a specialized treatment facility for re-use, recycling and recovery. By ensuring
this product is disposed of correctly, you will help to prevent potential negative consequences for the environment
and human health. Please contact the installer or local authority for more information.
Batteries must be removed from the remote controller and disposed of separately in accordance with relevant
local and national legislation.

1-5

IM-CCCW 0308(5)DK(asean)-EN.indd5 5 11/29/13 8:37:30 AM


INSTALLATION DIAGRAM

CORK TAPE FULLY INSULATED

INSULATION THROUGH OUT CHILLED WATER PIPING

INSTALLATION OF THE INDOOR UNIT


The indoor unit must be installed such that there is no short Center distance of axle (see drawing below)
circuit of the cool discharge. Respect the installation clearance. A
Do not put the indoor unit where there is direct sunlight on unit.
The location is suitable for piping and drainage and it must have
a large distance between a door and unit.
Ceiling Concealed Mounting
• Use the hanger supplied with the unit.
• Make sure that the ceiling is sufficiently strong to withstand L
the weight.

Insulation material See


(field supply) Detail A
Air inlet side
Air outlet side Provide clearance for servicing ease and optimal air flow as
shown in the diagram.

Aluminium tape Aluminium tape


(field supply) (field supply) 300mm
or more
Field supply
10mm

Washer for hanger bracket 300mm* or more Ceiling


(attached)
2300mm or more
Tighten
Floor
Detail A
* Can be smaller than 300mm if ceiling is removable.

CC FWPMM3A(Z)V1 FWPMM4A(Z)V1 FWPMM6A(Z)V1 FWPMM7A(Z)V1 FWPMM8A(Z)V1


A (mm) 741 881 1041 1176 959
L (mm) 225 225 225 225 339

CC FWPMM9A(Z)V1 FWPMM11A(Z)V1 FWPMM12A(Z)V1 FWPMM14A(Z)V1 FWPMM16A(Z)V1


A (mm) 956 1264 1076 1326 1526
L (mm) 266 401 266 266 266

! CAUTION
Do not install the unit at altitude over 2000m for both indoor and outdoor.
1-6

IM-CCCW 0308(5)DK(asean)-EN.indd6 6 11/29/13 8:37:30 AM


Ceiling Concealed Drain Piping Work

English
10mm (0.39")

Bottom of
the unit

Sla
nt

or more or more
Drain

100 100
trap

Insulate securely Do not leave in water Unit : mm

• The drain pipe must be installed as shown in the diagram (see diagram above) to avoid damage caused by leaks and
condensation.
• For the best result, keep the piping as short as possible. Slant the piping at an angle to improve the flow.
• Ensure the drain pipe is securely insulated.
• It is necessary to provide a drain trap in the drain outlet to relieve pressure that exists within the unit compared to the outside
atmospheric pressure when the unit is operating. The drain trap is to avoid possibility of splashes or an odor.
• Keep pipes as straight as possible for easy cleaning and to prevent the accumulation of dirt and debris.
• Conduct a water drainage test after the installation is completed. Make sure that the drainage flow is smooth.
• In humid environments, use an extra drain pan to cover the entire area of the indoor unit.

WATER PIPING CONNECTION

• The indoor unit is equipped with water outlet and inlet connection. There is an air-vent that is fitted along with the connection
for air purging.
• 3 way valve is required for cycling off or bypass the chilled water.
• Black steel pipe, closed cell polyurethane pipe and copper tube are recommended in the field installation. All types of piping
and connection must be insulated with closed cell polyurethane to avoid condensation.
• Do not use contaminated or damaged pipe and fitting for installation.
• Some main fitting components are needed in the system to enhance the capacity and ease of service, such as gate valve,
balancing valve, 2 way or 3 way valve, filter, strainer and etc.

Gate Valve Three Way Valve Gate Valve Two Way Valve Gate Valve

Chiller Gate Valve FCU Gate Valve FCU FCU

Gate Valve

Good Controlling Bad Controlling Worst Controlling

1-7

IM-CCCW 0308(5)DK(asean)-EN.indd7 7 11/29/13 8:37:31 AM


ELECTRICAL WIRING CONNECTION
Wire connection to the controller board is as show in the wiring diagram on the respective terminal box.

HEAT Jumper VALVE Jumper


Cooling Mode & Valve Application x P
Cooling Mode & Valveless Application x x
Heatpump Mode & Valve Application P P
Heatpump Mode & Valveless Application P x

FWPMM3A(Z)V1-N / FWPMM4A(Z)V1-N / FWPMM6A(Z)V1-N / FWPMM7A(Z)V1-N (without controller)

FCU 1 FCU 2 FCU 3

FL FM FH L N FL FM FH L N FL FM FH L N

FSC FSC FSC

TH TH TH
L L L

N N N
X1 220-240V/1ø/50Hz or 220-240V/1ø/50Hz or 220-240V/1ø/50Hz or
X2 X3
208-230V/1ø/60Hz 208-230V/1ø/60Hz 208-230V/1ø/60Hz

Chiller FL
FM
Fan Low
Fan Medium
! There must be an all pole
disconnection in the supply
FH Fan High mains with a contact separation
L Live
N Neutral of at least 3mm.
FSC Fan Speed Controller All power line must be from
X1, X2, X3 Relay (220 ~ 240V, 10A)
TH Thermostat
the same phase.

FWPMM9A(Z)V1-N / FWPMM11A(Z)V1-N / FWPMM12A(Z)V1-N / FWPMM14A(Z)V1-N /


FWPMM16A(Z)V1-N (without controller)

FCU 1 FCU 2 FCU 3

SH H M L N SH H M L N SH H M L N

FSC FSC FSC

TH TH TH
L L L

N N N
X1 220-240V/1ø/50Hz or 220-240V/1ø/50Hz or 220-240V/1ø/50Hz or
X2 X3
208-230V/1ø/60Hz 208-230V/1ø/60Hz 208-230V/1ø/60Hz

Chiller
SH
H
Fan Super High
Fan High ! There must be an all pole
disconnection in the supply
M Fan Medium
L Fan Low mains with a contact separation
N Neutral of at least 3mm.
FSC Fan Speed Controller All power line must be from
X1, X2, X3 Relay (220 ~ 240V, 10A)
TH Thermostat the same phase.

1-8

IM-CCCW 0308(5)DK(asean)-EN.indd8 8 11/29/13 8:37:31 AM


FWPMM3A(Z)V1 / FWPMM4A(Z)V1 / FWPMM6A(Z)V1 / FWPMM7A(Z)V1 / FWPMM8A(Z)V1 /

English
FWPMM9A(Z)V1 / FWPMM11A(Z)V1 / FWPMM12A(Z)V1 / FWPMM14A(Z)V1 / FWPMM16A(Z)V1
(with controller)
FCU 1 FCU 2 FCU 3

VALVE L N VALVE L N VALVE L N

3WV 3WV 3WV

L L L

N N N
220-240V/1ø/50Hz or 220-240V/1ø/50Hz or 220-240V/1ø/50Hz or
208-230V/1ø/60Hz 208-230V/1ø/60Hz 208-230V/1ø/60Hz

X1 X2 X3

3WV 3 way valve


Chiller ! There must be an all pole
disconnection in the supply Field supply
X1, X2, X3, Relay (220 ~ 240V, 10A)
mains with a contact separation
of at least 3mm.
All power line must be from
the same phase.

IMPORTANT: * These values are for information only. They should be checked and selected to comply with local and/or
national codes and/or national codes and regulations. They are also subject to the type of installation and
size of conductors.
** The appropriate voltage range should be checked with label data on the unit.
A main switch or other means for disconnection, having a contact separation in all poles, must be incorporated
in the fixed wiring in accordance with the relevant local and national legislation.

Model Indoor FWPMM3A(Z)V1 FWPMM4A(Z)V1 FWPMM6A(Z)V1 FWPMM7A(Z)V1 FWPMM8A(Z)V1


Voltage Range** Indoor 220V-240V/1Ph/50Hz + ! or 208V-230V/1Ph/60Hz + !
Power Supply Cable Size* mm2 1.5 1.5 1.5 1.5 1.5
Number of Conductors 3 3 3 3 3
Recommended Time Delay Fuse* A 1 2 4 4 6

Model Indoor FWPMM9A(Z)V1 FWPMM11A(Z)V1 FWPMM12A(Z)V1 FWPMM14A(Z)V1 FWPMM16A(Z)V1


Voltage Range** Indoor 220V-240V/1Ph/50Hz + ! or 208V-230V/1Ph/60Hz + !
Power Supply Cable Size* mm2 1.5 1.5 1.5 1.5 1.5
Number of Conductors 3 3 3 3 3
Recommended Time Delay Fuse* A 8 10 10 10 12

Note:
This is a proposed wiring connection. It may change subject to the chiller unit and must comply with the local and national
code and regulations.

1-9

IM-CCCW 0308(5)DK(asean)-EN.indd9 9 11/29/13 8:37:31 AM


• All wires must be firmly connected.
• Make sure all the wire do not touch the refrigerant pipings, compressor or any moving parts.
• The connecting wire between the indoor unit and the outdoor unit must be clamped by using provided cord anchorage.
• The power supply cord must be equivalent to H07RN-F which is the minimum requirement.
• Make sure no external pressure is applied to the terminal connectors and wires.
• Make sure all the covers are properly fixed to avoid any gap.
• Use round crimp-style terminal for connecting wires to the power supply terminal block. Connect the wires by matching
to the indication on terminal block. (Refer to the wiring diagram attached on the unit).

Attach insulation sleeve

Electric wire
Round crimp-style terminal

• Use the correct screwdriver for terminal screws tightening. Unsuitable screwdrivers can damage the screw head.
• Over tightening can damage the terminal screw.
• Do not connect wire of different gauge to same terminal.
• Keep wiring in an orderly manner. Prevent the wiring from obstructing other parts and the terminal box cover.

Connect wires of the Do not connect wires of the Do not connect wires
same gauge to both side. same gauge to one side. of different gauges.

INDICATOR LIGHTS

Error Description Cool LED Error Indication


Room Sensor error 1 blinks E1
Pipe Water Sensor error 2 blinks E2
Water Pump error 3 blinks E6
Pipe Water Temperature fault 5 blinks E5

OPERATING RANGE

Operating Limits:
Thermal carrier : Water
Water temperature : 4°C ~ 10°C (Cooling)
Maximum water pressure : 16 bar
Air temperature : (as below)

Cooling Mode
Temperature Ts °C/°F Th °C/°F
Minimum indoor temperature 19.0 / 66.2 14.0 / 57.2
Maximum indoor temperature 32.0 / 89.6 23.0 / 73.4

Ts: Dry bulb temperature. Th: Wet bulb temperature.

1-10

IM-CCCW 0308(5)DK(asean)-EN.indd10 10 11/29/13 8:37:31 AM


OVERALL CHECKING

English
Ensure the following, in particular:-
1. The unit is mounted solidly and rigid in position.
2. Piping and connections are leak proof after charging.
3. Proper wiring has been done.
Drainage check:- Pour some water into left side of drain pan (drainage are in right side of unit).
Note:
• The installation guide above covers only the fan coil unit. For installation guide of outdoor (chiller mini etc) please refer
to the installation guide for such unit.
• The installation of fan coil unit may vary according to the type of outdoor unit.
• Installation must be done by qualified personnel who are familiar with this type of product.

SERVICE AND MAINTENANCE

Service Parts Maintenance Procedures Period


Indoor Air Filter 1. Remove any dust adhered on the filter by using a vacuum cleaner or wash At least once every
in lukewarm water (below 40°C) with neutral cleaning detergent. 2 weeks.
2. Rinse the filter well and dry before placing it back onto the unit. More frequently if
3. Do not use gasoline, volatile substances or chemical to clean the filter. necessary.
Indoor Unit 1. Clean any dirt or dust on the grille or panel by wiping it off with soft cloth At least once every
soaked in lukewarm water (below 40°C) with neutral detergent solution. 2 weeks.
2. Do not use gasoline, volatile substances or chemicals to clean the indoor
unit. More frequently if
necessary.
Indoor Fan 1. Check for any abnormal noise. When necessary

TROUBLESHOOTING

For any enquiries on spare part please contact your authorized dealer. When any malfunction of the air
conditioner unit is noted, immediately switch off the power supply to the unit. Check the following fault
conditions and causes for some simple troubleshooting tips.

Fault Causes / Action


1. The air conditioner unit does not operate. – Power failure, or the fuse need to be replaced.
– The power plug is disconnected.
– It is possible that your delay timer has been set incorrectly.
2. The air flow is too low. – The air filter is dirty.
– The air suction and discharge are clogged.
– The regulated temperature is not high enough.
(applicable for auto fan mode only)
3. Discharge air flow has bad odor. – Odors may be caused by cigarettes, smoke particles, perfume
etc. which might have adhered onto the coil.
4. Condensation on the front air grille of the indoor – This is caused by air humidity after an extended long period
unit. of operation.
– The set temperature is too low, increase the temperature
setting and operate the unit at high fan speed.
5. Water flowing out from the air conditioner unit. – Switch off unit and call local dealer / serviceman.

If the fault persists, please call your local dealer / serviceman.

1-11

IM-CCCW 0308(5)DK(asean)-EN.indd11 11 11/29/13 8:37:32 AM


MEMO

IM-CCCW 0308(5)DK(asean)-EN.indd12 12 11/29/13 8:37:32 AM


CVR-IM-CCCW 0308(5)DK(asean).ind3 3 11/29/13 8:34:19 AM
• The manufacturer reserves the right to revise any of the specification and design contain herein at any time without prior
notification.

Zandvoordestraat 300, B-8400 Oostende, Head office:


Belgium Umeda Center Bldg., 2-4-12, Nakazaki-Nishi,
Kita-ku, Osaka, 530-8323 Japan
Tokyo office:
P.O.Box 18674, Galleries 4, 11th Floor, JR Shinagawa East Bldg., 2-18-1, Konan,
Downtown Jebel Ali, Dubai, UAE. Minato-ku, Tokyo, 108-0075 Japan
http://www.daikin.com/global/
Importer for Turkey

Hürriyet Mahallesi Yakacık D-100 Kuzey Yanyol Caddesi


No:49/1-2 Kartal − İstanbul

CVR-IM-CCCW 0308(5)DK(asean).ind4 4 11/29/13 8:34:19 AM

You might also like