IM Daikin FWPMM
IM Daikin FWPMM
CEILING CONCEALED
CHILLED WATER FAN COIL UNIT
(C Series)
IM-CCCW-0308(5)-DAIKIN (ASEAN)
Part No.: R08019031562E
English
Indoor Unit: Ceiling Concealed Fan Coil Unit C Series
Original Instruction
H
150 31
10
K
51
I
L
J
M
I
10
150 31
N G
O 10
20
40
40
WATER OUTLET
131
Q
P
131
E
178
WATER INLET
133
39
36 40
10
F
63
C
B
A
D
H
31 150
10
51
I
J
L
I
31 150
10
G N
10 O
20
40
40
WATER OUTLET
131
Q
131
P
E
WATER INLET
133
178
40
36 40
10
F
C 63
B
A
Dimension
A B C D E F G H I J K L M N O P Q
Model
FWPMM3AV1 808 774 702 741 267 36 662 662 93 225 115 218 76 411 351 211 211
1-1
10
WATER OUTLET WATER OUTLET 51
I
K
162
179
121
133
WATER INLET WATER INLET
J
61 60
84
I
M
10
R 31
SEE DETAIL A FOR FWPMM4 N G
SEE DETAIL B FOR FWPMM6/7 O
10
40
40
WATER INLET
131
131
Q
E
WATER OUTLET P
36 40
40
10
F
C
B
A
WATER OUTLET
WATER OUTLET
J
162
WATER INLET
179
60 61
84
10
31 R
G
WATER INLET
P
Q
131
131
E
WATER OUTLET
36 40
40
10
F
C
B
A
Dimension
A B C D E F G H I J K L M N O P Q R
Model
FWPMM4AV1 939 914 842 881 267 36 802 802 93 225 114 222 76 412 351 211 211 185
FWPMM6AV1 1108 1075 1002 1041 267 36 962 962 93 225 64 272 76 412 351 211 211 179
FWPMM7AV1 1243 1209 1137 1176 267 36 1097 1097 93 225 64 272 76 412 351 211 211 206
1-2
English
H
R 25
16
50
I
L
J
I
M
371 40
15
N G
O D
25
W
15
WATER OUTLET WATER INLET
P
S
160
Q
E
15
15
V
22
F
U C
T B
A
50
I
K
J
L
M
I
40 371
15
G N
D O
25
W
15
160
Q
E
15
15
V
22
F
U
C T
B
A
Dimension
A B C D E F G H I J K L
Model
FWPMM8AV1 987 997 920 959 296 36 824 869 131 339 136 367
FWPMM11AV1 1292 1297 1225 1264 316 36 824 1174 119 401 147 394
Dimension
M N O P Q R S T U V W
Model
FWPMM8AV1 97 600 521 121 213 410 91 137 87 167 31
FWPMM11AV1 97 638 559 186 233 563 156 148 97 149 51
1-3
15
50
I
L
J
M
I
N S 40
O G
60
40
WATER OUTLET WATER INLET
P
93
Q
188
E
40
15
59
15
F
U C
T B
A
50
I
K
L
J
M
I
40 S N
G O
60
40
188
Q
E
40
15
V
59
15
F
C U
B T
A
Dimension
Model A B C D E F G H I J K L
FWPMM9AV1 972 988 917 956 384 36 798 866 143 256 162 206
FWPMM12AV1 1088 1105 1033 1072 384 36 798 982 143 256 162 206
FWPMM14AV1 1342 1358 1287 1326 384 36 798 1236 143 256 159 209
FWPMM16AV1 1542 1558 1487 1526 384 36 798 1436 143 256 159 199
Dimension
Model M N O P Q R S T U V
FWPMM9AV1 173 541 462 173 307 409 359 159 109 196
FWPMM12AV1 173 541 462 173 307 467 359 159 109 196
FWPMM14AV1 173 541 462 173 307 594 359 156 106 196
FWPMM16AV1 183 541 462 173 307 694 359 154 104 196
1-4
English
This manual provides the procedures of installation to ensure a safe and good standard of operation for the air
conditioner unit.
Special adjustment may be necessary to suit local requirement.
Before using your air conditioner, please read this instruction manual carefully and keep it for future reference.
This appliance is intended to be used by expert or trained users in shops, in light industry and on farms, or for
commercial use by lay persons.
This appliance is not intended for use by persons, including children, with reduced physical, sensory or mental
capabilities, or lack of experience and knowledge, unless they have been given supervision or instruction concerning
use of the appliance by a person responsible for their safety.
Children should be supervised to ensure that they do not play with the appliance.
SAFETY PRECAUTIONS
! WARNING ! CAUTION
• Installation and maintenance should be performed by Please take note of the following important points when
qualified persons who are familiar with local code and installing.
regulation, and experienced with this type of appliance. • Ensure that the drainage piping is connected properly.
• All field wiring must be installed in accordance with the If the drainage piping is not connected properly, it may
national wiring regulation. cause water leakage which will dampen the furniture.
• Ensure that the rated voltage of the unit corresponds to that • Ensure that the unit’s panel is closed after service or
of the name plate before commencing wiring work according installation.
to the wiring diagram. Unsecured panels will cause the unit to operate
• The unit must be GROUNDED to prevent possible hazard noisily.
due to insulation failure. • Sharp edges and coil surfaces are potential locations which
• All electrical wiring must not touch the water piping or any may cause injury hazards. Avoid from being in contact with
moving parts of the fan motors. these places.
• Confirm that the unit has been switched OFF before • Before turning off the power supply set the remote
installing or servicing the unit. controller’s ON/OFF switch to the “OFF” position to
• Risk of electric shock, can cause injury or death. Disconnect prevent the nuisance tripping of the unit. If this is not done,
all remain electric power supplies before servicing. the unit’s fans will start turning automatically when power
• DO NOT pull out the power cord when the power is ON. resumes, posing a hazard to service personnel or the user.
This may cause serious electrical shocks which may result • Do not install the units at or near doorway.
in the fire hazards. • Do not install the units at area like hot spring or oil refinery
• Keep the indoor and outdoor units, power cable and plant where sulphide gas exists.
transmission wiring, at least 1m from TVs and radios, to • Do not operate any heating apparatus too close to the air
prevent distorted pictures and static. {Depending on the type conditioner unit or use in room where mineral oil, oil vapour
and source of the electrical waves, static may be heard even or oil steam exist, this may cause platic part to melt or
when more than 1m away}. deform as a result of excessive heat or chemical reaction.
• When the unit is used in kitchen, keep flour away from going
into suction of the unit.
• This unit is not suitable for factory used where cutting oil
mist or iron powder exist or voltage fluctuates greatly.
• Ensure the color of wires of the outdoor unit and the
terminal markings are same to the indoors respectively.
• IMPORTANT : DO NOT INSTALL OR USE THE AIR
CONDITIONER UNIT IN A LAUNDRY ROOM.
• Don’t use joined and twisted wires for incoming power
supply.
• The equipment is not intended for use in a potentially
explosive atmosphere.
NOTICE
Disposal requirement
Your air conditioning product is marked with this symbol. This means that electrical and electronic products shall
not be mixed with unsorted household waste.
Do not try to dismantle the system yourself: the dismantling of the air conditioning system, treatment of the
refrigerant, of oil and of other parts must be done by a qualified installer in accordance with relevant local and
national legislation.
Air conditioners must be treated at a specialized treatment facility for re-use, recycling and recovery. By ensuring
this product is disposed of correctly, you will help to prevent potential negative consequences for the environment
and human health. Please contact the installer or local authority for more information.
Batteries must be removed from the remote controller and disposed of separately in accordance with relevant
local and national legislation.
1-5
! CAUTION
Do not install the unit at altitude over 2000m for both indoor and outdoor.
1-6
English
10mm (0.39")
Bottom of
the unit
Sla
nt
or more or more
Drain
100 100
trap
• The drain pipe must be installed as shown in the diagram (see diagram above) to avoid damage caused by leaks and
condensation.
• For the best result, keep the piping as short as possible. Slant the piping at an angle to improve the flow.
• Ensure the drain pipe is securely insulated.
• It is necessary to provide a drain trap in the drain outlet to relieve pressure that exists within the unit compared to the outside
atmospheric pressure when the unit is operating. The drain trap is to avoid possibility of splashes or an odor.
• Keep pipes as straight as possible for easy cleaning and to prevent the accumulation of dirt and debris.
• Conduct a water drainage test after the installation is completed. Make sure that the drainage flow is smooth.
• In humid environments, use an extra drain pan to cover the entire area of the indoor unit.
• The indoor unit is equipped with water outlet and inlet connection. There is an air-vent that is fitted along with the connection
for air purging.
• 3 way valve is required for cycling off or bypass the chilled water.
• Black steel pipe, closed cell polyurethane pipe and copper tube are recommended in the field installation. All types of piping
and connection must be insulated with closed cell polyurethane to avoid condensation.
• Do not use contaminated or damaged pipe and fitting for installation.
• Some main fitting components are needed in the system to enhance the capacity and ease of service, such as gate valve,
balancing valve, 2 way or 3 way valve, filter, strainer and etc.
Gate Valve Three Way Valve Gate Valve Two Way Valve Gate Valve
Gate Valve
1-7
FL FM FH L N FL FM FH L N FL FM FH L N
TH TH TH
L L L
N N N
X1 220-240V/1ø/50Hz or 220-240V/1ø/50Hz or 220-240V/1ø/50Hz or
X2 X3
208-230V/1ø/60Hz 208-230V/1ø/60Hz 208-230V/1ø/60Hz
Chiller FL
FM
Fan Low
Fan Medium
! There must be an all pole
disconnection in the supply
FH Fan High mains with a contact separation
L Live
N Neutral of at least 3mm.
FSC Fan Speed Controller All power line must be from
X1, X2, X3 Relay (220 ~ 240V, 10A)
TH Thermostat
the same phase.
SH H M L N SH H M L N SH H M L N
TH TH TH
L L L
N N N
X1 220-240V/1ø/50Hz or 220-240V/1ø/50Hz or 220-240V/1ø/50Hz or
X2 X3
208-230V/1ø/60Hz 208-230V/1ø/60Hz 208-230V/1ø/60Hz
Chiller
SH
H
Fan Super High
Fan High ! There must be an all pole
disconnection in the supply
M Fan Medium
L Fan Low mains with a contact separation
N Neutral of at least 3mm.
FSC Fan Speed Controller All power line must be from
X1, X2, X3 Relay (220 ~ 240V, 10A)
TH Thermostat the same phase.
1-8
English
FWPMM9A(Z)V1 / FWPMM11A(Z)V1 / FWPMM12A(Z)V1 / FWPMM14A(Z)V1 / FWPMM16A(Z)V1
(with controller)
FCU 1 FCU 2 FCU 3
L L L
N N N
220-240V/1ø/50Hz or 220-240V/1ø/50Hz or 220-240V/1ø/50Hz or
208-230V/1ø/60Hz 208-230V/1ø/60Hz 208-230V/1ø/60Hz
X1 X2 X3
IMPORTANT: * These values are for information only. They should be checked and selected to comply with local and/or
national codes and/or national codes and regulations. They are also subject to the type of installation and
size of conductors.
** The appropriate voltage range should be checked with label data on the unit.
A main switch or other means for disconnection, having a contact separation in all poles, must be incorporated
in the fixed wiring in accordance with the relevant local and national legislation.
Note:
This is a proposed wiring connection. It may change subject to the chiller unit and must comply with the local and national
code and regulations.
1-9
Electric wire
Round crimp-style terminal
• Use the correct screwdriver for terminal screws tightening. Unsuitable screwdrivers can damage the screw head.
• Over tightening can damage the terminal screw.
• Do not connect wire of different gauge to same terminal.
• Keep wiring in an orderly manner. Prevent the wiring from obstructing other parts and the terminal box cover.
Connect wires of the Do not connect wires of the Do not connect wires
same gauge to both side. same gauge to one side. of different gauges.
INDICATOR LIGHTS
OPERATING RANGE
Operating Limits:
Thermal carrier : Water
Water temperature : 4°C ~ 10°C (Cooling)
Maximum water pressure : 16 bar
Air temperature : (as below)
Cooling Mode
Temperature Ts °C/°F Th °C/°F
Minimum indoor temperature 19.0 / 66.2 14.0 / 57.2
Maximum indoor temperature 32.0 / 89.6 23.0 / 73.4
1-10
English
Ensure the following, in particular:-
1. The unit is mounted solidly and rigid in position.
2. Piping and connections are leak proof after charging.
3. Proper wiring has been done.
Drainage check:- Pour some water into left side of drain pan (drainage are in right side of unit).
Note:
• The installation guide above covers only the fan coil unit. For installation guide of outdoor (chiller mini etc) please refer
to the installation guide for such unit.
• The installation of fan coil unit may vary according to the type of outdoor unit.
• Installation must be done by qualified personnel who are familiar with this type of product.
TROUBLESHOOTING
For any enquiries on spare part please contact your authorized dealer. When any malfunction of the air
conditioner unit is noted, immediately switch off the power supply to the unit. Check the following fault
conditions and causes for some simple troubleshooting tips.
1-11