Actuator Details
Actuator Details
DATED : 18.12.2021
Technical Clauses
IQ3 SPECIFICATION - DESCRIPTION
This description provides the basic specification, please refer to the Schedule of Equipment for actuator size, mounting flange,
area classification, power supply and performance data. Remote control and indication functions are described under the Wiring
Diagram. Additional options may also be found in Extras Included. Further technical details are provided in the IQ/IQT (3rd
Generation) product range brochure PUB002-038 which is available at http://www.rotork.com/en/master-record/8923
The Current Position Transmitter (CPT) provides a non-contact internally fed 4-20mA analogue signal proportional to valve
position. Selectable for minimum signal corresponding to fully Close or fully Open position with automatic zero and span setting.
The maximum external impedance that may be connected to the signal is 500 ohms at nominal supply voltage. Repeatability is
within +/- 1% and linearity +/-1% of total valve travel.
Wiring diagram 101B0000 is described in IQ/IQT Control and Monitoring publication (PUB002-041) and includes:
WIRING DIAGRAM
Wiring diagram 100B0000 is described in IQ/IQT Control and Monitoring publication (PUB002-041) and includes:
• CONTROL SUPPLY: 20 – 60VDC/40 – 120VAC or actuator derived 24VDC
• CONTROL INPUTS: 6 inputs for open, close, stop/maintain, ESD and interlock signals
• INDICATION CONTACTS: 4 volt-free (SPST) latching contacts (S1-S4), rated at 120VAC/30VDC, 5mA to 5A, each configurable NO
or NC to signal one of the following; open/closed or intermediate positions, moving (continuous or pulsing), Handwheel
operation, local selected, remote selected, open/close interlock active, ESD active, motor tripped on torque in mid travel/going
open/going closed, valve jammed, loss of power/phase or control supply, battery low, internal failure detected, thermostat
tripped, programmable service alarms.
• MONITOR AND AVAILABILITY RELAY: Independent relay with volt-free changeover contact, rated at 120VAC/30VDC, 5mA to 5A.
De-energises in case of; loss of power/phase or control supply, local control or local stop selected (can be excluded), motor
thermostat tripped or detected internal failure
POWER SUPPLY
The actuators offered are suitable for operation on a nominal supply of 415-3-50HZ.
TECHNICAL COMMENTS
-We have considered 1.5 safety factor for actuator sizing.
-We have offered hardwired wiring diagram for all the tags.
-Current Position Transmitter is included for tags which fall under Type 06A schematic.
-For actuator local controls, selector switches are available, not push buttons.
-Offered actuators have integral local controls, no separate local push button station is included.
-MOVs will not disconnect the power on idle mode.
-Rotork special paint to C5M High environment is included, copy of painting procedure attached.
Schedule of Equipment – Electric Actuators:
SQC00033111
Electric Actuators:
SQC00033111
Valve tag Description Wiring Actuator Op. Valve size Qty
number diagram Torque Time
(secs)
1 IQ12 F10 B4 [II2GD EX DB IIB T4] 415/3/50 72RPM + IW46R/F10/184:1 100B0000 2928 38 6" BALL/2500 24.00
2 IQ12 F10 B4 [II2GD EX DB IIB T4] 415/3/50 72RPM + IW5R/F14/288:1 100B0000 4368 60 10" BALL/600 5.00
3 IQ18 F10 B4 [II2GD EX DB IIB T4] 415/3/50 72RPM + IW6R/F16/304:1 100B0000 6693 63 12" BALL/600 3.00
4 IQ25 F14 B4 [II2GD EX DB IIB T4] 415/3/50 18RPM + IW6/F16/76:1 100B0000 10000 63 14" BALL/600 4.00
5 IQ25 F14 B4 [II2GD EX DB IIB T4] 415/3/50 144RPM+ IW76R/F25/505:1 101B0000 23542 53 12" BALL/2500 2.00
6 IQ70 F25 B4 [II2GD EX DB IIB T4] 415/3/50 192RPM+ IW116R/F40/785:1 101B0000 137126 61 10" BALL/2500 1.00
7 IQ12 F10 B4 [II2GD EX DB IIB T4] 415/3/50 72RPM+ IW5R/F14/288:1 101B0000 4368 60 12" BALL/600 1.00
8 IQ12 F10 B4 [II2GD EX DB IIB T4] 415/3/50 72RPM+ IW46R/F10/184:1 101B0000 2928 38 10" BALL/600 1.00
9 IQ12 F10 B4 [II2GD EX DB IIB T4] 415/3/50 72RPM+ IW5R/F14/288:1 101B0000 4368 60 14" BALL/600 1.00