S4L1S-E Wdg.

311 (Single Phase) - Technical Data Sheet


Standards
Stamford industrial alternators meet the requirements of IEC EN 60034 and the relevant section of other international
standards such as BS5000, VDE 0530, NEMA MG1-32, IEC34, CSA C22.2-100 and AS1359. Other standards and
certifications can be considered on request.

Quality Assurance
Alternators are manufactured using production procedures having a quality assurance level to BS EN ISO 9001.

Excitation and Voltage Regulators


Excitation System
AVR Type AS440 MX341 MX321
Voltage Regulation ± 1% ± 1% ± 0.5% with 4% Engine Governing

Excitation Type Self-Excited PMG PMG

No Load Excitation Voltage (V) 12 - 9


No Load Excitation Current (A) 0.7 - 0.5
Full Load Excitation Voltage (V) 41 - 39
Full Load Excitation Current (A) 2.3 - 2.2
Exciter Time Constant (seconds) 0.105

Page 1 S4L1S-E_ES10457533 Rev.A_15.07.2021


S4L1S-E Wdg.311 (Single Phase)

Electrical Data
Insulation System Class H

IP Rating IP23

Stator Winding Double Layer Concentric

Winding Pitch Two Thirds

Winding Leads 12

Winding Number 311

Number of Poles 4

RFI Suppresion EN 61000-6-2 & EN 61000-6-4, refer to factory for others

Waveform Distortion NO LOAD < 2.5% NON-DISTORTING LINEAR LOAD < 5.0%

Short Circuit Ratio 1/Xd

Steady Sate X/R Ratio 16.87

50Hz 60Hz
VOLTAGE DOUBLE DELTA 220 / 110 230 / 115 240 / 120 220 / 110 230 / 115 240 / 120

VOLTAGE PARALLEL DELTA 110 115 120 110 115 120

POWER FACTOR 0.8 0.8 0.8 0.8 0.8 0.8


kVA BASE RATING FOR
175 175 175 185 195 200
REACTANCE VALUES
Saturrated Values in Per Unit at Base Ratings and Voltages
Xd Dir. Axis Synchronous 2.24 2.05 1.88 2.84 2.74 2.58

X'd Dir. Axis Transient 0.15 0.14 0.13 0.19 0.19 0.18

X"d Dir. Axis Subtransient 0.11 0.10 0.09 0.14 0.13 0.13

Xq Quad. Axis Reactance 1.92 1.76 1.62 2.44 2.35 2.22

X''q Quad. Axis Subtransient 0.26 0.24 0.22 0.33 0.32 0.30

XL Leakage Reactance 0.05 0.05 0.05 0.07 0.07 0.06

X2 Negative Reactance 0.17 0.16 0.15 0.22 0.21 0.20

X0 Zero Sequence 0.08 0.07 0.06 0.10 0.09 0.09

Unaturrated Values in Per Unit at Base Ratings and Voltages


Xd Dir. Axis Synchronous 2.69 2.46 2.26 3.41 3.29 3.10

X'd Dir. Axis Transient 0.18 0.16 0.15 0.22 0.22 0.20

X"d Dir. Axis Subtransient 0.13 0.12 0.11 0.16 0.16 0.15
Xq Quad. Axis Reactance 1.98 1.81 1.66 2.51 2.42 2.28
X''q Quad. Axis Subtransient 0.31 0.29 0.26 0.40 0.39 0.36
XL Leakage Reactance 0.06 0.06 0.05 0.08 0.08 0.07
X2 Negative Reactance 0.21 0.19 0.18 0.27 0.26 0.24
X0 Zero Sequence 0.09 0.08 0.08 0.11 0.11 0.10
Time Constants (seconds)
T'd TRANSIENT TIME CONST. 0.08
T''d SUB-TRANSTIME CONST. 0.019
T'do O.C. FIELD TIME CONST. 1.7
Ta ARMATURE TIME CONST. 0.018

Page 2 S4L1S-E_ES10457533 Rev.A_15.07.2021


S4L1S-E Wdg.311 (Single Phase)

Resistances in Ohms (Ω) at 220C


Stator Winding Resistance (Ra)
0.006
per phase series star connected
Rotor Winding Resistance (Rf) 1.19
Exciter Stator Winding Resistance 18
Exciter Rotor Winding Resistance
0.068
per phase
Positive Sequence Resistance (R1) 0.01125
Negative Sequence Resistance (R2) 0.01296
Zero Sequence Resistance (R0) 0.01125
PMG Phase Resistance (Rpmg)
per phase 1.9

Mechanical data
Cooling Air 0.8 m³/sec (50Hz) 0.96 m³/sec (60Hz)
All alternator rotors are dynamically balanced to better than
Shaft and Keys
BS6861: Part 1 Grade 2.5 for minimum vibration in operation.

Bearing Single Bearing Double Bearing


Weight Complete Alternator 1024 kg 1030 kg
Weight Wound Stator 470 kg 470 kg
Weight Wound Rotor 400 kg 377 kg
Moment of Inertia 4.6331 kgm2 4.4343 kgm2
Shipping weight in a Crate 1095 kg 1100 kg
Packing Crate Size 155 x 87 x 107 (cm) 155 x 87 x 107 (cm)
Maximum Over Speed 2250 RPM for two minutes 2250 RPM for two minutes
Bearing Drive End N/A Ball Bearing, 6317
Bearing Non-Drive End Ball Bearing, 6314

Page 3 S4L1S-E_ES10457533 Rev.A_15.07.2021


S4L1S-E Wdg.311 (Single Phase)

Double Delta Efficiency Curves

50Hz Curves 60Hz Curves

Page 4 S4L1S-E_ES10457533 Rev.A_15.07.2021


S4L1S-E Wdg.311 (Single Phase)

Locked Rotor Motor Starting Curves - Separately Excited

50Hz
220V 230V 240V
35

30

25
PER CENT TRANSIENT VOLTAGE DIP

20

15

10

0
0 100 200 300 400 500 600 700 800 900 1000
LOCKED ROTOR kVA

60Hz
220V 230V 240V
35

30

25
PER CENT TRANSIENT VOLTAGE DIP

20

15

10

0
0 100 200 300 400 500 600 700 800
LOCKED ROTOR kVA

Transient Voltage Dip Scaling Factor Transient Voltage Rise Scaling Factor
PF Factor
< 0.5 1.00 For voltage rise multiply voltage dip by 1.25
0.5 0.97
0.6 0.93
0.7 0.90
0.8 0.85
0.9 0.83
1.0 0.80

Page 5 S4L1S-E_ES10457533 Rev.A_15.07.2021


S4L1S-E Wdg.311 (Single Phase)

Locked Rotor Motor Starting Curves - Self Excited

50Hz
220V 230V 240V
35

30

25
PER CENT TRANSIENT VOLTAGE DIP

20

15

10

0
0 100 200 300 400 500 600 700
LOCKED ROTOR kVA

60Hz
220V 230V 240V
35

30

25
PER CENT TRANSIENT VOLTAGE DIP

20

15

10

0
0 100 200 300 400 500 600 700
LOCKED ROTOR kVA

Transient Voltage Dip Scaling Factor Transient Voltage Rise Scaling Factor
PF Factor
< 0.5 1.00 For voltage rise multiply voltage dip by 1.25
0.5 0.97
0.6 0.93
0.7 0.90
0.8 0.85
0.9 0.83
1.0 0.80

Page 6 S4L1S-E_ES10457533 Rev.A_15.07.2021


S4L1S-E Wdg.311 (Single Phase)
Double Delta Short Circuit Decrement Curve

50Hz

SYMM. ASYMMETRICAL

10000
CURRENT (Amps)

1000
0.001 0.01 0.1 1 10
TIME (secs)

Sustained Short Circuit = 3181 Amps

60Hz
100000

SYMM. ASYMMETRICAL
CURRENT (Amps)

10000

1000
0.001 0.01 0.1 1 10
TIME (secs)

Sustained Short Circuit = 3364 Amps


Note 1
The following multiplication factors should be used to
adjust the values from curve between time 0.001
seconds and the minimum current point in respect of
nominal operating voltage :

50Hz 60Hz
Voltage Factor Voltage Factor
220V X 1.00 220V X 1.00
230V X 1.05 230V X 1.05
240V X 1.09 240V X 1.09

The sustained current value is constant irrespective of


voltage level

Page 7 S4L1S-E_ES10457533 Rev.A_15.07.2021


S4L1S-E Wdg.311 (Single Phase)

Typical Alternator Operating Charts


230V/50Hz

240V/60Hz

Page 8 S4L1S-E_ES10457533 Rev.A_15.07.2021


S4L1S-E Wdg.311 (Single Phase)

RATINGS
50Hz
Cont. F - Cont. H - Cont. F - Cont. H -
Class - Temp Rise
105/40°C 0.8pf 125/40°C 0.8pf 105/40°C 1.0pf 125/40°C 1.0pf
Double Delta (V) 220 230 240 220 230 240 220 230 240 220 230 240
Parallel Delta (V) 110 115 120 110 115 120 110 115 120 110 115 120
kVA 160 160 160 175 175 175 160 160 160 175 175 175
kW 128 128 128 140 140 140 160 160 160 175 175 175
Efficiency (%) 90.8 90.9 90.0 90.7 90.8 90.9 92.8 92.9 93.0 92.7 92.9 93.0
kW Input 141 141 142 154 154 154 172 172 172 189 188 188

60Hz
Cont. F - Cont. H - Cont. F - Cont. H -
Class - Temp Rise
105/40°C 0.8pf 125/40°C 0.8pf 105/40°C 1.0pf 125/40°C 1.0pf
Double Delta (V) 220 230 240 220 230 240 220 230 240 220 230 240
Parallel Delta (V) 110 115 120 110 115 120 110 115 120 110 115 120
kVA 165 180 185 185 195 200 165 180 185 185 195 200
kW 132 144 148 148 156 160 165 180 185 185 195 200
Efficiency (%) 91.2 91.3 91.6 90.8 91.1 91.4 92.9 93.1 93.3 92.6 92.8 93.1
kW Input 145 158 162 163 171 175 178 193 198 200 210 215

Page 9 S4L1S-E_ES10457533 Rev.A_15.07.2021


S4L1S-E Wdg.311 (Single Phase)

De-Rates
All values tabulated above are subject to the following reductions:
- 3% for every 500 meters by which the operating altitude exceeds 1000 meters above mean sea level
- 3% for every 5°C by which the operational ambient temperature exceeds 40°C
- For any other operating conditions impacting the cooling circuit please refer to applications
Note: Requirement for operating in an ambient exceeding 60°C and altitude exceeding 4000 meters must be
referred to applications.

Dimensional and Torsional Drawing


For dimensional and torsional information please refer to the alternator General Arrangement and rotor drawings
available on our website (http://stamford-avk.com/)

Note: Continuous development of our products means that the information contained in our data sheets can change
without notice, and specifications should always be confirmed with Cummins Generator Technologies prior to
purchase.

Page 10 S4L1D-C_ Rev.A_10.07.2019


Follow us @stamfordavk

Cummins Generator Technologies

View our videos at youtube.com/stamfordavk

news.stamford-avk.com

For Applications Support:


[email protected]