FXJ-22 Cell Internal Resistance Inspection Unit Instruction For Use
FXJ-22 Cell Internal Resistance Inspection Unit Instruction For Use
October 2,
2009
Version: v1.0
1 Overview
1.1 Scope
FXJ-22 Cell Internal Resistance Inspection Management Unit is a network-based measuring module
for 2V, 6V and 12V cells, which is produced by the Company with years of DC equipment
manufacturing experience, and can be used independently or jointly with WZCK-21 microcomputer
DC monitoring device.
2.1.4 Working Position: vertically with the maximum slope of no more than 5°.
2.1.5 The place where the device is used shall be provided with facilities for preventing sand, rain
and snow, free of corrosive and explosive gas.
2.1.6 The place where the device is used shall be free from strong shock or sharp pounding.
2.2.1 It is featured by rapid computing speed and high reliability with AVR single chip adopted.
2.2.2 The software watchdog and BOD used can significantly improve the stability and reliability of
the system.
2.2.3 Special chip used can ensure high accuracy and excellent anti-interference ability.
2.2.4 Tail cell parameters are set independently, which is convenient for grouping the cell and wiring.
3 Technical Data
3.1 Terminal Voltage/Internal Resistance Inspection Range: 2 V/10 mΩ; 12 V/50 mΩ. (Jumper
setting)
3.5 Communication Interface: RS485, 1 start bit + 8 data bits + 1 stop bit
3.8 Communication Protocol: MODBUS RTU protocol is adopted, see Annex II for details.
1
3.9 Communication Interval :> 200 mS
3.10 Power Supply: DC 90~260 V with the ripple factor of no more than 5%.
5 System Overview
There are two indicator lights on the module, one for operation and the other for communication.
After the unit is powered up, the indicator light for operation flashes once every 500 mS. The
indicator light for communication flashes once when the unit receives the message sent by the upper
computer and reports the message to upper computer after processing.
5.2 Workflow
After the unit is powered up, corresponding optical relays are switched in turn to introduce the
voltage of single cell to the unit for analog-digital conversion and data processing via special chip,
and then inform the CPU to read the data by means of interruption. The voltage of cell can be
2
calculated according to the data read by CPU, and then compared with the overvoltage and
undervoltage set. The overvoltage and undervoltage alarm information will be generated if the value
is out-of-limit for 3 consecutive times. CPU will measure the temperature every minute if the unit is
provided with temperature probe.WZCK-21 microprocessor DC monitoring and detecting device is
capable of setting parameters of the measuring unit via RS485 or reading the voltage of cell and
alarm data. If the address set by the dial switch of the unit is changed, the measuring unit shall be
powered up again. After alarm values of overvoltage and undervoltage, number of cells acquired and
other operation parameters are acquired, the measuring unit shall be powered on again, or the
correctness of operation parameters cannot be ensured.
After the unit is powered up, corresponding optical relays are switched in turn to introduce the
internal resistance inspection excitation current of single cell, and introduce the inspection voltage to
the unit for analog-digital conversion and data processing via special chip, and then inform the CPU
to read the data by means of interruption. The internal resistance of cell can be calculated according
to the data read by CPU. After the gear setting of the unit is changed, the measuring unit must be
powered up again, or the correctness of operation parameters cannot be ensured.
Sample terminals 1 and 20 are used to connect with 19 cells, with terminal 1 connecting to the
positive electrode of cell 1, terminal 2 connecting to negative electrode of cell 1 and positive
electrode of cell 2, and so forth, terminal 20 shall be connected to the negative electrode of cell 19.
Signal terminals 31 and 50 are used to connect with 19 cells, with terminal 31 connecting to the
positive electrode of cell 1, terminal 32 connecting to negative electrode of cell 1 and positive
electrode of cell 2, and so forth, terminal 50 shall be connected to the negative electrode of cell 19.
When the temperature probe is provided, the red wire of temperature probe shall be connected with
terminal 21, the green one with terminal 22 and blue one with terminal 23.
Terminal 25 shall be used to connect with positive input of working power, and terminal 27 with
negative input of working power and terminal 29 with ground wire.
Terminal 30 shall be used to connect with A of RS485 communication interface, terminal 31 with B of
RS485 communication interface and terminal 32 with the ground wire of RS485 communication
interface.
The Local address of FXJ-22 measuring unit can be set by 4-bit dial switch from No.2 to No.5 in
Element U19:
3
0x61 OFF OFF OFF ON
0x67 OFF ON ON ON
0x6b ON OFF ON ON
0x6d ON ON OFF ON
0x6e ON ON ON OFF
0x6f ON ON ON ON
Whether the FXJ-22 measuring unit can be used for monitoring the ambient temperature can be set
via No.1 dial switch in Element U19.
⚫ Note! when the module is used separately, the address shall be set as: 0x60; When
modules are used in combination, the address shall be set as follows in turn: 0x60
0x61…etc.
4
7.1 Products have been packed before leaving factory. Products shall be prevented from strong
collision and bump during transportation to avoid damages to the external packing.
Products shall be stored in a rain- and snow-proof room with the ambient temperature of
-20 °C∽+60 °C, relative humidity of no more than 80% and free from acid, alkaline or other
corrosive and explosive gas.
After equipment are delivered to installation site, unpack them carefully and check whether drawings
and spares are complete and the packing are all right and register the process.
9 Attached Documents
Documents attached with products include one piece of Instruction for Use and one piece of
certificate.
10 Warranty Services
⚫ In case of any quality problems even though the user complies with regulations for storage,
installation and use specified in this instruction after delivery;
⚫ In case of any product or accessories damage caused by transportation found by the user in
unpacking inspection after delivery.
⚫ The warranty of the quality of products is 12 month after the delivery of the products.
⚫ The manufacturer is responsible for replacing or repairing the products free of charge within the
warranty period.
⚫ The user shall consult with the manufacturer for paid replacement or repair beyond the warranty
period.
5
Annex I Schematic Diagram of Terminal
J5
GND
PE
P+
17
18
19
20
P-
D
Q
A
B
P
1
2
J2 LED2 LED1
3
J4 1 2 3 4 5 6 4
5
EARTH
IN+
IN- 6
Programmer 1
J3
interface
编程器接口 2
6 5
4 3
J1
2 1
J6
ON S1
No.1
No.2
No.3
No.4
No.5
01
02
03
04
05
06
07
08
09
10
11
12
13
14
15
16
S1 is a dial switch and the address of device can be set by setting No.2, No.3, No.4, and No.5 of S1.
The coding rule of address is: address of device
= No.2*0x08+No.3*0x04+No.4*0x02+No.5+0x60.
Terminal J1 is the cell voltage acquisition terminal. Port 01 shall be connected with positive electrode
of the first cell, port 02 with the negative electrode of the first cell, port 03 with the negative electrode
of the second cell, and so forth, port 20 of J2 terminal shall be connected with negative electrode of
the nineteenth cell.
P+ and P- of J2 terminal shall be respectively connected with positive electrode of power supply and
power ground. PE shall be connected with the ground. And port A and B are RS485 communication
ports.
RC reset circuit can be accessed into rest pin of single chip when J3 terminal shorts circuit with short
circuit ring. During the process of program burning, short circuit ring must be removed, or the
program cannot be burned. After the process of program burn, short circuit ring must be added for
increasing the reliability of system.
J4 terminal shall be connected with power panel of the device, and external input power shall be
provided to power panel. Port 1 is power +, and port 3 is the power supply GND, and port 6 is GND.
J5 terminal shall be connected with power panel to supply power for measuring plate. Port 1 is +5V1
and port 2 is GND1. These two ports are responsible for power supply of RS485 communications
chip. Port 4 is -5V, port 5 is GND and port 6 is +5V. These three ports are responsible for power
supply of single chip.
6
Annex Ⅱ Communication Protocol
Cell inspection supports 0.2H (remote signal command), 0.3H (command of reading definite value),
0.4H (command of remote measuring), 10H (writing definite value), 11H (report the ID of slave).
7
22 Undervoltage alarm in channel 4 BIT
For example: the host inquires data of register with input state beginning from 32 (20H) in 2200H
from the slave.
Inquire Response
8
CRC L - Data (31-24) 00
CRC H - CRC L -
CRC H -
Note: ON is checked when the slave responds the voltage to the host, the temperature enabling is
ON and the overvoltage alarm of channel 15 is ON.
9
2A Zero drift of channel 16
30 Factor of channel 00
32 Factor of channel 01
34 Factor of channel 02
36 Factor of channel 03
38 Factor of channel 04
3A Factor of channel 05
3C Factor of channel 06
3E Factor of channel 07
40 Factor of channel 08
42 Factor of channel 09
44 Factor of channel 10
46 Factor of channel 11
48 Factor of channel 12
4A Factor of channel 13
4C Factor of channel 14
4E Factor of channel 15
50 Factor of channel 16
52 Factor of channel 17
54 Factor of channel 18
One set of data shall be expressed by two registers, with the data format described as follows:
BIT31 BIT30 BIT29 BIT28 BIT27 BIT26 BIT25 BIT24 BIT23 …… BIT00
Description of sign bit: 0 shows that the item is a positive number, while 1 stands for negative
number;
10
Actual transmission value = (-1) symbol bit x data x 10 (- decimal digits)
For example: the host inquires contents of ten definite values beginning from 2400H from the slave.
Inquire Response
8bit L in register 3 00
8bit H in register 4 06
8bit L in register 4 40
8bit H in register 5 03
8bit L in register 5 00
8bit H in register 6 0A
8bit L in register 6 F0
8bit H in register 7 03
8bit L in register 7 00
8bit H in register 8 06
8bit L in register 8 40
8bit H in register 9 00
8bit L in register 9 00
8bit H in register 10 00
8bit L in register 10 13
11
CRC L --
CRC H --
Description: The definite values responded from the slave are respectively:
0 Temperature
12
22 Cell voltage of channel 16
One set of data shall be expressed by two registers, with the data format described as follows:
BIT31 BIT30 BIT29 BIT28 BIT27 BIT26 BIT25 BIT24 BIT23 …… BIT00
Description of sign bit: shows that the item is a positive number, while 1 stands for negative number;
For example: the host inquires contents of two registers beginning from 2800H from slave 1.
Inquire Response
CRC H -- CRC L --
CRC H --
The host inquires contents of two registers (measuring data of channel 00) beginning from 2800.
The measuring data of the response channel 00 of the slave is 5F2DH * 0.0001 = 2.4365.
13
00 Overvoltage value of single cell
One set of data shall be expressed by two registers, with the data format described as follows:
BIT31 BIT30 BIT29 BIT28 BIT27 BIT26 BIT25 BIT24 BIT23 …… BIT00
14
Sign Decimal digit Data
bit
Description of sign bit: 0 shows that the item is a positive number, while 1 stands for negative
number;
Inquire Response
8 bit L in register 1 00
8 bit H in register 2 0A
8 bit L in register 2 F0
CRC L -
CRC H -
Note: the host requests that the address of 2C00H and 2C01H of slave 1 shall be respectively
0300H and 0AF0H, i.e., definite value of overvoltage for single cell shall be 2.800 V. After the slave
receives and executes the command, the origin address and number of register which have been
revised shall be responded.
15