SUBMITTAL MWR-SH00N
Samsung Simplified Wired Indoor Unit Controller

Job Name Location


Purchaser Engineer
Submitted to Reference Approval Construction
Unit Designation Schedule #

)HDWXUHV
• Indoor unit operation ON/OFF

• Indoor unit operation mode, set temperature, and fan speed

• Error display

• Filter replacement alarm display and reset

• Single indoor unit control or multiple unit control (maximum 16


units)

• Partial controller button lock (operation mode button, temperature


setting buttons, fan speed button, timer button, and lock mode
button)

• Upper and lower temperature setting restriction Specifications


• Compatible with Samsung DVM S Systems
• Auto mode skip (AM****X****/AA, AM0***XMDCH/AA), and CAC systems
(AC0***N**CH/AA)
• Heat mode skip (cooling only)
• Can connect and control up to 16 indoor units on a single
• Restrict wireless controller signal (optional) system or across multiple systems
• Louver position setting (cassette and wall units) • 2 Conductor connection
• Single event timer function (ON/OFF control, 30 minutes ~ 18 • DC 12V power supplied by indoor unit
hours timer setting options)
• 1.5 W consumption
• System/indoor unit function and operation indication (defrost,
error, restricted controller, SPi status) • PLC (power line communication) is done on F3/F4 terminals.
• Quiet Mode setting (for supported units) • MWR-SH00N has screw terminals for all wiring connections,
wire is not included
• Service mode for connected indoor unit operation monitoring,
addressing, and setup • 16 AWG X 2 shielded cable is necessary for proper operation
• Can be used to specify "Mode Master" while connected to a single • Maximum wire length: 328' from MWR-SH00N to farthest
indoor unit when used with heat pump systems. indoor unit.





Samsung HVAC maintains a policy of ongoing development,specifications are subject to change without notice.

www.SamsungHVAC.com
QS-DVMS-092016A 888-699-6067
Page 2 of 2
SUBMITTAL MWR-SH00N
Samsung Simplified Wired Indoor Unit Controller
Common Controller Configurations/Options

Individual control - 1 indoor unit with 1 wired control


F1/F2 (main system communication)

Outdoor Unit F3/F4 F3/F4 F3/F4 F3/F4 F3/F4

Wired Controller

Group control - up to 16 indoor units on 1 wired controller


F1/F2 (main system communication)

Outdoor Unit
F3/F4 F3/F4
F3/F4 F3/F4 F3/F4

Wired Controller Wired Controller

Group control - up to 16 indoor units on 1 wired controller on multiple refrigerant systems


F1/F2 (main system communication)

F1/F2 (main system communication)

Outdoor Unit

F3/F4 F3/F4 F3/F4

Wired Controller Outdoor Unit

Group control - control 1 or multiple indoor units with 2 wired controllers


F1/F2 (main system communication)

Outdoor Unit F3/F4 F3/F4 F3/F4 F3/F4


F3/F4 F3/F4

Wired Controller Wired Controller Wired Controller

Group control - up to 16 indoor units on multiple refrigerant systems with 2 wired controllers
F1/F2 (main system communication)

F1/F2 (main system communication)

Outdoor Unit F3/F4


F3/F4
F3/F4
F3/F4

Outdoor Unit

Wired Controller

Samsung HVAC maintains a policy of ongoing development,specifications are subject to change without notice.
The diagrams on this page are for reference only. Refer to installation manual for wiring and installation instructions. Other configurations may be possible.
www.SamsungHVAC.com