SHEET CATALOG CUSTOMER- 12.30kW DC, 8.70kW AC , 11.

39kW CEC AC RATING VICINITY MAP


INDEX NO. DESCRIPTION

T-1 SITE PLAN


20.0 kWh BATTERY STORAGE SYSTEM
T-2 SITE PLAN SITE PLAN LAYOUT
M-1 MOUNTING DETAIL
M-2 STRUCTURAL DETAIL
E-1 SINGLE LINE DIAGRAM
PL-1 WARNING PLACARDS
SS SPEC SHEET(S)

4)
SS SPEC SHEET(S)

4)
OF

OF
(4

OF 4)
(3
5P

NE 4)
(1 OF
5P
RY
SCOPE OF WORK

(2

L
TE

RY

5P
AT

TE

) PA
P
QB

TE Y
AT

5
AT E R

ON E
Y
QB

TI IC
)I

R
QB ATT

CA R V
(N

)I
GENERAL SYSTEM INFORMATION:

QB

LO SE
(N

)I

N
EW AI
)I
(N
SYSTEM SIZE:

(N ) M
BAT4BAT3

(N
BAT1BAT2

(E
MSP
12300W DC, 8700W AC , 11398W CEC AC RATING - PERMIT PLANS

(N
01/03/24 JR

(N SW

)A
)R IT

C
MODULES:

D
AP C
REV DESCRIPTION DATE BY

IS
ID H(

CO
(30)REC410AA PURE

SH XT

N
N
27'

U ER
E

EC N
TD I

T
O OR
INVERTER:

W )
A A A
(30)ENPHASE IQ8PLUS-72-2-US(240V) A A A A A A A
BRANCH DETAILS: B B B B B B B B B
C C B

RSDACD
3X10 ENPHASE BRANCH C C C C C C C C
STORAGE SYSTEM:
(4) ENPHASE IQBATTERY 5P X (5.0kWh)

RESIDENCE (N)PV MODULES ARRAY ON FLOOR

APPLICABLE CODES
· ELECTRIC CODE:CEC 2022
· FIRE CODE:CFC 2022 CUSTOMER INFORMATION
· BUILDING CODE:CBC 2022
· RESIDENTIAL CODE:CRC 2022
NAME: Customer

GENERAL NOTES
1.MODULES ARE LISTED UNDER UL 1703 AND
CONFORM TO THE STANDARDS. ADDRESS: 10395 Barnett Valley Rd,
2.INVERTERS ARE LISTED UNDER UL 1741 AND Sebastopol, CA 95472
CONFORM TO THE STANDARDS.
3.DRAWINGS ARE DIAGRAMMATIC, INDICATING
GENERAL ARRANGEMENT OF THE PV SYSTEM AND APN: 119-092-02
THE ACTUAL SITE CONDITION MIGHT VARY.
4.WORKING CLEARANCES AROUND THE NEW PV AHJ:CA-MARIN COUNTY
ELECTRICAL EQUIPMENT WILL BE MAINTAINED IN
ACCORDANCE WITH NEC 110.26.
5.ALL GROUND WIRING CONNECTED TO THE MAIN PJN: 2897
SERVICE GROUNDING IN MAIN SERVICE PANEL/
SERVICE EQUIPMENT.
6.ALL CONDUCTORS SHALL BE 600V, 75°C
STANDARD COPPER UNLESS OTHERWISE NOTED.
7.WHEN REQUIRED, A LADDER SHALL BE IN PLACE
STRING CONFIGURATION
FOR INSPECTION IN COMPLIANCE WITH OSHA
REGULATIONS. BRANCH DETAILS
8.THE SYSTEM WILL NOT BE INTERCONNECTED BY A 10 MODULES
THE CONTRACTOR UNTIL APPROVAL FROM THE
LOCAL JURISDICTION AND/OR THE UTILITY. B 10 MODULES
9.ROOF ACCESS POINT SHALL BE LOCATED IN SITE PLAN
AREAS THAT DO NOT REQUIRE THE PLACEMENT OF C 10 MODULES
GROUND LADDERS OVER OPENINGS SUCH AS
WINDOWS OR DOORS, AND LOCATED AT STRONG DESIGNER/CHECKED
TOTAL AREA OF ROOF (SQ.FT) - BY: JR /DR
POINTS OF BUILDING CONSTRUCTION WHERE THE PAPER SIZE:17" X 11"
ACCESS POINT DOES NOT CONFLICT WITH
TOTAL ARRAY AREA (SQ.FT) 589.828
OVERHEAD OBSTRUCTIONS SUCH AS TREES,
WIRES OR SIGNS. SCALE:AS NOTED REV:A
TOTAL AREA OF ARRAY COVERED
10.PV ARRAY COMBINER/JUNCTION BOX PROVIDES SCALE:Personal -
IN THE ROOF (%)
TRANSITION FROM ARRAY WIRING TO CONDUIT
WIRING
DATE: 02/01/2024 T-1
SITE PLAN LAYOUT AERIAL VIEW

4)

4)
OF

OF
(4

OF 4)
(3
5P

NE 4)
(1 OF
5P
Y
ER

5P (2

L
Y
TT

ER

RY 5P

) PA
A

T
QB

TE Y
AT

AT E R

ON E
TI VIC
QB
)I

QB ATT
(N

Barnett va
)I

CA R
QB

E
(N

LO S
ller RD
)I

N
EW AI
)I
(N

(N ) M

BAT4BAT3
(N
BAT1BAT2

(E

4)
MSP

4)
OF

OF
(4

OF 4)
(3
5P

NE 4)
(1 OF
5P
RY

(2

L
TE

Y
ER

P
AT

) PA
T

P
QB

TE Y
AT

5
AT ER

ON E
RY

TI VIC
QB
)I

QB ATT
(N
-

)I
01/03/24 JR

CA R
PERMIT PLANS

QB

E
(N

LO S
)I

N
EW AI
DESCRIPTION

)I
(N
REV DATE BY

(N ) M
BAT4BAT3

(N
BAT1BAT2

(E
MSP

(N
(N SW

)A
)R I

C
D
AP TC

IS
ID H(

CO
SH XT

N
N
U ER
E

EC N
TD I

T
O OR
W )
A A A A A A A A A A
B B B B B B B B B
C C B
C

RSDACD
C C C C C C C

RESIDENCE (N)PV MODULES ARRAY ON FLOOR

CUSTOMER INFORMATION
NAME: Customer

ADDRESS: 10395 Barnett Valley Rd,


Sebastopol, CA 95472

APN: 119-092-02

AHJ:CA-MARIN COUNTY

PJN: 2897

(N
(N SW

)A
)R IT

C
D
AP C

IS
ID H(

CO
SH XT

N
N
U ER
E

EC N
TD I

T
O OR
W )
A A A A A A A A A A
B B B B B B B B B
C C B

RSDACD
C C C C C C C C

SITE PLAN 2
(N)PV MODULES ARRAY ON FLOOR
DESIGNER/CHECKED
BY: JR /DR PAPER SIZE:17" X 11"

SCALE:1/90" = 1'-0"
SCALE:AS NOTED REV:A

DATE:01/03/24 T-2
INSTALLATION NOTES SITE INFORMATION - WIND SPEED: 92 MPH AND SNOW LOAD: 0 PSF
1.STRUCTURAL ROOF MEMBER LOCATIONS ARE MAX
SR. NO. OF ARRAY AREA ROOF FRAME FRAME MAX RAIL OVER
ESTIMATED AND SHOULD BE LOCATED AND VERIFIED BY AZIMUTH PITCH ROOF TYPE ATTACHMENT FRAME TYPE UNSUPPORTED
NO MODULES (SQ. FT.) EXPOSURE SIZE SPACING SPAN HANG
THE CONTRACTOR WHEN LAG BOLT PENETRATION OR SPAN
MECHANICAL ATTACHMENT TO THE STRUCTURE IS
REQUIRED. METAL ROOF GREEN
2.ROOFTOP PENETRATIONS FOR SOLAR RACKING WILL MP-01 136° 18° 30 589.828 METAL RAFTERS 2X6 3'-0" 3'-0" 2'-0" 6'-0"
SCREW HOUSE
BE COMPLETED AND SEALED WITH APPROVED SEALANT
PER CODE BY A LICENSED CONTRACTOR.
3.LAGS BOLTS MUST HAVE A MINIMUM 2.5" THREAD
EMBEDMENT INTO THE STRUCTURAL MEMBER.
4.ALL PV RACKING ATTACHMENTS SHALL BE STAGGERED
BY ROW BETWEEN THE ROOF FRAMING MEMBERS AS
NECESSARY.
5.ROOF MOUNTED STANDARD RAIL REQUIRES ONE
THERMAL EXPANSION GAP FOR EVERY RUN OF RAIL
GREATER THAN 40'.
6.ALL CONDUCTORS AND CONDUITS ON THE ROOF
SHALL BE MINIMUM 7/8" ABOVE THE ROOF SURFACE
(INCLUDING CABLES UNDERNEATH MODULES AND
RACKING).
7.THE PV INSTALLATION SHALL NOT OBSTRUCT ANY
PLUMBING, MECHANICAL OR BUILDING ROOF VENTS.
ROOF ACCESS PATHWAYS AND SETBACKS:
1204.2.1 SOLAR PHOTOVOLTAIC SYSTEMS FOR GROUP - PERMIT PLANS 01/03/24 JR
R-3 BUILDINGS.SOLAR PHOTOVOLTAIC SYSTEMS FOR REV DESCRIPTION DATE BY
GROUP R-3 BUILDINGS SHALL COMPLY WITH SECTIONS
1204.2.1.1 THROUGH 1204.2.1.3.
EXCEPTIONS:
1.THESE REQUIREMENTS SHALL NOT APPLY TO
STRUCTURES DESIGNED AND CONSTRUCTED IN
ACCORDANCE WITH THE CALIFORNIA RESIDENTIAL
CODE.
2.THESE REQUIREMENTS SHALL NOT APPLY TO ROOFS
WITH SLOPES OF 2 UNITS VERTICAL IN 12 UNITS
HORIZONTAL OR LESS. 60'-0"
1204.2.1.1 PATHWAYS TO RIDGE. NOT FEWER THAN 3'-0" 6'-0"
TWO 36-INCH-WIDE (914 MM) PATHWAYS ON SEPARATE
ROOF PLANES,FROM LOWEST ROOF EDGE TO RIDGE,
SHALL BE PROVIDED ON ALL BUILDINGS. NOT FEWER
CUSTOMER INFORMATION
THAN ONE PATHWAY SHALL BE PROVIDED ON THE
STREET OR DRIVEWAY SIDE OF THE ROOF. FOR EACH
ROOF PLANE WITH A PHOTOVOLTAIC ARRAY, NOT
A A A A A A A A A A NAME:
FEWER THAN ONE 36-INCH-WIDE (914 MM) PATHWAY
FROM LOWEST ROOF EDGE TO RIDGE SHALL BE
PROVIDED ON THE SAME ROOF PLANE AS THE
PHOTOVOLTAIC ARRAY, ON AN ADJACENT ROOF PLANE
B B B B B B B B B B
ADDRESS:
OR STRADDLING THE SAME AND ADJACENT ROOF
PLANES
1204.2.1.2 SETBACKS AT RIDGE. FOR PHOTOVOLTAIC
ARRAYS OCCUPYING 33 PERCENT OR LESS OF THE PLAN
C C C C C C C C C C
VIEW TOTAL ROOF AREA, A SETBACK OF NOT LESS APN: 119-092-02
THAN 18 INCHES (457 MM)WIDE IS REQUIRED ON BOTH
SIDES OF A HORIZONTAL RIDGE. FOR PHOTOVOLTAIC AHJ:CA-MARIN COUNTY
ARRAYS OCCUPYING MORE THAN 33 PERCENT OF THE
PLAN VIEW TOTAL ROOF AREA, A SETBACK OF NOT LESS 2X6 RAFTERS@ 3'-0" SPACING
THAN 36 INCHES (457 MM) WIDE IS REQUIRED ON BOTH PJN: 2897
SIDES OF A HORIZONTAL RIDGE.
1204.2.2 EMERGENCY ESCAPE AND RESCUE ALUMINIUM RAILS
OPENINGS. PANELS AND MODULES INSTALLED ON
GROUP R-3 BUILDINGS SHALL NOT BE PLACED ON THE
ARRAY MP-01
PORTION OF A ROOF THAT IS BELOW AN EMERGENCY
ESCAPE AND RESCUE OPENING. A PATHWAY OF NOT
LESS THAN 36 INCHES (914 MM) WIDE SHALL BE
PROVIDED TO THE EMERGENCY ESCAPE AND RESCUE
OPENING
1204.2.1.3 ALTERNATIVE SETBACKS AT RIDGE.
WHERE AN AUTOMATIC SPRINKLER SYSTEM IS
INSTALLED WITHIN THE DWELLING IN ACCORDANCE MOUNTING DETAIL
WITH SECTION 903.3.1.3, SETBACKS AT THE RIDGE
SHALL CONFORM TO ONE OF THE FOLLOWING:
1.FOR PHOTOVOLTAIC ARRAYS OCCUPYING 66 PERCENT DESIGNER/CHECKED
OR LESS OF THE PLAN VIEW TOTAL ROOF AREA, A BY: JR /DR PAPER SIZE:17" X 11"
SETBACK OF NOT LESS THAN 18 INCHES (457 MM) WIDE
IS REQUIRED ON BOTH SIDES OF A HORIZONTAL RIDGE.
2.FOR PHOTOVOLTAIC ARRAYS OCCUPYING MORE THAN SCALE:AS NOTED REV: A
66 PERCENT OF THE PLAN VIEW TOTAL ROOF AREA, A SCALE:Personal
SETBACK OF NOT LESS THAN 36 INCHES (914 MM) WIDE
IS REQUIRED ON BOTH SIDES OF A HORIZONTAL RIDGE DATE: 01/03/24 M-1
DEAD LOAD CALCULATIONS 1 FLASHVUE
MODULES DATA
TOTAL SOLAR MODULE REC SOLAR - REC410A PURE
BOM QUANTITY LBS/UNIT
WEIGHT (LBS)
6" MAX MODULE DIMS 71.70"x40.00"x1.20"
MODULES 30 45 1350.00
RAIL
MID-CLAMP 38 0.050 1.90
END-CLAMP 8 0.050 0.40
RAIL LENGTH 124 0.680 84.32 FLASHING
SPLICE BAR 6 0.360 2.16
FLASHVUE 22 1.89 41.58
MICRO-INVERTER 30 2.38 71.40
TOTAL WEIGHT OF THE SYSTEM (LBS) 1551.76
TOTAL ARRAY AREA ON THE ROOF (SQ. FT.) 589.828
WEIGHT PER SQ. FT.(LBS) 2.63
WEIGHT PER PENETRATION (LBS) 70.53
STAINLESS STEEL 5/16" LAG SCREW
BOLT 2.5" EMBEDMENT
PILOT HOLE REQUIRED
- PERMIT PLANS 01/03/24 JR
REV DESCRIPTION DATE BY

SCALE:NTS

MID-CLAMP AND END-CLAMP ANATOMY ROOF FRAMING DETAILS


5/16" X 3.5" LAG SCREW
COMPOSITION
1 BOLT PER PENETRATION
END CLAMP SHINGLE ROOF
MODULE MID CLAMP
MODULE MODULE
2X6 RAFTERS
@3'-0" SPACING CUSTOMER INFORMATION
NAME:

ADDRESS:
LOAD BEARING WALL
SCALE:NTS

GROUNDING DETAILS APN: 119-092-02

AHJ:CA-MARIN COUNTY
MODULE TO MODULE & MODULE TO RAIL GROUNDING LUG RAIL TO RAIL
PJN: 2897

MID CLAMP XR10 RAIL


ASSEMBLY BONDING SPRING

MODULE
FRAME

STRUCTURAL DETAIL
RAIL

DESIGNER/CHECKED
XR10 INTERNAL SPLICE
BY: JR /DR PAPER SIZE:17" X 11"

GROUNDING MID-CLAMP T-BOLT


SCALE: NTS SCALE: NTS
SCALE:AS NOTED REV: A

DATE: 01/03/24 M-2


SINGLE LINE DIAGRAM: DC SYSTEM SIZE - 10250W, AC SYSTEM SIZE - 7250W, CEC AC SYSTEM SIZE 9499W ELECTRICAL NOTES
1.CONDUCTORS EXPOSED TO SUNLIGHT
SHALL BE LISTED AS SUNLIGHT RESISTANT
PER CEC 310.0(D).
2.CONDUCTORS EXPOSED TO WET
EXISTING 120/240V 1PH 60HZ LOCATIONS SHALL BE SUITABLE FOR USE
METER#:PG&E IN WET LOCATIONS PER CEC 310.8(C).
1009820836 3.MAXIMUM DC/AC VOLTAGE DROP SHALL
UTILITY
GRID
M 6 (N)200A
DISTRIBUTION
BE NO MORE THAN 2%.
4.ALL CONDUCTORS SHALL BE IN CONDUIT
PANEL UNLESS OTHERWISE NOTED.
NOTE: EACH MICRO INVERTER IS RAPID SHUTDOWN COMPLIANT
5.BREAKER/FUSE SIZES CONFORMS TO CEC
(E)200A END FED
MAIN PANEL (N) ENPHASE IQ SYSTEM 240.6 CODE SECTION.
CONTROLLER 3 6.AC GROUNDING ELECTRODE CONDUCTOR
SC200D111C240US01 (N) ENPHASE
(N) (30) REC 410AA PURE 410W ,MODULES WITH SIZED PER NEC 250.66.
(N) (30) ENPHASE IQ8PLUS-72-2-US 7.AMBIENT TEMPERATURE CORRECTION
IQ ENVOY
(N)200A MAIN
BREAKER

CONTROLLER
SMART SWITCH FACTOR IS BASED ON CEC 690.31(C).
(3) BRANCH OF (10) MICRO-INVERTERS 8.AMBIENT TEMPERATURE ADJUSTMENT
200A (N) ENPHASE IQ
6 COMBINER 5 FACTOR IS BASED ON CEC 310.15(B)(2)(C).
15A
DC CONDUCTORS 9.MAX. SYSTEM VOLTAGE CORRECTION IS
40A (N)JUNCTION PER CEC 690.7.
40A BOX OR EQUI.
(E) GROUND
ELECTRODE
15A
3
20A
2 1 10.CONDUCTORS ARE SIZED PER WIRE
20A
50A 20A
AC CONDUCTORS AMPACITY TABLE CEC 310.16.
5
80A AC COMBINER
X-IQ-AM1-240-5
120/240 NEMA 3R INSTALL
(3)20A PV 2P BREAKERS
7 (N)JUNCTION
BOX OR EQUI.

40A

40A
(N) RAPID BATTERY BATTERY BATTERY BATTERY
SHUTDOWN 5 KWH 5 KWH 5 KWH 5 KWH
OFF

SWITCH 4 4

(N) ENPHASE ENERGY (N) ENPHASE ENERGY (N) ENPHASE ENERGY (N) ENPHASE ENERGY
IQBATTERY-5P IQBATTERY-5P IQBATTERY-5P IQBATTERY-5P
3.84 kVA 3.84 kVA 3.84 kVA 3.84 kVA
CUSTOMER INFORMATION
NAME:

CONDUIT SCHEDULE
NOTE:
TAG ID CONDUIT SIZE CONDUCTOR NEUTRAL GROUND MAIN PANEL RATING:200A, MAIN BREAKER RATING:200A ADDRESS:
(2) 10AWG CABLE PER BRANCH WHOLE HOME 100% RULE: ALLOWABLE BACKFEED: 200A
1 NONE NONE (1) 6AWG BARE COPPER
CIRCUIT
OCPD CALCULATIONS:
2 3/4"EMT OR EQUIV (6) 10AWG THHN/THWN-2 NONE (1) 6AWG BARE COPPER INVERTER OVERCURRENT PROTECTION=
3 1"EMT OR EQUIV (2) 6AWG THHN/THWN-2 (1) 6AWG THHN/THWN-2 (1) 6AWG BARE COPPER INVERTER O/P I x #OF INVERTERS x CONTINUOUS LOAD(1.25) APN: 119-092-02
4 1/2"EMT OR EQUIV (2) 8AWG THHN/THWN-2 NONE (1) 10AWG THHN/THWN-2 =(1.21x30)x1.25 = 45.37A => PV BREAKER 50A OCPD = 50A
ALLOWABLE OCPD 50A => 50A BREAKER AHJ:CA-MARIN COUNTY
5 3/4"EMT OR EQUIV (2) 4AWG THHN/THWN-2 NONE (1) 8AWG THHN/THWN-2
BATTERY O/P I x # OF BATT x CONTINUOUS LOAD(1.25)
6 2" EMT OR EQUIV (2) 2/0AWG THHN/THWN-2 (1) 2/0AWG THHN/THWN-2 (1) 6AWG THHN/THWN-2
=(16x4)x1.25 = 80A => BATTERY BREAKER 80A OCPD = 80A PJN: 2897
7 3/4"EMT OR EQUIV (2) 12AWG THHN/THWN-2 NONE NONE ALLOWABLE OCPD 80A => 80A BREAKER
THE DESIGNED INTERCONNECTION MEETS THE 705.12(A) THROUGH (E) REQUIREMENTS.

ELECTRICAL CALCULATIONS
DC WIRE SIZING CALCULATIONS BASED OF FOLLOWING EQUATIONS>> AC WIRE CALCULATIONS:- MATERIAL:COPPER & TEMPERATURE RATING:90°C
· REQUIRED CONDUCTOR AMPACITY: 125% PER 690.8(A)(1) X Isc(A) X #OF
PARALLEL STRINGS = MAX CURRENT PER 690.8(A)(1) X 125% PER TAG
REQUIRED CONDUCTOR AMPACITY CORRECTED AMPACITY CALCULATION DERATED CONDUCTOR AMPACITY CHECK
690.8(B)(2)(a)=MAX CURRENT PER 690.8(B)(2)(a) ID
· CORRECTED AMPACITY CALCULATIONS:AMPACITY X TEMPERATURE DERATE 1 1.21 X 10 = 12.10 X 1.25 = 15.13A 40 X 0.87 X 1 = 34.80A 15.13A < 34.80A
FACTOR X CONDUIT FILL DERATE = DERATED CONDUCTOR AMPACITY
· DERATED CONDUCTOR AMPACITY CHECK: MAX CURRENT PER 690.8(B)(2)(2) < 2 12.1 X 1 = 12.10 X 1.25 = 15.13A 40 X 0.87 X 0.8 = 27.84A 15.13A < 27.84A SINGLE LINE DIAGRAM
DERATED CONDUCTOR AMPACITY
AC WIRE SIZING CALCULATIONS BASED OF FOLLOWING EQUATIONS >>
3 1.21 X 30 = 36.30 X 1.25 = 45.37A 75 X 0.87 X 1 = 65.25A 45.37A < 65.25A
DESIGNER/CHECKED
· REQUIRED CONDUCTOR AMPACITY: INVERTER OUTPUT CURRENT X #OF BY: JR /DR PAPER SIZE:17" X 11"
4 16.0 X 2 = 32.00 X 1.25 = 40.00A 55 X 0.87 X 1 = 47.85A 40.00A < 47.85A
INVERTERSXMAX CURRENT PER 690.8(A)(3)X125% PER 690.8(B)(2)(A)
· CORRECTED AMPACITY CALCULATIONS:AMPACITY X TEMPERATURE DERATE
FACTOR X CONDUIT FILL DERATE = DERATED CONDUCTOR AMPACITY 5 16.0 X 4 = 64.00 X 1.25 = 80.00A 95 X 0.87 X 1 = 82.65A 80.00A < 82.65A
SCALE:AS NOTED REV: A
· DERATED CONDUCTOR AMPACITY CHECK: MAX CURRENT PER 690.8(B)(2)(2) <
DERATED CONDUCTOR AMPACITY
DATE: 01/03/24 E-1
WARNING PLACARD

! WARNING PHOTOVOLTAIC SYSTEM AC DISCONNECT SWITCH


ELECTRIC SHOCK HAZARD RATED AC OPERATING CURRENT 35.09 AMPS AC
AC NOMINAL OPERATING VOLTAGE 240 VAC
TERMINALS ON BOTH LINE AND LOAD SIDES
MAY BE ENERGIZED IN THE OPEN POSITION
LABEL LOCATION
AC DISCONNECT , POINT OF INTERCONNECTION
DC VOLTAGE IS ALWAYS PRESENT WHEN
SOLAR MODULES ARE EXPOSED TO
[PER CODE: CEC 690.54]
Barnett va
SUNLIGHT ller RD
LABEL LOCATION WARNING
AC DISCONNECT,POINT OF INTERCONNECTION INVERTER OUTPUT
[PER CODE: CEC 690.17(E)] CONNECTION
DO NOT RELOCATE THIS
OVER-CURRENT DEVICE BATTERIES
WARNING-ELECTRIC SHOCK HAZARD LABEL LOCATION BAT4BAT3

BAT1BAT2
NO USER SERVICEABLE PARTS INSIDE POINT OF INTERCONNECTION (N
)A

(N SW
C
CONTACT AUTHORIZED SERVICE (PER CODE: CEC 705.12(D)(7)) D

)R I
IS

AP TC
CO

ID H(
N
[ Not Required if Panel board is rated not less than sum
PROVIDER FOR ASSISTANCE

SH XT
N
EC

U ER
E

TD I
T
of ampere ratings of all overcurrent devices supplying it]

O OR
W )
N
LABEL LOCATION A A A A A A A A A
- PERMIT PLANS 01/03/24 JR
B A
INVERTER, JUNCTION BOXES(ROOF), B B B B B DESCRIPTION
SOLAR DISCONNECT C C
B B B B REV DATE BY

RSDACD
AC DISCONNECT C C C C C C C C
[PER CODE: CEC 690.13.G.3 & CEC 690.13.G.4]
LABEL LOCATION
DISCONNECT, POINT OF INTERCONNECTION
WARNING:PHOTOVOLTAIC [PER CODE: CEC690.13(B)] RESIDENCE
POWER SOURCE (N)PV MODULES
LABEL LOCATION CAUTION: SOLAR ELECTRIC ARRAY ON FLOOR
CONDUIT, COMBINER BOX
[PER CODE: CEC690.31(G)(3)(4) & CEC 690.13(G)(4)]
SYSTEM CONNECTED
LABEL LOCATION
WEATHER RESISTANT MATERIAL, DURABLE
ADHESDIVE, UL969 AS STANDARD TO WEATHER
DUAL POWER SOURCE SECOND! WARNING RATING (UL LISTING OF MARKINGS NOT
SOURCE IS PHOTOVOLTAIC REQUIRED), MIN 3/8" LETTER HEIGHT ARIAL OR
CUSTOMER INFORMATION
SYSTEM SIMILAR FONT NON-BOLD,PLACED WITHIN
THE MAIN SERVICE DISCONNECT,PLACED ON THE NAME: Customer
LABEL LOCATION OUTSIDE OF THE COVER WHEN DISCONNECT IS
POINT OF INTERCONNECTION OPERATED WITH THE SERVICE PANEL CLOSED.
[PER CODE: CEC705.12(D)(4)] (PER CODE: CEC690.15 ,690.13(B))
ADDRESS: 10395 Barnett Valley Rd,
RAPID SHUTDOWN Sebastopol, CA 95472
SWITCH FOR SOLAR PV SOLAR PV SYSTEM EQUIPPED
SYSTEM WITH RAPID SHUTDOWN CUSTOMER INFORMATION
TURN RAPID SHUTDOWN APN: 119-092-02
LABEL LOCATION
SWITCH TO THE NAME: Customer
INVERTER AHJ:CA-MARIN COUNTY
[PER CODE: CEC 690.56(C)(3)] "OFF" POSITION TO SOLAR ELECTRIC SYSTEM UTILIZES
PV PANELS
SHUT DOWN PV SYSTEM MICRO-INVERTERS
AND REDUCE LOCATED UNDER 10395 Barnett Valley Rd,
SHOCK HAZARD EACH SOLAR MODULE PJN: 2897
ADDRESS: Sebastopol, CA 95472
IN THE ARRAY
LABEL LOCATION
AC DISCONNECT , DC DISCONNECT,POINT OF ALL PLACARDS SHALL BE OF WEATHER PROOF CONSTRUCTION, BACKGROUND ON ALL PLACARDS
INTERCONNECTION SHALL BE RED WITH WHITE LETTERING U.O.N.
(PER CODE: CEC690.56(C)(1)(A)) PLACARD SHALL BE MOUNTED DIRECTLY ON THE EXISTING UTILITY ELECTRICAL SERVICE.
FASTENERS APPROVED BY THE LOCAL JURISDICTION

WARNING PLACARDS

DESIGNER/CHECKED
BY: JR /DR PAPER SIZE:17" X 11"

SCALE:AS NOTED REV:A

DATE:01/03/24 PL-1