CONCRETE MIX

DESIGN
Class 30/37Mpa

Société Al Nasri Materials Testing


Rev.01
Laboratory (SANLAB)
Société Al Nasri Materials Testing Laboratory
Douda, Zone Boulaos
Republic of Djibouti
Tel. +253 77241899/776 69177
Email: [email protected]

Re: Concrete Mixture Design Submittal for 31MPa Footings, Columns and Walls, Beams and
elevated slabs and slabs on ground.

Dear Sir:

This letter outlines the information developed and compiled for the Portland cement concrete
mixture design intended to be used for the project which require a minimum compressive strength
of 37 Mpa for Footings, Columns and Walls, Beams and elevated slabs and slab on ground.

The concrete mixture is expected to be placed using a concrete pump and consolidated using
internal vibrators. This is non-air entrained concrete mixture with the following criteria:
1. Minimum Compressive Strength (f’c): 37 MPa at 28 days.
2. Maximum Water-Cementitious Materials Ratio: 0.60.
3. Minimum Cementitious Materials Content: 350 kg/m3.
4. Slump Limit: maximum 200 mm

Closing

We appreciate the opportunity and look forward to continued involvement with this project.

Very Respectfully

MUHIRWA Raymond, Civil Engineering


Laboratory Manager
Société Al Nasri

Attachments

• illustration the mix proportioning for a concrete of C 30/37


• Aggregate data and information
• Admixtures product data sheet
• Fly Ash data and information
• Cement data and information
• Calibration certificate for compression test machine
• Calibration certificate for concrete batching plant
• Summary of compressive strength test report for a previous project: this formulation was used.
Société Al Nasri Materials Testing Laboratory (SANLAB)
Camp Douda, Djibouti
Republic of Djibouti
Tel. +253 771 851 54/776 691 77
Email: [email protected]

Project: Travaux de réhabilitation de la RN 1- Doudoubalala-Dikhil


CONCRETE DESIGN-MIX CLASS C 30/37
(BS EN 206)
Dated : 10/05/2024
A-0 An example illustrating the mix proportioning for a concrete of C 30/37 RCC Class is given in A-1 to A14
A -1 STIPULATIONS FOR PROPORTIONING TRIAL MIX #14
a) Class designation C 30/37 Table 12
b) Exposure condition XC2 Table F.1
c) Maximum size of aggregate 25 mm Tender documents P-III.02
d) Minimum cement content 350 kg/cum Tender documents P-III.02
e) Maximum water - cement ratio 0,60 Table F.1
f) Workability (Slump) 100 -200 mm (S3) As per Table 3 (At Pouring Place)
g) Type of Cement CEM- V, Class 42.5R
h) Method of concrete placing Chute/Pump
i) Degree of supervision Very good
j) Type of aggregate Crushed angular aggregate
k) Chemical admixture type Water Reeducing and Retarding supersticizing,

A -2 SOURCE OF MATERIALS
a) Coarse Aggregate = AL NASRI, Douda Djibouti
b) Fine aggregate (Natural Sand) = Loyada, Djibouti
c) Crushed Sand = AL NASRI, Douda Djibouti
d) Cement = NAEL- Djibouti
e) Fly Ash = ASHTECH INDIA
e) Admixture = Sika UAE LLC
e) Water = Bore Well @ Batching plant, Douda Djibouti

A -3 TEST DATA FOR MATERIALS


a) Cement used CEM- V, Class 42.5R
b) Specific gravity of cement 3,08
c) Chemical admixture Sikament 3800
d) Specific Gravity of Admixture 1,070
e) Coarse & Fine Aggregates Specific gravity Water absorption Free (surface moisture)
1) 15/25 mm Aggregate (25mm - 15mm) 2,768 0,26 % 0 %
2) 5/15 mm aggregate (15mm - 5mm) 2,755 0,32 % 0 %
3) Crushed Sand CS (0 - 5mm) 2,658 0,98 % 0 %
3) Natural River Sand NS (0 - 2mm) 2,556 1,16 % 0 %
f) Sieve analysis
1)15/25 mm aggregate, 5/15 mm aggregate , Natural sand &Crushed Sand - (Combined Gradation)

COMBINED AGGREGATE GRADATION

Gradation Date: 08.04.2024

15/25mm Aggregate 5/15mm Aggregate Crushed Sand ( CS ) Natural Sand ( NS) Permissible Limits for All In
Sieve Size Mix
Aggregate Table:2&5, EN 12620,
Passage GA90
Passing Ratio Qntty. Passing Ratio Qntty. Passing Ratio Qntty. Passing Ratio Qntty.

(mm) (%) 28,0% (%) (%) 32,0% (%) (%) 25,0% (%) (%) 15,0% (%) 100,00% Lower Upper

37,5 100 28,0% 28,0 100 32,0% 32,0 100 25,0% 25,0 100 15,0% 15,0 100,0 100 100

31,5 100 28,0% 28,0 100 32,0% 32,0 100 25,0% 25,0 100 15,0% 15,0 100,0 98 100

20,0 93,3 28,0% 26,1 100 32,0% 32,0 100 25,0% 25,0 100 15,0% 15,0 98,1 90 99

10,0 4,7 28,0% 1,3 76,0 32,0% 32,0 100 25,0% 25,0 100 15,0% 15,0 73,3 50 90

2,0 0,5 28,0% 0,1 4,2 32,0% 24,3 57,9 25,0% 14,5 95,2 15,0% 14,3 39,0 20 60

1,4
120
uppr limit

Lower limit
100
%passing

80
% of passing

60

40

20

0
1,0 10,0 100,0
Sieve size in mm

Page 1 of 5
CONCRETE DESIGN-MIX CLASS C 30/37
(BS EN 206)
Dated : 10/05/2024

A- 4 TARGET STRENGTH FOR MIX PROPORTIONING


Characteristic Strength of Concrete (Cube) = 37 N/mm2
Standard Deviation (sd) = 4,5 N/mm2
Therefore, Target strength (fck+1.96 x sd)=37+ (1.96 x 4.5) = 45,8 N/mm2 EN 206 Annex H- H.2

A -5 SELECTION OF WATER CEMENT RATIO


Maximum Water cement Ratio as per BS EN 206 Table F.1 = 0,60
Based on experience, Adopt water - cement ratio as = 0,35
0,35< 0,6 Hence O.K.
A-6 SELECTION OF WATER CONTENT
From Table 20.47 ( DOE Method) & 100 - 180mm Slump = 225,00 Kgs.
Estimated water content = 225,00 Kgs.
Based on Trial with superplasticizer water content reduction of 31 percent can be expected. Hence, the reduced water
content =225 x69% = 155,25 Kgs. say 155

A-7 CALCULATION OF CEMENT CONTENT


Adopted Water cement ratio = 0,35
Cementitious content 443,6 kg/cum kg/cum Say 450,0 Kgs/Cum
Cementitious composition Cement, % 80,0 Fly ash,% 20,0
360 Kgs 90 Kgs
As Per Tender documents P-III.02, minimum cement content = 350 kg/cum
360> 350 Hence O.K.
Therefore, Adopted Cementitious Content = 450 Kgs/Cum
And Water Content = 157,5 Kgs. say 156

A-8 PROPORTION OF VOLUME OF COARSE AGGREGATE AND FINE AGGREGATE CONTENT


Volume of Coarse Aggregate (In reference Combined Aggregate Gradation, All In Aggregate) = 60,0 %

Volume of Fine Aggregate = 100-60 = 40,0 %


(Conforming to All In Aggregate Gradation, PD 6682-1/BS EN 12620)
Hence, Adopting the Volume of Coarse Aggt. = 60%
Volume of Fine Aggregate = 100-60 = 40,0 %

A-9 MIX CALCULATIONS


The mix calculations per unit volume of concrete shall be as follows:
a) Volume of Concrete 1,0 Cum
b) Volume of Cement Mass of Cement 1
x
Specific Gravity of Cement 1000
= (360/3.080x1/1000)
= 0,1143 Cum
c) Volume of Fly Ash Mass of Cement
Specific Gravity of Cement
= (U90/1,08x1/1000)
= 0,0286 Cum
d) Volume of water Mass of water 1
x
Specific Gravity of Cement 1000
= (156/1x1/1000)
= 0,156 cum
e) Volume of Chemical Admixture
@ 1,2 percent = 5,40 Kgs
by mass of cementitious material)
Mass of Chemical Admixture 1
x
Specific Gravity of admixture 1000
= (5,4/1,07x1/1000)
= 0,005 cum
f) Volume of all in aggregate
Aggt = [a - (b+c+d) ]
= 1 - (0,1143 + 0,156 + 0,005)
= 0,6961 cum
g) Mass of 15/25 mm aggregate
=
e x volume of Coarse aggregate x specific gravity of Coarse aggregate x 1000
= (0,6961 x 0,28 x 2,768 x 1000)
= 540 kgs
h) Mass of 5/15 mm aggregate
=
e x volume of Coarse aggregate x specific gravity of Coarse aggregate x 1000
= (0,6961 x 0,32 x 2,755 x 1000)
= 614 kgs
i) Mass of Fine aggregate NS
=
e x volume of Fine aggregate x specific gravity of Fine aggregate x 1000
= (0,6961 x 0,15 x 2,556 x 1000)
= 267 kgs
j) Mass of Fine aggregate CS
=
e x volume of Fine aggregate x specific gravity of Fine aggregate x 1000
= (0,6961 x 0,15 x 2,658 x 1000)
= 463 kgs

Page 2 of 5
CONCRETE DESIGN-MIX CLASS C 30/37
(BS EN 206)
Dated : 10/05/2024
A-10 MIX PROPORTIONS FOR TRIAL NUMBER #14

In case of dry condition of aggregate, the excess amount of water required will be

15/25 mm = 539,5 x 0,26/100 = 1,40 Kgs.


5/15 mm = 613,7 x 0,32/100 = 1,96 Kgs.
N .Sand = 266,9 x 1,16/100 = 3,10 Kgs.
C.Sand = 462,6 x 0,98/100 = 4,53 Kgs.
Water cement ratio; w/c = 0,35

Ingredients SSD Weight in Kg/cum DRY Weight in Kg/cum

Cement = 360 360

Fly Ash = 90 90

Water = 156 162

Coarse aggregate (15/25 mm) = 540 538

Coarse aggregate (5/15mm) = 614 612

Fine aggregate (Natural sand) = 267 264

Fine aggregate (Crushed sand) = 463 458

Admixture = 5,40 5,40

Density 2494 kg/cum 2490 kg/cum

Note: - Aggregates should be used in saturated surface dry condition. If otherwise, when computing the requirement of mixing water, allowance shall be
made for the free (surface) moisture contributed by the fine and coarse aggregates. On the other hand, if the aggregates are dry, the amount of mixing water
should be increased by an amount equal to the moisture likely to be absorbed by the aggregates. necessary adjustments are also required to be made in mass
of aggregates. The surface water and percent water absorption of aggregates shall be determined to calculated requirement of mixing water.

A-11 The slump shall be measured and the water content and dosage of admixture shall be adjusted for achieving the required slump based on trial, if required.
The mix proportions shall be reworked for the actual water content and checked for durability requirements.

M Raymond

Laboratory Manager
Societe Al Nasri

Page 3 of 5
CONCRETE DESIGN-MIX CLASS C 30/37
(BS EN 206)
Dated : 10/05/2024

A-12
TRIAL MIX OBSERVATION SHEET

Date of Casting : ######## Ref No.: : TRIAL MIX #14

Class of Concrete : C 30/37 Site: : AL Nasri Concrete Batching Plant -Douda

Cement Class/Brand : CEM- V, Class 42.5R - NAEL DJIBOUTI Location : Camp-Douda

Quantities Per Cubic meter of Concrete

Admixture @ 1,2 % of
SSD Condition (wt in kg)
Water Cement
Cement weightt in kg Fly Ash weightt in kg weightt Remarks
in kg
15/25 mm 5/15 mm Natural Sand Crushed Sand weight in kg

360 90 540 614 267 463 156 5,40

Batch Quantity for 9 Cubes = 0,03038 cum

Corrected
SSD Water Moisture Moisture
Batch Remarks
Condition Absorption Content Adjustment
Quantity
Mix Ingredients

(Kg) (%) (%) (%) (Kg) (Kg)

Cement 10,94 - - - - 10,94

Fly Ash 2,73 2,73

15/25 mm 16,39 0,3 0,0 0,3 0,0 16,35

5/15 mm 18,64 0,3 0,0 0,3 -0,1 18,58

Natural Sand 8,11 1,2 6,4 -5,2 0,4 8,53

Crushed Sand 14,05 1,0 4,2 -3,2 0,5 14,50

Water 4,74 - - - -0,3 4,42

Admixture 0,164 - - - - 0,16

Slump in mm

Ambient Temperature 29,8 Initial 230

30 Minutes 190

60 Minutes 160
Concrete Temperature 31,1
90 Minutes 140

Concrete Temperature 32,3 120 Minutes 120

Particulars of the Specimen casted: 9 cubes casted 150x150x150 mm mould

Remarks :

M Raymond

Laboratory Manager

Societe Al Nasri
Page 4 of 5
Société Al Nasri Materials Testing Laboratory (SANLAB)
Camp Douda, Djibouti
Republic of Djibouti
Tel. +253 771 851 54/776 691 77
Email: [email protected]
CONCRETE DESIGN-MIX CLASS C 30/37
(BS EN 206)
Dated : 10/05/2024
A-13 Test Results of Trial batches -Compressive Strength Results

Weight of Density compressive


Date of Date Of Age in Max. Load Avg. strength
cube in strength Remarks
Casting Testing Days Failure (KN) in (Mpa)
(gms) (Mpa)
(kg/m3)

8085 2,396 651,2 28,9

10-May-24 17 May 2024 7 days 8125 2,407 695,2 30,9 30,1

8090 2,397 688,1 30,6

8210 2,433 823,8 36,6

10-May-24 24-May-24 14days 8285 2,455 874,6 38,9 37,7

8245 2,443 844,9 37,6

8321 2,465 1060 47,1

10-May-24 07-Jun-24 28 days 8248 2,444 1052 46,8 46,5

8246 2,443 1025 45,6

Type of Fracture # : 7 DAYS 1 14 DAYS 2 28 DAYS 2

M Raymond
Laboratory Manager
Societe Al Nasri

Page 5 of 5
Société Al Nasri Materials Testing Laboratory (SANLAB)
Camp Douda, Djibouti
Republic of Djibouti
Tel. +253 771 851 54/776 691 77
Email: [email protected]

GRADATION OF COARSE AGGREGATE FOR CONCRETING


NF EN 12620-2002
Sample description Natural Sand Date of Sampling 07.04.2024
Locatiom loyada Date of Testing 09.04.2024
source Loyada Sample no 1
Sampled By Jointly Weight of sample 811,5

Individual Gradation
Requirement as
Cumm. %
Max.Size of Weight Cumm. Weight per NF EN
Sieve (mm) Weight % Passing
Aggrgate (mm) Retained (gm) Retained (gm) 12620-2002
Retained
(Table -2&4)
8 0 0 0 100 100
5,6 0 0 0 100 95-100
4,0 6,5 6,5 0,8 99,2 80-99
2,0 33,5 40 4,9 95,1 -
1,0 294,1 334,1 41,2 58,8 0-20
0/4mm
0,50 345,6 679,7 83,8 16,2
0,250 81,0 760,7 93,7 6,3 0-10
0,125 24,1 784,8 96,7 3,3
0,063 10,0 794,8 97,9 2,1 0-3
Pan

Fineness Modulus As per EN 12620-2002 Annex B Table B.2 -


3,2
∑{(>4)+(>2)+(>1)+(>0.500)+(>0.250)+(>0.125)}

Comment :-

AL NASRI Representative
Signature:
Date: 08,04,2024
QF/5267/QC/13/00

ociété Al Nasri Materials Testing Laboratory (SANLAB)


Camp Douda, Djibouti
Republic of Djibouti
Tel. +253 771 851 54/776 691 77
Email: [email protected]
DETERMINATION OF PARTICLE SIZE DISTRIBUTION
OF COARSE AGGREGATES (15/25 MM)
Test Method EN 933-1
Sample Descrption: Aggregate for Concrete Date of Sampling: 06.04.2024
Source/Location: AL NASRI CRUSHER PLANT DOUDA Date of Testing: 08.04.2024
Sample No.: 1 Sampled By: Jointly
Weight of sample (gm) 9655,5

Cumm. % Requirement as per


Max.Size of Weight Cumm. Weight
Sieve (mm) Weight % Passing NF EN 12620-2002
Aggrgate (mm) Retained (gm) Retained (gm)
Retained (Table -2,3&11)

50 0 0 0 100 100 100


31,5 0 0 0 100 98 100
25,0 241,4 241,4 2,5 97,5 90 99
20,0 2558,7 2800,1 29,0 71,0 - -
25 mm 16,0 5194,7 7994,8 82,8 17,2 - -
10,0 1573,8 9568,6 99,1 0,9 - -
2,0 19,3 9587,9 99,3 0,7 - -
0,063 38,6 9626,5 99,7 0,3 0 1,5
Pan 25,3 -

120

100

80
% of Passing

60

40

20

0
0,01 0,1 1 10 100
Sieve Size (mm)

AFCONS Representative

Signature:

Date:
QF/5267/QC/12/00

ociété Al Nasri Materials Testing Laboratory (SANLAB)


Camp Douda, Djibouti
Republic of Djibouti
Tel. +253 771 851 54/776 691 77
Email: [email protected]

DETERMINATION OF PARTICLE SIZE DISTRIBUTION OF COARSE AGGREGATES (5/15 MM)

Test Method EN 933-1


Sample Descrption: Aggregate for Concrete Date of Sampling: 06.04.2024
Source/Location: AL NASRI CRUSHER PLANT DOUDA Date of Testing: 08.04.2024
Sample No.: 2 Sampled By: Jointly
Weight of sample (gm) 2630
Cumm. % Requirement as per
Max.Size of Weight Cumm. Weight
Sieve (mm) Weight % Passing NF EN 12620-2002
Aggrgate (mm) Retained (gm) Retained (gm)
Retained (Table -2,3&11)
31,5 0 0 0 100 100 100
20,0 0 0 0,0 100 98 100
16,0 65,2 65,2 2,5 97,5 90 99
10,0 977,1 1042,3 39,6 60,4 10 85
15 mm
5,0 1269,8 2312,1 87,9 12,1 0 15
2,0 173,6 2485,7 94,5 5,5 0 5
0,063 129,8 2615,5 99,4 0,6 0 1,5
Pan 9,7

110
100
90
80
% of Passing

70
60
50
40
30
20
10
0
0,01 0,1 1 10 100
Sieve Size ( mm)

AL NASRI Representative

Signature:

Date:
ociété Al Nasri Materials Testing Laboratory (SANLAB)
Camp Douda, Djibouti
Republic of Djibouti
Tel. +253 771 851 54/776 691 77
Email: [email protected]

BULK DENSITY OF AGGREGATES


Test Method: EN 1097 - 3
Source AL NASRI CRUSHER PLANT Date of Sampling 06.04.2024

Location DOUDA Date of Testing 09.04.2024

Type of Material coarse Aggregate (15/25 mm) Sampled by Jointly

Blending Praportions 60% : 40% Tested by Jointly

A) LOOSE DENSITY

Sl.No Description Trail-1 Trail-2 Average

1 Number 1 2

2 Container (cc) 10029 10029

3 Material in 15678 15634

4 Bulk Density of Material (g/cc) 1,563 1,559 1,561

B)RODDED DENSITY

Sl.No Description Trail-1 Trail-2 Average

1 Container Number 1 1

2 Volume of Container (cc) 10029 10029

3 Weight of Material in Container(g) 16330 16337

4 Bulk Density of Material (g/cc) 1,628 1,629 1,629

AL NASRI Representative

Signature:

Date: 09,04,2024
Société Al Nasri Materials Testing Laboratory (SANLAB)
Camp Douda, Djibouti
Republic of Djibouti
Tel. +253 771 851 54/776 691 77
Email: [email protected]

BULK DENSITY OF AGGREGATES


Test Method: EN 1097 - 3
Source AL NASRI CRUSHER PLANT Date of Sampling 06.04.2024

Location DOUDA Date of Testing 09.04.2024

Type of Material Carse Aggregate (15/25 mm) Sampled by Jointly

Blending Praportions Tested by Jointly

A) LOOSE DENSITY

Sl.No Description Trail-1 Trail-2 Average

1 Number 1 2

2 Container (cc) 10029 10029

3 Material in 15342 15340

4 Bulk Density of Material (g/cc) 1,530 1,530 1,530

B)RODDED DENSITY

Sl.No Description Trail-1 Trail-2 Average

1 Container Number 1 1

2 Volume of Container (cc) 10029 10029

3 Weight of Material in Container(g) 16169 16151

4 Bulk Density of Material (g/cc) 1,612 1,610 1,611

AL NASRI Representative

Signature:

Date: 09,04,2024
Société Al Nasri Materials Testing Laboratory (SANLAB)
Camp Douda, Djibouti
Republic of Djibouti
Tel. +253 771 851 54/776 691 77
Email: [email protected]

BULK DENSITY OF AGGREGATES


Test Method: EN 1097 - 3
Source AL NASRI CRUSHER PLANT Date of Sampling 06.04.2024

Location DOUDA Date of Testing 09.04.2024

Type of Material Coarse Aggregate (5/15 mm) Sampled by Jointly

Blending Praportions - Tested by Jointly

A) LOOSE DENSITY

Sl.No Description Trail-1 Trail-2 Average

1 Number 1 2

2 Container (cc) 10029 10029

3 Material in 15050 15030

4 Bulk Density of Material (g/cc) 1,501 1,499 1,500

B)RODDED DENSITY

Sl.No Description Trail-1 Trail-2 Average

1 Container Number 1 1

2 Volume of Container (cc) 10029 10029

3 Weight of Material in Container(g) 15605 15752

4 Bulk Density of Material (g/cc) 1,556 1,571 1,563

AL NASRI Representative

Signature:

Date: 09,04,2024
Société Al Nasri Materials Testing Laboratory (SANLAB)
Camp Douda, Djibouti
Republic of Djibouti
Tel. +253 771 851 54/776 691 77
Email: [email protected]

BULK DENSITY OF FINE AGGREGATES


Test Method: EN 1097 - 3

Source Sampling date Date of Sampling 06.04.2024

Location Source Date of Testing 09.04.2024

Type of Material Fine Aggregate Sampled by Jointly

Material River sand Sand Tested by Jointly

A) LOOSE DENSITY

Sl.No Description Trail-1 Trail-2 Average

1 Container Number 1 1

2 Volume of Container (cc) 5078 5078

3 Weight of Material in Container(g) 7260 7210

4 Bulk Density of Material (g/cc) 1,430 1,420 1,425

AL NASRI Representative

Date: 10,04,2024
Société Al Nasri Materials Testing Laboratory (SANLAB)
Camp Douda, Djibouti
Republic of Djibouti
Tel. +253 771 851 54/776 691 77
Email: [email protected]

SPECIFIC GRAVITY & WATER ABSORPTION


Test Method: EN 1097 - 6
Sample Station Stock batching plant Sampling date 09.04.2024
Visual description of
Natural sand Source Loyada
material:
Purpose For concrete mix design Laboratory Base Camp-douda

Date of Sample: 08.04.2024 Sampled by Jointly

Tested by Jointly

Description of sample Test 1 Test 2 Average

A = Weight of Pyconometer + SSD sample + water (g) 1782,2 1857,3 -

B = Weight of Pyconometer + water (g) 1575,3 1574,4 -

C = Weight of SSD sample (g) 340,9 467,1 -

D = Weight of oven dry sample (g) 337,1 462,2 -

SSD Bulk Specific Gravity, C/{C-(A-B)} 2,544 2,536 2,540

Bulk Specific Gravity, D/{C-(A-B)} 2,516 2,509 2,512

Apparent Specific Gravity, D/{D-(A-B} 2,589 2,578 2,583

Water absorption, percentage, 100 X (C-D)/D 1,127 1,060 1,094

AL NASRI Representative

Date: 10,04,2024
Société Al Nasri Materials Testing Laboratory (SANLAB)
Camp Douda, Djibouti
Republic of Djibouti
Tel. +253 771 851 54/776 691 77
Email: [email protected]

SPECIFIC GRAVITY & WATER ABSORPTION


Test Method: EN 1097 - 6
Sample Station Stock batching plant Sampling date 09.04.2021

Visual description of
Crushed Aggregates Source AL NASRI CRUSHER PLANT DOUDA
material:

Purpose For concrete mix design Laboratory Base Camp-douda

Date of Sample: 08.04.2024 Sampled by Jointly

Tested by Jointly

Description of sample Test 1 Test 2 Average

A = Weight of oven dry sample (g) 1691,4 1888,9

B =Weight of SSD sample (g) 1702,3 1898,2

C = Weight of sample in water (g) 1080,2 1206,9

SSD Bulk Specific Gravity, B/(B-C) 2,736 2,746 2,741

Bulk Specific Gravity, A/(B-C) 2,719 2,732 2,726

Apparent Specific Gravity, A/(A-c) 2,767 2,770 2,768

Water absorption, percentage, 100 X (B-A)/A 0,644 0,492 0,57

AL NASRI Representative

Date: 10,04,2024
Société Al Nasri Materials Testing Laboratory (SANLAB)
Camp Douda, Djibouti
Republic of Djibouti
Tel. +253 771 851 54/776 691 77
Email: [email protected]

SPECIFIC GRAVITY & WATER ABSORPTION

Test Method: EN 1097 - 6


Sample Station Stock batching plant Sampling date 07.04.2021

Visual description of
Crushed Aggregates Source Loyada
material:

Purpose For concrete mix design Laboratory Base Camp-douda

Date of Sample: 08.04.2024 Sampled by Jointly

Tested by Jointly

Description of sample Test 1 Test 2 Average

A = Weight of oven dry sample (g) 2201,1 3152,3

B =Weight of SSD sample (g) 2209,5 3168,9

C = Weight of sample in water (g) 1410,2 2018,6

SSD Bulk Specific Gravity, B/(B-C) 2,764 2,755 2,760

Bulk Specific Gravity, A/(B-C) 2,754 2,740 2,747

Apparent Specific Gravity, A/(A-c) 2,783 2,781 2,782

Water absorption, percentage, 100 X (B-A)/A 0,38 0,53 0,45

AL NASRI Representative

Date: 10,04,2024
Société Al Nasri Materials Testing Laboratory (SANLAB) QF/5267/QC/02/01

Camp Douda, Djibouti


Republic of Djibouti
Tel. +253 771 851 54/776 691 77
Email: [email protected]
Los Angeles Test
(Test Mehtod: NF P18-573 or NF EN 1097-2)

Source/Location Mokora Sample No. 1


Material Type Coarse Aggregate for Concrete Sampled By Jointly
Sampling Date 06.04.2024 Tested By Jointly
Testing Date 11.04.2021

GRANULAR CLASSIFICATION AND STEEL SPHERES TEST AND RESULTS

Total Weight of steel spheres ᶲ 45-49 mm in gm


Weight of one Total Weight Los Angeles
Number of Sample taken
Granular class Sub -class steel sphere sample passing in a coefficient
steel spheres in gm Tolerated Tolerated Actual by sub-class
Recommanded taken 1.6mm sieve "LA"
minimum maximum Weight

1 2 3 4 5 6 7 8 9 10 11 12

4/6.3 7 3080 2930 3100


6.3/10 9 3960 3810 3980

10/14 11 4840 4690 4860 4796 5000 928 18,6


10/16
10/25 11 4840 4690 4860
16/25 400 - 445 5000 ± 5

16/25
16/31.5 12 5280 5130 5300
25/31.5
25/40
25/50 12 5280 5130 5300
40/50

Comments :- ________________________________________________________________________________________________________________________________________________________________________________

AL NASRI Representative

Signature

Date 11,04,2024
Société Al Nasri Materials Testing Laboratory (SANLAB)
Camp Douda, Djibouti
Republic of Djibouti
Tel. +253 77241899/776 691 77
Email:[email protected]

FINE AGGREGATES
SAND EQUIVALENT OF FINE AGGREGATES
ASTM D 2419

Sample No. : Sand 001 Sample Description : Sand 0/5mm

Source : AL NASRI Crusher Plant

Date Sampled: 06.4.2024 Tested By : Raymond

Date Tested : 09.04.2024 Sampled By : Raymond

SAND EQUIVALENT SE Required > 60

DESCRIPTION Test No 1 Test No 2 Test No 3

Clay Reading h1 9,8 9,7

Sand Reading (Weighted foot) 7,8 7,4


h2

Sand Equivalent (SE) 100h 2 /h 1 79,6 76,3

Average 77,9

Sand reading (View) 7,6 7,3


h2

Sand Equivalent (SE) 100h 2 '/h 1 77,6 75,3

Average 76,4

Remarks :

Submitted byː

Chef Labo Ali Nasri

QC Labo.Test
Société Al Nasri Materials Testing Laboratory (SANLAB)
Camp Douda, Djibouti
Republic of Djibouti
Tel. +253 77241899/776 691 77
Email:[email protected]

FINE AGGREGATES
SAND EQUIVALENT OF FINE AGGREGATES
ASTM D 2419

Sample No. : Sand 002 Sample Description : Sand 0/5mm

Source : Natural Sand - Loyada

Date Sampled: 09.4.2024 Tested By : Raymond

Date Tested : 10.04.2024 Sampled By : Raymond

SAND EQUIVALENT SE Required > 60

DESCRIPTION Test No 1 Test No 2 Test No 3

Clay Reading h1 9,5 9,5

Sand Reading (Weighted foot) 7,8 7,7


h2

Sand Equivalent (SE) 100h 2 /h 1 82,1 81,1

Average 81,6

Sand reading (View) 7,7 7,6


h2

Sand Equivalent (SE) 100h 2 '/h 1 81,1 80,0

Average 80,5

Remarks :

Submitted byː

Chef Labo Ali Nasri

QC Labo.Test
PRODUCT DATA SHEET
SikaPlast®-3800
WATER REDUCING AND RETARDING SUPERPLASTICIZING ADMIXTURE FOR CONCRETE

DESCRIPTION CHARACTERISTICS / ADVANTAGES


SikaPlast®-3800 is a polycarboxylate based superplas- SikaPlast®-3800 acts by surface adsorption on the ce-
ticizer developed particularly for use in ready mixed ment particles producing steric hindrance as well as
concrete to give extended slump retention and high electrostatic repulsion between cement particles
strength development of normal grade concrete which results in higher dispersion, flow and retention.
mixes. SikaPlast®-3800 provides the following beneficial
SikaPlast®-3800 is suitable for use in concrete mixes properties:
incorporating pozzolanic materials such as GGBS, PFA ▪ Substantial improvement in workability without in-
and microsilica. creased water
Suitable for use in hot and tropical climatic conditions. ▪ Low risk of segregation
▪ Normal set without retardation (within the dosage
USES limit)
▪ Improved density and surface finish
▪ High flow concrete ▪ Improved water tightness
▪ Concrete with high water reduction ▪ Excellent solution for continuous concrete casting of
▪ High strength concrete deep elements
▪ Slabs ▪ Does not contain chlorides or other steel corrosion
▪ Foundations promoting ingredients therefore may be used for rein-
▪ Walls forced and pre-stressed concrete construction
▪ Columns and piers
▪ Piles APPROVALS / CERTIFICATES
▪ Pre-stressed concrete
▪ Bridges and cantilever structures SikaPlast®-3800 follows the requirements of ASTM
C494;Type G and EN 934-2

PRODUCT INFORMATION
Composition Aqueous solution of modified polycarboxylates
Packaging 1000 L flowbins
Bulk supply in tanker trucks is possible on request
Shelf life 12 months from date of production if stored properly
Storage conditions Store in undamaged, unopened, original sealed packaging in dry conditions
at temperatures between +5°C and +45°C. Protect from direct sunlight and
frost
Appearance and colour Brown liquid
Density ~1.07 kg/l (+25°C)

Product Data Sheet


SikaPlast®-3800
October 2022, Version 01.01
021301011000003456

1/3
Total chloride ion content Nil (EN 934-2)

TECHNICAL INFORMATION
Concreting guidance The standard rules of good concreting practice for production and placing
must be observed when using SikaPlast®-3800 in concrete.
Refer to relevant standards.
Fresh concrete must be cured properly especially at high temperatures in
order to prevent plastic and drying shrinkage. Use Sika® Antisol® products
as a curing agent or apply wet hessian.

APPLICATION INFORMATION
Recommended dosage 0.5 – 2.0 % by weight of binder
Higher dosages by weight of binder can be used depending on the mix
design, raw materials, climatic conditions and concrete requirements. Trial
mixes must be performed to establish the exact dosage rate required.
Dispensing SikaPlast®-3800 is added to the gauging water or simultaneously poured
with it into the concrete mixer at the batching plant. Do not add Sika-
Plast®-3800 directly to the dry mix.
For optimum utilization of its high water reduction property we recom-
mend thorough mixing at a minimal wet mixing time of 60 seconds. The
addition of the remaining gauging water (to fine tune concrete consist-
ency) may only be started after two-thirds of the wet mixing time to avoid
surplus water in the concrete.
Compatibility SikaPlast®-3800 may be combined with all types of Portland cement and
the following Sika products:
▪ SikaPump®
▪ Sika® FerroGard®-901
▪ SikaFume®
▪ Sika-Aer®
▪ Sika® Control-40
▪ Sika®-WT 1
▪ SikaControl®-11 WT AE
We recommend performing trial mixes to establish the required perform-
ance when combined with the above products. Please consult our Sika
Technical Department.

BASIS OF PRODUCT DATA tures based on sulfonated naphthalene or melamine.

All technical data stated in this Data Sheet are based ECOLOGY, HEALTH AND SAFETY
on laboratory tests. Actual measured data may vary
due to circumstances beyond our control. User must read the most recent corresponding Safety
Data Sheets (SDS) before using any products. The SDS
IMPORTANT CONSIDERATIONS provides information and advice on the safe handling,
storage and disposal of chemical products and con-
When using SikaPlast®-3800 a mix design must be se- tains physical, ecological, toxicological and other
lected for the local material sources used and trial safety-related data.
mixes performed to verify suitability. If frozen and/or
if precipitation has occurred, it may only be used after LOCAL RESTRICTIONS
thawing slowly at room temperature and intensive
mixing. Note that as a result of specific local regulations the
SikaPlast®-3800 should not be added to dry cement. declared data and recommended uses for this product
Before pouring, suitability tests on the fresh concrete may vary from country to country. Consult the local
must be carried out. Due to the extended workability Product Data Sheet for exact product data and uses.
take special care that formwork is properly installed
and secured. In case the setting time of concrete is ex-
tended, if cured properly, other properties may not be
affected and higher ultimate strength is visualized.
SikaPlast® products are not compatible with admix-

Product Data Sheet


SikaPlast®-3800
October 2022, Version 01.01
021301011000003456

2/3
LEGAL NOTES
The information, and, in particular, the recommenda-
tions relating to the application and end-use of Sika
products, are given in good faith based on Sika's cur-
rent knowledge and experience of the products when
properly stored, handled and applied under normal
conditions in accordance with Sika's recommenda-
tions. In practice, the differences in materials, sub-
strates and actual site conditions are such that no war-
ranty in respect of merchantability or of fitness for a
particular purpose, nor any liability arising out of any
legal relationship whatsoever, can be inferred either
from this information, or from any written recom-
mendations, or from any other advice offered. The
user of the product must test the product’s suitability
for the intended application and purpose. Sika re-
serves the right to change the properties of its
products. The proprietary rights of third parties must
be observed. All orders are accepted subject to our
current terms of sale and delivery. Users must always
refer to the most recent issue of the local Product
Data Sheet for the product concerned, copies of which
will be supplied on request.

SIKA NORTHERN GULF SIKA SOUTHERN GULF Sika Saudi Arabia


Bahrain / Kuwait UAE / Oman / SIC Riyadh / Jeddah / Dammam
Tel: +973 177 38188 Tel: +971 4 439 8200 Tel. +966 11 217 6532
[email protected] [email protected] [email protected]
gcc.sika.com gcc.sika.com gcc.sika.com

SikaPlast-3800-en-AE-(10-2022)-1-1.pdf

Product Data Sheet


SikaPlast®-3800
October 2022, Version 01.01
021301011000003456

3/3
ASHTECH (INDIA) PVT. LTD.
Ashford Centre, 9th Floor, Lower Parel West, Mumbai 400013, INDIA
t. +91 22 61490200 e. [email protected]

Report No. BVIPL: FLYASH: 25941C/17895/11/2023 Date: 28.12.2023

TEST REPORT ON PHYSICAL PROPERTIES OF FLY ASH (PULVERIZED FUEL ASH)

Period of Test : 20.11.2023 to


Test Method : 24.11.2023 ASTM C311

Technical Requirements as per


Sr. No. Test Conducted Results
ASTM C618
1 Uniformity Test on 45 micron wet sieving (%) 13.6 Maximum 34%
2 Density (g/cc) 2.52 -
Minimum percent of control
3 7 Days Strength Activity Index (%) 80
sample 75
a 7 Days cement mortar strength (MPa) 24.5 -
b 7 Days test mortar strength (MPa) 19.9 -
Minimum percent of control
4 28 Days Strength Activity Index (%) 92
sample 75
a 28 Days cement mortar strength (MPa) 32.7 -
b 28 Days test mortar strength (MPa) 32.1 -
#
5 Reduction of mortar expansion (%) 68.5 Maximum 100%

# As furnished by the customer


The tests are not covered under the NABL scope of accreditation

Note:
1) The results stated are related to the sample/s tested only.
2) Contents of this report are meant for your guidance & should not be used for advertisement, evidence or litigation
3) This Test Report shall not be reproduced in part or full, without the written consent of Ashtech India Pvt. Ltd

for ASHTECH (INDIA) PVT. LTD.


Calibrated by: "ACTS Central Laboratory, Beirut,
Sanayeh area, George Assy st.
P.O.Box: 14/5918-Code:1105-2080
Tel: 01-737400; Fax: 01-737222"

CALIBRATION OF COMPRESSION TESTING MACHINE REPORT


Client: Al Nasri Date : 04/12/2023
Address: Djibouti Serial No. 2303960-52
Tel/Fax: +25377669177 - +25377824033 Page 1 of 1

Equipment Name: Compression Testing Machine Equipment Serial No. : 100310/14 Receipt Date : 04/12/2023
Equipment Reference No. : C0065 Equipment Range : 2000kN Calibration Date : 04/12/2023
Equipment Model No. : '----- Equipment Resolution (kN) : 0.001 Suggested Due Date : 04/12/2024
Manufacturer : alfalab Work Order No. : ACTS-2303960
We certify that the above object was calibrated for specific calibration points using certified standards traceable to international standards.
Calibration results, data and special condition on the use of the object are stated in the corresponding page(s).

Pre-Inspection: No damage that affects function was observed on the object prior to inspection.
Declaration of conformity: All values of the device are in the accuracy class specified according to the standard ASTM E4.

Reference Equipment Used


Reference No. Equipment Name Calibration Due Date Certificate No. Equipment Serial No.
R1461 Reference Load Cell 7-Jan-24 VCS2023-157 C140-08/AB/0011
R1462 Digital Indicator 7-Jan-24 VCS2023-157 C138PN192/AB/0005
C1717 Hygrometer 17-Oct-24 C1717-23 160854898

Environmental Conditions
Ambient Temperature 29.4°C
Relative Humidity 38%

Measurement Results
Machine Reference Load Cell Readings (kN)
Deviation from Repeatability Uncertainty
Reading Error %
Test 1 Test 2 Test 3 Test 4 Test 5 Avg. (kN) Reference (kN) (kN) (kN)
(kN)
0 0 0 0 0 0 0.000 ----- ----- ----- -----
200.0 198.968 199.633 199.762 198.989 199.549 199.380 0.62 0.375 0.310 0.790
400.0 399.354 399.781 398.852 398.928 399.524 399.288 0.71 0.395 0.178 0.895
600.0 598.684 598.367 598.558 598.412 598.675 598.539 1.46 0.146 0.243 1.692
800.0 798.127 798.614 798.328 798.534 798.485 798.418 1.58 0.193 0.198 1.835
1000.0 998.083 998.342 998.116 998.242 998.351 998.227 1.77 0.124 0.177 2.051
1200.0 1196.964 1197.251 1196.887 1196.798 1197.309 1197.042 2.96 0.226 0.247 3.433
1400.0 1396.606 1396.723 1396.814 1396.598 1396.685 1396.685 3.31 0.089 0.237 3.828
1600.0 1595.380 1595.476 1594.938 1595.561 1593.992 1595.069 4.93 0.648 0.308 5.693
1800.0 1792.675 1792.354 1791.856 1792.754 1792.853 1792.498 7.50 0.405 0.417 8.670
2000.0 1987.668 1988.563 1988.349 1988.467 1988.621 1988.334 11.67 0.386 0.583 13.471

Measurement Method :
The calibration is performed by direct measurement according to ASTM E4.
This calibration certificate is in accordance with the demands of the standard series EN ISO/IEC 17025. It documents the traceability to national
standards, standard measuring equipment and methods for the realization of physical units of measurement according to the International
System of Units (SI) .
Measurement Uncertainty :
The reported expanded uncertainty of measurement is stated as the standard uncertainty of measurement multiplied by the coverage factor k=2,
which for a normal distribution corresponds to a coverage probability of approximately 95%. The standard uncertainty of measurement has been
determined in accordance with EA’s Publication EA-4/02. The long term stability of the calibration object is not included in the reported
expanded uncertainty of measurement.

Calibrated by: Mohammad Sinno Reviewed by: Rabih Boukaidbey


Calibration Responsible Lab Manager
Calibrated by: "ACTS Central Laboratory, Beirut,
Sanayeh area, George Assy st.
P.O.Box: 14/5918-Code:1105-2080
Tel: 01-737400; Fax: 01-737222"

CALIBRATION OF ADMIXTURE SCALE IN CONCRETE BATCH PLANT REPORT

Client: M/S Societe AL Nasri SARL Date : 04/12/2024


Address: Djibouti (AL NASRI) Serial No. 2303960-79
Tel: +0025377669177 +0025377824033 Page 1 of 2

Location: Djibouti Batch Plant Batch Capacity: 3m 3 Receipt Date : 05/12/2023


Batch Type: Goker-1- Scale Range : 100kg Calibration Date : 05/12/2023
Serial Number: ----- Scale Resolution : 1kg Suggested Due Date : 05/12/2024
Work Order No. : ACTS-2303960
We certify that the above object was calibrated for specific calibration points using certified standards traceable to international standards.
Calibration results, data and special condition on the use of the object are stated in the corresponding page(s).

Pre-Inspection: No damage that affects function was observed on the object prior to inspection.
Declaration of conformity: All values of the device are in the accuracy class specified according to the standard ASTM C94-09.
Reference Equipment Used
Reference No. Equipment Name Equipment Serial No. Calibration Due Date Certificate Serial No.
R1400 Reference Weights ZW 3139 - ZW 3188 27-Jan-25 Z12 00996 - Z12 00997
C1717 Hygrometer 160854898 17-Oct-24 C1717-23

Environmental Conditions
Ambient Temperature 29.4°C
Relative Humidity 38%

Scale Reading (g)


Reference Average Scale
Scale Error (g) Scale error (%)
Weights (g) Reading (g)
Loading Unloading
0 0 0 0 0 0
500 510 510 510 10 0
1000 1020 1020 1020 20 0
1500 1530 1530 1530 30 0
2000 2030 2030 2030 30 0
2500 2530 2530 2530 30 0
3000 3040 3040 3040 40 0
3500 3490 3490 3490 10 0
4000 3980 3980 3980 20 0
4500 4480 4480 4480 20 0
5000 5040 5040 5040 40 0
5500 5530 5530 5530 30 0
6000 6030 6030 6030 30 0
6500 6520 6520 6520 20 0
7000 7030 7030 7030 30 0
7500 7530 7530 7530 30 0
8000 8010 8010 8010 10 0
8500 8520 8520 8520 20 0
9000 9030 9030 9030 30 0
9500 9530 9530 9530 30 0
10000 10030 10030 10030 30 0
10500 10540 10540 10540 40 0
11000 11040 11040 11040 40 0

Calibrated by: Mohammad Sinno Reviewed by: Rabih Boukaidbey


Calibration Responsible Lab Manager
Date : 04/12/2024
Serial No. 2303904-79
Page 2 of 2

Scale Reading (g)


Reference Average Scale
Scale Error (g) Scale error (%)
Weights (g) Reading (g)
Loading Unloading
12000 12060 12060 12060 60 0
12500 12550 12550 12550 50 0
13000 13050 13050 13050 50 0
13500 13560 13560 13560 60 0
14000 14060 14060 14060 60 0
14500 14560 14560 14560 60 0
15000 15780 15780 15780 780 0
15500 15570 15570 15570 70 0
16000 16070 16070 16070 70 0
16500 16570 16570 16570 70 0
17000 17110 17110 17110 110 0
17500 17610 17610 17610 110 0
18000 18130 18130 18130 130 0
18500 18620 18620 18620 120 0
19000 19140 19140 19140 140 0
19500 19630 19630 19630 130 0
20000 20160 20160 20160 160 0
20500 20660 20660 20660 160 0
21000 21150 21150 21150 150 0
21500 21650 21650 21650 150 0
22000 22160 22160 22160 160 0
22500 22660 22660 22660 160 0
23000 23170 23170 23170 170 0
23500 23670 23670 23670 170 0
24000 24170 24170 24170 170 0
24500 24680 24680 24680 180 0
25000 25180 25180 25180 180 0
25500 25680 25680 25680 180 0
26000 26180 26180 26180 180 0
26500 26680 26680 26680 180 0
27000 27180 27180 27180 180 0
27500 27680 27680 27680 180 0
28000 28180 28180 28180 180 0
28500 28690 28690 28690 190 0
29000 29190 29190 29190 190 0
29500 29690 29690 29690 190 0
30000 30190 30190 30190 190 0

Measurement Method :
The calibration is performed by direct measurement according to ASTM C94-09.
Measurement Uncertainty :
The reported expanded uncertainty of measurement is stated as the standard uncertainty of measurement multiplied by the coverage factor k=2,
which for a normal distribution corresponds to a coverage probability of approximately 95%. The standard uncertainty of measurement has been
determined in accordance with EA’s Publication EA-4/02. The long term stability of the calibration object is not included in the reported expanded
uncertainty of measurement.

Calibrated by: Mohammad Sinno Reviewed by: Rabih Boukaidbey


Calibration Responsible Lab Manager
Calibrated by: "ACTS Central Laboratory, Beirut,
Sanayeh area, George Assy st.
P.O.Box: 14/5918-Code:1105-2080
Tel: 01-737400; Fax: 01-737222"

CALIBRATION OF AGGREGATE SCALE IN CONCRETE BATCH PLANT REPORT

Client: M/S Societe AL Nasri SARL Date : 04/12/2024


Address: Djibouti (AL NASRI) Serial No. 2303960-80
Tel: +0025377669177 +0025377824033 Page 1 of 3

Location: Djibouti Batch Plant Batch Capacity: 3m 3 Receipt Date : 05/12/2023


Batch Type: Goker-1- Scale Range : 10 Ton Calibration Date : 05/12/2023
Serial Number: ----- Scale Resolution : 1Kg Suggested Due Date : 05/12/2024
Work Order No. : ACTS-2303960
We certify that the above object was calibrated for specific calibration points using certified standards traceable to international standards.
Calibration results, data and special condition on the use of the object are stated in the corresponding page(s).

Pre-Inspection: No damage that affects function was observed on the object prior to inspection.
Declaration of conformity: All values of the device are in the accuracy class specified according to the standard ASTM C94-09.
Reference Equipment Used
Reference No. Equipment Name Equipment Serial No. Calibration Due Date Certificate Serial No.
R1400 Reference Weights ZW 3139 - ZW 3188 27-Jan-25 Z12 00996 - Z12 00997
C1717 Hygrometer 160854898 17-Oct-24 C1717-23

Environmental Conditions
Ambient Temperature 29.4°C
Relative Humidity 38%

Scale Reading (g)


Reference Average Scale
Scale Error (g) Scale error (%)
Weights (g) Reading (g)
Loading Unloading
0 0 0 0 0 0
80 80 80 80 0 0
160 160 160 160 0 0
240 240 240 240 0 0
320 320 320 320 0 0
400 400 400 400 0 0
480 480 480 480 0 0
560 560 560 560 0 0
640 640 640 640 0 0
720 720 720 720 0 0
800 800 800 800 0 0
880 880 880 880 0 0
960 960 960 960 0 0
1000 1000 1000 1000 0 0
1080 1080 1080 1080 0 0
1160 1160 1160 1160 0 0
1240 1240 1240 1240 0 0
1320 1320 1320 1320 0 0
1400 1400 1400 1400 0 0
1480 1480 1480 1480 0 0
1560 1560 1560 1560 0 0
1640 1640 1640 1640 0 0
1720 1720 1720 1720 0 0
1800 1800 1800 1800 0 0

Calibrated by: Mohammad Sinno Reviewed by: Rabih Boukaidbey


Calibration Responsible Lab Manager
Date : 04/12/2024
Serial No. 2303904-80
Page 2 of 3

Scale Reading (g)


Reference Average Scale
Scale Error (g) Scale error (%)
Weights (g) Reading (g)
Loading Unloading
1880 1880 1880 1880 0 0
1960 1960 1960 1960 0 0
2000 2000 2000 2000 0 0
2080 2080 2080 2080 0 0
2160 2160 2160 2160 0 0
2240 2240 2240 2240 0 0
2320 2320 2320 2320 0 0
2400 2400 2400 2400 0 0
2480 2480 2480 2480 0 0
2560 2560 2560 2560 0 0
2640 2640 2640 2640 0 0
2720 2720 2720 2720 0 0
2800 2800 2800 2800 0 0
2880 2880 2880 2880 0 0
2960 2960 2960 2960 0 0
3000 3000 3000 3000 0 0
3080 3080 3080 3080 0 0
3160 3160 3160 3160 0 0
3240 3240 3240 3240 0 0
3320 3320 3320 3320 0 0
3400 3400 3400 3400 0 0
3480 3480 3480 3480 0 0
3560 3560 3560 3560 0 0
3640 3640 3640 3640 0 0
3720 3720 3720 3720 0 0
3800 3800 3800 3800 0 0
3880 3880 3880 3880 0 0
3960 3960 3960 3960 0 0
4000 4000 4000 4000 0 0
4040 4040 4040 4040 0 0
4080 4080 4080 4080 0 0
4120 4120 4120 4120 0 0
4160 4160 4160 4160 0 0
4200 4200 4200 4200 0 0
4240 4240 4240 4240 0 0
4280 4280 4280 4280 0 0
4320 4320 4320 4320 0 0
4360 4360 4360 4360 0 0
4400 4400 4400 4400 0 0
4440 4440 4440 4440 0 0
4480 4480 4480 4480 0 0
4520 4520 4520 4520 0 0
4560 4560 4560 4560 0 0
4600 4600 4600 4600 0 0
4640 4640 4640 4640 0 0
4680 4680 4680 4680 0 0
4720 4720 4720 4720 0 0
4760 4760 4760 4760 0 0
4800 4800 4800 4800 0 0

Calibrated by: Mohammad Sinno Reviewed by: Rabih Boukaidbey


Calibration Responsible Lab Manager
Date : 04/12/2024
Serial No. 2303904-80
Page 3 of 3

Scale Reading (g)


Reference Average Scale
Scale Error (g) Scale error (%)
Weights (g) Reading (g)
Loading Unloading
4840 4840 4840 4840 0 0
4880 4880 4880 4880 0 0
4920 4920 4920 4920 0 0
4960 4960 4960 4960 0 0
5000 5000 5000 5000 0 0
5040 5040 5040 5040 0 0
5080 5080 5080 5080 0 0
5120 5120 5120 5120 0 0
5160 5160 5160 5160 0 0
5200 5200 5200 5200 0 0
5240 5240 5240 5240 0 0
5280 5280 5280 5280 0 0
5320 5320 5320 5320 0 0
5360 5360 5360 5360 0 0
5400 5400 5400 5400 0 0
5440 5440 5440 5440 0 0
5480 5480 5480 5480 0 0
5520 5520 5520 5520 0 0
5560 5560 5560 5560 0 0
5600 5600 5600 5600 0 0
5640 5640 5640 5640 0 0
5680 5680 5680 5680 0 0
5720 5720 5720 5720 0 0
5760 5760 5760 5760 0 0
5800 5800 5800 5800 0 0
5840 5840 5840 5840 0 0
5880 5880 5880 5880 0 0
5920 5920 5920 5920 0 0
5960 5960 5960 5960 0 0
6000 6000 6000 6000 0 0

Measurement Method :
The calibration is performed by direct measurement according to ASTM C94-09.
Measurement Uncertainty :
The reported expanded uncertainty of measurement is stated as the standard uncertainty of measurement multiplied by the coverage factor k=2,
which for a normal distribution corresponds to a coverage probability of approximately 95%. The standard uncertainty of measurement has been
determined in accordance with EA’s Publication EA-4/02. The long term stability of the calibration object is not included in the reported expanded
uncertainty of measurement.

Calibrated by: Mohammad Sinno Reviewed by: Rabih Boukaidbey


Calibration Responsible Lab Manager
Calibrated by: "ACTS Central Laboratory, Beirut,
Sanayeh area, George Assy st.
P.O.Box: 14/5918-Code:1105-2080
Tel: 01-737400; Fax: 01-737222"

CALIBRATION OF CEMENT SCALE IN CONCRETE BATCH PLANT REPORT

Client: M/S Societe AL Nasri SARL Date : 04/12/2024


Address: Djibouti (AL NASRI) Serial No. 2303960-81
Tel: +0025377669177 +0025377824033 Page 1 of 1

Location: Djibouti Batch Plant Batch Capacity: 3m 3 Receipt Date : 05/12/2023


Batch Type: Goker-1- Scale Range : 1500Kg Calibration Date : 05/12/2023
Serial Number: ----- Scale Resolution : 1Kg Suggested Due Date : 05/12/2024
Work Order No. : ACTS-2303960
We certify that the above object was calibrated for specific calibration points using certified standards traceable to international standards.
Calibration results, data and special condition on the use of the object are stated in the corresponding page(s).

Pre-Inspection: No damage that affects function was observed on the object prior to inspection.
Declaration of conformity: All values of the device are in the accuracy class specified according to the standard ASTM C94-09.
Reference Equipment Used
Reference No. Equipment Name Equipment Serial No. Calibration Due Date Certificate Serial No.
R1400 Reference Weights ZW 3139 - ZW 3188 27-Jan-25 Z12 00996 - Z12 00997
C1717 Hygrometer 160854898 17-Oct-24 C1717-23

Environmental Conditions
Ambient Temperature 29.4°C
Relative Humidity 38%

Scale Reading (g)


Reference Average Scale
Scale Error (g) Scale error (%)
Weights (g) Reading (g)
Loading Unloading
0 0 0 0 0 0
80 80 80 80 0 0
160 160 160 160 0 0
240 240 240 240 0 0
320 320 320 320 0 0
400 400 400 400 0 0
480 480 480 480 0 0
560 560 560 560 0 0
640 640 640 640 0 0
720 720 720 720 0 0
800 800 800 800 0 0
880 880 880 880 0 0
960 960 960 960 0 0
1000 1000 1000 1000 0 0
1080 1080 1080 1080 0 0
1160 1160 1160 1160 0 0
1240 1240 1240 1240 0 0
1320 1320 1320 1320 0 0
1400 1400 1400 1400 0 0
1480 1480 1480 1480 0 0

Measurement Method :
The calibration is performed by direct measurement according to ASTM C94-09.
Measurement Uncertainty :
The reported expanded uncertainty of measurement is stated as the standard uncertainty of measurement multiplied by the coverage factor k=2,
which for a normal distribution corresponds to a coverage probability of approximately 95%. The standard uncertainty of measurement has been
determined in accordance with EA’s Publication EA-4/02. The long term stability of the calibration object is not included in the reported expanded
uncertainty of measurement.

Calibrated by: Mohammad Sinno Reviewed by: Rabih Boukaidbey


Calibration Responsible Lab Manager
Calibrated by: "ACTS Central Laboratory, Beirut,
Sanayeh area, George Assy st.
P.O.Box: 14/5918-Code:1105-2080
Tel: 01-737400; Fax: 01-737222"

CALIBRATION OF WATER SCALE IN CONCRETE BATCH PLANT REPORT

Client: M/S Societe AL Nasri SARL Date : 04/12/2024


Address: Djibouti (AL NASRI) Serial No. 2303960-82
Tel: +0025377669177 +0025377824033 Page 1 of 2

Location: Djibouti Batch Plant Batch Capacity: 3m 3 Receipt Date : 05/12/2023


Batch Type: Goker-1- Scale Range : 1000Kg Calibration Date : 05/12/2023
Serial Number: ----- Scale Resolution : 1Kg Suggested Due Date : 05/12/2024
Work Order No. : ACTS-2303960
We certify that the above object was calibrated for specific calibration points using certified standards traceable to international standards.
Calibration results, data and special condition on the use of the object are stated in the corresponding page(s).

Pre-Inspection: No damage that affects function was observed on the object prior to inspection.
Declaration of conformity: All values of the device are in the accuracy class specified according to the standard ASTM C94-09.
Reference Equipment Used
Reference No. Equipment Name Equipment Serial No. Calibration Due Date Certificate Serial No.
R1400 Reference Weights ZW 3139 - ZW 3188 27-Jan-25 Z12 00996 - Z12 00997
C1717 Hygrometer 160854898 17-Oct-24 C1717-23

Environmental Conditions
Ambient Temperature 29.4°C
Relative Humidity 38%

Scale Reading (g)


Reference Average Scale
Scale Error (g) Scale error (%)
Weights (g) Reading (g)
Loading Unloading
0 0 0 0 0 0
20 20 20 20 0 0
40 40 40 40 0 0
60 60 60 60 0 0
80 80 80 80 0 0
100 100 100 100 0 0
120 120 120 120 0 0
140 140 140 140 0 0
160 160 160 160 0 0
180 180 180 180 0 0
200 200 200 200 0 0
220 220 220 220 0 0
240 240 240 240 0 0
260 260 260 260 0 0
280 280 280 280 0 0
300 300 300 300 0 0
320 320 320 320 0 0
340 340 340 340 0 0
360 360 360 360 0 0
380 380 380 380 0 0
400 400 400 400 0 0
Measurement Method :
The calibration is performed by direct measurement according to ASTM C94-09.
Measurement Uncertainty :
The reported expanded uncertainty of measurement is stated as the standard uncertainty of measurement multiplied by the coverage factor k=2,
which for a normal distribution corresponds to a coverage probability of approximately 95%. The standard uncertainty of measurement has been
determined in accordance with EA’s Publication EA-4/02. The long term stability of the calibration object is not included in the reported expanded
uncertainty of measurement.

Calibrated by: Mohammad Sinno Reviewed by: Rabih Boukaidbey


Calibration Responsible Lab Manager
Société Al Nasri Materials Testing Laboratory (SANLAB)
Camp Douda, Djibouti
Republic of Djibouti
Tel. +253 771 851 54/776 691 77
Email: [email protected]
Project : Pad extension for genset #12 . New Concrete Trench on Gravel-Wall Section
CONCRETE TEST RESULTS SUMMARY - 37 Mpa -CEMENT TYPE-V with FLY ASH Class F
Samples: CUBES 150x150 mm
Slump & Temp. test results Breaking at 7 days Breaking at 14 days Breaking at 28 days
Date
sampled
Source DESTINATION W/C Ratio
Date Date Date
Slump Test Temp. N° Test (Mpa) Average N° Test (Mpa) Average N° Test (Mpa) Average
of of of
(mm) (°C) of sample Rc (MPa) of sample Rc (MPa) of sample Rc (MPa)
test test test

ALI NASRI BATCHING PLANT C001 35,70 C004 40..64 C007 42,04

CEMENT: TYPE -V AND FLY ASH Class F C002 36,10 36,23 C005 37,77 37,74 C008 44,30 42,98
FAUNDATION
24-Jun-24 0,35 31,2 1-Jul-24 8-Jul-24 22-Jul-24
COLUM
C37-C360-FA90-W/C=0.35 160 C003 36,90 C006 37,70 C009 42,60

Samples: CUBES

ALI NASRI BATCHING PLANT C010 34,93 C013 39,39 C016 44,30

CEMENT: TYPE -V AND FLY ASH Class F 160 C011 34,23 34,99 C014 40,35 39,91 C017 40,32 42,74
FAUNDATION
28-Jun-24 0,35 30,8 5-Jul-24 12-Jul-24 26-Jul-24
COLUM
C37-C360-FA90-W/C=0.35 C012 35,80 C015 40,00 C018 42,90

Samples: CUBES

ALI NASRI BATCHING PLANT C019 32,84 C022 37,19 C045 40,57

CEMENT: TYPE -V AND FLY ASH Class F 200 C020 32,56 33,47 C023 38,32 37,27 C046 41,27 40,81
FAUNDATION
1-Jul-24 0,35 32,1 8-Jul-24 15-Jul-24 29-Jul-24
COLUM
C37-C360-FA90-W/C=0.35 C021 35,00 C024 36,31 C047 40,60

Samples: CUBES

ALI NASRI BATCHING PLANT C046 30,10 C049 39,40 C052 45,60

CEMENT: TYPE -V AND FLY ASH Class F WATCH TOWER & 170 C047 34,80 31,57 C050 39,95 38,72 C053 43,50 46,30
8-Jul-24 FAUNDATION 0,35 31,5 15-Jul-24 22-Jul-24 5-Aug-24
C37-C360-FA90-W/C=0.35 COLUMN C048 29,80 C051 36,81 C054 49,80

Samples: CUBES 30,60

ALI NASRI BATCHING PLANT C055 32,20 C058 39,50 C061 46,80

CEMENT: TYPE -V AND FLY ASH Class F 130 C056 30,81 32,50 C059 38,70 39,20 C062 47,80 47,97
FENCE FOOTING
10-Jul-24 0,35 30,8 17-Jul-24 24-Jul-24 7-Aug-24
PAD
C37-C360-FA90-W/C=0.35 C057 34,50 C060 39,40 C063 49,30

Samples: CUBES

ALI NASRI BATCHING PLANT C064 30,20 C067 40,62 C070 45,32

CEMENT: TYPE -V AND FLY ASH Class F 190 C065 29,80 29,97 C068 41,33 41,18 C071 47,60 45,94
SERVICE GRADE
14-Jul-24 0,35 31,4 21-Jul-24 28-Jul-24 11-Aug-24
BEAM
C37-C360-FA90-W/C=0.35 C066 29,90 C069 41,59 C072 44,90

Samples: CUBES

]
Société Al Nasri Materials Testing Laboratory (SANLAB)
Camp Douda, Djibouti
Republic of Djibouti
Tel. +253 771 851 54/776 691 77
Email: [email protected]
Project : Pad extension for genset #12 . New Concrete Trench on Gravel-Wall Section
CONCRETE TEST RESULTS SUMMARY - 37 Mpa -CEMENT TYPE-V with FLY ASH Class F
Samples: CUBES 150x150 mm
Slump & Temp. test results Breaking at 7 days Breaking at 14 days Breaking at 28 days
Date
sampled
Source DESTINATION W/C Ratio
Date Date Date
Slump Test Temp. N° Test (Mpa) Average N° Test (Mpa) Average N° Test (Mpa) Average
of of of
(mm) (°C) of sample Rc (MPa) of sample Rc (MPa) of sample Rc (MPa)
test test test

ALI NASRI BATCHING PLANT C078 30,20 C081 39,80 C084 49,39

CEMENT: TYPE -V AND FLY ASH Class F 155 C079 32,50 36,23
31,47 C082 37,90 37,74
38,85 12-Aug-24 C085 49,99 42,98
50,60
FAUNDATION
FENCE
24-Jun-24
15-Jul-24 0,35 31,2
30,9 1-Jul-24
22-Jul-24 8-Jul-24
29-Jul-24 22-Jul-24
COLUM
FAUNDATION
C37-C360-FA90-W/C=0.35 C080 31,70 C083 38,20 C086 52,43

Samples: CUBES

ALI NASRI BATCHING PLANT C087 33,20 C090 38,90 C093 49,39

CEMENT: TYPE -V AND FLY ASH Class F 195 C088 32,40 32,80 C091 40,20 39,55 C094 49,99 50,60
FENCE SHEAR
18-Jul-24 0,35 30,8 25-Jul-24 1-Aug-24 15-Aug-24
WALL
C37-C360-FA90-W/C=0.35 C089 32,80 C092 40,60 C095 52,43

Samples: CUBES

ALI NASRI BATCHING PLANT C095 32,01 C098 39,80 C101 46,80

CEMENT: TYPE -V AND FLY ASH Class F 210 C096 33,20 33,24 C099 40,10 40,47 C102 45,80 46,37
SHEAR WALL
20-Jul-24 0,35 29,9 27-Jul-24 3-Aug-24 17-Aug-24
WATCH TOWER
C37-C360-FA90-W/C=0.35 C097 34,50 C100 41,50 C103 46,50

Samples: CUBES

ALI NASRI BATCHING PLANT C104 33,20 C107 39,10 C110 49,50

CEMENT: TYPE -V AND FLY ASH Class F 155 C105 31,40 31,83 C108 38,60 36,87 C111 47,80 48,60
EAST FENCE
22-Jul-24 0,35 31,2 29-Jul-24 5-Aug-24 19-Aug-24
FOOTING
C37-C360-FA90-W/C=0.35 C106 30,90 C109 32,90 C112 48,50

Samples: CUBES

ALI NASRI BATCHING PLANT C113 32,53 C116 34,07 C119 48,80

CEMENT: TYPE -V AND FLY ASH Class F 210 C114 29,75 29,88 C117 38,60 36,50 C120 49,70 49,00
FENCE SHEAR
30-Jul-24 0,35 30,4 6-Aug-24 13-Aug-24 27-Aug-24
WALL
C37-C360-FA90-W/C=0.35 C115 27,37 C118 36,84 C121 48,50

Samples: CUBES

]
Société Al Nasri Materials Testing Laboratory (SANLAB)
Camp Douda, Djibouti
Republic of Djibouti
Tel. +253 771 851 54/776 691 77
Email: [email protected]
Project : Pad extension for genset #12 . New Concrete Trench on Gravel-Wall Section
CONCRETE TEST RESULTS SUMMARY - 37 Mpa -CEMENT TYPE-V with FLY ASH Class F
Samples: CUBES 150x150 mm
Slump & Temp. test results Breaking at 7 days Breaking at 14 days Breaking at 28 days
Date
sampled
Source DESTINATION W/C Ratio
Date Date Date
Slump Test Temp. N° Test (Mpa) Average N° Test (Mpa) Average N° Test (Mpa) Average
of of of
(mm) (°C) of sample Rc (MPa) of sample Rc (MPa) of sample Rc (MPa)
test test test

ALI NASRI BATCHING PLANT C122 35,22 C125 39,80 C128 49,30

CEMENT: TYPE -V AND FLY ASH Class F 170 C123 36,50 36,23
35,45 C126 41,99 37,74
40,51 C129 48,50 42,98
48,70
FAUNDATION
24-Jun-24
7-Aug-24 G COLUM
S BLOCK 0,35 31,2
29,9 1-Jul-24
14-Aug-24 8-Jul-24
21-Aug-24 22-Jul-24
4-Sep-24
C37-C360-FA90-W/C=0.35 C124 34,64 C127 39,72 C130 48,30

Samples: CUBES

Minimum = 155,0 29,9 27,37 29,88 32,90 36,50 44,90 45,94

Average = 183,6 30,6 32,09 32,09 39,15 39,13 48,54 48,54

Maximum = 210,0 31,4 36,50 35,45 41,99 41,18 52,43 50,60

Submitted By :

RAYMOND M.
Lab Manager
SOCIETE AL NASRI