0% found this document useful (0 votes)
1K views66 pages

Manual: Installation and Operating Instructions

Uploaded by

yogesh
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
1K views66 pages

Manual: Installation and Operating Instructions

Uploaded by

yogesh
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 66

manual

Installation and operating instructions

Weishaupt Gas Burner WM - G10/3-A / ZM-LN (W-FM 50) 83250102 - 1/2007


Conformity Certification
to ISO/IEC Guide 22
Manufacturer Max Weishaupt GmbH

Address: Max Weishaupt Straße


D-88475 Schwendi

Product: Industrial burner


Type: WM-G 10/3-A / ZM-LN

The product described above conforms to

Document No.: EN 676


EN 60 335
EN 61 000-6-1
EN 61 000-6-4
EN ISO 12 100

In accordance with the directives

GAD 90/396/EU Gas Appliance Directive


MD 98/37/EU Machinery Directive
PED 97/23/EU Pressure Directive
LVD 73/23/EU Low Voltage Directive
EMC 89/336/EU Electromagnetic
Compatibility Directive

this product is labelled as follows

CE-0085 BQ 0027

Schwendi 04.12.2005

ppa. ppa.
Dr. Lück Denkinger

Comprehensive Quality Assurance is ensured by a


certified Quality Management System
to EN ISO 9001.

2
Contents
1 1 General instructions 5

2 2 Safety instructions 6

3 3 Technical description
3.1 Permissible application
8
8
3.2 Basic function 9
3.3 Gas regulating system 10

4 4 Installation
4.1 Safety notes on installation
11
11
4.2 Delivery, transport and storage 11
4.3 Preparations for installation 11
4.4 Installing the burner 12
4.5 Installing the valve train 14
4.6 Soundness test of valve train 16
4.7 Electrical connection 18

5 5 Commissioning and operation


5.1 Safety notes on initial commissioning
19
19
5.2 Preparation for initial commissioning 19
5.2.1 Minimum connection and setting pressure 23
5.3 Operating the W-FM 24
5.4 Commissioning and setting 25
5.4.1 Pre-set points 30
5.4.2 Burner ignition 31
5.5 Concluding work following commissioning 37
5.6 Shut down periods 39

6 6 Fault conditions and procedures for rectification


6.1 General faults on the burner
40
40
6.2 Faults on the W-FM 41

7 7 Servicing
7.1 Safety notes on servicing
42
42
7.2 Servicing 43
7.2.1 Testing, cleaning and function test (checklist) 43
7.2.2 Criteria for setting / replacement 43
7.3 Removing and refitting mixing head 44
7.4 Setting ionisation and ignition electrodes 45
7.5 Removing and refitting air damper stepping motor 46
7.6 Removing and refitting gas butterfly stepping motor 47
7.7 Removing and refitting FRS spring 48

3
8 8 Technical data
8.1 Burner equipment
49
49
8.2 Capacity graph 49
8.3 Permissible fuels 50
8.4 Mixing head dimensions 50
8.5 Permissible ambient conditions 50
8.6 Electrical data 51
8.7 Weight 51
8.8 Burner dimensions 52

A Appendix
Combustion analysis
53
53
Gas throughput calculation 54
Spare parts 56

4
1 General instructions 1
These installation and operating instructions Hand over and operating instructions
• are an integral part of the equipment and must be kept The contractor is responsible for passing the operating
permanently on site. instructions to the plant operator prior to hand-over. He
should also inform the plant operator that these
• is supplemented by installation and operating instructions should be kept with the heating appliance. The
instructions Combustion Manager W-FM. address and telephone number of the nearest service
centre should be entered on the reverse of the operating
• are to be used by qualified personnel only. instructions. The plant operator must note that an agent of
the contractor or other suitably qualified person must
• contain the relevant information for the safe assembly, inspect the plant at least once a year. To ensure regular
commissioning and servicing of the equipment. inspections, -weishaupt- recommends a service contract.

• are for the attention of all personnel working with the The contractor should instruct the plant operator in the use
equipment. of the equipment prior to hand-over and inform him as and
when necessary of any further inspections that are
required before the plant can be used.

Explanation of notes and symbols


This symbol is used to mark instructions,
which, if not followed, could result in death or Guarantee and liability
serious injury. Weishaupt will not accept liability or meet any guarantee
claims for personal injury or damage to property arising as
DANGER
a result of one or more of the causes below:

• Failure to use the equipment as intended.


This symbol is used to mark instructions, • Improper assembly, commissioning, operating or
which, if not followed, could result in life servicing of the equipment.
threatening electric shock. • Operating the appliance with defective safety
DANGER
equipment, or with non-recommended or non-
functioning safety and protection devices.
• Failure to follow the information in the Installation and
Operating Instructions.
This symbol is used to mark instructions, • Alterations made to the construction of the equipment
which, if not followed, could result in damage by the plant operator.
to, or the destruction of the equipment and • Fitting additional components not tested or approved
ATTENTION
environmental damage. for use with the equipment.
• Alterations made to the equipment by the plant
operator (e.g. motor ratio - rating and speed).
• Alterations made to the combustion chamber, which
hinders constructive, predetermined flame formation.
☞ This symbol is used to mark procedures, which • Inadequate monitoring of parts liable to wear and tear.
you should follow. • Improperly executed repairs.
• Acts of God.
1. Procedures with more than one step are • Damage caused by continued use despite the
2. numbered. occurrence of a fault.
3. • Use of incorrect fuel.
• Obstruction or damage of the supply lines.
❑ This symbol is used when you are required to • Use of non-original -weishaupt- spare parts.
carry out a test.

• This symbol is used to list points.

➩ This symbol indicates detailed information.

Abbreviations
Tab. Table
Ch. Chapter

5
2 Safety information
Dangers when using the equipment Electrical safety
Weishaupt products are manufactured in accordance with • Before starting work - isolate plant and protect against
the relevant existing standards and guidelines and the reactivation, check voltage is isolated, the unit is
recognised safety laws. However, improper use of the earthed, and protected from adjacent equipment that
equipment could endanger life of the user or a third party, might still be under voltage!
or result in damage to the plant. • Work on the electrical supply should be carried out by
a qualified electrician.
To avoid unnecessary danger, the equipment is only to be • Electrical components should be checked during
used: servicing. Loose connections and heat damaged
• for its intended purpose cables should be dealt with immediately.
• under ideal safety conditions • The control panel should be locked at all times. Access
• with reference to all the information in the installation should be restricted to authorised key holder
and operating instructions personnel.
• in accordance with inspection and service work • Should it be necessary to carry out work on live parts,
country specific safety regulations must be observed
Faults, which could affect the safe operation of the burner, and tools to EN 60900 must be used. A second
should be rectified immediately. person should be present to switch off the mains
supply in an emergency.

Personnel training Maintenance and fault rectification


Only competent personnel may work on the appliance. • Necessary installation, service and inspection work
Competent personnel according to this operating manual should be carried out at the specified time.
are persons who are familiar with the installation, • Inform the operator before beginning any service work.
mounting, setting and commissioning of the product and • For all service, inspection and repair work, electrically
have the necessary qualifications such as:- isolate the equipment and ensure the mains switch
• Training, instruction, certification and authorisation to cannot be accidentally switched back on. Isolate the
switch electrical circuits and electrical devices on and fuel supply.
off, to earth them and to mark them in accordance with • If, during servicing or testing, control seal joints have to
the safety standards. be opened, these have to be thoroughly cleaned to
• Training, instruction or authorisation to carry out ensure tight sealing when re-assembling.
installation, alteration and maintenance work on the Damaged seals must be replaced.
relevant fuel fired plant. • Flame monitoring devices, limit controls, correcting
elements and all other safety devices must be
Organisational measures commissioned by, and may only be replaced by, the
• Everyone working on the plant should wear the manufacturer or an authorised agent.
necessary protective clothing. • Screwed connections, which have been loosened,
• All safety devices should be checked regularly. must be re-tightened without cross-threading.
• Following service work, all safety devices should be
Informal safety measures tested to ensure they are functioning correctly.
• In addition to the installation and operating instructions,
local codes of practice should also be adhered to.
Special attention should be paid to the relevant Alterations to the construction of the equipment
installation and safety guidelines given. • No alterations to the equipment are to be made without
• All safety and danger notices should be kept in a the approval of the manufacturer.
legible condition. All conversions require written confirmation from
Max Weishaupt GmbH.
Safety measures in normal operation • Any parts not in perfect working order should be
• Only use the equipment when all the safety devices are replaced immediately.
fully functional. • No additional components may be fitted, which have
• At least once a year the equipment, including the safety not been tested for use with the equipment.
devices, should be checked for signs of visible damage • Use only -weishaupt- spares and accessories as
and to ensure that the safety devices are operating replacement parts. Parts from other manufacturers are
correctly. not guaranteed to be suitable to meet the necessary
• More frequent safety check may be required depending operational and safety requirements.
on plant conditions.
Alterations to the combustion chamber
Safety measures when gas can be smelt • No alterations are to be made to the combustion
• Avoid open flames and spark generation (e.g. switching chamber, which hinder constructive predetermined
lights and electric units on and off, including the use of flame formation.
mobile phones).
• Open windows and doors. Cleaning of the equipment and waste disposal
• Close gas shut off valve. • All materials used should be handled and disposed of
• Warn all occupants and evacuate the building. correctly, with due regard to the environment.
• Inform heating company/installer and gas supplier
from outside of the building.

6
2
Noise of the equipment Gas characteristics
The noise a combustion system makes is the result of a The following information must be obtained from
combination of components and factors, such as the gas supplier:
• burner • Type of gas
• flame • Calorific value in MJ/m3 or kWh/m3
• combustion chamber / boiler • Max. CO2 content of flue gas
• flue gas system • Gas supply pressure
• location and type of building.
Depending on these site conditions, noise could be of a
level sufficient to cause hearing damage. In this case the Pipe thread connection
operating personnel must be equipped with ear-defenders • Only tested and approved sealing material should be
or other such protection. used. Please observe the prevailing user instructions!

General information for gas operation


• When installing a gas combustion system, regulations Soundness test
and guidelines must be observed (i.e. Local Codes of • See Ch. 4.6
Practice and Regulations).
• Depending on the type of gas and gas quality the gas
supply must be designed in such a way that the Conversion to other gases
discharge of liquid substances (e.g. through • When converting to another gas type, a conversion kit
condensation) are avoided. This should be particularly and re-commissioning are required.
considered on liquid petroleum gas installations with
reference to the evaporation temperature.
• The subcontractor responsible for the installation or Gas valve train
changes to the gas system must inform the gas • Observe sequence and flow direction. To ensure
supplier of the type and extent of the installation trouble free start conditions, the distance between
planned and the intended work. The subcontractor DMV and burner should be kept to a minimum.
must ascertain that an adequate gas supply to the
installation is ensured.
• Installations, alterations and maintenance work on gas Thermal shut off device TAE
systems in buildings and below ground must only be • If require, the thermal shut off device TAE
carried out by installers who have a contract with the
gas supplier.
• The gas pipe work must be subject to a preliminary and
main test or the combined loading test and soundness
test, according to the pressure range intended.
• The air or purge gas required for the test must be
expelled from the pipe work. The pipe work must be
completely purged.

7
3 Technical description
3.1 Permissible applications
The Weishaupt gas burner type WM-G 10/3-A / ZM-LN Type codes:
is suitable for:
• heat exchangers according to EN 676 and EN 303-2. Type
• warm water plant WM –G 10 /3 –A / ZM -LN
• intermittent or continuous operation
• warm-air heat exchangers LowNox

The combustion air must be free from aggressive two stage modulating
compounds (Halogen, Chloride, Fluoride, etc.). If the
combustion air within the boiler room is contaminated, Construction type
more frequent cleaning and maintenance will be required.
In these cases operation with ducted air intake is Ratings size
recommended.
Size
Any other use is only permissible with the written
agreement of Max Weishaupt GmbH. Servicing G = Gas
requirements may be at more frequent intervals where
arduous operating conditions demand. Weishaupt burner type Monarch

To maintain certain NOx limit values specific minimum


combustion chamber dimensions and flue gas installation
layout must be observed.
Furthermore, the quality of fuel can have a negative
influence on NOx values.

• The burner must only be operated with the type of gas


given on the burner name plate.
• The gas connection pressure must not exceed the
gas pressure given on the burner name plate.
• The burner must only be operated under the
permissible ambient conditions (see Ch. 8.5).
• The burner must not be used outside. It is only suited
for operation inside.
• The burner must not be used outside of its capacity
range (capacity graph see Ch. 8.2).
• The burner must not be used on appliances having
flame reversal combustion chambers.

8
3
3.2 Basic function
Burner type Low gas pressure switch
• Automatic forced draught gas burner for two stage If the gas pressure is inadequate, the low gas program is
or modulating operation. initiated.
• Type tested to EN 676
• NOx to Emission Class 3
• Electronic compound regulation of all correcting High gas pressure switch
elements If the gas pressure exceeds the set value the high gas
• Operation and setting via display and pressure switch activates a safety shutdown at the
operating unit (ABE). combustion manager.
The gas pressure switch is inactive during standby. During
start-up the gas pressure switch function is delayed by up
Combustion manager to 2 secs., this is to allow for static pressure to dissipate.
• Controls the sequence of operation
• Monitors the flame
• Communicates with the stepping motor FRS gas governor
• Carries out valve proving of the gas valves Equalises variations in pressure from the gas supply
• Is equipped with speed control network, thus providing a constant gas control pressure.
The control gas pressure is set with this device.

Flame sensor
Monitors the flame during all phases of operation. If the DMV double solenoid valve
flame signal does not correspond to the sequence of Automatic release or safety shut off of the gas flow. The
operations, a safety lockout will occur. limiting of the valve stroke, and with it a change of the pres-
sure drop is possible via adjustment of the setting screw.

Stepping motors
Separate stepping motors on: Gas butterfly valve
• Air damper The gas butterfly valve regulates the gas quantity relative to
• Gas butterfly valve the control gas pressure.
Providing precise, direct control of the correcting elements
in compound.
The setting is checked by optical transmitter fitted in the Mixing head
stepping motor. Adjustable combustion head relative to the full load rating
required.

Air damper
The air damper control regulates the combustion air
quantity for optimum combustion.

Air pressure switch


Should there be a fall in the air supply pressure the air
pressure switch causes a safety shutdown at the
combustion manager.

9
3
3.3 Gas regulating system
Valve trains
In accordance with EN 676 all burners must be fitted with In accordance with EN 676 the use of a valve proving sys-
two Class A solenoid valves. Weishaupt gas and dual fuel tem is required for thermal inputs of 1,200 kW or more.
burners are fitted with DMV double solenoid valves as Other valve train components such as gas filter and gas
standard. governor can be found in the Weishaupt accessories list.

Valve train with double solenoid valve (DMV)

9 0

V1 V2

P P P

1 2 3 4 5 6 7 8

1 Ball valve 6 Valve proving gas pressure switch


2 Gas filter 7 Double solenoid valve (DMV)
3 Gas pressure governor/regulator 8 Gas butterfly valve
4 High gas pressure switch 9 Pressure gauge with push button valve
5 Low gas pressure switch 0 Burner

Valve proving Sequence diagram valve proving


Following each controlled shutdown, the combustion
manager carries out a valve proving test of the gas 1st Test phase 2nd Test phase
solenoid valves. Following lockout or power failure, the
valve proving test is carried out prior to burner start.
Valve 1
Function 3 secs.
sek. 10 sek.
10 secs. 33 secs.
sek. 10 sek.
10 secs.
1st Test phase: Valve 2
During a controlled shutdown valve 1 closes
immediately, and valve 2 has a slight delay in closing P between
which permits the volume between V1 and V2 to V1 and V2
depressurise via the gas butterfly valve. The section
between V1 and V2 must remain depressurised once Gas press.
switch VP
the second valve has closed.

2nd Test phase:


Valve 1 opens and immediately closes again, allowing
gas pressure build-up between V1 and V2. During the
test phase, the pressure between the valves must not
fall to below the pressure set at the gas pressure
switch 6.

Result of the test


If a pressure increase (1st test phase) or a pressure loss
(2nd test phase) is detected, the combustion manager
initiates a shutdown.

Pressure switch setting


See Ch. 5.5

10
4 Installation 4
4.1 Safety notes on installation
Electrically isolate plant Only valid in Switzerland:
Prior to installation switch off the mains When installing and operating -weishaupt- gas burners in
switch and the safety switch. Failure to Switzerland the regulations of SVGW and VKF, as well as
comply could cause death or serious injury by local and Cantonal regulations must be observed.
electric shock.
DANGER

Risk of explosion!
Gas leaks can lead to the build-up of
explosive gas / air mixtures. With the presence
of an ignition source, these then result in
explosions.
DANGER

4.2 Delivery, transportation and storage


Check delivery Transportation
Check the delivery to see that it is complete and that there For burner weight see Ch. 8.7.
has been no damage in transit. If the delivery is
incomplete or damaged, contact the deliverer. Storage
Be aware of the permissible ambient conditions for
storage (see Ch. 8.5)

4.3 Preparation for installation


Check burner name plate Space requirement
❏ The burner rating must be within the operating range Burner dimensions see Ch. 8.8
of the heating appliance. The ratings given on the
burner name plate are the minimum and maximum
possible firing rates of the burner; see capacity
graphs (Ch. 8.2).

11
4
4.4 Burner installation
Prepare heating appliance Combustion head extension
The diagram shows the refractory for a heating appliance Boiler constructions with deep refractories or thick doors
without a cooled front. The refractory must not project require a combustion head extension.
beyond the front edge of the combustion head. The Head extensions of 100, 200 and 300 mm are available.
refractory can take a conical shape (≥ 60°). Dimension l1 then changes relative to the head extension
Refractory may not be required on boilers with water- used. Burners with head extensions can still be hinged
cooled fronts, unless the manufacturer gives other open.
instructions. It is important that the burner can be hinged open by
approx. 90° to allow easy, rearwards removal of the mixing
head, which also has the same length extension.

Combustion Dimensions in mm
head d1 d2 d3 d4 d5 I1

G5/3a 162x50 200 240 M10 210 235 1771…1972

1 Combustion head closed


2 Combustion head open

Refractory and drilling dimensions (basic drawing)

Refractory
Drilling dimensions
on the appliance
60° d3
Flange gasket

45°
l1 d1 d2

Fill the air gap with resilient


refractory insulation material
(do not make solid) d4
d5

Limit switch Limit switch


When the burner is hinged closed, a screw on the burner
flange operates the limit switch and electrically completes
the safety circuit.

12
4
Mounting the burner Danger of getting burnt!
Before mounting the burner observe: Some burner parts (e.g. flame tube, burner
❏ Mixing head setting, see Ch. 5.2 flange, etc.) become hot during burner
❏ Ionisation and ignition electrode setting, see Ch. 7.4 operation and should be allowed to cool prior
DANGER to service work being carried out.
1. Screw studs M10 to boiler plate.
2. Fit hinge flange and flange gasket to boiler plate with
nuts and washers.
3. Remove view port cover.
4. Using suitable lifting equipment lift burner and mount
onto boiler plate and secure with hinge pin (observe
hinging direction required).
5. Secure burner with dome nut and washer.
6. Connect the ionisation and ignition cables and re-fit
view port cover.
7. Fit plug to gas butterfly valve motor.

Mounting the burner

13
4
4.5 Gas valve train installation
Risk of explosion! ☞ Flange seals must be fitted correctly on machined
Gas leaks can lead to the build-up of explosive faces.
gas/air mixtures. With the presence of an ☞ Tighten screws evenly diagonally opposite.
ignition source, these then result in ☞ Valve trains must be mounted tension-free.
explosions. Do not compensate for misalignment by over-
DANGER tightening.
☞ The valve trains must be fixed and supported securely.
To avoid accidents, please follow the following safety They must not be allowed to vibrate during operation.
instructions on valve train installation. Supports suitable for the site should be fitted during
installation.
☞ Before beginning work, close all the relevant shut off ☞ Observe the maximum permissible total pressure in the
devices and ensure they cannot be accidentally valve trains. Ask your gas supplier for the correct gas
reopened. main supply pressure.
☞ Ensure the valve train components are correctly The supply pressure must not exceed the permissible
aligned and that all the joints are clean. total pressure.

Additional installation notes:


A vent hose leading to atmosphere should be connected To improve start conditions, the distance between burner
to vent the valve train. and solenoid valves (ignition and mains gas) should be as
short as possible.
To allow the appliance door to be hinged open, a flange Observe sequence and flow direction of valve train
‘break-point’ should be fitted - if possible at door level. components.

If a thermal shut off device TAE is required, this must be Installation position double solenoid valve and FRS
fitted upstream of the ball valve. • DMV and FRS can be positioned with the actuator axis
angled from standing vertical to lying horizontal in
horizontal pipework.
• High pressure regulator see Installation and operating
instruction Pressure regulating units Print No. 12.
Installation example high pressure supply with DMV

1 2 3 4 56 7

9 8

1 Double solenoid valve DMV 6 Pressure gauge with push button valve
2 Test burner 7 Ball valve
3 High gas pressure switch 8 Low gas pressure switch
4 High pressure pressure regulator/governor 9 Valve proving gas pressure switch
5 Filter
14
4
Installation example low pressure supply with flanged DMV

1 2 3 4 5 6 7

0 9 8

Installation example low pressure supply with screwed DMV

1 2 3 4 5 6 7

0 9

1 Double solenoid valve DMV 6 Pressure gauge with push button valve
2 Test burner 7 Ball valve
3 High gas pressure switch 8 Compensator
4 Low pressure pressure regulator/governor 9 Low gas pressure switch
5 Filter 0 Valve proving gas pressure switch

15
4
Mount gas pressure switch to DMV Mount gas pressure switch to DMV
1. Remove closing plug 1 on DMV
2. Fit sealing ring 2 provided to the gas pressure switch Flanged version
3, ensuring that sealing surfaces are clean.
3. Mount gas pressure switch on the DMV with the
screws 4 provided.

2
3

4
3

Screwed version

1
1

2
2
3
3
4
4

4.6 Soundness test of valve trains


Following service work on gas carrying fittings
and connection points a soundness test
should be carried out.
DANGER

❏ Soundness test of the gas train must be carried out


with the main isolating cock and gas valves closed.

Test pressure in valve train: ___________ 100 to 150 mbar


Wait. time for pressure equalisation: _________ 5 minutes
Test duration: ____________________________ 5 minutes
Max. permissible pressure loss: ________________ 1 mbar

16
4
First test phase: Soundness test
Ball valve up to first valve seat
1. Connect test assembly to the filter and on inlet of valve
V1 (test point 1; min. gas pressure switch).
2. Open test point between V1 and V2.

Note When using high pressure regulators it may be


necessary to temporary close the vent line
during the soundness test if the safety relief V1 V2
valve opens during the soundness test
pressure is being applied.
It is important to re-open the vent line once the
soundness test is complete.
5
1
Second test phase:
2
Valve section and second valve seat
1. Connect test assembly to test point between V1 and
V2. (valve proving gas pressure switch) 3 3

Third test phase:


Valve train connection parts up to gas butterfly
The third test phase can only be carried out during
operation and by using a leak detection solution.

Note: only use leak detection foaming solutions, which


do not cause corrosion

☞ Following a soundness test close all test points!

Checking zero-flow shut-off (only with high pressure


regulator):
1. Open ball valve and wait until the output pressure of 4
the regulator is stabilised.
During this time the safety relief valve (SBV) must not
open.
2. Close the ball valve and check that the pressure
difference between inlet and outlet pressure of the
4
regulator remains constant.

Documentation
☞ Results of the pressure test must be recorded on the 1 Rubber hose with T piece
service/commissioning report. 2 Aspirator
3 Manometer (U tube or pressure gauge)
4 Hose clamp
5 Double solenoid valve DMV

Test points on DMV-D 507 to 520 Test points on DMV-D 5065/11 to 5100/11

4 5 6 7 1 2 3 5
1 2 3 4

3 4 pmax. = 500 mbar 6 7


2 pmax. = 500 mbar 4 5 2 5
1 V1 V2
1 3 V1 V2
4
1 2 3 5
1 2 3

Test point 1 and 4 : Pressure into V1 Test point 1, 2 and 6 : Pressure into V1
Test point 2 : Pressure between V1 and V2 Test point 3 : Pressure between V1 and V2
and ignition gas outlet Test point 4 : Ignition gas outlet
Test point 3 : Pressure after V2 Test point 5 and 7 : Pressure after V2
Test point 5 : Pressure after V2

17
4
4.7 Electrical connection
De-energise plant
Prior to installation switch off the mains switch
and the safety switch.
Failure to comply could cause death or
DANGER serious injury by electric shock.

Note Applicable only if a frequency converter is Installation of terminal box gas valve train
used: It is possible that electrical components • Connect solenoid valve plug Y2 in accordance with the
continue to carry voltage even after the mains burner wiring diagram.
have been switched off because a frequency Depending on plant conditions, the connection of an
converter is fitted. A waiting time of 5 minutes external gas solenoid valve (Y3) may be required.
should therefore be observed prior to starting
work. • Connect gas pressure switch in accordance with the
burner wiring diagram.

A burner specific wiring diagram is supplied with the


burner. All electrical connections must be made to this Installation fan motor
wiring diagram. Local regulations must be observed. Open terminal box on motor and carry out connection in
accordance with wiring diagram (observe motor rotation).
Note Carry out electrical installation in such a way that The motor must be protected against heat radiation and
it is possible to hinge the burner open. short circuits. The use of a motor protection switch is
recommended. Prior to replacing the motor contactor it is
recommended to mark the cables in accordance with the
Installation W-FM terminal numbers.
Connect inputs, outputs, and voltage supply to the
W-FM in accordance with the wiring diagram supplied.
☞ Use cable entry on burner housing. Notes for Austria
Electrical isolation with a minimum of 3 mm contact gap,
Voltage supply : acting on all poles, must be fitted adjacent to the burner.
It is of paramount importance that the electric supply is Possibilities are:
provided and connected correctly. Local requirements • Switch (without micro-contacts) with required
have to be adhered to, and it must be ensured that both separation characteristics
neutral (N) and earth potential (PE) conductors at the • Circuit breaker
installation, have zero potential, that is to say exhibits no • Contactor
trace of any voltage. It might be permissible to connect the • Screw in type fuse with clearly recognisable
neutral to a proven earth, as this will usually drain any designation
induced voltage.
Do not confuse phase (L) and neutral conductor (N)
connections, otherwise operational safety will be jeopar-
dised. It is also important that the neutral is not switched,
and if it is desirable to isolate the neutral a removable link
is preferred. This is to prevent voltage spikes, and also to
alleviate problems that could occur if the neutral was
switched-off prior to the voltage being switched-off.
Observe the requirements of EMC 89/336/EEC and LVD
73/23/EEC.

Cables:
The cross sectional area of the cables for L, N, and E, and
of the safety circuit must be in accordance with the
nominal current of the prefusing (max.16 AT).
All other cable connections must be designed in
accordance with the internal unit fusing (6.3 AT).

For the cable length the following applies:


• Display and operating unit, BCI maximum 10 m
(100 pF/m).
• Load controller, safety circuit, burner flange, reset
button maximum 20 m (100 pF/m).

18
5 Commissioning and operation 5
5.1 Safety notes on commissioning
Check installation Safety notes on initial commissioning
All installation work must be completed and The initial commissioning must only be carried out by the
checked prior to commissioning. The burner supplier, manufacturer or their appointed agent. At this
must be fitted to the heating appliance ready time, all the control and safety equipment must be checked
for operation and must be wired to all control to ensure correct operation and, if an item can be adjusted,
DANGER and safety devices it should be checked that it has been set correctly.

Furthermore the correct fusing of the circuits and the


❏ Burner mounted, annulus between the flame tube and measures for contact protection of electrical equipment
refractory filled with ceramic fibre. (see Ch. 4.4). and of all wiring must be checked.
❏ Fuel supply complete
❏ Electrical connections and controls complete

5.2 Preparations for initial commissioning


Venting the gas lines Note If work has been carried out on the gas
The gas supply pipe work should be purged/vented only supply lines, i.e. replacement of parts, fittings
by the local gas authority. These supply lines should be or gas meter, re-commissioning of the burner
purged with gas until the air or the inert gas has been fully may only commence once the affected parts
expelled. of the gas line have been vented and a sound-
ness test has been carried out by the local gas
authority.

Check gas connection pressure


Risk of explosion! 1. Connect manometer to filter (on high pressure
Excessive gas pressure can damage the valve supplies the inlet to the high pressure regulator is
train components. fitted with a manometer as standard).
The mains gas pressure must not exceed the 2. Slowly open the ball valve on the gas train and
DANGER max. permitted pressure of the valve trains monitor the manometer reading at all times.
listed on the burner nameplate. The mains gas 3. Close the ball valve immediately if the mains gas
pressure must be checked prior to pressure exceeds the max. permitted pressure of the
purging the valve train. valve train.
The burner must not be started!
Contact the plant operator.

Venting the valve train Vented valve train


❏ Ensure gas connection pressure is correct.
1. A hose leading to safe open atmosphere is connected
to test point V1 of the solenoid valve. Use a test burner to ensure that
2. With the ball valve opened the gas mixture in the valve no air is present in the valve train.
train vents via the hose to safe atmosphere until neat
gas is detected.
3. Close the ball valve and remove the venting hose, and
immediately close V1 test point.
4. Use a test burner to ensure that no air is present in the
valve train.

Note The test burner must not be used to vent the


valve train.

19
5
Setting the mixing head Set dimensions e
The mixing head (dimension e) should be set to the
required combustion heat rating QF. Flame tube setting
open closed
Dimension e:
Distance from hinged flange to flame tube.
When setting pay attention to the centralisation of the e
flame tube, it is therefore recommended to determine
dimension e at three points (120° radially).

Example 1

Required burner rating QF 550 kW


Combustion chamber pressure 2.0 mbar
Results in: Flame tube setting (dim. e) 172 mm
Air damper setting 46°

Example 2
Hinge open the burner
Required burner rating QF 750 kW The mixing head can be adjusted while it is fitted to the
Combustion chamber pressure 4.0 mbar appliance. The burner can be hinged open towards the
Results in: Flame tube setting (dim. e) 186 mm hinge pin.
Air damper setting 60°-70° ➩ see Ch. 7.3

Setting diagram mixing head (dimension e)

10

9
Air damper setting 30° 40° 50° 60°
8

7 20°
Combustion chamber pressure [mbar]

5
10°
4
2
3

2
1
1

0 192

-1

-2
Dimension e [mm] 172 175 178
-3
Flame tube setting (dimension e)
-4
0 100 200 300 400 500 600 700 800 900 1000

Combustion heat rating [kW]

The setting diagram is sectioned into two areas:

• Flame tube setting (dimension e) 172 mm • Air damper setting 60° - 70°
• Air damper setting depending on rating • Flame tube setting (dimension e) depending on rating
required required

20
5
Connecting manometer Pressure measurement (pressure into mixing head)
To test the fan pressure into the mixing head during initial
commissioning.

Measuring ionisation current Measuring ionisation current


When a flame exists, an ionisation current is produced.

Ionisation current Display flame signal ABE

min. 4 µA DC approx. 30 %

max. 16 ... 40 µA DC approx. 100 %

Measuring device:
Multi meter or micro-ammeter.

Connection:
Disconnect the ionisation lead from the plug coupling and
connect meter in series.

Checklist for initial commissioning


❏ The heating appliance must be assembled ready for ❏ Fuel carrying parts must be purged of air.
operation. ❏ Burner hinge flange must be closed and secured
❏ The operating instructions of the heat exchanger must ❏ Soundness test of the valve train must have been car-
be adhered to. ried out and documented.
❏ The whole plant must be wired correctly. ❏ Gas connection pressure must be correct.
❏ The heating appliance and the heating system must be
sufficiently filled with heating medium.
❏ Flues must be free from obstructions.
❏ Flue gas dampers must be open.
❏ Sufficient clean combustion air must be available.
❏ The required test points for combustion analysis must
be available.
❏ Water level controls and interlocks must be set
correctly. Note Dependent on site requirements, further
❏ Thermostat, pressure switch and other safety devices checks may be necessary. Note the
must be in operating position. instructions for the individual items of plant
❏ There must be a heat demand. equipment.

21
5
Calculate setting pressure Preset setting pressure
Determine the control pressure setting for full load from table
“Minimum connection pressure and setting pressure”
(see Ch. 5.2.1) and note it down.

Note The combustion chamber pressure has to be


added to the control pressure setting determined.

Preset setting pressure


❏ Check output pressure range of the spring fitted to the
governor/regulator.

1. De-regulate gas governor/regulator for initial


commissioning.

2. With the ball valve closed, open test point before V1


and connect manometer.

3. Slowly open ball valve and using a test burner


measure available pressure before V1.

4. Adjust the spring setting to the control pressure


already determined.

5. Close ball valve.


Springs for FRS
Type of spring / colour output pressure range

orange 5 to 20 mbar
blue 10 to 30 mbar
red 25 to 55 mbar
yellow 30 to 70 mbar
black 60 to 110 mbar
pink 100 to 150 mbar

Check valve lift on V1 (on DMV) Set valve lift V1


The maximum valve lift should have been set on the DMV.

22
5
5.2.1 Minimum connection pressure and setting pressure
Burner type: WM-G 10/3-A / ZM-LN

Connection pressure Control pressure


Burner Low pressure supply High pressure supply
rating (gas pressure in mbar into isolating valve, (setting pressure in mbar
pemax = 300 mbar) into double solenoid valve)

Nominal diameter of valve trains Nominal diameter of valve trains


3
/4” 1” 11/2” 2” 65 80 100 3
/4” 1” 11/2” 2” 65 80 100
Nominal diameter of gas butterfly valve Nominal diameter of gas butterfly valve
[kW] 50 50 50 50 50 50 50 50 50 50 50 50 50 50

Natural Gas E (N), Hi = 37.26 MJ/m3 (10.35 kWh/m3), d = 0.606


450 87 30 14 12 10 9 9 46 12 8 8 7 6 6
500 106 37 17 14 12 11 10 57 15 10 10 8 8 8
550 128 44 20 16 13 12 12 69 18 12 12 10 9 9
600 152 51 23 19 15 14 13 82 21 14 14 12 11 11
650 177 59 26 21 17 15 15 96 25 16 16 13 12 12
700 204 67 28 23 18 16 15 110 27 17 17 14 13 13
750 232 75 31 24 19 17 16 125 30 19 18 15 14 13
800 263 84 34 26 20 18 17 – 33 20 20 16 15 14
850 295 94 36 28 22 19 18 – 36 22 21 17 16 15
900 – 103 39 30 23 20 19 – 40 23 23 18 16 16

Natural Gas LL (N), Hi = 31.79 MJ/m3 (8.83 kWh/m3), d = 0.641


450 123 41 17 14 11 10 10 65 16 10 10 8 7 7
500 151 49 21 17 13 12 11 81 20 12 12 10 9 9
550 182 59 24 19 15 14 13 97 23 14 14 12 11 10
600 216 70 28 22 18 16 15 116 28 17 17 14 12 12
650 252 81 32 25 20 17 16 135 32 19 19 15 14 14
700 291 92 36 28 21 18 17 – 36 21 21 17 15 14
750 – 104 39 30 23 20 18 – 40 23 23 18 16 15
800 – 117 43 33 24 21 19 – 44 25 25 19 17 16
850 – 130 47 35 26 22 20 – 48 27 27 20 18 17
900 – 145 52 38 28 23 21 – 53 29 29 22 19 18

The details given for calorific value Hi relate to 0° C and With low gas pressure supplies pressure
1013 mbar. governors/regulators to EN 88 with safety diaphragm are
used. Maximum permissible connection pressure into
The results of the tables have been calculated on flame isolating valve is 300 mbar on low gas pressure
tubes under idealised conditions. The values are therefore installations.
guidelines for basic settings. Small variations may occur With high pressure supplies HP regulators to DIN 3380
when commissioning depending on individual installations. are selected from the technical brochure “Pressure
regulating and safety assemblies for Weishaupt gas and
Note The combustion chamber pressure in mbar dual fuel burners”. HP regulators for connection pressure
must be added to the minimum gas pressure up to 4 bar are detailed in this brochure.
determined.
Maximum connection pressure, see nameplate.
The min. connection pressure should not be
below 15 mbar.

23
5
5.3 Operating the W-FM
Button designation Button designation

Button Function

1 Enter:
Saves value changes.
Reset of lockout
Access to parameters and values
Press 1… 3 seconds = Info level
Press 3… 5 seconds = Service level
Navigation in Service and Info level

2/3 + or –:
Navigation through the parameter structure
Change setting values

2&3 Press + and – simultaneously (esc):


Stop / return via Escape function

4 A (Air):
Selects the air stepping motor

5 F (Fuel)
Selects the fuel stepping motor

4&5 Press A and F simultaneously (VSD):


● Selects the frequency converter

● Calls up service expert level (SE)

Emergency Off Function


Simultaneous pressing of ‘Enter/Info’ and one other button
will initiate an immediate lockout.

Display Display
The black dashes of the symbols show the status of the
inputs and outputs, the unit of values and the active level.

1 Heat demand by heater controls


2 Burner fan motor
3 Ignition
4 Fuel valve
5 Flame signal on
6 Flame failure or lockout
7 Load point angle setting
8 Percentage value
9 not used
0 Throughput Oil (total)
q not used
w Throughput Gas (total)
e Stepping motor opening
r Stepping motor closing
t Service level
z Info level
u Parameter mode (service expert level)

24
5
5.4 Commissioning and setting
➩ In addition to this chapter the installation and
operating instructions Combustion Manager W-FM
should be observed.
This document includes further information about:
• Menu structure and navigation
• Parameter settings
• Editing of load points
• Function, etc.

Pre-setting gas and air pressure switches These settings for the gas and air pressure
Air pressure switch: __________________ approx. 8 mbar switches are only valid during commissioning.
Low gas pressure switch: ____ approx. 1/2 control press. Once commissioning is complete, the gas and
High gas pressure switch: __ approx. twice control press. air pressure switches should be set to
Valve proving gas press. switch: approx. 1/2 control press. DANGER Ch. 5.5.
The low gas pressure switch should be
Note The value set on the gas pressure switch for re-adjusted once the setting pressure has
valve proving should be greater than the maxi- been pre-set in ignition position.
mum mixing pressure during pre-purge and
less than the static gas pressure existing.

Voltage supply ON Display for commissioning


The display shows either OFF or OFF UPr.
S S
P P

OFF = burner off i i

UPr = not programmed m3 m3/h l l/h % m3 m3/h l l/h %

not programmed programmed

Enter password Enter password


1. Press button [F] and [A] simultaneously until the dis-
play shows CodE.
2. Using button [+] or [–] enter first digit and confirm with
[ENTER]. S
Repeat procedure until password has been entered. P
i
3. Exit password entry via [ENTER]. S
The display shows PArA for a short time and then m3 m3/h l l/h % P
i
changes over to 400: SEt and a black dash ap-
pears next to the P symbol. m3 m3/h l l/h %

S
P
i

S
P m3 m3/h l l/h %
i

m3 m3/h l l/h %

Burner ON Burner on
1. Open fuel shut off devices.
S

2. Check appliance's safety devices, STB, pressure and P


i
temperature controllers, etc. must be in operating
position. m3 m3/h l l/h %

3. Start burner in manual operation.


A black dash appears below the S symbol on the
display.
For the duration of the commissioning a heat demand is
required from the appliance controller, that means
signal on input X5-03/1.

25
5
Start setup Start set-up
Press [ENTER] button.
S
P
If the combustion manager has been pre-set, the display i

shows run. You can now start the adjustment of m3 m3/h l l/h %
operating point P1.

or

If the combustion manager has not been programmed programmed not programmed
(i.e. first commissioning) the display shows parameter S S
P P
201 and the following parameters have to be defined i i

prior to any adjustment being made. m3 m3/h l l/h % m3 m3/h l l/h %

201 : Type of operation


542 : Activation frequency convertor
641 : Speed standardisation

Now adjustments can be made, starting with the


pre-setting of ignition load point P0.

Set type of operation Set type of operation


1. Press [ENTER] button, the display shows only
the parameter value. S
P
i

2. Using [+] or [–] set type of operation 1 (direct ignition) m3 m3/h l l/h %
and confirm with [ENTER].
S
P
3. Exit entry using [esc]. i

The display shows parameter 201 with the current S


P m m /h l l/h %
3 3

type of operation. i

m3 m3/h l l/h %

S
P
i

m3 m3/h l l/h %

26
5
Activate/deactivate frequency converter Activate/deactivate frequency converter
1. Press [+] button, the display shows parameter 542.

2. Press [ENTER] button, the display now only shows the


parameter value. S
P
i
3. Using [+] or [–] activate or deactivate the frequency
m3 m3/h l l/h %
converter and confirm by pressing [ENTER].
0 = without frequency converter S

1 = with frequency converter P


i

S
P m m /h l l/h %
3 3

4. Exit entry using [esc]. i


The display shows parameter 542 with the current
m3 m3/h l l/h %
setting.
S
P
i

m3 m3/h l l/h %

Carry out speed standardisation Speed standardisation


1. Press [+] button, the display shows parameter 641.

Note Speed standardisation should only be carried


out if a frequency converter is fitted. S

If a frequency converter is not fitted, the P


i
following steps can be skipped.
m3 m3/h l l/h %

2. Press [ENTER] button. S


P
i
3. Using [+] set value to1 and start standardisation by S
P m m /h l l/h %
3 3

pressing [ENTER]. i
The fan motor starts when the air damper opens.
m3 m3/h l l/h %
Once standardisation is complete, the display changes
from 1 to 0.

4. Exit speed standardisation using [esc]. S


P
i

S
P m3 m3/h l l/h %
i

m3 m3/h l l/h %

S
P
i

m3 m3/h l l/h %

27
5
Pre-set ignition and full load points Pre-setting ignition and full load points
For details of pre-set values for fuel and air stepping mo-
tors see burner installation and operating instructions. S
P
i

Note The ignition and full load point must only be m3 m3/h l l/h %
pre-set on combustion managers, which have
not been programmed. If the combustion
manager has already been programmed,
pre-setting is skipped. S
P
i

1. Press [+] button, the display shows the ignition m3 m3/h Pl


S
l/h %
load point P0. i

m3 m3/h l l/h %
2. Press and hold button [A] and using buttons [+]/[–]
enter air damper position 4° - 6°. S
P
i

3. Press and hold button [F] and using buttons [+]/[–] m3 m3/h l l/h %
enter gas butterfly valve position 9° - 12°.
S VSD
P
4. Press and hold button [A] and [F] (VSD) i
only when using a
simultaneously and using button [+]/[–] enter speed S
frequency converter
P m3 m3/h l l/h %
(only when using a frequency converter). i

The ignition speed should not fall below 70%. m3 m3/h l l/h %

5. Press [+] button, the display shows the full load


point P9.
S
P
6. Press and hold button [A] and using buttons [+]/[–] i

enter air damper position from setting diagram, Ch. 5.2. m3 m3/h Pl
S
l/h %
i

7. Press and hold button [F] and using buttons [+]/[–] m3 m3/h l l/h %
enter gas butterfly valve position 45° - 50°.
S
P
8. Press and hold buttons [A] and [F] (VSD) i

simultaneously and using buttons [+]/[–] enter speed m3 m3/h l l/h %


(only when using a frequency converter).
Set speed to 100%. S VSD
P
i
only when using a
9. Press [+] button, exit pre-setting. S
frequency converter
P m3 m3/h l l/h %
The display changes over to run. i

m3 m3/h l l/h %

S
P
i

m3 m3/h l l/h %

28
5
Select type of setting Select type of setting
Pre-setting without flame and adjustment with flame can
be selected. S
P
Pre-setting without flame is only used, if the operating i

points are already known, for example if the combustion m3 m3/h l l/h %
manager is exchanged.

Adjustment with flame (Ch. 5.4.2):


Press [ENTER] button, the burner starts pre-purge
and stops in ignition position without igniting. The with flame without flame
display shows the ignition load point P0. S S
P P
i i

or m3 m3/h l l/h % m3 m3/h l l/h %

Pre-setting without flame (Ch. 5.4.1):


Press [esc] button, the display shows the S
P
operating point P1 and the black dash below the i

S symbol disappears. m3 m3/h l l/h %

S
P
i

m3 m3/h l l/h %

29
5
5.4.1 Pre-set points
Pre-set operating points (without flame) Pre-set operating stages
This step must only be carried out, if the type of setting
“without flame” has been selected. S
P
The adjustment with flame is not replaced by this process. i

S
m3 m3/h Pl l/h %
1. Press and hold button [A] and using buttons [+]/[–] i

pre-set air damper position. m3 m3/h l l/h %


Press and hold button [F] and using buttons [+]/[–]
pre-set fuel stepping motor position. S
P
Press and hold buttons [A] and [F] (VSD) i

simultaneously and using buttons [+]/[–] pre-set the S


m3 m3/h l l/h %
P
speed (only when using a frequency converter). i

m3 m3/h l l/h %
2. Press [+] button, the combustion manager starts
the calculation. The display briefly shows CALC and
then changes over to P2.
S
P
3. Set fuel and air damper stepping motor positions and i

speed. S
m3 m3/h l l/h %
P
i

4. Using the [+] button select and pre-set points P3 to P9 m3 m3/h Pl


S
l/h %
in sequence. i

m3 m3/h l l/h %
Note If the [+] button is pressed for more than
4 secs., a new calculations starts from the S
P
point displayed to point P9. i

S
P m3 m3/h l l/h %
5. Exit pre-setting using [esc], the display i

shows 400 SEt. m3 m3/h l l/h %

6. Press [ENTER] button, the display shows run.

7. Press [ENTER] button, the burner starts pre-purge and S


P
stops in ignition position without igniting, the display i

shows the ignition load point P0. m3 m3/h l l/h %

S
P
i

m3 m3/h l l/h %

S
P
i

m3 m3/h l l/h %

S
P
i

m3 m3/h l l/h %

S
P
i

m3 m3/h l l/h %

30
5
5.4.2 Burner ignition
Set mixing pressure in ignition position Set mixing pressure in ignition position
approx. 0.5…2 mbar
S
P
1. Press and hold button [A] and using buttons [+]/[–] i

set air damper position. m3 m3/h Pl


S
l/h %
i

2. Press and hold buttons [A] and [F] (VSD) S


m3 m3/h l l/h %
P
simultaneously and using buttons [+]/[–] set the speed i

(only when using a frequency converter). m3 m3/h l l/h %


Ignition speed min. 70%.

Ignition
Press [+] button, the burner ignites and stops in ignition Ignition
position.
The display shows the operating phases:
Ph 38 (ignition on),
Ph 40 (fuel valve), S

Ph 42 (ignition off), P
i
Ph 44 (flame in ignition position). S
P m3 m3/h l l/h %
i

S
P m3 m3/h l l/h %
i

S
P m3 m3/h l l/h %
i

S
P m3 m3/h l l/h %
i

m3 m3/h l l/h %

Pre-set fuel pressure


The setting pressure can be found in table Setting
pressure (see Ch. 5.2.1).

Carry out combustion analysis


Determine CO and O2 values and if necessary optimise
combustion by adjusting the ignition positions.

31
5
Pre-set operating point P1 Pre-set operating point P1
1. Press [+] button, the display shows the
operating point P1.

2. Pre-set fuel throughput and air quantity whilst S

observing the combustion values. Operating point P1 P


i
should lie below the required partial load and within
m3 m3/h l l/h %
the capacity graph (see Ch. 8.2).
S

Note When using a frequency converter, operating P


i
point P1 should have a minimum speed of
m3 m3/h l l/h %
50%. To achieve this, open air damper and
reduce speed alternately. S
P
i
3. Press [+] button, the display shows operating
m3 m3/h l l/h %
point P2.
If no other points have been defined, the combustion S VSD
manager carries out a calculation and calculates all P only when using a
i
frequency converter
missing points up to P9. S
m3 m3/h l l/h %
The display briefly shows CALC. P
i

m3 m3/h l l/h %

S
P
i

S
P m3 m3/h l l/h %
i

m3 m3/h l l/h %

32
5
Drive to full load Drive to operating points P2 to P9
1. Using the [+] button drive to points P2 to P9 in
sequence. P
S

2. Check and correct combustion values (air excess, m3 m3/h Pl


S
l/h %
flame stability) at each point. i

It is usually sufficient to alter the fuel throughput. P


S
m3 m3/h l l/h %
i

Note If the [+] button is pressed for more than m3 m3/h l l/h %
4 secs., a new calculations starts from the
point displayed to point P9.
S
P
i

m3 m3/h l l/h %

S
P
i

S
m3 m3/h Pl l/h %
i

S
P m3 m3/h l l/h %
i

m3 m3/h l l/h %

Adjusting full load Adjusting full load


1. Determine and set fuel throughput in full load P9 whilst
observing the ratings information given by the boiler S
P
manufacturer and the capacity graph of the burner. i

Adjust gas throughput at approx. 60°…70° gas m3 m3/h Pl


S
l/h %
butterfly setting using the setting screw on the i

pressure regulating valve. m3 m3/h l l/h %

2. Determine combustion limit and set excess air. S


P
When using a frequency converter, the fan speed i

should be selected as slow as NOx and flame stability m3 m3/h l l/h %


permit, however it should not be less than 80%.
S VSD
3. Re-determine fuel quantity throughput and adjust if
P only when using a
i
frequency converter
necessary. S
m3 m3/h l l/h %
P
i

➩ See burner installation and operating instructions for m3 m3/h l l/h %


detailed notes on combustion analysis.

Note The fuel pressure must not be altered once


this work has been completed.

33
5
Initiate a calculation Initiate a calculation
To achieve a linear air damper and/or speed setting, it is
necessary to initiate a calculation of points P9 to P1. P
S

1. Press [–] button for approx. 4 seconds, until the display m3 m3/h l l/h %
shows CALC.
approx. 4 secs.
2. Release [–] button, the display shows the operating
point P8. P
S

m3 m3/h l l/h %
S
P
i

m3 m3/h l l/h %

Adjusting the operating points Adjusting the operating points


The combustion optimisation of the operating points
should only be carried out using the gas butterfly valve S
P
stepping motor. i

If the air quantity is altered, this influences the linearity, m3 m3/h Pl


S
l/h %
which has a negative effect on the load control and/or i

speed control. S
m3 m3/h l l/h %
P
i

1. Carry out combustion analysis. m3 m3/h l l/h %

2. Press and hold button [F] and using buttons [+]/[–]


optimise combustion.
S
P
3. Repeat procedure until operating point P1 has been i

reached. m3 m3/h l l/h %

Note If a calculation is triggered accidentally, any


operating points already adjusted will be S
P
overwritten. i

S
m3 m3/h Pl l/h %
i

S
P m3 m3/h l l/h %
i

m3 m3/h l l/h %

34
5
Set upper load limit Upper load limit
Full load can be limited via parameter 546.
S
P
1. Exit setting mode using [esc], the display shows 546 i

(– – – – = no load limit). m3 m3/h l l/h %


If no load limit is to be defined skip steps 2 to 4.

2. Press [ENTER] button, the display shows only the


parameter value. P
S

3. Set load limit using buttons [+] or [–] and confirm with m3 m3/h l l/h %
[ENTER].
S
P
4. Exit entry using [esc] button. i

The display shows parameter 546 with the current 3


S
P m m /h l
3
l/h %
load limit. i

m3 m3/h l l/h %

S
P
i

m3 m3/h l l/h %

Set lower load limit (partial load) Lower load limit


Partial load can be limited via parameter 545.
S
P
1. Press [+] button, the display shows 545 i

(– – – – = no load limit). m3 m3/h l l/h %

2. Press [ENTER] button, the display shows only the


parameter value.
S
P
3. Using buttons [+] or [–] set load limit and confirm with i

[ENTER], burner drives to value set. m3 m3/h l l/h %

4. Measure fuel throughput and if necessary adjust the P


S

value. i

S
P m m /h l l/h %
3 3

5. Exit entry using [esc] button. i

The display shows parameter 545 with the current m3 m3/h l l/h %
load limit.
S
P
i

m3 m3/h l l/h %

35
5
Save points Exit commissioning
1. Exit level using [esc] button, the display shows
400 SEt. P
S

2. Exit entry using [esc] button, the black dash m3 m3/h l l/h %
next to the P symbol disappears and the display shows
oP with the current load.
S
P
i

m3 m3/h l l/h %

S
P
i

m3 m3/h l l/h %

Check start behaviour


1. Switch off burner and restart.

2. Check start behaviour. If necessary adjust ignition load.

Note If the ignition load setting has been changed,


the start behaviour has to be re-checked.

36
5
5.5 Concluding work following commissioning
Set low gas pressure switch Gas pressure switch
The switch point must be checked and if necessary
adjusted during commissioning.
Test point
1. Connect manometer to the test point of the low gas
pressure switch.
2. Start the burner and run it to high fire (full load).
3. Slowly close ball valve until either:
• the gas pressure drops to 70% of the control
pressure 10
• flame stability considerably worsens, 20

• the CO value increases (< 1000 ppm),

30

150
• or the flame signal reading falls below the minimum

50

130
value.

70
11
4. Determine gas pressure and open ball valve.
0
90
5. Set the gas pressure determined on the setting dial.
6. Check the switch point at 40-50% of rating:
If the ball valve is now slowly closed again, the switch
off pressure can be checked. The burner control must
not initiate a lockout shutdown.

Set valve proving gas pressure switch Calculate setting pressure gas pressure switch
The switch point is set between regulating pressure PR
and mixing pressure at pre-purge PV.
1. Following controlled shutdown, use test burner to re-
duce static gas pressure and determine gas control
pressure PR at inlet of valve V1.
2. Determine maximum mixing pressure at pre-purge PV
downstream of valve V2.
3. Calculate setting pressure using the formula below and
set at gas pressure switch.
4. Check: Following a controlled shutdown, the burner
must carry out a valve proving without
initiating a valve proving lockout shutdown.

PR + PV
= setting pressure PV
2
PR / PF
Set high gas pressure switch
Must be set to 1.3 x PF (flow pressure at full load).
(Function see Ch. 3.2).

37
5
Set air pressure switch Differential pressure measurement
The switching point setting must be checked and if
necessary adjusted during commissioning.
1. Remove closing cap from air pressure switch and
connect a manometer. 10 5 2,5
2. Using T piece connect low-pressure hose to

15

m
ba
r
20
manometer.

50
5

45
3. Start burner.
2
30 40 35

4. Carry out differential pressure measurement across the


whole ratings range and determine the lowest
differential pressure.
5. Set 80% of the determined scale value on the setting
dial.

lowest differential pressure:___________________13 mbar


switch point air pressure switch: ____13 x 0.8 = 10.4 mbar

Note Installation dependant influences on the air


pressure switch, such as flue gas recirculation,
heating appliance installation, or air supply,
may result in slight adjustments having to be
made to the settings.

Concluding work
☞ Operation of the safety devices (i.e. pressure switches,
thermostats, etc.) on the plant should be checked and
adjusted during operation.

☞ Document burner settings and combustion readings.

☞ Inform the operator about the use of the equipment.

38
5
5.6 Shutdown periods
For short breaks in operation
(e.g. flue cleaning etc.):
☞ Isolate the burner from the power supply.

For longer breaks in operation:


☞ Isolate the burner from the power supply.
☞ Close all fuel shut off devices.

39
6 Fault conditions and procedures for rectification
6.1 General faults on the burner
If the burner is found out of operation in lockout, read error To avoid damage to the plant, do not reset the
codes and proceed according to the error message. burner more than twice. If the burner locks out
If faults occur, check first that the basic requirements for for a third time call for a service engineer.
operation are met.
ATTENTION

❏ Check the electric supply


❏ Check that the correct gas pressure is available from
the gas main and that the ball valve is open. Fault conditions should be rectified only by
❏ Check that all controls e.g. thermostats, pressure qualified and experienced personnel.
switches, and water level interlocks, limit and time
switches are set correctly. DANGER

If it has been established that the lockout is not due to any


of the above, all the burner functions must be checked.

Condition Cause Rectification


Burner motor

Does not run No voltage Check voltage supply

Overload relay has tripped Check setting

Contactor defective Replace contactor

Fan motor defective Replace fan motor

Ignition

Ignition failure Ignition electrode Adjust setting


spark gap incorrect

Ignition electrode dirty or wet Replace ignition electrode

Ceramic insulator fault Replace ignition electrode

Ignition cable charred Replace, find cause and rectify

Ignition unit W-ZG defective Replace ignition unit

Combustion manager
with flame sensor

Does not respond to flame Flame signal insufficient Measure flame signal, adjust position of
ionisation electrode; rectify poss. transition
resistance (terminal, plug); correct burner
setting

Ionisation current not With mains supply without a neutral, the


present or too low control neutral must be earthed at the
control circuit transformer.

Break in the flame Repair or replace cable


sensor line

40
6
Condition Cause Rectification
Solenoid valve

Does not open No voltage Check connections

Coil faulty Replace coil

Does not close tightly Particles on valve seat Replace solenoid valve

Cleaning and lubrication regulations

Depending on the degree of contamination of the combustion air, fan rotor, ignition electrode, flame sensor and air intake
should be cleaned as required.
Bearing damage, which is recognised and rectified early, will protect the burner from further damage. Pay attention to noise
levels from the motor bearing and replace bearing if necessary.

General operating problems

Start problems, burner does Flame signal insufficient Check burner setting for unstable and
not start, no flame formation pulsating flame. By adjusting flame
despite ignition and fuel supply sensor improve signal.

Pressure into mixing head too high Check mixing pressure at ignition load
setting, if necessary adjust.

Wrong setting of ignition electrode Correct setting (see Ch. 7.4)

Burner or combustion Wrong setting of mixing head Check setting of mixing head,
pulsating or booming distance of the diffuser to front correct position of air stepping motor.
edge of flame tube too small

6.2 Fault conditions W-FM


For error codes see Installation and operating instructions
Combustion Manager W-FM 50.
The error history stores up to 25 errors. These should be
selected and checked prior to replacing the
W-FM. If the same errors occur frequently this indicates
that a component part of the burner is defective.

41
7 7
Servicing
7.1 Safety notes on servicing
Failure to carry out maintenance and service
work properly can have severe consequences,
including the loss of life. Pay close attention to
the following safety notes.
DANGER

Qualified personnel Endangering operational safety


Only qualified and experienced personnel must carry out Maintenance work on the following parts may only be
maintenance and service work. carried out by the manufacturer or their appointed agent
on the individual components.
Prior to all maintenance and service work: • Stepping motor
1. Electrically isolate the equipment. • Flame sensor
2. Close the ball valve. • Combustion manager
• Pressure regulator
After all maintenance and service work do: • Solenoid valves
1. Function test. • Gas pressure switch
2. Check exhaust gas analysis for CO2 / O2 / CO • Air pressure switch
values.
3. Complete a test sheet.
Risk of explosion due to a gas leak
Take care when dismantling and assembling parts in the
gas line to ensure they are correctly cross bonded,
aligned, clean and in good condition, and that the fixing
screws are correctly tightened.

De-energise plant
Prior to service work switch off the mains
switch and the safety switch.
Failure to comply could cause death or
DANGER serious injury by electric shock.

Danger of getting burnt!


Some burner parts (e.g. flame tube, burner
flange, electrodes, etc.) become hot during
burner operation and should be allowed to
DANGER cool prior to service work being carried out.

42
7
7.2 Servicing
The operator should ensure that combustion plant is
serviced at least once a year by an agent of the supplier or
other suitably qualified person. During this service all
system components with high wear and tear, or
components with a specific life span should be exchanged
and replaced.

7.2.1 Testing, cleaning and function test (checklist)

Checklist Checklist
Test and clean Function test
❏ Fan wheel and air inlet ❏ Carry out soundness test of valve trains
❏ Air damper (when replacing parts; see Ch. 4.6)
❏ Stepping motors ❏ Purge the valve train
- including the coupling to correcting elements, lever (when replacing parts; see Ch. 5.2)
and bearing ❏ Operation of the burner to the correct sequence of
❏ Combustion head and diffuser operation
❏ Gas filter ❏ Ignition
❏ Ignition unit ❏ Air pressure switch
❏ Flame sensor ❏ Gas pressure switch
❏ Flame monitoring
❏ Carry out combustion check and adjust burner if
required

7.2.2 Criteria for setting /replacement


Component Criteria Limit Measure

Ionisation electrode Run time, soiling 2 years Recommendation: replace

Ignition electrode Spark function 2 years Recommendation: replace

Ignition cable Run time visible damage Replace

Air damper Clearance min. 0.3 mm Adjust

Sleeve bearing air damper shaft Play 0 mm Replace air damper shaft

View port cover seal Tightness Air escaping during operation Replace

Set aperture of air damper

min. 0.3 mm

1 1

If the upper clearance is less than 0.3 mm, loosen screw Note Only shake-proof screws should
1 and adjust air damper horizontally (equal clearance be used in the vicinity of the air regulation.
top/ bottom).
43
7
7.3 Removal and refitting the mixing head
On heating appliances with high media
temperatures, such as steam generators,
during burner shutdown parts of the mixing
head become very hot to temperatures above
DANGER 100° C. When removing the mixing head, as
well as during preparation work, protective
gloves should be worn.

Any other service work should only be car-


ried out once the mixing head has been al-
lowed to cool completely.

Removal Refitting
➩ Observe safety note Ch. 7.1. Refit the mixing head in reverse order.
❑ Has the hinge pin been fitted to the correct side?
Ensure correct alignment of mixing head.
1. Remove view port cover 1.
2. Unplug ionisation and ignition cables 2.
3. Remove cover nut 3 and hinge open the burner.
4. Loosen lock nut 4.
5. Lift mixing chamber 5 and remove.

Removing the mixing head

1
4

44
7
7.4 Setting ionisation and ignition electrodes
Set ignition electrode Note Site-specific conditions (start problems, weak
Loosen screw on terminal plate and set electrode to flame signal) may make it necessary to adjust
the dimensions given. the position of the electrode tips.

Set ionisation electrode


Loosen screw on terminal plate and set ionisation
electrode as shown below.

Setting electrodes

app
rox
. 5…
6m Ignition electrode Ionisation electrode
m

approx. 1.5…2 mm

45
7
7.5 Removing and refitting air damper stepping motor
Removing Refitting
➩ Observe safety notes Ch. 7.1. Refit the stepping motor in reverse order, paying attention
1. Remove cable entry cover 1 and cable seal 2. to the correct fit of the shaft key 7.
2. Remove cover 3.
3. Unplug stepping motor plug 4 on combustion
manager. Note Following the replacement of a stepping motor
4. Remove cover 8 of air intake housing. carry out a combustion analysis and adjust
5. Set stepping motor to 0 position. burner as required.
If the stepping motor is faulty and cannot be set to 0
position, it is possible to manually turn the air damper
shaft carefully.
6. Remove lock nut 5 on the coupling.
7. Loosen stepping motor 6 and remove from the air
damper shaft.

Removing and refitting air damper stepping motor

7
6
2
1
5

46
7
7.6 Removing and refitting gas butterfly stepping motor
Removing Refitting
➩ Observe safety notes Ch. 7.1. Refit in reverse order, ensuring correct fit of shaft key 6.
1. Undo screwed connection and remove plug 1. The coupling should slide onto the shaft without having to
2. Remove view port glass 2 from intermediate use force.
housing 3 and loosen grub screw of coupling 4.
3. Loosen fixing screws and carefully remove stepping Note Following the replacement of a stepping motor
motor 5 (do not damage coupling). carry out a combustion analysis and adjust
4. Loosen second grub screw and carefully pull off burner as required.
coupling 4 from the drive shaft.
5. Remove shaft key 6
6. Loosen fixing screws and remove intermediate
housing 3

Note Steps 4 to 6 are only necessary if the


intermediate housing or coupling require
replacing.

Removing and refitting gas butterfly stepping motor

2
6

6
3 4

47
7
7.7 Removing and refitting FRS spring
Removing Remove and refit spring on pressure regulator
1. Remove protective cap 1.
2. De-regulate the spring by turning the adjusting screw
2 anticlockwise until you reach its stop.
3. Remove complete adjusting device 3. 1
4. Remove spring 4.

Refitting 2
Refit in reverse order.
Please note: 3
☞ If the spring range is changed stick new label for new
spring onto the nameplate.

4
Springs for FRS
Type of spring / colour Outlet pressure range

orange 5 to 20 mbar
blue 10 to 30 mbar
red 25 to 55 mbar
yellow 30 to 70 mbar
black 60 to 110 mbar
pink 100 to 150 mbar

48
8 Technical data 8
8.1 Burner equipment
WM-G 10/3-A / ZM-LN

Combustion Manager Motor Stepping motors

W-FM 50 D90/90-2/1 EC90/90-2/1 Air damp./Gas b/fly:


380-400 V 220-230 V, 1~ STE 50…
50 Hz; 2800 rpm 50 Hz; 2880 rpm 4.5 secs./90°
1.5 kW; 3.5 A 0.76 kW; 6 A 1.2 Nm
Cond. 25µF

Flame sensor Ignition unit

Ionisation electrode W-ZG 02/2


2 x 7000V

8.2 Capacity graph


Burner type WM-G 10/3-A / ZM-LN The capacity graphs are in accordance with EN 676, and
relate to an installation at sea level. There is a rating
Combustion head G5/3a 162x50 reduction dependent on the altitude of the installation:
Combustion heat rating 125…900 kW approx. 1% per 100 m above sea level.

Ratings range
The burner has a maximum turndown ratio of 7:1. Please
note that the lowest operating point must lie within the
burner’s capacity chart.

10
Rating with
9 combustion head

8 OPEN
CLOSED
7
Combustion chamber pressure [mbar]

-1

-2

-3

-4
0 100 200 300 400 500 600 700 800 900 1000
Combustion heat rating [kW]

49
8
8.3 Permissible fuels
Natural Gas E
Natural Gas LL

8.4 Dimensions mixing head


Burner type Flame tube Diffuser

Type external internal external internal


D1 [mm] D2 [mm] D3 [mm] D4 [mm]

WM-G10/3-A / ZM-LN G5/3a 200 148 162 50

D4 D3 D2 D1

8.5 Permissible ambient conditions


Temperature Humidity Requirements for EMC Low voltage guideline

In operation: max. 80% rel. humidity Guideline 89/336/EU Guideline 73/23/EU


-15° C to 40° C no dew point EN 61 000-6-1 EN 60335
Transport / storage: EN 61 000-6-4
-20 C to +70° C

50
8
8.6 Electrical data
Mains voltage Pre-fuse Electrical rating

Burner control 230V 16 AT (external) Inrush 250 VA*


50Hz, 1~ 6.3 AT (internal) Operation 160 VA

Fan motor 380 - 400 V, 50Hz, 3~ 10 A max. approx. 1.9 kW


220 - 230 V, 50Hz, 1~ 20 A max. approx. 1.3 kW
* Ignition start rating

8.7 Weight
Burner
approx. 56 kg

Gas valve train


3
Nominal diameter /4” 1” 11/2” 2” DN 65 DN 80 DN 100

Weight in kg 7 9 10 11 18 28 36

Gas valve train consists of double solenoid valve and reducing flange elbow

Screwed valve train (3/4” to 2”) Flanged valve train (DN65 to DN100)

51
8
8.8 Burner dimensions

161 445

313

167
108

279
8
71

200

307
68
2

8 205

177…197
833

52
Appendix A
Combustion analysis
For safe, economic and environmentally friendly operation Determination of flue gas losses
of the plant, flue gas measurements are essential when The oxygen content of the undiluted flue gas and the
commissioning. difference between the flue gas and the combustion air
temperature must be determined. The oxygen content and
Example of a simplified calculation for determining the the flue gas temperature must be measured at the same
CO2 setting value time at one point. Instead of oxygen content, the carbon
dioxide content of the flue gas can also be measured. The
Given that: CO2 max. = 12% combustion air temperature is measured in the proximity of
the burner air intake.
At CO limit (≈ 100 ppm), measured: CO2meas. = 11.5%
The flue gas losses are calculated when measuring the
CO2 max. 12 oxygen content according to the equation:
Gives excess air: λ ≈ = ≈ 1.04
CO2meas. 11.5 A2
qA = (tA - tL) • ( +B)
To provide for a safe amount of excess air, increase air λ by 21 – O2
15% to 20% (soiling of intake air, deviations in intake air
temperature and chimney draughts, etc. should be If the carbon dioxide content is measured instead of the
included in the calculation): oxygen content, the calculation is carried out according to
the equation:
1.04 + 0.15 = 1.19
A1
CO2 value to be set with excess air λ = 1.19 and 12% qA = (tA - tL) • ( +B)
CO2max.: CO2

CO2 max. 12 whereby:


CO2 ≈ = ≈ 10.1 % qA = flue gas losses in %
λ 1.19 tA = flue gas temperature in °C
tL = combustion air temperature in °C
The CO content must not be more than 50 ppm. CO2 = % volume of carbon dioxide content in dry flue
gas
Observe flue gas temperature O2 = % volume of oxygen content in dry flue gas
Flue gas temperature for full load (nominal load) is the
result of burner setting at nominal loading.
The flue gas temperature at partial load is the result of the Natural Towns Coke LPG and
commissioned control range. The appliance gas gas oven LPG/Air mix
manufacturer’s instructions must be adhered to in respect gas
of the partial load setting. This might be 50 - 60% of
nominal load setting,or even higher with an air heater, A1 = 0.37 0.35 0.29 0.42
whereas a condensing boiler may require the maximum A2 = 0.66 0.63 0.60 0.63
available turndown within the burners capacity range. B = 0.009 0.011 0.011 0.008
Often the partial load is shown on the appliance;s data
plate.
The flue gas installation should also be set out to protect
against damage through condensation (excluding
acid proof chimneys).

Calorific values and max. CO2 (guide values) of various types of gases.

Gas type Calorific value Hi CO2 max.


MJ/m3 kWh/m3 %

1st gas family


Group A (Town Gas) 15.12…17.64 4.20…4.90 12…13
Group B (Grid Gas) 15.91…18.83 4.42…5.23 10

2nd gas family


Group LL (Natural Gas) 28.48…36.40 7.91…10.11 11.5…11.7
Group E (Natural Gas) 33.91…42.70 9.42…11.86 11.8…12.5

3rd gas family


Propane P 93.21 25.99 13.8
Butane B 123.81 34.30 14.1

For the various maximum CO2 contents contact the gas supplier.

53
A Calculation of gas throughput

To provide the correct thermal input to the heat exchanger, Example:


the required gas throughput must be determined Height above sea level = 500 m
beforehand. Barometric air pressure PBaro. from Tab. = 953 mbar
Gas pressure PG at meter = 30 mbar
Conversion from standard to operating conditions Total pressure Pmeas.(PBaro+PG) = 983 mbar
The calorific value (Hi) of combustible gases is generally Gas temperature tG = 10 °C
given in relation to the standard barometric conditions Conversion factor f from Tab. = 0.933
(0° C, 1013 mbar). Appliance rating QN = 800 kW
Efficiency η (assumed) = 90 %
Calorific value Hi = 10.35 kWh/m3

Normal volume VN:


QN 800
VN = VN = → VN ≈ 85.9 m3/h
η • Hi 0.90 • 10.35

Operating volume VB:


VN QN 85.9
VB = or VB = VB = → VB ≈ 92.1 m3/h
f η • Hi,B 0.933

Measuring time in seconds for 10m3 of gas Measuring time when gas meter reads 5 m3:
throughput:
3600 • 5
3600 • 10 [ m3 ] Measuring = –––––––––– → Measuring ≈ 195 s
Measuring = time 92.1 time
time [ s ] VB [ m3/h ]
Operating volume when gas meter reads 2 m3 after 78
Calculation based upon a stop watch-meter reading s measuring time:
volume.:
3600 • 2.0
3600 • V [ m3 ] VB [ m3/h ] = –––––––––– → VB = 92.3 m3/h
3
VB [ m /h ] = 78
Measuring time [s]
Determination of factor f
Total pressure PBaro + PG Conversion factor f
in Gas temperature tG in °C
mbar1) 0 5 10 15 20 25
900 0.888 0.872 0.857 0.842 0.828 0.813
920 0.908 0.892 0.876 0.861 0.846 0.832
940 0.928 0.911 0.895 0.880 0.865 0.850
960 0.948 0.931 0.915 0.899 0.884 0.868
980 0.967 0.950 0.933 0.917 0.901 0.886

1000 0.987 0.969 0.952 0.936 0.920 0.904


1020 1.007 0.989 0.972 0.955 0.939 0.922
1040 1.027 1.009 0.991 0.974 0.957 0.941
1060 1.046 1.027 1.009 0.992 0.975 0.958
1080 1.066 1.047 1.029 1.011 0.994 0.976
1100 1.086 1.066 1.048 1.030 1.012 0.995
1120 1.106 1.086 1.067 1.048 1.031 1.013
1140 1.125 1.105 1.086 1.067 1.049 1.031
1160 1.145 1.124 1.105 1.085 1.067 1.049
1180 1.165 1.144 1.124 1.104 1.086 1.067
1200 1.185 1.164 1.144 1.123 1.104 1.085
1220 1.204 1.182 1.162 1.141 1.122 1.103
1240 1.224 1.202 1.181 1.160 1.141 1.121
1260 1.244 1.222 1.200 1.179 1.159 1.140
1280 1.264 1.241 1.220 1.198 1.178 1.158
1300 1.283 1.260 1.238 1.216 1.196 1.175
1320 1.303 1.280 1.257 1.235 1.214 1.194
1340 1.323 1.299 1.277 2.254 1.233 1.212
1360 1.343 1.319 1.296 1.273 1.252 1.230
1380 1.362 1.338 1.314 1.291 1.269 1.248
1400 1.382 1.357 1.334 1.310 1.288 1.266
1420 1.402 1.377 1.353 1.329 1.307 1.284
1440 1.422 1.396 1.372 1.348 1.325 1.303
1460 1.441 1.415 1.391 1.366 1.342 1.320
1480 1.461 1.435 1.410 1.385 1.362 1.338
1500 1.481 1.454 1.429 1.404 1.380 1.357
1520 1.500 1.473 1.448 1.422 1.398 1.374
1540 1.520 1.493 1.467 1.441 1.417 1.392
1560 1.540 1.512 1.486 1.460 1.435 1.411
1580 1.560 1.532 1.505 1.479 1.454 1.429

54
A
Total pressure PBaro + PG Conversion factor f
in Gas temperature tG in °C
mbar1) 0 5 10 15 20 25
1600 1.579 1.551 1.524 1.497 1.472 1.446
1620 1.599 1.570 1.543 1.516 1.490 1.465
1640 1.619 1.590 1.562 1.535 1.509 1.483
1660 1.639 1.610 1.582 1.554 1.528 1.501
1680 1.658 1.628 1.600 1.572 1.545 1.519
1700 1.678 1.648 1.619 1.591 1.564 1.537
1720 1.698 1.667 1.639 1.610 1.583 1.555
1740 1.718 1.687 1.658 1.629 1.601 1.574
1760 1.737 1.706 1.676 1.647 1.619 1.591
1780 1.757 1.725 1.696 1.666 1.638 1.609
1800 1.777 1.745 1.715 1.685 1.656 1.628
1820 1.797 1.765 1.734 1.704 1.675 1.646
1840 1.816 1.783 1.752 1.722 1.693 1.663
1860 1.836 1.803 1.772 1.741 1.711 1.682
1880 1.856 1.823 1.791 1.759 1.730 1.700
1900 1.876 1.842 1.810 1.778 1.748 1.718
1920 1.895 1.861 1.829 1.796 1.766 1.736
1940 1.915 1.881 1.848 1.815 1.785 1.754
1960 1.935 1.900 1.867 1.834 1.803 1.772
1980 1.955 1.920 1.887 1.853 1.822 1.791
2000 1.974 1.938 1.905 1.871 1.840 1.802
2050 2.024 1.988 1.953 1.919 1.886 1.854
2100 2.073 2.036 2.000 1.965 1.932 1.899
2150 2.122 2.084 2.048 2.012 1.978 1.944
2200 2.172 2.133 2.096 2.059 2.024 1.990
2250 2.221 2.181 2.143 2.106 2.070 2.034
2300 2.270 2.229 2.191 2.152 2.116 2.079
2350 2.320 2.278 2.239 2.199 2.162 2.125
2400 2.369 2.326 2.286 2.246 2.208 2.170
2450 2.419 2.375 2.334 2.293 2.255 2.216
2500 2.468 2.424 2.382 2.340 2.300 2.261
2550 2.517 2.472 2.429 2.386 2.346 2.306
2600 2.567 2.521 2.477 2.434 2.392 2.351
2650 2.616 2.569 2.524 2.480 2.438 2.396
2700 2.665 2.617 2.572 2.526 2.448 2.441
2750 2.715 2.666 2.620 2.574 2.530 2.487
2800 2.764 2.714 2.667 2.620 2.576 2.532
2850 2.813 2.762 2.715 2.667 2.662 2.577
2900 2.863 2.812 2.763 2.714 2.668 2.623
2950 2.912 2.860 2.810 2.761 2.714 2.667
3000 2.962 2.909 2.858 2.808 2.761 2.713
3100 3.060 3.005 2.953 2.901 2.852 2.803
3200 3.159 3.102 3.048 2.995 2.944 2.894
3300 3.258 3.199 3.144 3.089 3.036 2.984
3400 3.356 3.296 3.239 3.181 3.128 3.074
3500 3.455 3.393 3.334 3.275 3.220 3.165
3600 3.554 3.490 3.430 3.369 3.312 3.255
3700 3.653 3.587 3.525 3.463 3.405 3.346
3800 3.751 3.684 3.620 3.556 3.496 3.436
3900 3.850 3.781 3.715 3.650 3.588 3.527
4000 3.949 3.878 3.811 3.744 3.680 3.617

1 mbar = 1 hPa = 10.20 mm w.g. 1 mm w.g. = 0.0981 mbar = 0.0981 hPa

The figures in the table are based on the following simple The moisture content of the gas is negligible and therefore
formula: is not considered in the table or the conversion formula.

PBaro + PG 273
f = •
1013 273 + tG

Average yearly air pressure


Average altitude from 1 51 101 151 201 251 301 351 401 451 501 551 601 651 701
of installation to 0 50 100 150 200 250 300 350 400 450 500 550 600 650 700 750
Average yearly air pressure mbar 1016 1013 1007 1001 995 989 983 977 971 965 959 953 947 942 936 930

Legend:
QN = Appliance rating [kW] f = Conversion factor
η = Efficiency [%] PBaro. = Barometric pressure [mbar]
Hi = Calorific value [kWh/m3] PG = Gas pressure at meter [mbar]
Hi,B = Operating calorific value [kWh/m3] tG = Gas temperature at meter [°C]
55
Spares
D list
A

1.01 1.07
1.02 1.05
1.03
1.06
1.08 1.11

1.04

1.10
1.09

1.15

1.12

1.13

1.14

56
A
Pos. Description Order No.

1.01 View port cover WM10 cpl. 211 104 01 02 2

1.02 View port glass 211 153 01 15 7

1.03 View port closing cover 211 104 01 13 2


incl. spring clip

1.04 View port cover seal 211 104 01 12 7

1.05 Hinge pin 14 x 208 111 652 01 04 7

1.06 Circlip 10 431 604

1.07 Hinge flange WM10 217 104 01 03 7


– stud screw M10 x 50 421 021
– washer A 10.5 430 600
– Hexagon nut 411 502

1.08 Stud screw M12 x 45 401 068

1.09 Dome nut M12 DIN 1587 412 401

1.10 Washer B 13 430 801

1.11 Flange gasket 260 x 202 111 612 00 10 7

1.12 Cable entry W-FM cpl. 211 104 01 05 2

1.13 Air intake cover WM10 211 104 02 02 2


incl. foam cladding

1.14 Cable glands set 211 104 01 50 2

1.15 -weishaupt- badge 211 104 01 10 7

57
A

2.05

2.13
2.04
2.22 2.01 2.14 2.16

2.15
2.21
2.02 2.06

2.17
2.06 2.17
2.03
2.23 2.20

2.07 2.22

2.21

2.10 2.11
2.17
2.08
2.18

2.09 2.12
2.19
2.10

58
A
Pos. Description Order No.

2.01 Motor including motor contactor


D90/50-2/1 380-400V 50Hz 3~ 211 104 07 02 0
EC90/90-2/1 220-230V 50Hz 1~ 211 103 07 02 0

2.02 Motor contactor B7, 230V 50Hz 702 818

2.03 Cable gland set 211 104 01 50 2

2.04 Motor D90/50-2/1 220-230/380-400 50Hz 211 104 07 04 0


for frequency converter fitted

2.05 Frequency converter MI 75/3 795 795

2.06 Shaft key 5 x 6.5 DIN 6888 490 151

2.07 Fan wheel TLR 225 x 92 (50Hz) 211 104 08 01 2


Fan wheel puller (tool) 111 111 00 01 2

2.08 Inlet nozzle 161 WM10 211 104 02 17 7

2.09 Inlet mesh WM-G10/1+2-A 211 104 02 06 7

2.10 Air damper WM10 211 104 02 12 7


– screw M4 x 10 DIN 912 Tuflock 402 264

2.11 Fixing plate for intake cover WM10 211 104 02 08 7

2.12 Intake cover bracket WM10 211 104 02 15 7

2.13 Stepping motor STE 50 1.2 Nm f. W-FM50 651 475

2.14 Shaft key 3 x 3.7 DIN 6888 490 157

2.15 Air damper shaft with coupling 211 104 02 09 2

2.16 Air damper shaft with spring cotter 211 104 02 11 2

2.17 Sleeve bearing set 211 104 02 50 2

2.18 Adjusting lever 211 104 02 04 7


– Threaded pin M5 x 14 DIN 914 Tuflock 420 497

2.19 Double crank arm EGZM 06-75 EK 499 288


– screw M6 x 14 Tuflock 402 265

2.20 Air pressure switch LGW 50 A2P 691 373


– Cap for LGW 446 011

2.21 Hose 4.0 x 1.75 250 mm lang 217 104 24 01 7

2.22 Threaded socket R1/8 453 003

2.23 Threaded socket M12 x 1 x G1/4 x 37,5 217 104 24 01 7

59
A
3.01
3.02

3.10

3.03

3.05

3.07

3.04 3.08 3.05

3.09

3.06

3.11
3.13

3.12
3.14
3.15

3.16

3.16

3.17

3.18

60
A
Pos. Description Order No.

3.01 Flame tube WM-G10/3 ZM-LN (G5/3a) 151 518 14 32 2


– Flame tube extension by 100 mm* 150 518 14 05 7
– Flame tube extension by 200 mm* 150 518 14 06 7
– Flame tube extension by 300 mm* 150 518 14 01 2

3.02 Locking screw M12 x 92 151 518 01 07 7

3.03 Gasket 55 x 165 x 2 151 518 00 12 7

3.04 Gas butterfly valve DN50, complete 217 304 25 02 0

3.05 Shaft key 3 x 3.7 DIN 6888 490 157

3.06 Intermediate housing f. butterfly Series B 217 704 25 02 7

3.07 View port glass 33 x 33 x 6 211 404 17 02 7

3.08 Spring coupling bar Series 2 217 704 15 10 7

3.09 Stepping motor STE 50 for butterfly 651 476

3.10 Mixing head G5/1-D-LN, complete 151 518 14 28 2


– Mixing head G5/1-D-LN, ext. by 100 mm * 150 518 14 06 2
– Mixing head G5/1-D-LN, ext. by 200 mm * 150 518 14 07 2
– Mixing head G5/1-D-LN, ext. by 300 mm * 150 518 14 08 2

3.11 Sensor electrode 232 100 14 20 7

3.12 Ignition electrode 6 x 80 132 101 14 03 7

3.13 Diffuser 162 x 50 G5/1-D-LN 151 518 14 53 7

3.14 Nozzle element G5 vers. LN 150 501 14 03 7

3.15 Mixing head G5/1-D-LN 151 518 14 28 1

3.16 Clamp 2 x 17 x 20 251 303 14 08 7

3.17 Ionisation cable 390 mm long 250 103 14 25 2


– 490 mm long* 250 103 14 26 2
– 590 mm long* 150 518 14 09 2
– 690 mm long* 150 707 14 20 2

3.18 Ignition cable 550 mm long 151 518 11 02 2


– 650 mm long* 217 304 11 01 2
– 750 mm long* 150 518 11 01 2
– 850 mm long* 217 504 11 01 2

* only in conjunction with head extension

61
A

4.15

4.04

4.03 4.14

4.13

4.02
4.05

4.01
4.06 4.10

4.12

4.08

4.11
4.07

4.09

62
A
Pos. Description Order No.

4.01 ABE for W-FM 50 600 405

4.02 Cover incl. gasket


and fixing sleeves for W-FM
- ABE inbuilt 211 104 12 01 2
- ABE external 211 104 12 02 2

4.03 Stay bolt cover W-FM 211 104 12 03 7

4.04 Mounting plate WM for W-FM 50 211 204 12 04 7

4.05 W-FM Plug


– X3-02 Air pressure switch 716 301
– X3-03 Limit switch burner flange 716 302
– X3-04 Mains and safety circuit 716 303
– X3-05 Fan, alarm 716 410
– X4-02 Ignition unit 716 305
– X5-01 Low pressure switch 716 307
– X5-02 High pressure switch 716 308
– X5-03 Control circuit 716 309
– X6-03 Safety valve 716 312
– X7-01 DMV Valve 2 716 313
– X8-02 DMV Valve 1 716 317
– X8-04 Operation + LO Reset 716 411
– X9-04 Valve proving press. switch 716 418
– X10-05 Flame sensor 716 413
– X74 Connection frequency converter 716 417
– X75 Fuel meter 716 415

4.06 Combustion Manager WFM50 230 V 600 400

4.07 Plug cable ABE-W-FM 50 600 406

4.08 Plug cable W-FM 50 mains / safety circuit 217 104 12 02 2

4.09 Plug cable W-FM 50 for DMV 217 104 26 01 2

4.10 Plug cable W-FM 50 for


– Low gas pressure switch 217 104 26 02 2
– High gas pressures switch 217 104 26 03 2
– Valve proving pressure switch 217 104 26 04 2

4.11 Plug cable W-FM50 speed cont. FC 217 104 12 10 2

4.12 Plug cable W-FM50 motor contactor 217 104 12 09 2

4.13 Ignition unit W-ZG 02/V for W-FM 230V 217 704 11 03 2

4.14 Sealing ring for W-ZG 02 44 x 18 x 4 211 163 11 02 7

4.15 Limit switch WM 211 104 01 06 2

63
A

5.03

5.02

5.04

5.01

5.11

5.05

5.11
5.07

5.07
5.06

5.03

5.05

5.08 5.02

5.04

5.01

5.05 5.10
5.05
5.08

5.07 5.06
5.07

5.06

5.09

64
A
Pos. Description Order No.

5.01 Double solenoid valve:


– DMV-D 507/11; 230V 605 204
– DMV-D 512/11; 230V 605 206
– DMV-D 520/11; 230V 605 208
– DMV-D 5065/11; 230V 605 216
– DMV-D 5080/11; 230V 605 218
– DMV-D 5100/11; 230V 605 220

5.02 Solenoid, complete for:


– 507/11 Type 1111 220-240V / 50-60Hz 605 941
– 512/11 Type 1211 220-240V / 50-60Hz 605 942
– 520/11 Type 1212 220-240V / 50-60Hz 605 943
– 5065/11 Type1411 220-240V / 50-60Hz 605 945
– 5080/11 Type 1511 220-240V / 50-60Hz 605 946
– 5100/11 Type 1611 220-240V / 50-60Hz 605 947

5.03 Printed circuit board DMV-D; 230V


– DMV-D 507 605 996
– DMV-D 512, 520, 5065, 5080 605 997
– DMV-D 5100 605 998

5.04 DMV plug 4 pole, 250V AC, 16A 217 304 26 01 2

5.05 GW plug 4 pole, 250V AC, 16A 217 304 26 02 2

5.06 Gas pressure switch


– GW 50 A5/1 5-50 mbar 691 378
– GW 150 A5/1 10-150 mbar 691 379
– GW 500 A5/1 100-500 mbar 691 380

5.07 O Ring GW A5/1 10.5 x 2.25 445 512

5.08 Gas pressure switch


– GW 50 A6/1 5-50 mbar 691 381
– GW 150 A6/1 10-150 mbar 691 382
– GW 500 A6/1 100-500 mbar 691 383

5.09 Flange
– DMV 507 RP 3/4 605 227
– DMV 512 RP 1 605 228
– DMV 520 RP 1 1/2 605 230
– DMV 520 RP 2 605 231

5.10 Adaptor set DMV 605 251

5.11 Sealing ring DIN 2690


– DN65 77 x 127 x 2 441 861
– DN80 90 x 142 x 2 441 044
– DN100 115 x 162 x 2 441 045

65
Weishaupt products Max Weishaupt GmbH, D-88475 Schwendi
Tel. (0 73 53) 8 30, Fax (0 73 53) 8 33 58
Print No 83250102, January 2007

and service Printed in Germany. We reserve the right to


make changes. All rights reserved.

Weishaupt (U.K.) Ltd.


Neachells Lane, Willenhall
West Midlands, WV13 3RG
Tel. (01902) 60 98 41
Fax (01902) 63 33 43
www.weishaupt.co.uk

Product Description Performance

W-Burners The compact series, proven millions of times over: Up to 570 kW


Economical, reliable, fully automatic. Gas, oil and
dual fuel burners for domestic and commercial
applications.

Monarch and The legendary industrial burner: Up to


industrial burners Tried and tested, long lived, clear construction. 10900 kW
Gas, oil and dual fuel burners for district heat provision.

multiflam® burners Innovative Weishaupt technology for large burners: Up to


Minimal emission values particularly at ratings 12000 kW
over one megawatt. Oil, gas and dual fuel burners with
patented fuel distribution system.

WK Modular powerhouses: Up to
industrial burners Adaptable, robust, powerful. 17500 kW
Oil, gas and dual fuel burners for industrial plant.

Control technology / From control panels to complete building management


building systems – at Weishaupt you can find the entire
management spectrum of modern control technology.
Future oriented, economical and flexible.

Service Customer service completes the Weishaupt range.


Weishaupt customer service is available 24/7.
We’re there when you need us. Everywhere.

You might also like