Ept. 3
Ept. 3
UNIT- III
EXTRA HIGH VOLTAGE TRANSMISSION
3.1 EHVAC TRANSMISSION LINE:
Define EHV line:-
• EHV line means transmission voltage between 400 KV To 765 KV is known as EHV line
• We know that, P = √3 VL IL cos ɸ
• For,
➢ Same power to be transferred
➢ At same power factor
1
➢ At same transmission line distance 𝐼 ∝ 𝑉 from This Equation It is clear that due
• These components divert the flow of current to the ground and therefore protect the
system’s conductor as well as insulation from harm.
6. Wave-Trapper
• The wave-trapper is located on incoming lines to trap the high-frequency signal.
• This signal (wave) comes from the remote station which interrupts the current and
voltage signals.
• This component trips the high-frequency signal and redirects them to the telecom board.
7. Circuit-Breaker
• This is a type of electrical switch, used to open or close the circuit when an error arises in
the system. It includes two moving parts that are usually closed.
• When an error happens in the system, then the relay transmits the signal to the circuit-
breaker & therefore their parts are moved separately. Therefore, errors occur in the
system turns into clear.
8. Bus Bar
• The bus bar is a very important component in an electrical substation. It is a kind of
current carrying conductor where many connections are made.
• In other terms, it can be defined as it is one type of electrical connection where the
incoming current and outgoing current take place.
• As the fault takes place in this component, then all the circuit components associated to
the section ought to be tripped-out for giving entire isolation in the quick time so that the
fault is neglected to the fitting because of conductors heating.
9. Isolator in Substation
• The isolator is one type of electrical switch, used to isolate the circuit whenever the flow
of current has been disrupted.
• These switches are named as disconnected switches, and it works under a no-load
condition. Isolators are not inbuilt by arc-quenching apparatus, and they don’t have any
particular current-making or current-breaking capacity.
• In some situations, it is used to break the current charging of the line of transmission.
10. Batteries
• In large power stations or substations, the operation of lighting, relay system, or control
circuits are powered by batteries.
• These batteries are connected to a particular accumulator cell based on the operating
voltage of the particular DC circuit.
• The batteries are classified into two types namely acid-alkaline as well as lead acid. Lead
acid batteries are applicable for substations, power stations due to their high voltage &
very economical low voltage.
11. Switchyard
• The switchyard is the inter-connector among the transmission as well as generation, &
equal voltage is maintained in this device.
• Switchyards are used to transmit the power which is generated from the substation at the
preferred level of voltage to the near transmission line or power station.
12. Relay
• The relay is an electrical device, and the main role of this device in the substation is, it
guards the grid component against the irregular conditions like faults.
• This is one type of detecting device, used to detect and determine the fault location, and
then it sends the signal to the circuit breaker.
• After receiving the signal from the relay, the circuit breaker will detach the faulted part.
Relays are mainly useful for protecting the devices from hazards, damages.
13. Capacitor Bank
• This device is inbuilt with capacitors that are connected either in series or else parallel.
The main function of this is to store the electrical energy in electrical charge form.
• This bank draws primary current which amplifies the PF (power factor) of the system. As
a source, the capacitor bank works for reactive-power, and the phase-difference among
the current as well as the voltage will be decreased.
• They will enhance the capacity of ripple current of the power supply, and it removes the
unnecessary characteristics within the system.
• The capacitor bank is an efficient method for preserving power factor as well as power-
lag problem correction.
14. Insulator
• The insulator is used for insulating as well as fixing the bus-bar systems in substations.
Insulators are separated into two types namely post type & bushing type.
• A post type insulator comprises of the ceramic body and the cap of this insulator is
designed with a cast iron material. It is straightly connected to the bus bar.
• The second type of insulator (bushing) includes ceramic shell body, higher & lower
locating washes which are useful for fitting the bus-bar position.
3.1.3 EHVAC TRANSMISSION LINE ADVANTAGES:-
1
• As Transmission voltage increases, current decreases. ( as 𝐼 ∝ 𝑉 )
The phenomenon of violet glow, hissing noise and production of ozone gas in an
overhead transmission line is known as corona.
CORONA FORMATION
• Some ionization is always present in air due to cosmic rays, ultraviolet radiations and
radioactivity.
• Therefore, under normal conditions, the air around the conductors contains some ionized
particles (i.e., free electrons and +ve ions) and neutral molecules.
• When p.d. is applied between the conductors, potential gradient is set up in the air which
will have maximum value at the conductor surfaces.
• Under the influence of potential gradient, the existing free electrons acquire greater
velocities. The greater the applied voltage, the greater the potential gradient and more is
the velocity of free electrons.
• When the potential gradient at the conductor surface reaches about 30 kV per cm (max.
value), the velocity acquired by the free electrons is sufficient to strike a neutral molecule
with enough force to dislodge one or more electrons from it.
• This produces another ion and one or more free electrons, which is turn are accelerated
until they collide with other neutral molecules, thus producing other ions.
• Thus, the process of ionization is cumulative. The result of this ionization is that either
corona is formed or spark takes place between the conductors.
1. Magnitude of Voltage:
• If voltage across two conductors is greater than 30 KV/cm, i.e. breakdown voltage of air
than corona formation starts. Corona will not start if voltage is below 30 KV/cm
2. Distance between two conductors:
• If spacing between two conductors is very large as compare to their diameter than there is
no possibility of corona formation. Because value of voltage at which corona occurs
increases.
3. Size of conductor:
• If size (Cross section) of conductor is more, than magnitude of voltage required to occur
the corona increases.
4. Condition of conductor & Hardware:
• Rough and irregular surface of conductor and hardware will give more corona than solid,
smooth body conductor & hardware.
5. Atmospheric Condition:
• As corona takes place due to ionization of air so it depends on condition of air so for dry
air formation of corona occurs late than in wet air (damp atmosphere condition/ rainy
season/thunderstorms/fog air becomes more conductivity)
6. Effect of supply Frequency:
• Corona loss varies directly as the supply frequency
7. Effect of density of air:
• Corona loss increases with the decrease in the density of air (The corona loss of
transmission line passing through hilly area is higher than that of a similar line in plain
due to reduced value of air density at high level /altitude)
IMPORTANT TERMS:
1. Critical disruptive voltage:
• It is the minimum phase-neutral voltage at which corona occurs.
• Consider two conductors of radii r cm and spaced d cm apart. If V is the phase-neutral
potential, then potential gradient at the conductor surface is given by:
• In order that corona is formed, the value of g must be made equal to the breakdown
strength of air.
where mv is another irregularity factor having a value of 1·0 for polished conductors and
0·72 to 0·82 for rough conductors.
3. Power loss due to corona.
• Formation of corona is always accompanied by energy loss which is dissipated in the
form of light, heat, sound and chemical action.
• When disruptive voltage is exceeded, the power loss due to corona is given by :
ADVANTAGES OF CORONA:-
1. Due to formation of corona air around the conductor gets ionized. Hence effective diameter of
conductor increases. So its resistance decreases.
2. It reduces electrostatic stresses as cross section of conductor’s increases.
3. It provides safety valve against over voltage due to lighting stroke.
4. It reduces effect of transient produced by surge.
DISADVANTAGES OF CORONA:-
OR
Converting Station:
• At the substation, Rectifier terminal converts an AC to DC whereas Inverter substation
converts DC to AC.
• Every terminal is designed in such a way that they work in both mode (Rectifier and
Inverter), so then each terminal is known as converter terminal.
Converting Unit:
• As we discuss, converter unit converts AC to DC, and its vice-versa is used at three-
phase bridge converters.
• This circuit is also known as Graetz Circuit.
• There is 12-pulse bridge converter is used in HVDC transmission, and that converter
obtains by connecting two or 6-pulse bridge converter .
Converting Valves:
• However new HVDC converter uses 12-pulse converter units.
• Thyristor based modules are used to make series connection valves.
• The amount of thyristor valve depends upon the required voltage across the valve.
Converting T/Fs :
• The converter transformer changes over the AC to DC systems or the other way around.
They have two arrangements of three stage windings, First is AC side winding and
second is Valve side winding.
Filters:-
• Filtration of Harmonics is exceptionally essential and furthermore for generation of
receptive power at line cumulative converter station.
• Filtration is almost obligatory for generation of reactive power at range expanding
converter station.
Power Source (Reactive):-
• Converter tasks are required Reactive power. Extra power can likewise be accomplished
from the synchronous stage modifiers of shunt capacitors and STATIC VAR frameworks.
Smoothing Reactors:-
• The smoothing reactor like as oil cooled reactor stuffed with high inductance oil. The
converter is associated with this reactor just before DC. It can be situated at impartial or
the line side
A) MONOPOLAR LINK –
• Monopolar link has only one conductor and return path is provided by permanent earth.
• The line usually operated with negative polarity w.r.t ground so as to reduce corona loss
and radio interference.
• Monopolar line is more economical than bipolar line because the ground return saves the
cost of the one metallic conductor and losses in it
• It is used only for low power rating and mainly for cable transmission.
B) BIPOLAR LINK –
• Bipolar dc link widely used for overhead long distance HVDC transmission system and
also for back to back HVDC system.
• This link has two conductor- one operating with positive polarity and other with negative
polarity w.r.t earth
• There are two converter of equal voltage rating and connected in series at each end of dc
line.
• The junction between converters may be grounded at one end or both end.
• If it is grounded at both ends each pole can operate independently.
• If it is grounded at one end, each pole can operate dependently to each other.
• The earth carries a small out of balance current during the normal operation.
C) HOMOPOLAR LINK–
D) LONG-DISTANCE TRANSMISSION:-
• This kind of transmission is connected when the voltage to be conveyed is high, and the
separation between both AC stations is more than make back the initial investment
remove. Fig.is demonstrating the Long separation HVDC transmission system.
• This type of transmission is connected when the voltage to be conveyed high, and the two
stations work at various frequencies.
• An electrical distribution system, based on this method would eliminate the need for an
inefficient, costly, and capital intensive grid of cables, towers, and substations.
• It will rid the landscape of wires, cables, and transmitting towers.
• The electrical energy can be economically transmitted without wires to any terrestrial
distance, so there will be no transmission and distribution loss.
• More efficient energy distribution systems and sources are needed by both developed and
under developed nations.
• To transmit wireless power to any distance without limit. It makes no difference what the
distance is.
• The power failure due to short circuit and fault on cables would never exist in the
transmission.
• Power theft would be not possible at all.
1. INDUCTION PROCESS
• In this process whenever a current with a voltage is passed through a induction coil, it
stores a energy and produce electric flux which leads production of electromagnetic field.
• This field carries electric voltage and current with them.
• When this electric field links with the coil produces voltage in the other coil by
electromagnetic induction process
• This process is not suitable for health and environment as electromagnetic field causes
blood clotting and cancer among human