Rev C Gc2e Install Programming Guide Web
Rev C Gc2e Install Programming Guide Web
CONTENTS
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
About this Guide . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
About the 2GIG Go!Control System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Important Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Installing the System in Residential Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Installing the System in Commercial Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
System Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Optional Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
2GIG GC2e Security Panel XCVR Compatibility . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
System Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Control Panel Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
External Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Internal Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Installation Outline . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Wireless Installation Tips . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Sensors and Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Wireless System Sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Wireless System eSensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
System Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Control Panel Mounting Plate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Wireless Sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Hardwired Loop . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Remote Alarm Sounder . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
LTE (Cellular) Radio Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Control Panel Wiring Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Control Panel Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Terminal Block Wiring Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Backup Battery Connection and Power Supply Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Wire Size and Length . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Control Panel and Power Supply Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Commercial Installations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
NFPA Standard 72 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Main Display Screens . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Home Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Security Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Arming Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Menu Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
System Status Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Toolbox and Installer Toolbox . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Toolbox Screens . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Accessing the Toolbox . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Installer Toolbox Screens . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Accessing the Installer Toolbox . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Accessing the System Configuration for System and Sensor Programming . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
System Configuration Screens . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
System Status Icons . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
AC Power On/OFF . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Sounder Disabled . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Low Backup Battery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Test Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Touch Screen Keypad Traffic . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Cell Radio . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Interior sensor open . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Programming Navigation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Questions without Sub-Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Questions with Sub-Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Questions with Data Entry . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Additional Buttons . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Programming Outline . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
ANSI/SIA CP-01 Compliance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
2GIG is a registered trademark of Nortek Security & Control LLC. ©2020 Nortek Security & Control LLC. All rights reserved. 1
GC2e Wireless Security System | Installation and Programming Guide
2GIG is a registered trademark of Nortek Security & Control LLC. ©2020 Nortek Security & Control LLC. All rights reserved. 2
GC2e Wireless Security System | Installation and Programming Guide
2GIG is a registered trademark of Nortek Security & Control LLC. ©2020 Nortek Security & Control LLC. All rights reserved. 3
GC2e Wireless Security System | Installation and Programming Guide
Introduction
Important Information
The 2GIG Go!Control security system conforms to the Security Industry Alarm Coalition’s ANSI/SIA CP‐01: Control Panel
Standard‐Features for False Alarm Reduction. It also meets the residential security system certification criteria for the ETL
Listed Mark.
The recommended storage temperature for all Control Panels is ‐10°C to 60°C (14°F to 140°F). For optimal Control
Panel use, operation temperature is 0°C to 49°C (32°F to 120°F). No altitude range limitations have been reported while
transporting Control Panel.
2GIG is a registered trademark of Nortek Security & Control LLC. ©2020 Nortek Security & Control LLC. All rights reserved. 4
GC2e Wireless Security System | Installation and Programming Guide
2GIG is a registered trademark of Nortek Security & Control LLC. ©2020 Nortek Security & Control LLC. All rights reserved. 5
GC2e Wireless Security System | Installation and Programming Guide
Introduction
Optional Accessories
Optional modules, keypads, radios, and sensors that can be purchased to enhance the system include:
• 2GIG LTE (Cellular) Radio Module. An on‐board digital communicator reports alarms and trouble to a Central
Station receiver and a two (2)‐way voice communication with the Central Station. It also supports OTA updates
and remote control of the system using a Web‐enabled device through the Internet.
• 2GIG 900 MHz Transceiver Module. It sends and receives signals with wireless touch screen keypads and image
sensors. Touch screen keypads allow remote control of the system through the same graphic interface design as
the 2GIG Control Panel. Note that the 2GIG 900 MHz Transceiver Module, touch screen keypad, and image sensor
are only available in some regions.
• 2GIG Wireless Touch Screen Keypad. A wall‐mounted, full‐color, touch screen interface that provides many of
the same easy‐to‐use keypad functions available on the Control Panel. It is designed for indoor use only and gives
users the ability to control lights, thermostats, and door locks, as well as to view the status of every sensor zone.
When the 2GIG 900 MHz Transceiver Module is installed in the Control Panel, the system can be programmed to
communicate with up to four (4) Wireless Touch Screen Keypads.
• 2GIG Go!Bridge IP Communicator. The Go!Bridge provides Internet connectivity between the monitoring
service’s Central Station and the Go!Control® Panel (requires the 2GIG 900 MHz Transceiver Module and supports
automatic firmware updates, provides interactive security services, and increases supervision using signal‐
forwarding to the Central Station.
• 2GIG Super Switch Takeover Module. The takeover module communicates with the 2GIG Control Panel and is
designed to convert up to eight (8) pre‐wired zones to supervised wireless zones.
• 2GIG Hardwire Conversion Kit. This kit provides installers with an easy way to convert the zones of a pre‐wired
security alarm system to 2GIG wireless zones. The kit includes one (1) Super Switch Takeover Module (Wireless
Takeover of an Alarm System, US Patent No. 8,638,218). You can also install two (2) additional modules, which
provides installers with the capability to convert up to 24 pre‐wired security zones to wireless zones.
2GIG is a registered trademark of Nortek Security & Control LLC. ©2020 Nortek Security & Control LLC. All rights reserved. 6
GC2e Wireless Security System | Installation and Programming Guide
System Configuration
This illustration details the entire system configuration (including optional features). See “Optional Accessories” on page 6.
Figure 1 Complete System Configuration
Subscriber
Siren
Voice
Subscriber’s
Full-Color Smart Phone
Touch Screen LCD or Tablet
Land IP
Hardwired Cell Site Network
Loop #2
Speaker &
Hardwired Microphone Land IP
Loop #1
Hardwire Inputs
CPU
PIR
Motion Wireless Wireless
Detectors Keypads Touch Screen
Security Keypad‡
Receiver
Cell Radio
Smoke/Heat/ Glass Break Install up to four (4) Telephone
Freeze Alarms Detectors Wireless Touch Screen Network
Keypads per system
Door/
Remote
Window
Key Fobs
Contacts CONTROL PANEL
Bell Z-Wave System
CO Panic
Output Radio Power
Alarms Buttons Central Station
Receiver
Install up to 60
14 VDC
wireless sensors per system
Remote
Power Services
Supply Provider (RSP)
Piezo Server
Siren
Input
Power
RSP
Infrastructure
2GIG is a registered trademark of Nortek Security & Control LLC. ©2020 Nortek Security & Control LLC. All rights reserved. 7
GC2e Wireless Security System | Installation and Programming Guide
External Features
Figure 2 Control Panel External Features
A B
C
D
E
Sounds all system local alarms, voice prompts, system sounds, and audio for two (2)-way voice
A Alarm Sounder and Speaker communications with the Central Station
Shows all system information, status, programming, and functions as the keypad.
B Color Display with Touchscreen
Display cycles clock, calendar, and weather with your service provider account (tap manually to change)
C Emergency Button/Indicator Lights WHITE when enabled for emergency alarms and flashes during emergency alarms
D Microphone For voice communication with the Central Station
Sensor Status
Lights BLUE when all sensors are closed (ready to arm)
Not lit when any sensor is open (not ready to arm)
Arming Status
Lights RED when system is armed
Flashes RED during the Entry Delay
Alarm Memory
E Home Button/Indicator
Flashes RED during an alarm
Flashes RED after an alarm while system is still armed
Power Outage
Flashes WHITE during power outage (system on battery backup)
Flashes BLUE when all sensors are closed (ready to arm)
Flashes ORANGE when any sensor is open (not ready to arm)
Flashes RED while system is armed
2GIG is a registered trademark of Nortek Security & Control LLC. ©2020 Nortek Security & Control LLC. All rights reserved. 8
GC2e Wireless Security System | Installation and Programming Guide
Internal Features
Figure 3 Control Panel Internal Features
A F
C E
The standard backup battery that is included with all 2GIG Control Panels does not support UL 985 installations
A Backup Battery Pack To comply with the secondary supply requirement in UL 985 Household Fire Warning System Units, you must
install the 2GIG Console Battery Pack (2GIG-BATT2X).
B Terminal Block Connections for power, solid state output bell, and hardwire loops.
C Alternate Power Supply Alternate connection for power. (Plug-in barrel connector)
D J4 Pin Connector Connector for the Firmware Update Cable used to update the firmware version on the Control Panel.
E Cell Radio Module 2GIG Go!Control Module for over-the-air communication with the Central Station.
Receiver for peripheral device transmissions (or an optional 2GIG 900 MHz Transceiver Module for use with the
F Main Receiver Module Wireless Touch Screen Keypad).
G Third-Hand Hanger Strap Hooks onto mounting plate during installation to hold the Control Panel while wiring.
2GIG is a registered trademark of Nortek Security & Control LLC. ©2020 Nortek Security & Control LLC. All rights reserved. 9
GC2e Wireless Security System | Installation and Programming Guide
Installation Outline
Use the following outline in conjunction with this Installation and Programming Guide to guide you through the installation steps.
1. Unpack the system and identify the system components.
2. Create an Installation Floor Plan to determine the best centralized location for the Control Panel.
3. Decide where to best install the wired and/or wireless sensors. Guidelines are available in the Installation Instructions included
with each sensor.
4. Identify an unswitched wall outlet to use for the Control Panel’s power supply.
5. (Optional) Install the LTE (Cellular) Radio Module in the Control Panel. See “LTE (Cellular) Radio Module” on page 15.
6. Use the Control Panel’s backplate to mark the drywall cutouts for the Control Panel. Then make the cutouts and attach the
backplate to the wall. See “Control Panel Mounting Plate” on page 13.
7. Install each of the system’s wireless sensors. If the hardware zone is used, install the contacts and route the loop wire to the
Control Panel’s wall cutout.
8. Install the optional hardwired sounder, and route the connection wire to the Control Panel’s wall cutout.
9. Use the third‐hand hanger strap to hang the Control Panel on the mounting plate. Then connect all wiring to the Control
Panel’s terminal block. See “Control Panel Wiring” on page 17 and “Terminal Block Wiring Diagram” on page 17.
10. Plug the backup battery connector into the connector on the circuit board.
11. Swing the Control Panel up, placing the bottom over the lip of the mounting bracket. Push the top of the Control Panel into the
mounting bracket until it snaps into place, then secure it with the retaining screw.
12. Plug the power supply into the unswitched wall outlet.
13. Program the system as described in this manual and document any custom setup options for the end user in the space
provided in the User Guide.
14. Test the system as described “Installer Testing” on page 61.
15. Educate the end user(s) about basic system operations and provide them with the Control Panel’s User Guide.
2GIG is a registered trademark of Nortek Security & Control LLC. ©2020 Nortek Security & Control LLC. All rights reserved. 10
GC2e Wireless Security System | Installation and Programming Guide
CORRECT INCORRECT!
Centrally Locate Sensors at the other end of the
Control Panel house might be too far away
CONTROL
PANEL
CONTROL
Basement Basement PANEL
CORRECT INCORRECT!
Mount Control Panel as HIGH Locating Control Panel below
above earth level as practical earth level impairs range
Location of Sensors
SENSOR
SENSOR SENSOR
2GIG is a registered trademark of Nortek Security & Control LLC. ©2020 Nortek Security & Control LLC. All rights reserved. 11
GC2e Wireless Security System | Installation and Programming Guide
2GIG is a registered trademark of Nortek Security & Control LLC. ©2020 Nortek Security & Control LLC. All rights reserved. 12
GC2e Wireless Security System | Installation and Programming Guide
Installation
Control Panel Mounting Plate
Mount the Control Panel on the wall in a convenient location (or use the optional desk mount). These tools may be required to mount the Control
Panel onto the wall:
• Screwdriver
• Wire Stripper
• Staple Gun
• Drywall Saw (or equivalent)
• Ladder Figure 5 Control Panel Mounting Procedure
1. To remove the optional desk mount, press the inward on the tabs connecting the base and
panel.
2. Hold firmly, then use your fingernail to detach and remove the panel faceplate (A). Desk Mount
3. Unlock the two captive screws (B) and two latches (C) with a small flathead screwdriver to
separate the panel (D) from the bottom mounting plate.
4. Depress the two tabs and pull apart to unlock the unit from the mounting plate.
5. Use the level on the mounting plate, then mark the wall for the wiring cutout slot. Use a
drywall saw to cut the slot. Four Tabs
6. If using the optional LTE (Cellular) Radio Module with an external antenna, remove the plastic
knockout labeled “ ” on the mounting plate (E). Mark and cut a slot in the drywall for the
external antenna.
7. Attach the mounting plate to the wall using four (4) screws.
8. Remove the two top screws from the Panel, then replace the screws attaching the Hanger (G).
9. Hang the panel from the mounting plate.
A C D
Mount Holes
E
A Remove Face Plates
B Unlock Locking Screws
C Unlatch Latches
D Remove from Mounting Plate
If using external antenna, remove knockout
plate. Use mounting plate as a template
E to mark wire cutout hole in dry wall (four
screws).
G Hanger
Mount Hole
2GIG is a registered trademark of Nortek Security & Control LLC. ©2020 Nortek Security & Control LLC. All rights reserved. 13
GC2e Wireless Security System | Installation and Programming Guide
Installation
Wireless Sensors
Install wireless sensors in the appropriate location using the Installation Instructions included with each wireless sensor as a guide.
Hardwired Loop
Hardwired loops can be programmed either Normally Open (N/O) or Normally Closed (N/C). End‐of‐Line Resistors (EOLR) can also
be used to supervise the loops. Only contacts should be used with the hardwired loops.
NOTE: The Control Panel does not support powering external devices (PIR’s, etc.).
NOTE: Hardwired loops cannot be used for a CO or Fire sensor loop.
1. If either of the two (2) hardwired loops are going to be used, install the contacts and then route the loop wire to the Control
Panel’s wall cutout.
2. If end‐of‐line supervision is required for the loop, install a 2.2kΩ resistor (not supplied) as shown in Figure 6 Hardwired Loop
Wiring.
2GIG is a registered trademark of Nortek Security & Control LLC. ©2020 Nortek Security & Control LLC. All rights reserved. 14
GC2e Wireless Security System | Installation and Programming Guide
Installation
2GIG is a registered trademark of Nortek Security & Control LLC. ©2020 Nortek Security & Control LLC. All rights reserved. 15
GC2e Wireless Security System | Installation and Programming Guide
Installation
2.2 K
Normally Closed
Contact
OBSERVE POLARITY
when connecting the
Power Supply.
Terminal 1 only
provides power when
the Control Panel’s
power supply is 1 2 3 4 5 6
connected to an 1 – 14VDC Power Input (+)
AC power source.
2 – 14VDC Power Input (–)
3 – Common (GND)
4 – Bell (+)
ALL output
CONTROL PANEL 5 – Bell (–) voltages are
6 – Hardwire Zone Class 2
2GIG is a registered trademark of Nortek Security & Control LLC. ©2020 Nortek Security & Control LLC. All rights reserved. 16
GC2e Wireless Security System | Installation and Programming Guide
Installation
2GIG is a registered trademark of Nortek Security & Control LLC. ©2020 Nortek Security & Control LLC. All rights reserved. 17
GC2e Wireless Security System | Installation and Programming Guide
Installation
NOTE: In the United States, wiring routed inside walls, ceilings,
Figure 14 Connecting Battery and Closing Panel
and floors must comply with requirements of ANSI/NFPA 70:
National Electrical Code (NEC) and local building codes. For D
wiring from the output of the 2GIG Class II Power Supply, wiring C
rated CL2, CL2X, CL2R, or PLTC is recommended to satisfy these
requirements. If this wiring is installed in an air plenum (space
used for environmental air exchange) it must be rated CL2P
(plenum‐rated).
D
Figure 13 Power Supply Wiring
E
B A
A
D
A Connect battery
B Align mounting plate tabs inside of console bottom edge
C Swing console up and snap into the mounting plate
Power Supply
2GIG is a registered trademark of Nortek Security & Control LLC. ©2020 Nortek Security & Control LLC. All rights reserved. 18
GC2e Wireless Security System | Installation and Programming Guide
Commercial Installations
For commercial installations, the Control Panel is designed for use only as a burglary alarm system, and not for fire protection.
Installation location and wiring methods shall be in accordance with ANSI/NFPA 70: National Electric Code, UL 681: Installation
and Classification of Burglar and Holdup Alarm Systems, and UL 827: Central‐Station Alarm Services.
NOTE: When used with the Alarm.com service, this security system has been evaluated and complies with UL 1610: Central‐
Station Burglar Alarm Units. For commercial UL 1610 installations, you must install the LTE (Cellular) Radio Module.
See “LTE (Cellular) Radio Module” on page 15.
NOTE: All entries and exits within a commercial installation setup must be protected according to the criteria provided by UL
681: Installation and Classification of Burglar and Holdup Alarm Systems.
Door
Safe
Lock
or
Vault Glass Break
Key Fob Subscriber’s Detector
Workspace
Thermostat
Master User TS1
Subscriber
Door Appliance
Contact Module
Door Lock Wireless
Keypad
Door
Contact
Z-Wave Radio
and
POTS Module
System Door
Cell Radio Module Power Other Users Contact Door
Locks
Glass Break
Detector
Control
Panel Camera
Glass Break
Detector
2GIG is a registered trademark of Nortek Security & Control LLC. ©2020 Nortek Security & Control LLC. All rights reserved. 19
GC2e Wireless Security System | Installation and Programming Guide
NFPA Standard 72
In the United States and Canada, smoke detectors must be installed in accordance with National Fire Protection Association
(NFPA) Standard 72: National Fire Alarm and Signaling Code, which reads as follows:
“2‐1.1.1 Smoke alarms shall be installed outside of each separate sleeping area in the immediate vicinity of the bedrooms and
on each additional story of the family living unit including basements and excluding crawl spaces and unfinished attics. In new
construction, a smoke alarm shall be installed in each sleeping room.
2‐1.1.2 For family living units with one or more split levels (i.e., adjacent levels with less than one full story separation between
levels), a smoke alarm shall suffice for an adjacent lower level, including basements. (Exception: Where there is an intervening
door between one level and the adjacent lower level, a smoke alarm shall be installed on the lower level.)
• Ceiling mounted smoke alarms should be located in the center of the room or hall, or not less than 4 inches from any
wall. When the alarm is mounted on a wall, the top of the alarm should be 4 to 12 inches from the ceiling.
• Do not install smoke alarms where normal ambient temperatures are above 100°F (37.8°C), or below 40°F (4°C). Also, do
not locate alarm in front of air conditioners, heating registers, or other locations where normal air circulation will keep
smoke from entering the detector.
A‐2.5.2.1 Smoke Detection ‐ Are More Smoke Alarms Desirable? The required number of smoke alarms might not provide
reliable early warning protection for those areas separated by a door from the areas protected by the required smoke alarms.
For this reason, it is recommended that the residential user consider the use of additional smoke alarms for those areas for
increased protection. The additional areas include the basement, bedrooms, dining room, furnace room, utility room, and
hallways not protected by the required smoke alarms. The installation of smoke alarms in kitchens, attics (finished or unfinished),
or garages is not normally recommended, as these locations occasionally experience conditions that can result in improper
operation or false alarms”.
NOTE: Smoke alarms are not to be used with detector guards unless the combination has been evaluated and found suitable for
the purpose.
Figure 17 Recommended Smoke Alarm Locations
D
BEDROOM BASEMENT
ROOM alarms are optional where a door is
provided between a living and
recreation room.
BEDROOM
IMPORTANT: Regulation pertaining to smoke alarm installations vary. For more information, contact your local fire
department or local authority having jurisdiction.
2GIG is a registered trademark of Nortek Security & Control LLC. ©2020 Nortek Security & Control LLC. All rights reserved. 20
GC2e Wireless Security System | Installation and Programming Guide
• Security. Opens the Security screen. See Security • Silent Exit Select this check box to silently arm the
Screen. system without sounding the exit delay beeps. Arming
the system in Stay mode always uses silent exit.
• Services. Opens the Services screen. See the Control
Panel’s User Guide for more information. Figure 20 Arming Screen
• Silent Control. Opens the Bypass screen. See the
Control Panel’s User Guide for more information.
• Display OFF. Turn OFF the Control Panel screen.
Menu Screen
The Menu screen includes the Arm and Toolbox buttons.
Figure 21 The Menu Screen
Security Screen
The Security screen displays three (3) buttons for Arm,
Menu, and Status. It also shows the time, date, and
weather display (requires that the feature is supported by
the Remote Service Provider).
Figure 19 Security Screen
2GIG is a registered trademark of Nortek Security & Control LLC. ©2020 Nortek Security & Control LLC. All rights reserved. 21
GC2e Wireless Security System | Installation and Programming Guide
2GIG is a registered trademark of Nortek Security & Control LLC. ©2020 Nortek Security & Control LLC. All rights reserved. 22
GC2e Wireless Security System | Installation and Programming Guide
The Control Panel includes two (2) different toolboxes for Figure 25 Toolbox (2 of 3)
programming the system:
• Toolbox. Individuals with a user code can access basic
programming functions in the end user Toolbox.
• Installer Toolbox. Individuals with the installer code can
access both the basic programming functions of the user
Toolbox and the more advanced programming functions
of the Installer Toolbox.
Toolbox Screens
The Toolbox provides individuals who possess a user code with
the ability to access basic programming functions.
2GIG is a registered trademark of Nortek Security & Control LLC. ©2020 Nortek Security & Control LLC. All rights reserved. 23
GC2e Wireless Security System | Installation and Programming Guide
NOTE: The other buttons let you restore the default Control The System Configuration screens present installers with
Panel settings and provide access to a variety of system tests. a sequential list of programming questions. For a list of all
available programming questions, see “Programming Question
Table on page 29.
Figure 27 Installer Toolbox Screen
Figure 28 Q1: Select RF Sensor # (01-48, 63-74).
2GIG is a registered trademark of Nortek Security & Control LLC. ©2020 Nortek Security & Control LLC. All rights reserved. 24
GC2e Wireless Security System | Installation and Programming Guide
A Status Bar
B Status Icons
Cell Radio
Figure 31 AC Power OFF
Figure 36 Cell Radio
The AC Power icon shows the status of the AC If the option LTE (Cellular) Radio Module is installed,
power to the Control Panel. A RED “X” appears the Cell Radio icon appears while the Control Panel
over the WHITE plug when AC power is absent. is receiving Over‐the‐Air (OTA) firmware updates.
Test Mode
Figure 34 Test Mode
This icon displays when the system is in Walk
Test mode.
2GIG is a registered trademark of Nortek Security & Control LLC. ©2020 Nortek Security & Control LLC. All rights reserved. 25
GC2e Wireless Security System | Installation and Programming Guide
Programming Navigation
When the installer is using the System Configuration menus, • The ↑ and ↓ arrows select the next or previous
the Control Panel will present each programming question programming sub‐question.
sequentially. Most programming questions have a single • The ← and → arrows choose values for the question on
numeric value response or a simple enabled/ disabled selection. or move the cursor left and right along the white data
Some programming questions have sub‐ options that can be set. entry field.
These sub‐options are displayed for the question selected and
can be accessed through navigation keys on the display. Figure 40 Questions with Sub-options
Navigation Arrows & Go To Button
The programming question screens display up, down, left, and
right navigation arrows. Use these arrows to scroll through the
programming questions and to select sub‐ options.
Tap the Go To button and then enter a two (2)‐digit code to
jump directly to a programming question. See “Programming
Question Table” on page 28. The Go To button changes to Cancel
when waiting for you to enter a question number. Tap Cancel to
back out.
Figure 38 Navigation Arrows & Go To Button
2GIG is a registered trademark of Nortek Security & Control LLC. ©2020 Nortek Security & Control LLC. All rights reserved. 26
GC2e Wireless Security System | Installation and Programming Guide
Programming Navigation
2GIG is a registered trademark of Nortek Security & Control LLC. ©2020 Nortek Security & Control LLC. All rights reserved. 27
GC2e Wireless Security System | Installation and Programming Guide
Programming Outline
Each system installed will require programming. Most After completing all setup and programming tasks, refer to the
installations being performed by the professional alarm installer Control Panel’s User Guide for information about operating the
for a specific organization will have common values set in every system. Check off the programmed options for the system in the User
Control Panel that is reporting to the Central Station. Other Guide.
programming values, such as the account number and sensor NOTE: Instruct the end user about proper system operations, and
setup, may be unique for each installation. leave the User Guide at the installation site for reference.
Use the following outline to guide you through the installation
process. Understanding the Control Panel’s programming ANSI/SIA CP-01 Compliance
structure will help to save time during each installation. Several programmable options have the defaults preset to provide
At this stage the following should be already completed: compliance with the American National Standards Institutes/
Security Industry Association CP‐01 Control Panel Standard. The
• All hardwired sensors installed table below details the settings that comply with ANSI/SIA CP‐01
• All wireless sensors installed and permanently programmed into the Console. The ANSI/SIA CP‐01
• Control Panel mounted, connected, and powered up settings documented in the table be low cannot be changed:
1. At the Home screen, tap the system logo in the lower right
corner. ANSI/SIA CP-01
Programming Questions Range
Setting
Figure 43 The Home Screen Q1> Q: Select RF Sensor# (0) Disabled or
(1) Enabled
Dialer Delay (0 to 1) (1) Enabled
Q2 > Q: Select Wired (0) Disabled or
Sensor (1) Enabled
(1) Enabled
Dialer Delay (0 to 1)
Q5 Enter Exit Delay, in
60 Seconds 45-120 Seconds
Seconds (45-120)
Q6 Enter Entry Delay 1, in 30 Seconds 30-240 Seconds
seconds (45-120)
6. When prompted, enter the master user code. The default Q32 Select Cancel (0) Disabled or
(1) Enabled
master user code is 1111. Display (0 to 1) (1) Enabled
7. Tap the User Management button and then setup the Q35 Select Abort Window
30 Seconds 15 to 45 Seconds
user codes. Be sure to set up the Duress Code as User #8. Dialer Delay (0 to 2)
Tap Back when finished.
8. Tap Brightness/Volume and set the levels for the
installation.
9. The volume setting does not affect the volume of alarm
sounds.
10. Tap → to view the second toolbox screen.
11. Tap Back Light Timeout and set the display lighting
timeout.
12. Tap Set Date and Set Time and set the calendar and clock.
If the LTE (Cellular) Radio Module is installed,the date and
time sets automatically.
13. Press the button to return to the Home screen.
2GIG is a registered trademark of Nortek Security & Control LLC. ©2020 Nortek Security & Control LLC. All rights reserved. 28
GC2e Wireless Security System | Installation and Programming Guide
2GIG is a registered trademark of Nortek Security & Control LLC. ©2020 Nortek Security & Control LLC. All rights reserved. 29
GC2e Wireless Security System | Installation and Programming Guide
2GIG is a registered trademark of Nortek Security & Control LLC. ©2020 Nortek Security & Control LLC. All rights reserved. 30
GC2e Wireless Security System | Installation and Programming Guide
2GIG is a registered trademark of Nortek Security & Control LLC. ©2020 Nortek Security & Control LLC. All rights reserved. 31
GC2e Wireless Security System | Installation and Programming Guide
Zone Numbering
The Control Panel supports 60 wireless protection zones. When programming zones, keep the following numbering ranges in mind:
Zones Descriptions
1-48 Wireless Zones
47-48 Wireless Cross-Sensor Zone
49-50 Wired Zones
51-58 Keyfobs
59-62 Keypads
63-74 Wireless Zones
92 Duress
95 Fire
96 Medical
99 Police Panic
2GIG is a registered trademark of Nortek Security & Control LLC. ©2020 Nortek Security & Control LLC. All rights reserved. 32
GC2e Wireless Security System | Installation and Programming Guide
(16) 24-Hour Fire with For verification, this sensor type must be violated twice in two (2) minutes, or remain violated for 30 seconds. If any
other fire sensor (verified sensor type or not) violates within two minutes, both sensors will cause a fire alarm.
Verification †
WARNING
THIS UNIT INCLUDES AN ALARM VERIFICATION FEATURE THAT WILL RESULT IN A DELAY OF THE SYSTEM ALARM
SIGNAL FROM THE INDICATED CIRCUITS. THE TOTAL DELAY (CONTROL UNIT PLUS SMOKE DETECTORS) SHALL NOT
EXCEED 60 SECONDS. NO OTHER SMOKE DETECTOR SHALL BE CONNECTED TO THESE CIRCUITS.
2GIG is a registered trademark of Nortek Security & Control LLC. ©2020 Nortek Security & Control LLC. All rights reserved. 33
GC2e Wireless Security System | Installation and Programming Guide
2GIG is a registered trademark of Nortek Security & Control LLC. ©2020 Nortek Security & Control LLC. All rights reserved. 34
GC2e Wireless Security System | Installation and Programming Guide
Voice Descriptors
The Control Panel includes a system vocabulary. When programming sensors when using firmware version 1.13, you can use the codes
detailed in this table:
Figure 44 List of Voice Descriptors
2GIG is a registered trademark of Nortek Security & Control LLC. ©2020 Nortek Security & Control LLC. All rights reserved. 35
GC2e Wireless Security System | Installation and Programming Guide
Voice Descriptors
2GIG is a registered trademark of Nortek Security & Control LLC. ©2020 Nortek Security & Control LLC. All rights reserved. 36
GC2e Wireless Security System | Installation and Programming Guide
Equipment Codes
The table below details the available equipment codes:
Code Description
0000 Other
0470 HW R-D/W “5818MNL”
0475 Existing Glass Break Detector
0491 HW Panic Pendant “5802MN2”
0519 HW Glass Break “5853”
0530 HW PIR “5894PI”
0533 HW PIR “5890”
0556 Existing Flood/Temp Sensor
0557 HW Heat Sensor “5809”
0577 Existing Keyfob Remote
0589 HW Smoke “5808W3”
0609 Existing Motion Detector
0616 Existing Smoke Detector
0624 HW Flood Sensor “5821”
0637 HWD/W”5816”
0655 Existing Door/Window Contact
0692 Existing CO Detector
0708 Existing Heat Sensor
0859 CO1-345C CO Detector (Canada)
0860 CO1-345 CO Detector (USA)
0862 2GIG Thin Door/Window Contact
0863 2GIG Recessed Door Contact
0864 2GIG Glass Break Detector
0865 2GIG Outdoor Door/Window Sensor
0866 2GIG 4-Button Keyfob Remote
0867 2GIG Wireless Keypad
0868 2GIG Panic Button Remote
0869 2GIG PIR with Pet Immunity
0871 SMKE1-345C Smoke Detector (Canada)
0872 SMKE1-345 Smoke Detector (USA)
0873 2GIG Takeover Module
0895 Smoke/Heat Detector (USA/Canada)
1026 2GIG CO Detector
1058 2GIG Smoke Detector
1059 2GIG-TS1 Wireless Touchscreen Keypad
1061 Tilt Sensor
1062 2GIG Tilt Sensor
1063 2GIG Doorbell
1064 2GIG Bypass Sensor
1065 2GIG Flood Sensor
1067 2GIG Repeater
1068 2GIG Translator
1069 2GIG FireFighter SMKT/CO Listener
9999 Alarm.com Image Sensor
2GIG is a registered trademark of Nortek Security & Control LLC. ©2020 Nortek Security & Control LLC. All rights reserved. 37
GC2e Wireless Security System | Installation and Programming Guide
Installer Programming
Account Registration • Q: Select RF Sensor # Equipment Code. Select the four (4)‐
digit equipment code for the sensor model. See “Equipment
Register the account to enroll the Control Panel with the remote Codes” on page 37.
service provider’s Central Station.
• Q: Enter RF Sensor # Other Equipment Code. If you select
Typically, the account registration data is created with the service (0000) Other in the previous question, you must enter this
installation contract and then stored in a database managed by code.
the Central Station. The data includes items such as the customer
• Q: Enter RF Sensor # Serial #. Enter the serial number
name, address, and the Central Station telephone number, and the (typically a label on the sensor or its packaging) or tap Shift
account number assigned to the Control Panel. then Learn on the panel. Then trip the sensor to transmit
If you will be installing the 2GIG Go!Bridge IP Communicator, the serial number to the panel.
additional registration information is required. For details, see • Q: Select RF Sensor # Equipment Age. Specify whether the
the Installation Instructions included with the Go!Bridge IP sensor is (0) New or (1) Existing.
Communicator.
• Q: Select RF Sensor # Loop Number. Specify the
Wireless (RF) Sensor Programming appropriate loop number(s) for the sensor. See “Q: Select RF
Sensor # Loop Number (1 to 3)” on page 40.
The Control Panel can be programmed with up to 60 RF sensors
of different types. In addition to the 60 multi‐ purpose RF sensors, • Q: Select RF Sensor # Dialer Delay. Specify whether to use
delayed or instant digital communicator reports for the
you can also program eight (8) RF remote control key fobs and four
sensor. The delay time is set on the Dialer Abort screen.
(4) RF remote control keypads into the system.
• Q: Construct RF Sensor # Voice Descriptor. Specify the
RF sensors # 01‐48 and #63‐74 report as wireless zones 01‐ 60. name assigned to the sensor that is announced if this
Programming questions for RF sensor programming include: feature is programmed.
• Q1: Select RF Sensor Number. Select sensor number 01‐48 or • Q: Select RF Sensor # Reports. Specify (0) Disabled or (1)
63‐74. Enabled whether or not RF sensors trigger a report to the
Central Station.
• Q: Select RF Sensor # Type. Select (01) Exit/Entry 1, (02)
Exit/Entry 2, (03) Perimeter, and so on. For options, see • Q: Select RF Sensor # Supervised. Specify whether or not
“Zone Numbering” on page 32. the Control Panel checks for status reports from the sensor.
• Q: Select RF Sensor # Equipment Type. Some sensor types • Q: RF Sensor # Chime. Select voice announcement and
ask for the equipment type, others do not. See “Q: Select chime options for the sensor.
RF Sensor # Equipment Type” on page 40.
2GIG is a registered trademark of Nortek Security & Control LLC. ©2020 Nortek Security & Control LLC. All rights reserved. 38
GC2e Wireless Security System | Installation and Programming Guide
Installer Programming
Q: SELECT RF SENSOR #
ENTER ON KEYPAD
EQUIPMENT TYPE
2GIG is a registered trademark of Nortek Security & Control LLC. ©2020 Nortek Security & Control LLC. All rights reserved. 39
GC2e Wireless Security System | Installation and Programming Guide
Installer Programming
Sensor Types (Zone) RF Wired • For automatic entry. Tap Shift, then tap Learn to place
the Control Panel into learning mode. Then trigger the RF
(08) 24-Hour Auxiliary Alarm* Y Y sensor. The Control Panel will beep four (4) times and learn
(09) 24-Hour Fire Y N the sensor’s serial number. If the sensor being learned is
already in memory, the Control Panel will display a sensor
(10) Interior with Delay* Y Y learning failure screen when the programming changes are
(14) 24-Hour Carbon Monoxide Y N being saved.
For certain sensors with more than two loops, the tamper switch
(16) 24-Hour Fire Verification Y N must be used to send a signal to the Control Panel during sensor
(23) No Response Type* Y Y learning. The fir st press of the tamper switch will learn the sensor
(24) Silent Burglary Y Y
into the panel as Loop #1. The second press of the tamper switch
will learn the sensor into the panel as Loop #2, and the third press
Q: Select RF Sensor # Equipment Type of the tamper switch will learn the sensor into the panel as Loop
#3. Pa use 15 seconds between each press of the tamper switch.
DEFAULT: Varies by RF Sensor Type
NOTE: Some sensor types (zones) will require you to specify an The programmed loop number of the sensor in the Control Panel
equipment type selection, which affects the sensor’s extended may need changing to suit the operation of the device. For details,
reporting code. see the Installation Instructions included with the sensor.
Simply enter the appropriate equipment type code (see table below)
or tap the ← or → arrows to select the appropriate equipment type.
Q: Select RF Sensor # Equipment Age (0 to 1)
DEFAULT: (0) New
The table below shows the Equipment Types available for each Sensor
Type (Zone): The Control Panel can be used with new or existing RF sensors.
• If this RF sensor is new for the installation, leave the default
Sensor Type (Zone) Equipment Types setting of (0) New.
• If this RF sensor is already installed, select (1) Existing.
(04) Interior Follower (1) Motion
(2) Contact NOTE: If the RF sensor has more than one loop and is being
programmed into multiple sensor numbers to support the loops,
(06) 24-Hour Silent Alarm (1) Contact set only one loop as “new” and the other loops as “existing”. This
(11) Emergency will prevent incorrect inventory of the installed sensors.
(07) 24-hour Audible Alarm (1) Contact
(11) Emergency Q: Select RF Sensor # Loop Number (1 to 3)
(08) 24-Hour Auxiliary (1) Contact DEFAULT: Varies with sensor model selected
(6) Freeze The 2GIG Door/Window Contact sensors have two (2) inputs: an
(8) Water internal magnetic contact and an external Normally Closed (N/C)
(10) Temperature hardwired input. Either or both sensor inputs can be used.
(11) Emergency
TIP: Some sensors are capable of three (3) loop inputs.
(10) Interior with Delay (1) Motion
NOTE: When using both the internal magnetic contact and the
(2) Contact
external input, the magnet contact AND the external contact must
(23) No Response Type (1) Contact be assigned a different RF sensor number. Both sensor numbers
(2) Motion will share the same sensor serial number.
• When programming the sensor to use the built‐in magnetic
Q: Select RF Sensor # Equipment Code contact, set the loop number to (2) 2.
DEFAULT: (0000) Other • When programming the sensor to use its hardwired input,
Select the four (4)‐digit equipment code that corresponds to the set the loop number as (1) 1.
appropriate sensor model. See “Equipment Codes” on page 37. • When programming a three (3)‐loop sensor to use an
additional input, set the loop number as (3) 3.
• When programming eSensors (Wireless & Keyfobs), the
equipment code must match the sensor being installed. • When entering the sensor number for the sensor’s loop 2
or 3, tap Paste to recall the last programmed sensor’s serial
number. (The sensor number will be filled in automatically
Q: Select RF Sensor # Other Equipment Code if Learn is used).
NOTES:
• This sub‐question is only displayed if (0000) Other is selected as
Q: Select RF Sensor # Dialer Delay (0 to 1)
the RF Sensor # Equipment Code. DEFAULT: (1) Enabled
Enter the equipment code number directly on the keypad for the RF If this feature is enabled, the delay time must be set to a minimum
sensor. Enter “0” if the new equipment code is unknown. of 30 seconds for ANSI/SIA compliance. To set the delay time, see
“Q35: Abort Window Dialer Delay (0-2)” on page 52.
Q: Enter RF Sensor # Serial Number (7 Digits) • RF sensors can trigger the digital communicator
immediately or after a delay. The default setting (1) Enabled
DEFAULT: 0000000 causes delayed dialing for this RF sensor number.
RF sensor serial numbers can be manually entered or automatically • For immediate dialing for this RF sensor number, select (0)
transmitted from the sensor to the Control Panel. Disabled.
• For manual entry. Enter the sensor number that was logged NOTE: This setting for CO and Smoke Alarms is automatically set
for the sensor being programmed. Tap Shift to access to (0) Disabled, and this sub‐question is skipped for these sensor
alphabetic characters. types.
2GIG is a registered trademark of Nortek Security & Control LLC. ©2020 Nortek Security & Control LLC. All rights reserved. 40
GC2e Wireless Security System | Installation and Programming Guide
Installer Programming
2GIG is a registered trademark of Nortek Security & Control LLC. ©2020 Nortek Security & Control LLC. All rights reserved. 41
GC2e Wireless Security System | Installation and Programming Guide
Installer Programming
Scroll between op ons using the ← and → arrows. Move to Sensor Types (Zone) RF Sensors Wired Sensors
the previous or next prompt by tapping the ↑ and ↓ arrows.
(00) Unused Yes Yes
1. To program another sensor tap Next.
(01) Exit/Entry 1 Yes Yes
2. To exit programming, tap Skip then End and Exit. Upon
exit, the panel takes several seconds to restart (02) Exit/Entry 2 Yes Yes
(03) Perimeter Yes Yes
2GIG is a registered trademark of Nortek Security & Control LLC. ©2020 Nortek Security & Control LLC. All rights reserved. 42
GC2e Wireless Security System | Installation and Programming Guide
Installer Programming
Sensor Types (Zone) RF Sensors Wired Sensors Q: Select Wired Sensor# Normal State
(04) Interior Follower Yes Yes DEFAULT: (0) Not Used
(05) Day Zone Yes Yes The two hardwired loops can be wired for normally open (N/O) or
normally closed (N/C) contacts, or for end‐of‐line (EOL) resistor.
(06) 24-Hour Silent Alarm Yes Yes
• The default setting (0) Not Used disables this wired sensor.
(07) 24-Hour Audible Alarm Yes Yes • To use this wired sensor, select the way the loop is wired:
(08) 24-Hour Auxiliary Alarm Yes Yes Wired Sensor Normal State
(09) 24-Hour Fire Yes No • (0) Not Used
(10) Interior with Delay Yes Yes • (1) Closed
(14) 24-Hour Carbon Monoxide Yes No • (2) Open
• (3) End‐of‐Line Resistor
Q: Select Wired Sensor# Equipment Type Q: Select Wired Sensor# Dialer Delay (0 to 1)
DEFAULT: Varies by wired sensor type DEFAULT: (1) Enabled
NOTE: This question is only displayed when certain sensor types If this feature is enabled, the delay time must be set to a minimum of
(zones) are selected. 30 seconds for ANSI/SIA compliance. To set the delay time, see “Q35:
The equipment type selection will affect the sensor’s extended Abort Window Dialer Delay (0-2)” on page 52.
reporting code. Wired sensors can trigger the digital communicator immediately or
The following sensor types require equipment type selection: after a delay.
• The default setting (1) Enabled causes delayed dialing for this
Sensor Type (Zone) Equipment Types wired sensor number.
(04) Interior Follower (1) Motion
• For immediate dialing for this wired sensor number, select (0)
Disabled.
(2) Contact
(06) 24-Hour Silent Alarm (1) Contact Q: Construct Wired Sensor # Voice Descriptor
(11) Emergency
DEFAULT: No Default
(07) 24-hour Audible Alarm (1) Contact NOTE: For a list of voice descriptors, see “Voice Descriptors” on
(11) Emergency page 35.
(08) 24-Hour Auxiliary (1) Contact The voice descriptors are the words the Control Panel will announce
(6) Freeze for this wired sensor if this wired sensor is programmed for voice
(8) Water annunciation. Up to five (5) words are allowed.
(10) Temperature
1. Tap Insert to place a word from the vocabulary into the data
(11) Emergency
entry field.
(10) Interior with Delay (1) Motion
2. Use the ← or → arrows to scroll through the words, or enter the
(2) Contact word’s three (3)‐digit number.
(23) No Response Type (1) Contact 3. Tap Insert again for the next word. Up to five (5) words are
(2) Motion allowed.
4. To move between words, tap the Fwd and Back buttons.
Select the equipment type that matches the sensor equipment using 5. To remove a word, tap Delete.
the ← or → arrows, or enter the equipment type number directly on
the keypad.
Q: Select Wired Sensor# Reports (0 to 1)
NOTE: This Control Panel does not provide auxiliary accessory output DEFAULT: (1) Enabled
power.
Wired sensors can be programmed to trigger a report to the Central
Connecting a hardwire PIR using equipment type “motion” will Station or not.
require an external stand‐alone battery backed‐up power supply for
the PIR. • The default setting (1) Enabled activates reporting for this wired
sensor number.
Q: Wired Sensor # Equipment Code (0-9999) • To prevent reporting for this wired sensor number, select (0)
Disabled.
DEFAULT: (0 )
Select the four (4)‐digit equipment code that corresponds to the Q: Select Wired Sensor# Chime (00 to 13)
appropriate sensor model. See “Equipment Codes” on page 37.
DEFAULT: (0) Disabled
Q: Select Wired Sensor# Equipment Age (0 to 1) Each wired sensor can be set to sound a “ding‐dong” chime and/or
sound its voice descriptor when the sensor is triggered.
DEFAULT: (0) New
• The default setting (0) Disabled inactivates the chime for this
The Control Panel can be used with new or existing wired sensors. wired sensor.
• If this wired sensor is new for the installation, leave the • If a chime and/or voice is required for this wired sensor,
default setting of (0) New. choose one of the other chime options (next page):
• If this wired sensor is already installed, select (1) Existing.
2GIG is a registered trademark of Nortek Security & Control LLC. ©2020 Nortek Security & Control LLC. All rights reserved. 43
GC2e Wireless Security System | Installation and Programming Guide
Installer Programming
Sensor Chime
Code Sensor Chime See Figure 49 Key Fob Programming Outline for the steps
required to program fobs into the Control Panel. The options
(0) Disabled
that can be set for each fob are:
(1) Voice Only
(2) Ding-Dong with Voice #1 • Q3: Select Fob Number. Select key fob number 1‐8.
(3) Ding-Dong #2 • Q: Select Fob # Used. Select (0) Disabled or (1) Enabled.
(4) Ding-Dong with Voice #2 • Q: Select Fob # Equipment Code. Select the four (4)‐digit
(5) Ding-Dong #1 equipment code that corresponds to the appropriate
keyfob. See “Equipment Codes” on page 37.
(6) Ding-Ding
• Q: Enter Fob # Other Equipment Code. Enter the special
(7) Ding-Ding with Voice
equipment code. This is only required when the Key Fob
(8) Ding-Dong #3 # Equipment Code is set to (0000) Other.
(9) Ding-Dong with Voice #3 • Q: Enter Fob # Serial #. Enter the serial number (typically
(10) Chime #1 a label on the keyfob or the keyfob packaging) or tap
(11) Chime #1 with Voice #1 Shift then Learn to place the panel into learning mode.
(12) Chime #2 Then trip the keyfob to transmit the serial number to the
(13) Chime #2 with Voice #2 panel.
• Q: Select Fob # Equipment Age. Specify whether the
sensor is a (0) New or (1) Existing sensor.
Wireless (RF) Key Fob Programming • Q: Select Fob # Emergency Key. Choose the function of
The Control Panel can be programmed with up to eight (8) RF key double‐tapping the top buttons (0) Disabled, (1) Auxiliary
fobs. Alarm, (2) Audible Alarm, (3) Silent Panic, or (4) Fire.
Programming the fobs into the Control Panel involves selecting • Q: Select Fob # Key # Can Disarm. Choose (0) Disabled or
the sensor number for a particular device, setting or learning the (1) Enabled to specify if the key fob is allowed to disarm
serial number, and selecting the other options for the sensor. the system.
• Q: Construct Fob # Voice Descriptor. Construct the
IMPORTANT: RF key fobs 1 ‐ 8 report to the Control Panel as name assigned for the keyfob announcement. See “Voice
sensors 51 ‐ 58 (opening/closing, emergency, and low battery Descriptors” on page 35.
reports). • Q: Select Fob # Arm No Delay. Choose if key fob will arm
the system instantly without an exit delay.
Fob# Reports as Sensor# • Q: Select Fob # Key # Output. Select an action for the key
1 51 fob auxiliary button.
2 52
3 53
4 54
5 55
6 56
7 57
8 58
2GIG is a registered trademark of Nortek Security & Control LLC. ©2020 Nortek Security & Control LLC. All rights reserved. 44
GC2e Wireless Security System | Installation and Programming Guide
Installer Programming
2GIG is a registered trademark of Nortek Security & Control LLC. ©2020 Nortek Security & Control LLC. All rights reserved. 45
GC2e Wireless Security System | Installation and Programming Guide
Installer Programming
Q: Enter Fob # Serial Number (7 Digits) Q: Select Fob (#) Arm No Delay (0 to 1)
DEFAULT: 0000000 DEFAULT: (0) Disabled
Key fob serial numbers can be manually entered or learned from Key fobs can be set to arm the Control Panel with or without an
the fob. entry delay.
• For manual entry, enter the fob number that was logged for • The default setting (0) Disabled sets this fob to arm the
the fob being programmed. Use the Shift button to access system with an entry delay.
alpha characters. • To set this fob to arm the system without an entry delay,
• For automatic entry, tap Shift, then tap Learn. The Control select (1) Enabled.
Panel will wait for a fob transmission. Trigger the fob being
programmed and the Control Panel will learn the fob’s serial
number. Wireless (RF) Keypad Programming
The Control Panel can be programmed with up to four (4) RF
Q: Select Fob # Equipment Age (0 to 1) keypads or RF touch screen keypads.
DEFAULT: (0) New NOTE: RF Keypads 1 ‐ 4 report to the Control Panel as sensors 59
The Control Panel can be used with new or existing key fobs. ‐ 62 (for emergency, and low battery reports).
• If this fob is new for the installation, leave the default
setting of (0) New. RF Keypad Reporting Codes
• If this fob is already installed, select (1) Existing. Keypad 1 Reports as sensor #59
Keypad 2 Reports as sensor #60
Q: Select Fob # Emergency Key (0 to 4) Keypad 3 Reports as sensor #61
DEFAULT: (0) Disabled
Keypad 4 Reports as sensor #62
Pressing the and buttons on a key fob at the same time for
5 seconds can trigger an emergency alarm. • User Codes #1 ‐ #8 are reported for openings and closings
• The default setting (0) Disabled inactivates the emergency • User Code #0 is reported for Quick Arming The following
function the fob #. options can be set for each RF keypad:
• To enable the emergency function for this fob, select one (1) • Select RF Keypad Number. Select keypad number 1‐4.
of the four (4) options: • Select RF Keypad # Used. Enable or disable the keypad.
• Select RF Keypad # Equipment Code. Select the
• (0) Disabled equipment code for the keypad. See “Equipment Codes”
• (1) Auxiliary Alarm on page 37.
• (2) Audible Alarm • Select RF Keypad # Other Equipment Code. If you
• (3) Silent Panic selected (0000) Other, enter the special equipment code.
• (4) Fire • Select RF Keypad # Serial #. Enter the serial number from
the keypad or “learn” by sending a signal.
Q: Select Fob# Key # Can Disarm (0 to 1) • Select RF Keypad # Equipment Age. Select (0) New or (1)
DEFAULT: (1) Enabled Existing.
As an installer, consult the user as to whether to set the key • Select RF Keypad # Emergency Keys. Select (1) Enabled or
fob to allow disarming the Control Panel with the key fob’s (0) Disabled.
buttons. If the user wants the key fob used as a stationary wall • Construct RF Keypad # Voice Descriptor. Construct the
fob, it can also be set to prevent using the key fob to disarm the name assigned for the keypad announcement. See “Voice
system. Descriptors” on page 35.
• The default setting (1) Enabled allows the fob to disarm the
system.
• To not allow the fob to disarm the system, select (0)
Disabled.
2GIG is a registered trademark of Nortek Security & Control LLC. ©2020 Nortek Security & Control LLC. All rights reserved. 46
GC2e Wireless Security System | Installation and Programming Guide
Installer Programming
2GIG is a registered trademark of Nortek Security & Control LLC. ©2020 Nortek Security & Control LLC. All rights reserved. 47
GC2e Wireless Security System | Installation and Programming Guide
Installer Programming
• The keypad displays “Network ID: xxxx” which is its unique serial
number.
• Tap OK on both the Control Panel and the Wireless
• Touch Screen Keypad to continue.
NOTE: The Wireless Touch Screen Keypad will display “The security
system is temporarily not operational” after learning the Keypad. This
is normal, and will be displayed anytime the Control Panel is in system
configuration (programming) mode.
2GIG is a registered trademark of Nortek Security & Control LLC. ©2020 Nortek Security & Control LLC. All rights reserved. 48
GC2e Wireless Security System | Installation and Programming Guide
Programming Questions
Q1: RF Sensor Programming Q13: 2-Way Voice (0-2)
To learn about RF sensor programming, see “Wireless (RF) DEFAULT: (1) Stay On Line
Sensor Programming” on page 38. The Control Panel supports two (2)‐way voice communications
Q2: Wired Sensor Programming between the subscriber and the Central Station operator over
the LTE (Cellular) Radio Module (if installed) after an alarm has
To learn about wired sensor programming, see “Wired been reported.
Sensor Programming” on page 41.
• The (1) Stay On Line allows two (2)‐way audio over the cell
Q3: RF Key Fob Programming radio.
To learn about RF key fob programming, see “Wireless (RF) • Selecting (2) Stay On Line, Including Fire and CO Alarms
Keyfob Programming” on page 44. allows 2‐way audio over cell radio during fire and CO alarms.
• To turn off the two (2)‐way audio feature OFF, select (0)
Q4: RF Keypad Programming Disabled.
To learn about RF keypad programming, see “Wireless (RF) When the Control Panel connects with the operator, it will beep
Keypad Programming” on page 46. once per second (every 6 seconds with a cell radio connection).
The beep alternates between two tones and indicates the
Q5: Exit Delay, in Seconds (45-120) Control Panel is waiting for a session command. If the operator
DEFAULT: 60 seconds fails to issue a command within one (1) minute (or three (3)
The default minimum setting of 60 seconds is required for minutes if using the cell radio connection), the call is terminated.
ANSI/SIA CP‐01 compliance. The delay time can be increased Once the operator presses a command option, the beeps will
without affecting compliance. stop and a five (5)‐minute audio session will start (or three (3)‐
The exit delay timer can be set to a value between 45 to 120 minute audio session if using the cell radio connection).
seconds. When two (2)‐way voice communications have been established,
• The default setting 60 sets the exit delay to 60 seconds. the Central Station operator can use the following telephone
keys to control the communications. Each time the operator
• To change the exit delay timer, enter a value between uses a command key, the session is extended for five additional
45‐120 seconds. minutes (three minutes with a cell radio connection). During the
Q6: Entry Delay 1, in Seconds (30-240) last minute of communications, the system beeps two (2) time s
every 15 seconds to indicate that time is running out.
DEFAULT: 30 seconds
• Tap 1 to enable Talk mode one (1)‐way communication from
The default minimum setting of 30 seconds is required for the Central Station to the premises and allows the operator
ANSI/SIA CP‐01 compliance. to talk.
NOTE: For compliance with ANSI/SIA CP‐01, the total • Tap 2 to enable VOX mode two (2)‐way communications
number of minutes for the combination of Q6: Entry Delay 1 from the Central Station to the premises.
and Q35: Abort Window Dialer Delay cannot exceed one (1)
minute. • Tap 3 to enable Listen mode one (1)‐way communication
from the premises to the Central Station.
The timer for Entry Delay 1 can be set to a value between 30
• Tap 7 to extend the session five (5) minutes without
to 240 seconds. changing the mode of operation.
• The default setting 30 sets the timer to 30 seconds. • Tap 9 to end the audio session an terminate the call.
• To change the setting, enter a value between 30‐240
seconds. Q14: Silent Panic/Burglary Listen Only
Q7: Entry Delay 2, in Seconds (30-240) DEFAULT: (1) Enabled
The Control Panel supports audio listen‐in of the subscriber
DEFAULT: 45 seconds premises from the Central Station after a silent panic (police
The default minimum setting of 45 seconds is required for emergency), silent burglary, or duress alarm has been reported.
ANSI/SIA CP‐01 compliance.
• The default setting (1) Enabled allows the Central Station to
NOTE: For compliance with ANSI/SIA CP‐01, the total number use listen‐in over audio after a silent panic, silent burglary,
of minutes for the combination of Q7: and Q35: or duress alarm.
Abort Window Dialer Delay cannot exceed one (1) minute. • This option is permanently set and cannot be disabled.
The ti mer for Entry Delay 1 can be set to a value between
30‐240 seconds:
• The default setting of 45 sets the timer to 45 seconds.
• To change the timer setting, enter a value between
30‐240 seconds.
2GIG is a registered trademark of Nortek Security & Control LLC. ©2020 Nortek Security & Control LLC. All rights reserved. 49
GC2e Wireless Security System | Installation and Programming Guide
Q16: Police Emergency Key (0-2) Q21: Siren Supervision Time (0-3)
DEFAULT: (1) Audible DEFAULT: (0) Disabled
The Control Panel’s panic emergency button action can be The wiring connection to the external sounder can be
programmed. The panic emergency button is displayed by supervised. If the wiring to the sounder is cut for 15, 30, or 45
pressing the button. seconds, a bell trouble report can be sent to the Central Station.
• The default (1) Audible allows the panic emergency • The default setting (0) Disabled turns external sounder
button to sound an audible alarm. supervision OFF.
• For silent activation, select (2) Silent Panic. • To supervise the external sounder wiring, select:
• To not display the panic emergency button, select (0) • (1) 15 Seconds
Disabled. • (2) 30 Seconds
NOTE: Setting this programming question for (2) Silent Panic • (3) 45 Seconds
makes the Police button on all RF keypads silent also.
Q22: CS Lack of Usage Notification Time
Q17: Fire Emergency Key (0-1)
(0-255)
DEFAULT: (1) Audible
The Control Panel’s fire emergency button can be enabled or DEFAULT: 7 days
disabled. The fire emergency button is displayed by pressing If this system has not been armed for a specified number of
the Control Panel’s button. days, inactivity reports can be sent to the Central Station.
• The default setting (1) Audible allows the fire • The default setting is 7 days.
emergency button to sound an audible alarm. • To change the duration, select a value between 1 to 255
• To disable and not display the fire emergency button, days.
select (0) Disabled. • To turn this feature OFF, select 0 days.
Q18: Emergency Key (0-1) Q23: Radio Modem Network Failure Time
DEFAULT: (1) Audible (0-255)
The Control Panel’s emergency button can be enabled or
disabled. The panel’s emergency button is displayed by DEFAULT: 30 Minutes
pressing the Emergency button on the panel. NOTE: LTE (Cellular) Radio Module must be installed to use this
function.
• The default setting (1) Audible sounds an audible alarm
when the button is pressed. If the optional LTE (Cellular) Radio Module loses its cellular
connection, specify the amount of down time that must pass
To disable this button, select (0) Disabled.
before triggering a trouble condition.
NOTE: If all three (3) Emergency buttons are disabled, the • The default setting is 30 minutes.
Control Panel displays a message when its Emergency
button is pressed. • To specify a different amount of time, enter a value
between one (1) to 255 minutes.
Q19: Quick Arming (0-1) • To turn this feature OFF, select 0 minutes.
DEFAULT: (1) Enabled NOTE: After cellular service is restored for five (5) minutes, the
Quick arming allows the subscriber to arm the system trouble condition automatically clears.
without having to enter a user code. If Open/Close Reports
are being sent, quick arming is reported as User 0. Q24: Radio Modem Network Failure Causes
• The default (1) Enabled allows quick arming. Trouble (0-1)
• To turn off quick arming, select (0) Disabled. DEFAULT: (1) Enabled
NOTE: LTE (Cellular) Radio Module must be installed to use this
Q20: Swinger Shutdown Count (1-6) function.
DEFAULT: (2) Two Trips Selects whether the Control Panel will sound and display
The minimum setting of (2) Two Trips is required for ANSI/ trouble if the optional LTE (Cellular) Radio Module has lost its
SIA CP‐01 compliance. This default setting can be increased cellular connection. The trouble sounder can be silenced by the
to three or more trips without affecting ANSI/SIA CP‐01 user at the Control Panel (cell radio trouble is logged regardless
compliance. of this setting). When the cellular radio module connection is
An unwanted series of multiple faults (usually caused by a bad restored, the trouble indications automatically clear.
contact or sensor) is called a “swinger”. Swinger shutdown • The default (1) Enabled allows radio module failure trouble
sets the maximum number of alarms that any sensor or indications.
hardwire loop can trigger during a single arming period.
• To turn off radio module failure trouble indications, select
NOTE: CO and Smoke detector alarms are not limited by the (0) Disabled.
swinger shutdown count. Other types of 24‐hour zones are
limited by the swinger shutdown count.
• The default setting (2) Two‐Trips sets the swinger
shutdown count at two (2) trips.
• To change this count, select (1‐6).
2GIG is a registered trademark of Nortek Security & Control LLC. ©2020 Nortek Security & Control LLC. All rights reserved. 50
GC2e Wireless Security System | Installation and Programming Guide
Q25: Radio Modem Network Failure Q31: Cancel Time, in Minutes (5-255)
Reports (0-1) DEFAULT: 5 minutes
DEFAULT: (1) Enabled The minimum setting for ANSI/SIA CP‐01 compliance is 5 minutes.
NOTE: LTE (Cellular) Radio Module must be installed to use The number of minutes can be increased without affecting ANSI/
this function. SIA CP‐01 compliance.
If the optional LTE (Cellular) Radio Module loses its cellular A cancel report will be sent to the Central Station after an alarm, if
connection, the Control Panel can report the fault and the system is disarmed within the programmed time.
restore communication. • The default setting for the cancellation time is five (5)
minutes.
• The default (1) Enabled allows radio module failure/
restore reporting. • To ex tend this time interval, enter a value between six (6) to
254 minutes.
• To turn off radio module failure/restore reporting,
select (0) Disabled. • To always send a cancel report when the system is disarmed
after an alarm, enter 255.
Q26: Auto Stay (0-1)
NOTE: See Q32: Cancel Display for information on displaying when
DEFAULT: (1) Enabled a cancel report is sent.
This feature must be enabled for ANSI/SIA CP‐01
compliance. Q32: Cancel Display (0-1)
When auto stay is enabled and the system is armed in the DEFAULT: (1) Enabled
Away mode, if an exit/ entry sensor is not violated during This feature must be enabled for ANSI/SIA CP‐01 compliance.
the Exit Delay, the system will arm in the Stay mode. A cancel report will be sent to the Central Station after an alarm, if
• The default setting is (1) Enabled which turns the auto‐ the system is disarmed within the programmed time. The Control
stay feature ON. Panel can also display that a cancel report was sent.
• To turn this feature off, select (0) Disabled. • The default setting (1) Enabled enables the cancel display
NOTE: If the system is remotely armed in Away mode using a feature.
key fob, mobile app, or computer, the auto‐stay feature will • To turn off the cancel display feature, select (0) Disabled.
not switch the system to Stay mode. NOTE: See Q31: Cancel Time, in Minutes for information on
Q27: Exit Delay Restart (0-1) setting the cancel report trigger time.
2GIG is a registered trademark of Nortek Security & Control LLC. ©2020 Nortek Security & Control LLC. All rights reserved. 51
GC2e Wireless Security System | Installation and Programming Guide
Q35: Abort Window Dialer Delay (0-2) NOTE: After the AC power alert is displayed or clears, the
DEFAULT: (1) 30 Seconds AC power loss report or AC power restore report can be sent to
the Central Station immediately, or at a random time, see Q39:
The default minimum setting for ANSI/SIA CP‐01 compliance is 30 Random AC Loss Report Time.
seconds.
NOTE: The Control Panel’s AC Power Icon immediately displays the
The delay time can be increased to 45 seconds without affecting power status. See “AC Power ON/OFF” on page 25.
ANSI/SIA CP‐01 compliance only if the combination of Q35 and Q6
or Q7 does not exceed one (1) minute. Q39: Random AC Loss Report Time (0-1)
NOTE: The dialer delay can be disabled for each sensor without DEFAULT: (1) Enabled
affecting ANSI/SIA CP‐01 compliance. See “RF Sensor Programming
This feature allows the system to report AC power loss and AC
Questions” on page 39.
power restore at a random time of up to 45 minutes after the
The system delays calling the Central Station to allow the user event occurs. This helps to reduce Central Station congestion due
enough time to cancel a false alarm before it is reported. to a wide‐spread power outage affecting many Control Panels at
• The default setting is (1) 30 Seconds. once. The random AC power status report timer is triggered based
on the time set by Q38: Random AC Loss Report Time.
• To change the setting, select (0) 15 Seconds or (2) 45 Seconds.
• The default setting (1) Enabled turns this feature ON.
Q36: Burglary Bell Cutoff (0 to 4) • To turn this feature OFF, select (0) Disabled.
DEFAULT: (0) 4 Minutes NOTE: The installer code must be unique from the master user
When a burglary alarm is triggered, the bell will sound until the code and all other user codes.
burglary bell cutoff time expires.
Q43: Installer Code (4 or 6 Digits)
• The default setting for the burglary bell cutoff is (0) 4 Minutes.
DEFAULT: 1561
• To change the cutoff time, select an option below.
The installer code is a unique code that installation technicians use
to access the Installer Toolbox on the Control Panel.
Burglary Bell Cutoff Time
• The default installer code is 1561.
(0) 4 Minutes
• To change the installer code, enter a new four (4)‐ digit code.
(1) 8 Minutes
IMPORTANT: If you change the installer code, always write it
(2) 12 Minutes
down so that you can access the system later.
(3) 16 Minutes
Q44: Lock Installer Programming (0-2)
(4) Unlimited
DEFAULT: (0) Disabled
NOTE: The 24‐hour Auxiliary Alarm Zone (08) does not follow the The installer programming lockout feature is provided to prevent
burglary bell cutoff time and will sound the Control Panel’s local takeovers. The Control Panel can be set to limit an installer’s access
alarm until a User Code is entered. The Auxiliary Alarm Zone does to programming questions after a period of 48 hours. The 48‐Hour
not trigger the external siren (if used). Lockout timer starts when the installer exits System Configuration
mode.
Q37: Fire Bell Cutoff (0-4) Three (3) options are available:
DEFAULT: (0) 4 Minutes • Unlimited full access to programming (no lockout).
When a fire alarm is triggered, the bell sounds until the fire bell
• Limited access to programming after 48 hours.
cutoff time expires.
• The default setting (0) 4 Minutes sets the burglary bell cutoff • No access to programming after 48 hours The default setting
to four (4) minutes. (0) Disabled selects unlimited full access to programming (no
• To change the fire bell cutoff time, select an option below: lockout).
To deny access to programming after 48 hours, select (1) No
Fire Bell Cutoff Time Access to Programming.
(0) 4 Minutes If you select (2) Limited Access to Programming the installer will
be able to view, but not change the following attributes after the
(1) 8 Minutes
system has run for 48 hours, the Central Station phone number,
(2) 12 Minutes Central Station account number, lock installer programming,
(3) 16 Minutes download ID, and default lockout fields.
(4) Unlimited After the 48 hour lockout timer has locked out the system, the
timer can be reset through the cell radio or PC download by
remotely setting this question to (0) or (2). Setting the option to
Q38: Time to Detect AC Loss, in Minutes (0-30) (0) or (2) will restart the 48 hour lockout timer.
DEFAULT: (10) 10 Minutes
When AC power is lost, they system displays a power loss alert
after the specified time length. When power is restored, the alert is
automatically cleared after one (1) minute.
2GIG is a registered trademark of Nortek Security & Control LLC. ©2020 Nortek Security & Control LLC. All rights reserved. 52
GC2e Wireless Security System | Installation and Programming Guide
Q45: Lock Default Programming (0-2) Q49: Programming Mode Entry Reports to
DEFAULT: (0) Default All CS (0-1)
The Control Panel may be able to be hard reset (or soft DEFAULT: (0) Disabled
reset from the Installer Toolbox) to its factory default values A report can be sent to the Central Station any time installer
depending on the value entered for this programming question. programming mode is entered and exited.
The Control Panel is hard reset by pressing and holding the • The default setting (0) Disabled prevents reporting
and buttons while applying power to the Control Panel. programming mode entry and exit.
The default lockout feature is provided to prevent takeovers. • To report programming mode entry and exit, select (1)
Three options are available: allow default of all options, allow Enabled.
default of some but not all options, not allow default of any
options. NOTE: This report can only be sent through the telephone dialer.
It is not supported through the LTE (Cellular) Radio Module.
• The default setting of (0) Default All allows resetting the
Control Panel to all its factory defaults. Q50: Trouble Reports to CS (0-1)
• To allow resetting the Control Panel to all its factory DEFAULT: (1) Enabled
defaults except the Central Station phone number, Central
Station account number, lock installer programming, Trouble reports can be sent to the Central Station when any
download ID, and default lockout fields, select (1) Default sensor trouble condition occurs.
All Except CSID, Account/ Phone, Lockouts. • The default setting (1) Enabled allows reporting sensor
• To deny hard and soft resetting of the Control Panel, select trouble conditions.
(2) Default None. • To not report sensor trouble conditions, select (0) Disabled.
If option 1 or 2 is selected, the option takes effect after the NOTE: This setting does not affect trouble reports caused
system runs for 48 hours. This allows the installer to go back by Control Panel conditions, only trouble reports caused by
and make changes if required. sensors.
Q46: Trouble Doesn’t Sound at Night (0-1) Q51: Manual Bypass Reports to CS (0-1)
DEFAULT: (1) Enabled DEFAULT: (0) Disabled
NOTE: For UL 985: Household Fire Warning System Units Manual bypass reports can be sent to the Central Station when
installations, this setting must be set to (0) Disabled any sensor has been manually bypassed by the user.
The Control Panel will sound trouble beeps caused by AC loss, • The default setting (0) Disabled prevents sending manual
system low battery, sensor low battery or RF supervision, failure bypass reports.
to communicate, Control Panel tamper while disarmed, and cell • To allow sending manual bypass reports, select (1) Enabled.
radio faults.
Q52: AC Loss Reports to CS (0-1)
To prevent annoying the subscriber, the system can be set to
suppress trouble beeps from sounding from 10 PM to 9 AM. The DEFAULT: (1) Enabled
trouble alerts are still displayed and immediately reported to AC power loss reports can be sent to the Central Station if the
the Central Station, and can be acknowledged, but they won’t Control Panel loses AC power.
sound beeps until after 9 AM.
• The default setting (1) Enabled allows AC power loss
If the trouble condition(s) self‐clear or are acknowledged reports.
before 9 AM, no trouble beeps sound after 9 AM (the conditions
• To turn off AC power loss reports, select (0) Disabled.
are still recorded in the event log).
NOTE: The AC power will have to be absent from the Control
• The default setting (1) Enabled suppresses trouble beeps
from 10 PM to 9 AM. Panel for the time set by programming question Q38 before the
AC power loss trouble alert is displayed (the default is 10
• To allow trouble beeps at any time, select (0) Disabled. minutes). If programming question Q39 is enabled, the actual
AC power loss report will occur at a random time of up to four
Q47: Trouble Resound After Hold Off (0-7) hours after the AC power loss trouble alert is displayed.
DEFAULT: (0) Disabled NOTE: The Control Panel’s AC power icon displays the power
Fire and CO sensors are required to re‐sound trouble beeps status immediately. A red “X” over the icon indicates no AC
every four hours until the trouble is resolved, even if the power.
trouble is acknowledged at the Control Panel. The Control Q53: System Low Battery Reports to CS (0-1)
Panel can be set to delay re‐sounding these types of trouble
beeps for 1‐7 days. DEFAULT: (1) Enabled
NOTE: This feature is not allowed in UL 985 installations. The Low battery reports can be sent to the Central Station if the
setting must be (0) Disabled in this grade of installation. Control Panel’s battery tests low.
• The default setting (0) Disabled allows trouble beeps for • The default (1) Enabled allows Control Panel low battery
CO and fire sensors to re‐sound every four (4) hours after reports.
being acknowledged • To turn off Control Panel low battery reports, select (0)
• To delay re‐sounding trouble beeps for CO and Fire Disabled.
sensors, select (1‐7) days
2GIG is a registered trademark of Nortek Security & Control LLC. ©2020 Nortek Security & Control LLC. All rights reserved. 53
GC2e Wireless Security System | Installation and Programming Guide
2GIG is a registered trademark of Nortek Security & Control LLC. ©2020 Nortek Security & Control LLC. All rights reserved. 54
GC2e Wireless Security System | Installation and Programming Guide
2GIG is a registered trademark of Nortek Security & Control LLC. ©2020 Nortek Security & Control LLC. All rights reserved. 55
GC2e Wireless Security System | Installation and Programming Guide
Q76: Force Bypass Reports (0-1) Q82: Z-Wave Door Locks Feature (0-1)
DEFAULT: (0) Disabled DEFAULT: (1) Enabled
The system can report which sensors have been force bypassed by Display of the Home Service’s Door Locks button can be enabled or
the user when the system is armed. Forced bypassed sensors are disabled. This programming question only functions if the Z‐Wave
always recorded in the event log, regardless of the setting of this feature enable question Q79: Z‐ Wave Feature is set to (2) or (3).
programming question. • The default setting (1) Enabled shows the Door Locks button.
• The default setting (0) Disabled prevents reporting forced • To hide the Door Locks button, select (0) Disabled.
bypassed sensors.
• To report forced bypassed sensors, select (1) Enabled. Q83: Select Temperature Display Units (0-1)
Q77: Event Log (0-3) DEFAULT: (0) Degrees Fahrenheit
The Home Service’s Z‐Wave thermostat display screens can show
DEFAULT: (3) All Events the temperature in degrees Fahrenheit or degrees Celsius.
To control the amount of event log entries, the events that get
recorded into the system’s event log can be selected by type. This NOTE: This programming question only functions if Q79: Z‐ Wave
setting filters the events that populate the event log. Feature is set to (2) or (3) and Q81: Z‐Wave Thermostats Feature
is set to (1) Enabled.
• The default setting (3) All Events records all events in the
event log. • The default setting is (0) Degrees Fahrenheit.
• To choose different options, select one of these filters: • To change the setting, select (1) Celsius.
NOTE: The setting you select here also changes the display units
Event Log Filters shown on the weather forecast on the Control Panel’s Home screen.
(0) Disabled (no events logged) Q84: Services Require Master Code (0 to 1)
(1) All Events Except Open, Closing, and Bypass DEFAULT: (0) Disabled
(2) All Events Except Open and Closing The Services button can be configured to require the use of the
(3) All Events master user code to access Services.
• The default setting (0) Disabled overrides the requirement to
enter a master user code to access the Services menu.
Q79: Z-Wave Feature (0-3)
To require the use of the master user code to access the Services
DEFAULT: (3) (3) Enabled on Panel; Rules Disabled, Remote Access Enabled
menu, select (1) Enabled.
The Z‐Wave home services feature can be enabled or disabled with
When enabled then the master user code is required to access
various remote control access options.
the Services and the Z‐Wave device configurations. This keeps
• The default setting (3) Enabled on Panel; Rules Disabled, unauthorized users from being able to change Z‐ Wave settings,
Remote Access Enabled displays the Services button, but will such as temperature, lights and locks.
show a message that the feature is currently disabled and the
user should call the installer. Q85: Master User Access to Z-Wave Toolbox
• To hide the Services button, select (0) Disabled and Hidden. (0-1)
• To show the Services button but disable it from use, select (1) DEFAULT: (0) Disabled
Disabled but Visible. The Z-Wave Toolbox menu can be set to require the use of the
• To show the Services button and disable off‐ site remote master user code or the installer code. By default, the installer
control, select (2) Enabled on Panel, Remote Access Disabled. code is required for users to access the Z-Wave Toolbox.
• The default setting (0) Disabled requires users to enter the
Q80: Z-Wave Switches Feature (0 to 1) installer code to access the Z-Wave Toolbox menu and all of
its features, including the Advanced Toolbox.
DEFAULT: (1) Enabled
Display of the Home Service’s Switches button can be enabled or • To require the use of the master user code or the installer
disabled. code to access the Z-Wave Toolbox menu, select (1) Enabled.
NOTE: This programming question only functions if Q79: Z‐ Wave NOTE: When (1) Enabled, the Installer code will still be required
Feature is set to (2) or (3). to access the Advanced Toolbox menu. This prevents end users
from adding or removing Z-Wave devices.
• The default setting (1) Enabled shows the Switches button.
• To hide the Switches button, select (0) Disabled. Q86: Disable Siren After Two-Way Audio (0-1)
DEFAULT: (0) Disabled
Q81: Z-Wave Thermostats Feature (0 to 1)
This setting enhances system operation in personal emergency
DEFAULT: (1) Enabled applications and also provides the dealer with the option of the
Show or hide the Home Service’s Thermostats button on the siren sounding until the bell cut off or to the end of a two-way-
Control Panel. voice session.
NOTE: This programming question only functions if Q79: Z‐ Wave • The default setting (0) Disabled will cause the siren to resume
Feature is set to (2) or (3). after two-way audio (if the bell cut off timer has not expired).
• The default setting (1) Enabled shows the Thermostats button. • (1) Enabled will cause the siren to shut off after a two-way
audio session.
• To hide the Thermostats button, select (0) Disabled.
2GIG is a registered trademark of Nortek Security & Control LLC. ©2020 Nortek Security & Control LLC. All rights reserved. 56
GC2e Wireless Security System | Installation and Programming Guide
• The default setting (0) Disabled will automatically bypass all Q: Network Device ID (read only)
sensors that are open when the system is armed remotely. If a Tap Learn. Then go to the Go!Bridge device and tap the Learn
sensor restores while the system is armed, the sensor’s bypass button. For details, see the Go!Bridge IP Communicator
will be removed, and the sensor will be ready to trigger an Installation Instructions.
alarm.
Q: Select Configuration Source
• To automatically bypass all sensors that are open when the
system is armed remotely, and keep all bypasses in place DEFAULT: (0) DHCP
during the arming cycle, even if a sensor restores, select (1) Select between (1) Static or (2) DHCP (Dynamic Host
Auto‐Bypass. Configuration Protocol). The default setting is (0) DHCP and is
• To prevent arming remotely when any sensor is open, select the most common selection. The other option is (1) Static and
(2) Arm Only When Ready. requires entry of a Device IP Address, Gateway IP Address, and
Subnet Mask.
Q89: Allow Backlight Always On (Demo Mode) Q: Enter Device IP Address
(0-1) DEFAULT: 000.000.000.000
NOTE: May cause ghost/image retention. NOTE: This question only requires an answer if you selected
DEFAULT: (0) Disabled (1) Static in Q: Select Configuration Source.
When set to (1) Enabled the customer can program the “always on” Use the numeric keypad to enter the IP Address for the
option for backlight programming. Due to a small percentage of Go!Bridge IP Communicator.
image “ghosting” on the panel (because the backlight never goes
off), this question was been created but has been defaulted to (0) Q: Enter the Gateway IP Address
Disabled. DEFAULT: 000.000.000.000
NOTE: This question only requires an answer if you selected
Q90: Energy Feature (0 to 1) (1) Static in Q: Select Configuration Source.
DEFAULT: (0) Disabled and Hidden Use the numeric keypad to enter the IP Address for the access
Select (1) Disabled but Visible to show but not activate the energy point to the external network. Typically, this is the IP Address of
features. You can also select (2) Enabled to turn the energy feature the local network router.
ON.
Q: Enter the Subnet Mask
Q91: Radio Modem Supplier DEFAULT: 000.000.000.000
NOTE: This question only requires an answer if you selected
DEFAULT: (0) No Radio Modem Supplier
NOTE: If you enable Q44: Select Lock Installer Programming, you (1) Static in Q: Select Configuration Source.
will not be able to change this setting. Use the numeric keypad to enter the IP Address for the subnet
NOTE: For compliance with UL 1610, Q91: Select Radio Modem mask for the network.
Supplier (0 to 5) must be set to (1) Radio Modem Supplier 1. Q: Select Port # (1 to 8)
Select the option that corresponds to the appropriate supplier. DEFAULT: (1) Port 1
Options include: NOTE: Typically, you will skip this question unless additional
programming is required.
Option Supplier
Select the port number for the backend server. After configuring
(0) No Radio Modem Supplier This is the default setting. the required port, tap Next on the Control Panel.
(1) Radio Modem Supplier 1 Alarm.com • (1) Port 1
(2) Radio Modem Supplier 2 • (2) Port 2
(3) Radio Modem Supplier 3 • (3) Port 3
(4) Radio Modem Supplier 4 • (4) Port 4
(5) Radio Modem Supplier 5 SecureNet • (5) Port 5
(6) Radio Modem Supplier 6 • (6) Port 6
• (7) Port 7
• (8) Port 8
2GIG is a registered trademark of Nortek Security & Control LLC. ©2020 Nortek Security & Control LLC. All rights reserved. 57
GC2e Wireless Security System | Installation and Programming Guide
2GIG is a registered trademark of Nortek Security & Control LLC. ©2020 Nortek Security & Control LLC. All rights reserved. 58
GC2e Wireless Security System | Installation and Programming Guide
Exiting Programming (System Configuration) NOTE: User codes 0000, 0001, 000000, 000001 and the Installer
After programming the Control Panel, all the changes need to be Code are not permitted.
saved in memory. After saving, the programmed settings will remain 7. Setup each user code with the User Access Option screen.
in memory, even after a total power loss. Each User Code can be set to be currently valid or not, or to
have conditional validity. Refer to the User Guide for details
1. After setting all the required programming values for the
on setting User Code Access Schedules. When done, tap
sensors and the Control Panel, tap End.
Back.
2. Review the Summary of System Configuration screen. Use the
8. At the Toolbox (1 of 3) screen, tap Brightness/Volume.
↓ and ↑ arrows to scroll through the listing. Verify that each
option is set correctly. Then set the brightness level for the display screen and the
volume for the chime & voice. When done, tap OK.
Figure 51 Summary of System Configuration Screen
Figure 53 Brightness/Volume Screen
2GIG is a registered trademark of Nortek Security & Control LLC. ©2020 Nortek Security & Control LLC. All rights reserved. 59
GC2e Wireless Security System | Installation and Programming Guide
11. At the Toolbox (2 of 3) screen, tap Set Date. Then use the
↓ and ↑ arrows to set the month, day, and year. When
done, tap OK.
Figure 55 Set Date Screen
2GIG is a registered trademark of Nortek Security & Control LLC. ©2020 Nortek Security & Control LLC. All rights reserved. 60
GC2e Wireless Security System | Installation and Programming Guide
Installer Testing
When installation and programming is complete, use the Sensor Type (Zone) Report Test
option in the Installer Toolbox to test for proper system
operations. To verify that the Central Station correctly receives reports
from each zone (sensor type):
Access the Installer Toolbox 1. Notify the Central Station. Because the system sends
To access the Installer Toolbox: test signals, notify the Central Station that you will be
testing the system.
1. At the Home screen, tap the system logo in the lower‐
right corner. 2. Fire Test. Trigger a 24‐Hour fire sensor (if installed)
or tap the Control Panel’s Emergency button
2. At the Enter a Code screen, enter the installer code (the and then tap the Fire button (if enabled). Wait for
default installer code is 1561). approximately 45 seconds for the report to complete,
then disarm the console.
The Installer Toolbox(1 of 3) screen appears.
3. Panic Test. Trigger a 24‐Hour Panic sensor (if
Disable/Enable Sounder installed) or tap the Control Panel’s Emergency
button and then tap the Panic button (if enabled).
When testing the Control Panel, both the internal and external Wait about 45 seconds for the report to complete,
sounder (if installed) will be activated. To limit noise during then disarm the console.
the testing process, the Control Panel offers an option to
4. Emergency Test. Trigger a 24‐Hour emergency sensor
disable the sounder.
(if installed) or tap the Emergency button (if
enabled), wait ab out 45 seconds for the report to
Disable the Sounder complete, then disarm the console.
To disable the sounder: 5. Burglary Test. Arm the system, then trigger a
1. At the Installer Toolbox (1 of 2) screen, tap Disable burglary sensor, wait for the system to go into alarm
Sounder. mode, then wait about 45 seconds for the report to
complete, and then disarm the console.
2. At the Disable Sounder? screen, tap OK. NOTE: The
internal sounder emits a siren for two (2) seconds. If 6. Verify Tests with Central Station. Check with the
an external sounder is connected, four (4) chirps are Central Station that each zone (sensor type) was
emitted. reported, then inform the Central Station that the
testing is complete.
3. At the Sounder Disabled screen, tap OK.
NOTE: The sounder will be automatically re‐enabled in 30
minutes or you can manually enable it. See “Enable the
Sounder”, below. Walk Test
4. While disabled, the Sounder Disabled icon appears in the Radio quality can vary when there is background noise on
status bar. the operating frequency. Examples of background noise
sources include telephones, microwaves, high‐frequency
Figure 57 Sounder Disabled Icon digital products, and other radio communications.
To determine the best location to mount each sensor, it is
recommended that you place each sensor in the desired
mounting location and then perform a Walk Test. This
helps you to identify whether the desired location has
good/weak signal strength. When you find a location with
good signal strength, you can then mount the sensor.
To place the panel into Walk Test mode:
1. At the Installer Toolbox (1 of 2) screen, tap Walk Test.
NOTE: When placing the Control Panel into Walk Test
mode, you have 25 minutes to complete the test before
the screen times out. The system also sends a “Start Test”
report to the Central Station and beeps once every 30
Enable the Sounder seconds. During the last five (5) minutes of the test, the
If the sounder is disabled, you can manually re‐enable it as system beeps two (2) times every 30 seconds and the
follows: icon flashes in the status bar.
1. At the Installer Toolbox screen, tap Enable Sounder.
2. At the Sounder Enabled screen, tap OK.
2GIG is a registered trademark of Nortek Security & Control LLC. ©2020 Nortek Security & Control LLC. All rights reserved. 61
GC2e Wireless Security System | Installation and Programming Guide
Installer Testing
2. When the System Test: Sensors screen appears, you can Radio Status Test
tap the ↓ and ↑ arrows to scroll through the sensor list.
If the LTE (Cellular) Radio Module is installed in the Control
Figure 58 System Test: Sensors Screen Panel, use the Radio Status screen to view signal strength,
serial number, registration status, and other information for
the cellular connection. The is a helpful tool to use when
troubleshooting the installation.
3. Walk to the first sensor in the list, and then activate that
sensor to test it.
4. Repeat the test for each sensor in the list. If you are
testing a sensor with multiple loops, (for example, a
Smoke/Heat/Freeze alarm), wait 15 seconds between The Cell Phone Test screen appears to reveal status
each loop’s test. messages and test results
NOTE: If a sensor is not detected, no signal will register. Tap Figure 63 Cell Phone Test Screen
OK. Then at the Sensors Test Failed screen, tap OK.
5. At the System Test: Console screen, tap each button to
test the panel’s LED buttons and audio.
Figure 60 System Test: Console
2GIG is a registered trademark of Nortek Security & Control LLC. ©2020 Nortek Security & Control LLC. All rights reserved. 62
GC2e Wireless Security System | Installation and Programming Guide
Installer Testing
Soft Reset
A soft‐reset lets you select which settings to restore back
to the factory defaults.
To perform a soft‐reset:
1. At the Installer Toolbox screen, tap the Restore
Default button. The Restore Default System
Configuration screen appears.
Hard Reset
A hard‐reset restores all of the programming settings back to
the factory defaults.
NOTE: Be fore performing a hard reset, Q44: Lock Installer
Programming must be set to option (1) or (2) and Q45: Lock
Default Programming must be set to (0). See “Q44: Lock
Installer Programming (0-2)” on page 52.
To perform a hard reset:
1. Remove the Control Panel cover and completely
disconnect all power to the Control Panel.
2. On the inside back of the Control Panel, plug in the
backup battery.
3. Tap and hold down the Emergency and Home
buttons.
4. Continue to hold down the Emergency and Home
buttons and then connect DC Power to the Control
Panel.
5. Release the buttons only after both the Emergency
and Home buttons are lit and the Control Panel
screen appears.
2GIG is a registered trademark of Nortek Security & Control LLC. ©2020 Nortek Security & Control LLC. All rights reserved. 63
GC2e Wireless Security System | Installation and Programming Guide
Regulatory Information
FCC Notice
This equipment generates and uses radio frequency energy and if not installed and used properly, that is, in strict
accordance with the manufacturer’s instructions, may cause interference to radio and television reception. It has been type
tested and found to comply with the limits for a Class B computing device in accordance with Part 15 of FCC Rules, which
are designed to provide reasonable protection against such interference in a residential installation. However, there is no
guarantee that interference will not occur in a particular installation. If this equipment does cause interference to radio
or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to
correct the interference by one or more of the following measures:
• Relocate the Console away from the TV/radio receiver.
• Plug the Console into a different wall outlet so that the Console is on a different branch circuit.
• Re‐orient the TV/radio antenna.
• If necessary, the user should consult the dealer or an experienced radio/television technician for additional
suggestions.
2GIG is a registered trademark of Nortek Security & Control LLC. ©2020 Nortek Security & Control LLC. All rights reserved. 64
GC2e Wireless Security System | Installation and Programming Guide
Regulatory Information
2GIG is a registered trademark of Nortek Security & Control LLC. ©2020 Nortek Security & Control LLC. All rights reserved. 65
GC2e Wireless Security System | Installation and Programming Guide
Limited Warranty
This Nortek Security & Control LLC product is warranted against defects in material and workmanship for one (1) year. This
warranty extends only to wholesale customers who buy direct from Nortek Security & Control LLC or through Nortek Security
& Control LLC’s normal distribution channels. Nortek Security & Control LLC does not warrant this product to consumers.
Consumers should inquire from their selling dealer as to the nature of the dealer’s warranty, if any.
There are no obligations or liabilities on the part of Nortek Security & Control LLC for consequential damages arising out of or
in connection with use or performance of this product or other indirect damages with respect to loss of property, revenue, or
profit, or cost of removal, installation, or reinstallation. All implied warranties for functionality, are valid only until the warranty
expires. This Nortek Security & Control LLC Warranty is in lieu of all other warranties expressed or implied.
All products returned for warranty service require a Return Authorization Number (RA#). Contact Returns at 1‐855‐546‐3351 for
an RA# and other important details.
2GIG
Nortek Security & Control LLC
5919 Sea Otter Place, Suite 100, Carlsbad, CA 92010 USA
For technical support in the USA and Canada:
855‐2GI G‐TECH (855‐244‐4832)
Email: [email protected]
Visit www.nortekcontrol.com or dealer.2gig.com for technical support hours of operation
For technical support outside of the USA and Canada:
Contact your regional distributor
Visit 2gig.com/dealers/ for a list of distributors in your region
10022312 Rev-C
A Nortek Company
2GIG is a registered trademark of Nortek Security & Control LLC. ©2020 Nortek Security & Control LLC. All rights reserved. 66