Transient Analysis - Lab5 Report
Transient Analysis - Lab5 Report
Practical Report
Submitted by
Electrical Engineering
Rinchending, Phuentsholing
Result
Fault clearing time of 0.08 seconds.
Fault clearing time 0.2 second. Fault clearing time of 0.25 second.
Fault clearing time 0.3 second Fault time after 0.45 second
The effect of Fault clearing time on the rotor angle of the generator
Table I Rotor angle of the Generator
Generator Fault Angle (Degree)
clearing Initial angle Maximum Minimum settling
time an e ðm an e ð
Gen 2 0.08 sec 13.133 24.47 4.3 13.2
Gen 3 2.75 5.124 1.09 2.719
Gen 2 0.2 sec 13.133 43.171 -10 13.473
Gen 3 2.75 7.912 1.625 2.72
Gen 2 0.25 sec 13.133 53.284 -17.43 13.59
Gen 3 2.75 8.47 -3.059 2.67
Gen 2 (k3 sec 13.133 65.38 -25.99 13.98
Gen 3 2.75 9.291 -4.67 2.57
Result Interpretation:
The data indicates a clear correlation between fault clearing time and rotor angles for two generators, Gen
1 and Gen 2. In Gen 2, as fault clearing time rises from 0.08 to 0.3 seconds, there's a consistent
increase in maximum rotor angle (24.41 to 65.38 degrees) and a progressive rise in critical angle
(13.98 degrees).
Similarly, for Gen l, the maximum rotor angle grows from 5.24 to 9.291 degrees, while the critical
angle decreases from 2.74 to 2.57 degrees with extended fault clearing time. These trends emphasize
the dynamic nature of rotor angles in relation to fault clearing time, underscoring their vital role in
evaluating and sustaining generator system stability. The importance of swift fault clearing is
highlighted to minimize the risk of equipment damage as fault clearing time affects fault current
magnitude.
Result:
Switch Event of Circuit breaker.
CB closing time of 0.08 second
378'
3) With increase in fault clearing time if the rotor angle is not stable, try changing inertia
constant (H) of Generators (G2, G3) by one or two higher values and simulate the effect of
Inertia constant.
Result
The clearing time is kept constant = 0.2 seconds
Result interpretation:
The findings indicate that elevating the generator inertia constant in a power system brings about several
favorable outcomes for system dynamics. A higher inertia constant contributes positively to transient
stability by offering greater resistance to speed changes, resulting in diminished angular deviations
during faults. This heightened kinetic energy facilitates an extended fault clearing time, allowing
protective devices to operate effectively and bolstering overall system resilience. The system benefits
from improved synchronization of generators and a reduction in frequency instabilities, as higher inertia
aids in balancing generation and load changes. However, excessively high inertia may result in slower
response times. Therefore, it is crucial to maintain inertia constant to specific value.
Conclusion
In summary, the study underscores the intricate relationship between the generator rotor angle,
disturbance response, and system stability. By understanding and optimizing critical load angles and
clearing times, power system operators can make informed decisions to mitigate the impact of
disturbances and maintain a robust and stable power system. These findings contribute to the broader
objective of enhancing the resilience and reliability of power systems in the face of dynamic operating
conditions.