3200

SERIES

Temperature/Process
Controllers
Specification Sheet
● 8 Segment programmer The innovative range of 3200 controllers offer precision control of
temperature and other process variables together with a host of advanced
● Heater failure features not normally found in this class of controller.
detection
The emphasis is on ease of use. A simple ‘Quick Start’ code is used to
● Current monitoring configure all the functions essential for controlling your process. This
includes input sensor type, measurement range, control options, and
● Internal timer alarms, making ‘Out the Box’ operation truly achievable. In operator mode
every parameter has a scrolling text message describing its function and is
● Scrolling text messages
available in English, German, French, Spanish or Italian. More advanced
● Recipes features are configured using iTools, a PC based configuration wizard which
is an easy to use and instructive guide to all the functions in the controller.
● Modbus comms
Heater current monitoring
● Modbus SP A current transformer input provides display of the heater current and a
retransmission health check on the load. Partial load failure, heater open circuit and SSR
faults are detected and displayed as scrolling alarm messages as well as
● Analogue providing an alarm output. On the 3208 and 3204 a front panel ammeter
retransmission displays the heater current.
● Remote setpoint
Setpoint programmer
● Help text Heat treatment profiles can be programmed using the 8-segment
programmer. Holdback, at the beginning of each segment can be used to
guarantee the soak periods. A digital event output can be triggered in any
segment to initiate actions within the process.

Custom text messaging


Custom messages can be created with iTools and downloaded to the 3200
to display when an event, alarm or process condition occurs. This
provides the operator with good visibility of the status of the process.

Remote setpoint
An option exists for the 3200 to have a Remote Analogue Input. This can
be either volts or mA and is used to allow the setpoint to be generated by
a master controller or PLC.

•EUROTHERM ® FLEXIBLE SOLUTIONS•


Recipes SPECIFICATION
Using iTools, recipes can be created that may be used to change the
operating parameters of the 3200 simply by selecting a new recipe General
using the 3200 HMI. This is very useful where multiple products are Environmental performance
processed using the same controller but require different Temperature limits Operation: 0 to 55°C
parameters to be set. Storage: -10 to 70°C
Humidity limits Operation: 5 to 90% RH non condensing
Storage: 5 to 90% RH non condensing
Timer Panel sealing: IP65, Nema 4X
An internal timer is configurable as an interval timer, delay timer or Shock: BS EN61010
to provide a soft start for hot runner control. Vibration: 2g peak, 10 to 150Hz
Altitude: <2000 metres
Setpoint retransmission Atmospheres: Not suitable for use in explosive or
corrosive atmosphere
Sending the setpoint or other parameters from the 3200 to slave
devices can be achieved either using conventional analogue Electromagnetic compatibility (EMC)
Emissions and immunity: BS EN61326
communications or using Master Modbus communications. Master
Modbus in the 3200 allows a broadcast of a single parameter to the Electrical safety
network. (BS EN61010): Installation cat. II; Pollution degree 2
A typical application is a setpoint being retransmitted to a number INSTALLATION CATEGORY II
of slave controllers in a multi-zone furnace. The rated impulse voltage for equipment on nominal 230V mains is 2500V.

POLLUTION DEGREE 2
Modbus communications
Normally, only non-conductive pollution occurs. Occasionally, however, a
All units support both EIA232 and 2-wire EIA485 communications temporary conductivity caused by condensation shall be expected
using the Modbus protocol. The 3216 supports 4-wire EIA485.
Physical
Configuration adaptor Panel mounting 3216: 1/16 DIN
iTools configuration to all 3200 controllers can be achieved by using 3208: 1/8 DIN
3204: 1/4 DIN
a configuration adaptor. It provides iTools with the ability to
32h8: 1/8 DIN, horizontal
communicate with and configure devices without the need for any
power being connected. Weight 3216: 250g
3208: 350g
3204: 420g
32h8: 350g
Panel cut-out dimensions 3216: 45W x 45Hmm
3208: 45W x 92Hmm
3204: 92W x 92Hmm
32h8: 92W x 45Hmm
Panel depth All: 90mm
Operator interface
Type: LCD TN with backlight
Main PV display: 4 digits, green
Lower display 3216, 3208, 3204: 5 character starburst, green
32h8: 9 character starburst, green
Status beacons: Units, outputs, alarms, active setpoint
Power requirements
iTools wizard 3216: 100 to 240Vac, –15%, +10%,
48 to 62 Hz, max 6W
Used to simplify the set up of 3200 series controllers. The wizard 24Vac, -15%, +10%.
guides the user through the configuration process with interactive 24Vdc, -15% +20% ±5% ripple voltage
help and graphical demonstrations of features. max 6W
3208/h8/04: 100 to 240Vac, –15%, +10%,
48 to 62 Hz, max 8W
24Vac, -15%, +10%.
24Vdc -15% +20% ±5% ripple voltage
max 8W
Approvals
CE, cUL listed (file E57766), Gost,
DIN 3440 (3216 only)
Suitable for use in Nadcap and
AMS2750D applications under Systems
Accuracy Test calibration conditions
Transmitter PSU (not 3216)
Rating: 24Vdc, >28mA, <33mA
Isolation: 264Vac double insulated

Communications
Serial communications option:
Protocol: Modbus RTU slave
Modbus RTU Master broadcast
(1 parameter)
Isolation: 264Vac, double insulated
Transmission standard: EIA232 or EIA485 (2 wire)
EIA485(4 wire) on 3216 only
Process variable input Triac output
Calibration accuracy: <±0.25% of reading ±1LSD (1) Rating: 0.75A (rms) 30 to 264V(rms) resistive
Sample rate: 4Hz(250ms) load
Isolation: 264Vac double insulation from the PSU Isolation: 264Vac double insulated
and communication Functions: Control outputs, alarms, events
Resolution (μV): <0.5μV with 1.6sec filter Analogue output (3)
Resolution (effective bits): >17 bits
Linearisation accuracy: < 0.1% of reading OP1, OP2
Drift with temperature: <50ppm (typical) <100ppm (worst case) Rating: 0-20mA into <500Ω
Common mode rejection: 48-62Hz, >-120db Accuracy: ± (<1% of Reading + <100μA)
Series mode rejection: 48-62Hz, >-93dB Resolution: 13.5 bits
Input impedance: 100MΩ Isolation: 264Vac double insulated from PSU and
communications
Cold junction compensation: >30:1 rejection of ambient change
Module code C provides full 264Vac
External cold junction: Reference of 0°C
double isolated
Cold junction accuracy: <±1°C at 25°C ambient
Functions: Control outputs, retransmission
Linear(process) input range: -10 to 80mV, 0 to 10V with
100KΩ/806Ω external divider module OP 3 (not on 3216)
Rating: 0-20mA into <500Ω
Thermocouple types: K, J, N, R, S, B, L, T, C, custom
Accuracy: ±(<0.25% of Reading + <50μA)
download (2)
Resolution: 13.6 bits
Resistance thermometer types: 3-wire Pt100 DIN 43760
Isolation: 264Vac double insulated
Bulb current: 0.2mA
Functions: Control outputs, retransmission
Lead compensation: No error for 22 ohms in all leads
Input filter: Off to 59.9s Remote setpoint input
Zero offset: User adjustable over full range Calibration accuracy: <±0.25% or reading ±1LSD
User calibration: 2-point gain & offset Sample rate: 4Hz (250ms)
Isolation: 264Vac double insulation from instrument
Notes Resolution: <0.5mV (for 0-10V) or <2μA (for 4-20mA)
(1) Calibration accuracy quoted over full ambient operating range and for all Resolution (effective bits): >14bits
input linearisation types Drift with temperature: <50ppm (typical) <150ppm (worst case)
(2) Contact Eurotherm® for details of availability of custom downloads for Common mode refection: 48-62Hz, >-120dB
alternative sensors Series mode rejection: 48-62Hz, >-90dB
Input impedance: Voltage: 223KOhm and Current: 2R49
AA relay Normal input range: 0 to 10V and 4 to 20mA
Type: Form C (changeover) Max input range: -1V to 11V and 3.36mA to 20.96mA
Rating: Min 100mA@12Vdc, max 2A@264Vac
Software features
resistive
Functions: Control outputs, alarms, events Control
Number of loops: 1
Current transformer input Loop update 250ms
Input range: 0-50mA rms, 48/62Hz. 10Ω burden Control types: PID, ON/OFF, VP
resistor fitted inside module Cooling types: Linear, fan, oil, water
Modes: Auto, manual, standby, forced manual
Calibration accuracy: <1% of reading (Typical),
Overshoot inhibition: High, low
<4% of reading (Worst case)
Isolation: By using external CT Alarms
Input impedance: <20Ω Number: 4
Measurement scaling: 10, 25, 50 or 100 Amps Type: Absolute high & low, deviation high, low
Functions: Partial load failure, SSR fault or band, rate of change
Latching: Auto or manual latching, non-latching,
Digital input (DigIn A/B, B not on 3216) event only
Output assignment: Up to four conditions can be assigned to
Contact closure: Open >600Ω, closed <300Ω
one output
Input current: <13mA
Isolation: None from PV or system Other status outputs
Functions: Including sensor break, manual mode,
264Vac double insulated from PSU and
timer status, loop break, heater
communications
diagnostics, program event
Functions: Includes alarm acknowledge, SP2 select,
Output assignment: Up to four conditions can be assigned to
manual keylock, timer functions, standby
one output
select, RSP select
Setpoint programmer
Logic I/O module Program function: 1 program x 8 segments with 1 event
output (4)
Output
Start mode: Servo from PV or SP
Rating: ON 12Vdc@<44mA,
Power fail recovery: Continue at SP or Ramp back from PV
OFF <300mV@100μA
Guaranteed soak: Inhibits dwell timing until PV within
Isolation: None from PV or system.
limits
264Vac double insulated from PSU and
Timer
communications
Modes Dwell when setpoint reached
Functions: Control outputs, alarms, events
Delayed control action,
Digital input Soft start limits power below PV threshold
Contact closure: Open >500Ω, closed <150Ω Current monitor
Isolation: None from PV or system Alarm types: Partial load failure, over current, SSR
264Vac double insulated from PSU and short circuit, SSR open circuit
communications Indication type: Numerical or ammeter
Functions: Includes alarm acknowledge, SP2 Custom messages
select, manual, keylock, timer functions, Number: 15 scrolling text messages
standby select, RSP select No of characters: 127 characters per message max
Languages: English, German, French, Spanish, Italian
Relay output channels Selection: Active on any parameter status using
Type: Form A (normally open) conditional command
Rating: Min 100mA@12vdc, max 2A@264Vac Recipes
resistive Number: 5 recipes with 38 parameters
Functions: Control outputs, alarms, events Selection: HMI interface, communications or
digital IO
Notes
(3) Voltage output can be achieved by external adaptor
(4) By using recipes five SP programs can be stored
Isolation diagrams
3216 3208/h8/04

264Vac 264Vac
Double Double

Serial comms Serial comms


Remote Setpoint Remote Setpoint
Rectification
Power Rectification
Power 264Vac Power 264Vac
Double Power All logic inputs and
Supply Double outputs & Non-isolated
Supply
Circuits 0-20mA output
Circuits
All logic inputs and
outputs & non isolated
264Vac μP & 0-20mA output μP & Micro mounted
Double system 264Vac system PV Input
circuits Double circuits
0-20mA
Isolated module CT measurement
Micro mounted Relays & Triacs
PV Input

264Vac 264Vac 264Vac


Double Double Double

Relays & Triacs CT Measurement Analogue (OP3) output Transmitter PSU

Dimensional details
3216 3208
48mm
48mm (1.89in)
(1.89in) 101mm
101mm (3.94in)
(3.94in)

48mm
(1.89in)
96mm
(3.78in)
90mm
(3.54in)
Panel cut-out
-0.0 -0.0
45mm+0.6 45mm+0.6 90mm
Panel cut-out (3.54in)

3204
-0.0 -0.0
45mm+0.6 92mm +0.8
96mm 101mm
(3.78in) (3.94in)

96mm
32h8
(3.78in)

96mm 101mm
(3.78in) (3.94in)
90mm
Panel cut-out (3.54in) 48mm
(1.89in)

90mm
-0.0 -0.0
Panel cut-out (3.54in)
92mm +0.8 92mm +0.8
-0.0 -0.0
92mm +0.8 45mm +0.6
Ordering code
1 2 3 4 5 6 7 8 9 10 11 12

Basic Product 4 AA Relay 6 Fascia Colour 9 Warranty


3216 48 x 48mm unit X Disabled G Green XXXXX None
3208 48 x 96mm vertical unit R Relay S Silver WL005 Extended
32h8 96 x 48mm horizontal unit W Washdown (not 32h8/04)
3204 96 x 96mm unit 5 Options 10 Calibration Certificates
7 Product Language
1 Function XXX Not fitted XXXXX None
RCL Remote SP, CT & Dig in A ENG English CERT1 Certificate of conformity
CC PID controller XCL CT & Dig in A FRA French CERT2 Factory input calibration
CP Programmer 2CL RS232, CT & Dig in A GER German per input
VC Valve controller 4CL RS485, CT & Dig in A SPA Spanish
VP Valve programmer 3216 only ITA Italian
2XL RS232 Dig in A 11 Custom Label
4XL RS485 Dig in A 8 Manual Language
2 Supply Voltage XXXXX None
6XX 4-wire RS485
VH 85-264Vac XXL Dig in A ENG English
VL 24V ac or dc FRA French 12 Specials and Accessories
GER German
SPA Spanish XXXXX None
3 Outputs ITA Italian RES250 250R resistor for 0-5Vdc OP
3216 RES500 500R resistor for 0-10Vdc OP
OP1 OP2 Where
L X X X L = Logic Example ordering code
L R X X R = Relay 3216 - CP - VH - LDXX - R - 4CL - S - ENG - ENG - WL005 - XXXXX -
R R X X D = 0-20mA XXXXX - RES250
L L X X C = Isolated 0-20mA
L D X X T = Triac 3216 controller with setpoint programmer, OP1 as Logic, OP2 as 0-20mA, AA Relay,
D D X X X = Not fitted RS485 Comms, CT Input, Dig In A, English language, 5 year warranty, resistor for 0-
5V output
D R X X
R C X X 3200 Accessories
L C X X
HA029714 Installation guide
D C X X
HA027986 Engineering manual
Not available with Low Voltage PSU
L T X X SUB35/ACCESS/249R.1 2.49R Precision resistor
T T X X CTR100000/000 10A Current transformer
3208/h8/04 CTR200000/000 25A Current transformer
OP1 OP2 OP3 CTR400000/000 50A Current transformer
L R R X CTR500000/000 100A Current transformer
R R R X
iTools/None/3000CK Configuration clip
L L R X
L R D X SUB21/IV10 0-10V input adaptor
R R D X
D D D X
L L D X 3208/h8/04
L D D X
D R D X + + 1A AA
Not available with Low Voltage PSU *OP1
- - AA
L T R X 1B AB Relay
T T R X + + 2A AC or with
L T D X OP2
Remote Setpoint
- - COM
T T D X 2B HD HD

LB HE A(+) HE V
Dig in B mA
LC HF A (-) HF

3A CT
Rear terminals OP3
+
3B C
CT
-
Dig in A
+ 3C LA
24Vdc transmitter
3216 supply - 3D VI
RTD
Line L V+
+ + 1A CT AA 100 to 240Vac 50/60Hz or 24 Vac/dc mV mA
*OP1 CT AA Neutral N V-
- - 1B C AB Relay
Dig in
A
+ + 2A LA AC
OP2
- - 2B COM HD VI
RTD
Line L A(+) HE V+ 32h8 orientation
3A

mA N L 3D 3C 3B
100 to 240Vac 50/60Hz or 24 Vac/dc mV
Neutral N B(-) HF V-

or with Remote Setpoint


HD

HE V
mA
V+

CT
LA
VI

V-
C

HF
Optional quick start code (Optional)

1 2 3 4 5 6 7 8 9 10
3208/h8/ 3208/h8/
04 only 04 only

1 Input Type 2 Setpoint Limits 3 4 5 OP1, OP2, AA Relay, OP3 6 CT Input


Thermocouple Temperature XX Not fitted XX Not fitted
B Type B H Heat (PID) Relay, Triac or Logic outputs 1 10 Amps
J Type J C Cool (PID) Control 2 25 Amps
K Type K Centigrade H Heat (PID) 5 50 Amps
L Type L 0 0 to 100 deg C C Cool (PID) 6 100 Amps
N Type N 1 0 to 200 deg C J Heat (On/off)
R Type R 2 0 to 400 deg C K Cool (On/off)
S Type S 3 0 to 600 deg C Alarm output 7 8 Dig in A, Dig in B, OP1
T Type T 4 0 to 800 deg C Energised in alarm
X Unconfigured
C Custom/Type C 5 0 to 1000 deg C 0 High alarm
W Alarm acknowledge
RTD 6 0 to 1200 deg C 1 Low alarm
M Manual select
P Pt100 7 0 to 1400 deg C 2 Deviation high
R Timer/Prog Run
Linear 8 0 to 1600 deg C 3 Deviation low
L Keylock
M 0-80mV 9 0 to 1800 deg C 4 Deviation band P Setpoint 2 select
2 0-20mA Fahrenheit Alarm output T Timer/prog reset
4 4-20mA G 32 to 212 deg F De-energised in alarm U Remote SP select
X Unconfigured H 32 to 392 deg F 5 High alarm V Recipe 2/1 select
J 32 to 752 deg F 6 Low alarm A Remote up button
K 32 to 1112 deg F 7 Deviation high B Remote down button
L 32 to 1472 deg F 8 Deviation low G Time/prog run/reset
M 32 to 1832 deg F 9 Deviation band I Timer/prog hold
N 32 to 2192 deg F DC outputs Q Standby select
P 32 to 2552 deg F Control
R 32 to 2912 deg F H 4-20mA heating
T 32 to 3272 deg F C 4-20mA cooling 10 Lower Display
X Unconfigured J 0-20mA heating
K 0-20mA cooling T Working setpoint
Retransmission S Target setpoint
D 4-20mA setpoint P Output demand
E 4-20mA Process value R Time to run
F 4-20mA output E Elapsed time
N 0-20mA setpoint 1 Alarm setpoint
Y 0-20mA Process value A Load amps
Z 0-20mA output D Dwell/ramp - time/target
Logic input C WSP with output meter
W Alarm acknowledge M WSP with ammeter
M Manual select N None
R Timer/Prog Run
L Keylock
P Setpoint 2 select
T Timer/prog reset
U Remote SP select
V Recipe 2/1 select
Example ordering code (Quick Start)
A Remote up button
K-6-H-E-5-5-P-X-X-T B Remote down button
G Time/prog run/reset
This code will provide a controller configured as 0-1200 °C, Type K, Heat Output,
4-20mA PV retrans, High Alarm, 50A CT measurement, SP select via Dig In A, I Timer/prog hold
Lower display showing working setpoint Q Standby select

Eurotherm: International sales and service


AUSTRALIA Sydney Beijing Office GERMANY Limburg KOREA Seoul SWEDEN Malmo
T (+61 2) 9838 0099 T (+86 10) 63108914 T (+49 6431) 2980 T (+82 31) 2738507 T (+46 40) 384500
E [email protected] E [email protected] E [email protected] E [email protected] E [email protected]
AUSTRIA Vienna Guangzhou Office HONG KONG NETHERLANDS Alphen a/d Rijn SWITZERLAND Wollerau
T (+43 1) 7987601 T (+86 20) 38106506 T (+85 2) 28733826 T (+31 172) 411752 T (+41 44) 7871040
E [email protected] E [email protected] E [email protected] E [email protected] E [email protected]
BELGIUM & LUXEMBOURG DENMARK Copenhagen INDIA Chennai NORWAY Oslo UNITED KINGDOM Worthing
T (+32) 85 274080 T (+45 70) 234670 T (+91 44) 24961129 T (+47 67) 592170 T (+44 1903) 268500
E [email protected] E [email protected] E [email protected] E [email protected] E [email protected]
BRAZIL Campinas-SP FINLAND Abo IRELAND Dublin POLAND Katowice www.eurotherm.co.uk
T (+5519) 3707 5333 T (+358) 22506030 T (+353 1) 4691800 T (+48 32) 2185100 U.S.A. Leesburg VA
E [email protected] E [email protected] E [email protected] E [email protected] Eurotherm Inc.
CHINA FRANCE Lyon ITALY Como SPAIN Madrid T (+1 703) 443 0000
T (+86 21) 61451188 T (+33 478) 664500 T (+39 031) 975111 T (+34 91) 6616001 E [email protected]
E [email protected] E [email protected] E [email protected] E [email protected] www.eurotherm.com ED56

© Copyright Eurotherm Limited 2008


Invensys, Eurotherm, the Eurotherm logo, Chessell, EurothermSuite, Mini8, Eycon, Eyris, EPower and Wonderware are trademarks of Invensys plc, its subsidiaries and affiliates.
All other brands may be trademarks of their respective owners.
All rights are strictly reserved. No part of this document may be reproduced, modified, or transmitted in any form by any means, nor may it be stored in a retrieval system
other than for the purpose to act as an aid in operating the equipment to which the document relates, without the prior written permission of Eurotherm limited.
Eurotherm Limited pursues a policy of continuous development and product improvement. The specifications in this document may therefore be changed without notice.
The information in this document is given in good faith, but is intended for guidance only.
Printed on
Eurotherm Limited will accept no responsibility for any losses arising from errors in this document.
recycled paper
Part No. HA028600 Issue 7 3200 Specification Sheet in England 03.08