DI-9301E

Digital Single Input and Output Module

Features
 The dry contact input port can be programmed to
NC or NO and monitored.
 The input can also be programmed as
2831-CPR-F2021
“self-answering”, which means that the Input port GST-0018-01
monitoring is disabled, and the module will
18
directly send a “status” signal to FACP when the
dry-contact output changes state.
 Addressable unit. Address can be programmed
in field.
 Input port utilizes AD sampling technology for
precise testing. 548m/05

 DIN-Rail mounted or Wall mounted.


 Standard: EN 54-18:2005
2) Before installation, make sure the enclosure is in
Description good condition and markings are complete.
3) The module can be mounted on a 35mm
With a microprocessor, the DI-9301E Digital Single DIN-Rail as shown on Fig. 2.
Input and Output Module (the module) can
4) The module can also be wall mounted by 4
communicate with fire alarm control panel (FACP), mounting screws as shown in Fig. 3. Minimum
check loop power-cut, control output, circuit faults, mounting space is 67mm×40.5mm.
logic state of input signals, and state LEDs. On
receiving start command from the FACP, it will close
the output relay and illuminate the active indicator.

Connection and Cabling


Terminals of the module are shown in Fig. 1.

Fig. 2

Fig. 1
 (Z1, Z2) IN & OUT: Connect with the loop of
FACP, polarity-insensitive.
 I, G: Connect with normally open dry contact of Fig. 3
an input device that closes when the device is in
alarm or changes state. It may also be set to Application
normally closed input by hand held programmer.
 COM, NO, NC: Dry contact output terminals The module connects with fire control devices which
(Note: there is 30kΩ resistance between NO and are activated by the FACP.
COM). The address and working mode of the module can be
 CODE: Connect with the programmer. programmable by a programmer in field. Please refer
to P-9910B Hand Held Programmer Installation and
Recommended Wiring: 1.0mm2 or above fire cable for
Operation Manual for details.
all terminals. Subject to local codes.

Installation Programming Parameters:


In standby state of the programmer, Inputting “456”
Warning:
and then pressing “Clear” can unlock the programmer,
Before installing the module, disconnect power
from the loop. press Fn and then number 3, “—“will be popped up on
1) Before installation, make sure the enclosure is in the screen to indicate it is in programming mode. Write
good condition and markings are complete. a parameter and then pressing “Program”, a “P” will
show on the screen meaning the parameter is
programmed.

30310466 Issue 1.04


Press Fn and then number 3, input and output Notes:
checking methods can be set.  It’s only applied for not more than 30VDC or
Parameters AC.
Setting Input Output
 There is 30kΩ between COM and NO so that
1 Self-answering NO checking weak current occurs during operating. It’s not
2 Normally-closed NO checking suitable to control those devices controlled by
3 Normally-open NO checking weak current.
11 Self-answering Checking
12 Normally-closed Checking
 Some fire door control panel, elevator control
box has low starting current because of using
Others(Default) Normally-open Checking
comparator, logic level. We don’t recommend that
Press Fn and then number 4, the number of address the module is adopted due to false alarms caused
points can be set. by circuit or special interference. Please add
Parameters relays between the module and the control
Address
Setting devices if the module is used necessarily.
Occupies two addresses, one for
2
the input and one for output.  The module is not used for gas extinguishing
equipment.
One address for both input and
Others(Default)
output. Specification
The relationship between the input port resistance and Operating Voltage Loop 24VDC(16VDC - 28VDC)
the product state is shown in the following table:
Standby Current ≤ 0.26mA
I/G port
Detection mode
resistance
Input state Action Current Loop≤ 0.7mA
< 1 kΩ Active Relay Output NO or NC
Normally-open > 11.7 kΩ Fault 2A@30VDC. Contact resistance
Output Capacity:
is 30kΩ in normal. It closes after
other Normal
starting.
< 1 kΩ Fault
Programming Electronically addressing
Normally-closed > 11.7 Active
Two options preset by
other Normal manufacturer:
The relationship between the output port voltage and Option 1: Both Input and Output
the product state is shown in the following table: occupy one address that ranges
Output port voltage Output state from 1 to 242.
< 12 V fault Address Range Option 2: Occupy two addresses
representing Input and Output.
> 13 V normal
Input address range is 1 to 241.
 Connection of the module to field devices with Output address is automatically
normally open dry contact is shown in Fig. 3. programmed as input address
plus 1.
Input LED: Red. It lights in
FACP

FACP

Z1 Z1
Z2 Z2
receiving feedbacks, lights 0.5s
on, 0.5s off in input faults, and
Z2
Z1 Z2 Z1
flashes in other states.
LED
DI-9301E DI-9301E Output LED: Red. It lights in
I G NO COM NC I G NO COM NC relay action, 0.5s on and 0.5s off
Feedback 4.7kΩ
Control
Input Feedback 4.7kΩ
Control
Input as there is output fault. It turns
off in other states.
Controlled Device Controlled Device Ingress Protection
IP30
Rating
a b
Operating
-10°C - +55°C
Temperature
Fig. 3
Relative Humidity ≤ 95%,non-condensing
 Connection of the module to devices controlled Compatible
by 24V is shown in Fig. 3. 35mm DIN-Rails
DIN-Rail
Materials of the
Power +24V Power +24V ABS, white(RAL9016)
GND GND Enclosure
Z1 Z1
FACP
Z2
FACP
Z2 Dimension(L×W×H) 85.3mm×78mm×33mm
Weight About 66.5g
Z1 Z2 Z1 Z2
DI-9301E DI-9301E
Accessories and Tools
I G NO COM NC I G NO COM NC

4.7kΩ 4.7kΩ 4.7kΩ 4.7kΩ Model Name Remark


P-9910B Hand Held Supplied
Electric Tripping Device Electric Tripping Device
Programmer separately
b
RT-0.25W-4.7kΩ Resistor Provided
a
±5%-25mm
Fig. 4

30310466 Issue 1.04


Limited Warranty
GST warrants that the product will be free from defects
in design, materials and workmanship during the
warranty period. This warranty shall not apply to any
product that is found to have been improperly installed
or used in any way not in accordance with the
instructions supplied with the product. Anybody,
including the agents, distributors or employees, is not
in the position to amend the contents of this warranty.
Please contact your local distributor for products not
covered by this warranty.

Product warnings and disclaimers


THESE PRODUCTS ARE INTENDED FOR SALE TO,
AND INSTALLATION BY, AN EXPERIENCED
SECURITY PROFESSIONAL. UTC FIRE &
SECURITY CANNOT PROVIDE ANY ASSURANCE
THAT ANY PERSON OR ENTITY BUYING ITS
PRODUCTS, INCLUDING ANY “AUTHORIZED
DEALER”, IS PROPERLY TRAINED OR
EXPERIENCED TO CORRECTLY INSTALL
SECURITY RELATED PRODUCTS.
For more information on warranty disclaimers and
product safety information, please check
https://firesecurityproducts.com/policy/product-warnin
g/ or scan the following code: