McDonalds Building Systems Guide - Ver 1.0 - Nov 2012
McDonalds Building Systems Guide - Ver 1.0 - Nov 2012
Version 1.0
November, 2012
Frank Kohout
Building Systems Manager
McDonald’s Corporation
1
CONTRIBUTORS
The idea for this guide began as a lunchtime conversation with LS Cher and Bosko
Nikolic during a November 2011 Development Meeting in Shanghai. After a year of
writing, reviewing, and revising, it is ready to be released.
Following Ray Kroc’s philosophy that “None Of Us Is As Good As All Of Us” I’d like to
thank the following AOW people whose assistance made this guide possible:
Mike Slikas – US Principal Electrical Engineer
Jason Greenberg - US Principal Mechanical Engineer
Doni Ma – China M&E Manager
Kevin Jang – Korea Development Director
LS Cher & Bosko Nikolic – APMEA Development Senior Directors
Both India Development Teams (Mumbai and Delhi)
Since this guide will be a living document, there will be additional contributors as it
evolves.
If you would like to contribute content to future versions, or just provide your
feedback, please feel free to contact me at [email protected].
Frank Kohout, PE
Building Systems Manager
2 Building Systems Guide: Version 1.0 Nov 2012
OVERVIEW
(What, Why, Who, Where, When, & How)
THE WHAT:
This guide covers the critical details to consider and incorporate when
designing the Building Systems for a McDonald’s restaurant.
The Building Systems Design benefits for using this guide include:
Better Value Designs.
Quality Designs.
Efficient Designs.
Predictable Building Systems Construction.
Budgets and Timelines.
More Efficient Building Systems Operations.
Be sure to check this webpage frequently to ensure you have the latest building
systems information.
Post-
Pre-Design Design Construction Acceptance
Acceptance
The colored square at the top right of the slide will indicate the standard under
which it falls. This slide shows a RED standard indicator.
If the landlord supplies the any part of the HVAC, the following terms must be
included in the lease agreement:
“If at any time it is determined the landlord’s HVAC system for any reason is
causing failure to provide a reasonably comfortable condition; 24-
26°Celsius during the air conditioning season or 20-21°Celsius during the
heating season in all air conditioned or heated areas of the restaurant
during occupied hours the landlord then agrees to providing a means and
suitable, acceptable space for installing an HVAC system exclusively used
and controlled by the restaurant. In this case if the new, independent HVAC
system will be purchased and maintained by McDonald’s the lease rent
charges shall be reduced by the amount associated with the landlord
supplying HVAC to the restaurant space.”
McDonald’s restaurant’s have very large heat gains from the kitchen equipment
and utilize a large amount of make-up air for their exhaust systems. These
factors must be taken into account when calculating the Heating and Cooling
Loads.
NOTE: The loads from the envelope are relatively small when compared to the
make-up air and kitchen equipment loads. Also, the total HVAC heat
requirements will typically be much less than the HVAC cooling requirements.
The method to calculate the envelope loads shall follow ASHRAE’s process for
nonresidential heat and cooling loads as outlined in Chapter 18 of the 2009
Fundamentals Handbook
For this reason the HVAC heat gain from the kitchen equipment is larger than
most other restaurants. Also we do not install exhaust hoods over most
equipment which produces only heat (ovens, warmers, etc..) because the cost
of operating the associated fan and make-up air is greater than the cost of the
additional cooling required to address this additional heat gain. The exception to
this is for equipment which produces a large amount of heat. See the section
on “Hoods for Heat Removal”.
Listed on the next slide is the heat gain from our kitchen equipment for a typical
restaurant. Note that these values are different from the numbers we have
communicated in the past; these latest values are based on a recent ASHRAE
research project.
25 Building Systems Guide: Version 1.0 Nov 2012
HVAC - Load Calculations - Kitchen
Equipment Heat Gains
Listed below is the heat gain from our kitchen equipment for a typical MFY restaurant.
KITCHEN EQUIPMENT TOTAL HEAT REJECTED
HEAT REJECTED
(UPDATED ON 10JAN2012)
(KILOCALORIES/HOUR) (KILOWATTS) (BTU/HOUR)
BASE EQUIPMENT
( ALL UNHOODED HEAT PRODUCING
19,270 sensible 22.42 sensible 76,500 sensible
EQUIPMENT I.E. TOASTERS, BUN
STEAMERS, SHAKE & SUNDAE MACHINE, 2,419 latent 2.5 latent 8,530 latent
COFFEE MAKERS ETC.)
3 FT. FLAT GRILL (HOODED) 932 1.08 3,700
3 FT. CLAM 2-PLATEN GRILL (HOODED) 1,234 1.44 4,900
4 VAT FRYER OR FILET (HOODED) 1,108 1.29 4,400
3 VAT FRYER OR FILET (HOODED) 831 0.97 3,300
2 VAT FRYER OR FILET (HOODED) 554 0.64 2,200
PRESSURE FRYER (HOODED) 202 0.23 800
NOTE:
- The heat rejected to the kitchen space by the "BASE EQUIPMENT" is sensible, latent, and radiant.
- The heat rejected to the kitchen space by the GRILL, FRYER, and FILET" is only radiant since these items are under a
hood and the sensible and latent heat will be exhausted up through the hood.
FOR McDONALD’S INDIA the “BASE EQUIPMENT” heat rejection for the kitchen is 90,000 Btu/hr
(26.38 Kw) sensible and 8,530 Btu/hr (2.5 kW) latent. This is due to the addition of a vegetarian prep area.
NOTE: ONLY use these recommended indoor design temperatures for sizing your
HVAC equipment. The set points at which these systems actually operate should be
determined by the restaurant’s Manager while taking into account customer comfort,
crew comfort, and energy use.
NOTE: As a reference, any HVAC unit with a COP above 3.5 (EER above 12) is
considered high efficiency by McDoanld’s.
Due their modular design, packaged rooftop units are the preferred choice over
split systems since they include the following benefits:
Simple one item installation.
Air side economizers, which provide “free cooling” during mild weather,
can be easily added.
75" 1 CLAM/2 VAT (2) 10" X 16" & (2) 10" X 20" 1050 720 168 250 10 1930 0.35
75" 1 FLAT/2 VAT (2) 10" X 16" & (2) 10" X 20" 1155 720 185 275 10 2104 0.42
75" 1/2 CLAM/3 VAT (2) 10" X 16" & (2) 10" X 20" 1050 720 168 250 10 1930 0.35
75" 1/2 FLAT/3 VAT (2) 10" X 16" & (2) 10" X 20" 1155 720 185 275 10 2104 0.42
83-3/4" 2 CLAM (4) 10" X 20" 1175 800 168 250 11.25 1702 0.35
83-3/4" 2 FLAT (4) 10" X 20" 1295 800 186 275 11.25 1876 0.42
83-3/4" 5 VAT (4) 10" X 20" 1175 800 168 250 11.25 1702 0.35
90-1/2" 1 CLAM/3 VAT (3) 10" X 16" & (2) 10" X 20" 1255 880 166 245 11.25 1818 0.34
90-1/2" 1 FLAT/3 VAT (3) 10" X 16" & (2) 10" X 20" 1400 880 186 270 11.25 2028 0.42
106-3/4" 1 CLAM/4 VAT (5) 10" X 20" 1475 1000 166 256 12 1878 0.82
133-3/4" 1 CLAM/4 VAT/FRZR (8) 10" X 16" 1555 1280 140 245 12 1980 1.05
40" MIN. 4
2
3
5
7 6
16
9 8 10
14 11
15 12
10
15
EXHAUST FAN
DUCT CLEAN-OUT
(TYPICAL)
EXHAUST HOOD
(TYPICAL)
Kitchen exhaust fans shall be listed for cooking exhaust use; UL 762 is an
acceptable listing.
If available, Upblast centrifugal fans are preferred due to their simple
installation. They also allow easy access to clean the duct.
Utility set fans can be also utilized. Proper cleanout access must be
included.
TRANSITION
MINIMUM STRAIGHT DUCT 45 ELBOW TO MINIMIZE
LENGTH. STRAIGHT LENGTH RAIN COLLECTION. ELBOW
CAN BE LONGER SO DISCHARGE BEND SHALL BE IN THE SAME
WILL CLEAR FROM OTHER DIRECTION AS FAN WHEEL
ROOFTOP EQUIPMENT OR ROTATION.
OTHER OBSTACLES. STRAIGHT
LENGTH CAN BE SHORTER TO
LIMIT THE VISIBILITY OF THE
DISCHARGE OUTLET, HOWEVER
FAN EFFICIENCY WILL BE REDUCED.
CENTRIFUGAL UTILITY SET
COOKING EXHAUST FAN.
HINGED ACCESS DOOR
NOTE: FAN DISCHARGE CAN
TO ALLOW CLEANING OF BE ROTATED FOR A
FAN WHEEL.
(NOTE: IF FAN IS
HORIZONTAL DISCHARGE.
LOCATED INDOOR,
THE FAN SCROLL
ROOF DISCHARGE OUTLET MUST BE
HOUSING SHALL
BE WELDED)
EXHAUST DUCT FROM DIRECTED UP AWAY FROM THE
KITCHEN HOODS
25mm (1") DRAIN AT
ROOF AND MUST BE A
DRAIN INTO
3 LITER GREASE
BOTTOM OF FAN MINIMUM OF 1020 MM (40 IN)
HOUSING.
TRAP.
ABOVE AND AWAY FROM ANY
ROOF SURFACES.
47 Building Systems Guide: Version 1.0 Nov 2012
HVAC – Kitchen Exhaust: Utility Set
Fan Discharge Detail (END VIEW - NO SCALE)
For the Public Toilets and Crew Change Rooms, HVAC supply air should be
delivered at 50% to 75% of the room’s exhaust air quantity to ensure
temperature comfort.
CEILING SUPPLY
AIR
DIFFUSER
The listed HVAC standards shall be followed unless more stringent local codes
and requirements supersede.
1. All HVAC ducts shall be fabricated and installed in accordance with SMACNA
standards for a 500 pascal (2 in.wc.) pressure. (See www.smacna.org for
their standards).
2. All flexible duct connections, duct sealants, connectors, and flexible ducts shall
be UL 181 Listed and Labeled.
3. All supply and return sheet metal air ducts located in the ceiling space shall be
externally insulated to an SI R-value of 0.9 (IP R-value of 5.0)
4. All exterior supply and return sheet metal ducts located outdoors shall be
internally lined with 25mm (1”) thick fiberglass with a minimum SI R-value of
0.74 (IP R-value of 4.5) and externally insulated with 40 mm (1-1/2”) rigid
polystyrene or polyurethane board with a minimum SI R-value of 1.3 (IP R-
value of 7.5). Duct and insulation shall be wrapped with a UV barrier which
also protects against water infiltration and corrosion.
5. All flexible ducts shall have a minimum SI R-value of 1.06 (IP R-value of 6.0),
include an integral vapor barrier, and be installed according to the
manufacturers instructions.
To prevent grease-laden hot exhaust air from the kitchen exhaust fan(s)
from being drawn into the air cooled condensers of other outdoor
mechanical equipment.
To prevent air discharged from HVAC or refrigeration condensers from
being drawn into other air cooled condensers or cooling towers.
To prevent bad or harmful odors expelled from plumbing vents and
water heater flue vents from being drawn into the HVAC equipment
outdoor air intakes.
Example showing the ideal clearances NO PARAPET AIR FLOW AIR FLOW
TOILET EXHAUST
3M (10 FT) FAN
3M (10 FT) .6M (2 FT)
1M (3 FT)
1M (3 FT) .6M (2 FT)
.6M (2 FT)
3M (10 FT)
GAS WATER
3M (10 FT) HEATER VENT
(IF USED)
FRESH AIR
INTAKE
1M (3 FT)
DINING PARAPET
A/C UNIT WALL
PARAPET
WALL
The consulting engineer should use 1, 2, 3 and 4-way directional air flow as
required to properly distribute supply air while avoiding directing supply air onto
kitchen equipment surfaces.
Perforated ceiling diffusers with directional are flow control, 60 cm x 60 cm (24
inch x 24 inch) nominal size, made for "lay-in" T-bar suspended ceiling
application, are the first choice diffuser for this application.
These diffusers must have adjustable directional air flow pattern controllers
which can be rotated to direct the discharge air away from any kitchen
equipment. This attribute is necessary to avoid direct down blasts of supply air
that can have adverse effects on food temperature and quality and create
uncomfortably drafty conditions for employees.
Note the locations of the supply air diffusers and return air grilles.
67 Building Systems Guide: Version 1.0 Nov 2012
HVAC - Air Distribution: Kitchen
Perforated Diffuser (preferred)
600 mm x 600 mm nominal face
size
For t-bar grid ceiling lay-in
installation.
Recommended air flow-rate: 200
to 330 liters/second
Perforated diffusers are to have
adjustable directional air flow
control to avoid dumping supply
air directly down.
Use 1, 2, 3 and 4-way flow
direction as required.
Other laminar flow diffusers can
also be utilized.
McDonald’s conditions (heats and cools) all the outside make-up air introduced
into the restaurant. This is accomplished by ducting the make-up air directly into
the return air for the HVAC unit. This quantity is typically between 20% and 30%
of the HVAC unit’s total supply air quantity. (In very mild climates the HVAC unit
can handle make up air up to 50% of the supply air; this is the exception and not
normal).
This diagram illustrates the proper way to introduce make-up air into the
restaurant. While this diagram shows a free standing store utilizing rooftop units,
the same approach can be used with ducted split system units.
This diagram also illustrates the proper building pressurization and space
pressurization within the restaurant for a free standing restaurant.
HVAC TOILET HVAC
UNIT EXHAUST UNIT
O.A. O.A.
KITCHEN
(+) DINING OUTDOOR
(++) (Ǿ)
KITCHEN
EXHAUST
An air balance table shall be shown in the mechanical plans to indicate the general
air balance scheme. This table is useful to ensure the proper amount of make-up
air (or Outside Air) is brought into the restaurant. Shown below is an example for a
free standing restaurant (air quantities listed are in CFM).
The following 7 slides present the step-by-step process for determining the
necessary
FREE quantity distribution of make-up air for a McDonald’s
and properEXAMPLE
STANDING
Restaurant.
The result will be the creation of the Air Balance Schedule based on the following
airflow.
TOILET RM
(MORE POSITIVE THAN
OUTSIDE)
TOILET RM LOBBY/
(MORE POSITIVE THAN DINING ROOM
OUTSIDE)
(MORE
POSITIVE
THAN
KITCHEN,
TOILET RMS, &
OUTSIDE)
KITCHEN
(MORE POSITIVE
THAN OUTSIDE)
KITCHEN EXHAUSTED AIR EXFILTRATES OUT
BY GRILL AND FRYERS OF THE RESTAURANT
(TYPICAL)
TOILETS DINING
AREA
KITCHEN 100 SEATS
TOILETS DINING
AREA
KITCHEN 100 SEATS
TOILETS DINING
AREA
KITCHEN 100 SEATS
TOILETS
DINING
AREA
KITCHEN 100 SEATS
TOILETS
Exhaust Air =
350 CFM DINING
KITCHEN AREA
100 SEATS
This is only an example. The numbers for an actual restaurant will be different.
HVAC HVAC
TOILET
UNIT UNIT
EXHAUST
O.A. 350 O.A.
1262 2000
KITCHEN OUTDOOR
EXHAUST 297
2615
( FILTER #1 FILTER #2
+ + FILTER #3 FILTER #4
+
VELOCITY VELOCITY VELOCITY VELOCITY ) AVERAGE EXHAUST FILTER
= FACE AIR VELOCITY
4
NOTE: The procedure when utilizing a digital vane anemometer requires a simpler method
with only a few measurements per filter required.
87 Building Systems Guide: Version 1.0 Nov 2012
HVAC - Air Balancing McDonald’s
Hoods
After measuring and calculating the filter face velocity, compare the readings to
the Filter Velocity values highlighted in RED on the Universal Hood Exhaust
Design Data which is shown on the next slide.
(NOTE: The Filter Velocity values for the Universal Hoods were obtained in a
controlled laboratory environment by:
1. Adjusting the exhaust air so the hood captures the smoke from cooking
2. Measuring the exhaust air using the laboratories duct mounted
instrumentation.
3. Measuring the corresponding filter velocity with a 100 mm (4 inch) rotating
vane anemometer and recording.
Do not calculate the exhaust air volume by multiplying the filter velocity by the
filter area – it will yield an incorrect answer.
However, extrapolating velocity readings will yield a good estimate of the correct
volume. As an example, measuring a filter velocity of 270 fpm for a 3 vat fryer will
equate to:
(270 fpm/255 fpm) * 720 cfm = 762 cfm
88 Building Systems Guide: Version 1.0 Nov 2012
UNIVERSAL HOOD EXHAUST SYSTEM DESIGN DATA
HOOD COOKING CAPTURE FILTER CFM/FT FILTER VEL DUCT DUCT VEL
LENGTH EQUIPMENT FILTERS (QTY) SIZE CFM SQ. IN. HOOD FPM DIA IN. FPM DUCT INLET S.P.
26" 1 VAT (1) 10" X 20" 345 200 159 295 5.5 2091 0.32
26" 1/2 CLAM (1) 10" X 20" 345 200 159 295 5.5 2091 0.32
26" 1/2 FLAT (1) 10" X 20" 380 200 175 325 5.5 2303 0.38
34-1/2" 2 VAT (2) 10" X 16" 550 320 193 295 7.25 1918 0.45
43-1/2" 1 CLAM (2) 10" X 20" 600 400 166 255 7.25 2093 0.34
43-1/2" 1 FLAT (2) 10" X 20" 660 400 182 280 7.25 2302 0.41
43-1/2" 1/2 CLAM/1VAT (2) 10" X 20" 600 400 166 255 7.25 2093 0.34
43-1/2" 1/2 FLAT/2 VAT (2) 10" X 20" 600 400 166 255 7.25 2093 0.34
50" 3 VAT (3) 10" X 16" 720 480 173 255 9 1630 0.37
59-1/4" 1/2 CLAM/2 VAT (3) 10" X 20" 865 600 175 245 9 1958 0.38
59-1/4" 1/2 FLAT/2 VAT (3) 10" X 20" 955 600 193 270 9 2162 0.45
59-1/4" 1 CLAM/1 VAT (3) 10" X 20" 865 600 175 245 9 1958 0.38
59-1/4" 1 FLAT/1 VAT (3) 10" X 20" 955 600 193 270 9 2162 0.45
65-1/2" 4 VAT (4) 10" X 16" 980 640 180 260 10 1801 0.4
68-1/2" 1 CLAM/1/2 CLAM (4) 10" X 16" 950 640 166 250 10 1742 0.34
68-1/2" 1 CLAM/1/2 FLAT (4) 10" X 16" 950 640 166 250 10 1742 0.34
68-1/2" 1 FLAT/1/2 CLAM (4) 10" X 16" 950 640 166 250 10 1742 0.34
68-1/2" 1 FLAT/1/2 FLAT (4) 10" X 16" 950 640 166 250 10 1742 0.34
75" 1 CLAM/2 VAT (2) 10" X 16" & (2) 10" X 20" 1050 720 168 250 10 1930 0.35
75" 1 FLAT/2 VAT (2) 10" X 16" & (2) 10" X 20" 1155 720 185 275 10 2104 0.42
75" 1/2 CLAM/3 VAT (2) 10" X 16" & (2) 10" X 20" 1050 720 168 250 10 1930 0.35
75" 1/2 FLAT/3 VAT (2) 10" X 16" & (2) 10" X 20" 1155 720 185 275 10 2104 0.42
83-3/4" 2 CLAM (4) 10" X 20" 1175 800 168 250 11.25 1702 0.35
83-3/4" 2 FLAT (4) 10" X 20" 1295 800 186 275 11.25 1876 0.42
83-3/4" 5 VAT (4) 10" X 20" 1175 800 168 250 11.25 1702 0.35
90-1/2" 1 CLAM/3 VAT (3) 10" X 16" & (2) 10" X 20" 1255 880 166 245 11.25 1818 0.34
90-1/2" 1 FLAT/3 VAT (3) 10" X 16" & (2) 10" X 20" 1400 880 186 270 11.25 2028 0.42
106-3/4" 1 CLAM/4 VAT (5) 10" X 20" 1475 1000 166 256 12 1878 0.82
133-3/4" 1 CLAM/4 VAT/FRZR (8) 10" X 16" 1555 1280 140 245 12 1980 1.05
The category of Plumbing includes supply water, waste water, and gas fuel
piping.
Additionally, free standing restaurants will have storm water drainage systems
for their roof area.
Finally, the restaurant’s fuel gas system (if applicable) which serves gas fired
cooking equipment, water heating, and HVAC heating will be covered under
this section.
Objectives:
Providing water which is healthy, safe, good tasting, and odorless.
Providing adequate water to all points of use.
Providing quality water for use in our food and drinks.
Provide tempered and hot water
Resources
“Water Quality Manual for McDonald’s Restaurants” 2010.
The following fixtures require the listed temperature potable water; local
codes may list different requirements:
Water Closets and Urinals – Cold.
Toilet Room Lavatories – Cold and Tempered.
Mop Sink – Cold and Hot.
3 Compartment Sink – Cold and Hot.
Kitchen Hand Sink – Cold and Tempered.
Hose Bibb – Cold.
Clothes Washer – Cold and Hot.
Ware Washer – Cold and Hot.
Vegetable Preparation Sink – Cold and Tempered.
Trap Primer – Cold.
Beverage Filtration System Supply Connection – Cold.
Water Heater – Cold inlet; Hot outlet.
The following is an example of the equipment which are typically connect to the beverage
filtration system. The final kitchen design drawings will list the exact equipment and locations.
All Beverage Equipment
Ice Machines
Steamers
Below is an example of the different equipment connected to the beverage filtration system.
This detail is from the US prototype drawings.
Following is a list of the types of devices and where they shall be used.
Air gap – between drain pipes and top of floor drain/floor sink/hub drain.
Atmospheric Vacuum Breakers – where a hose can be connected.
Single Check Valve - on the hot and cold water at the 3 compartment sink; to
prevent the two different water temperatures from cross flow when the chemical
dispenser is used.
Double Check - between beverage filtration system and each individual piece of
beverage equipment.
Double Check with Atmospheric Vent - between beverage filtration system and
soda tower (soda towers can operate at greater pressures than the beverage
filtration system).
Reduced Pressure Principal (RPZ) – Between the supply water and the
beverage filtration system; prevents possible contamination of the entire
restaurant’s supply water system from the beverage system. Also strongly
recommended to be installed at the restaurant’s incoming water service.
106 Building Systems Guide: Version 1.0 Nov 2012
Plumbing - Supply Water: Storage
Tanks
If supply water service has frequent interruptions then a water
storage tank is required
The Water Quality Manual has a section on designing and
maintaining a these tanks.
The location of the tank needs to be considered.
Typically, the total daily hot water demand is about 2.6kL/day (700 gal/day).
Most of the usage occurs during peak demand periods such as the changeovers
from breakfast to lunch or lunch to dinner and at closing time.
See ASHRAE 2011 Applications, Chapter 50, Service Water Heating, for more
information.
High efficiency tank water heaters are recommended over standard efficiency
tank heaters and tankless or instantaneous water heaters. An independent
research report has shown that for Quick Service Restaurants, High Efficiency
Tank Type water heaters will use less energy than High Efficiency Tankless
Instantaneous water heaters.
(http://www.fishnick.com/publications/fieldstudies/QSR_water_heater_report.pdf)
Water heaters are available which utilize electric, natural gas, and propane as
their fuel source. All water heaters should have a temperature and pressure
relief installed as a safety measure.
Some suppliers offer heat pump models which heat the water while providing
cooling to the kitchen.
All food service and drink waste (kitchen and self-serve) may be
connected to an exterior grease interceptor. The grease interceptor
shall drain in to the restaurant’s main sanitary drain.
Everything else (toilet rooms, front janitor’s sink) should be connected
to the sanitary.
Some local codes require the roof drains and trash corral drains to be
connected to the grease interceptor.
System components:
Grease Trap: to remove solids from grease wastewater. Can be located
either inside the restaurant, or outside underground. (Outside is
preferred).
Septic Tank: to remove solids from all wastewater.
Distribution Box: to evenly distribute flow throughout piping network.
Absorption Field: the network of underground piping so the soil can
absorb the wastewater.
SEPTIC
RESTAURANT TANK
HOUSEHOLD - TOILET
WASTEWATER
PROCESS -
GREASE
WASTEWATER
All gas pipe shall be schedule 40 carbon steel. All fittings shall be
malleable iron.
Only low pressure gas shall be run inside the restaurant.
Either natural gas or Liquid Propane (LPG) can be utilized.
If LPG is utilized then NFPA Standard 58 shall also be utilized for the
design of the
storage and piping system.
ELECTRCITY
METER (S)
MAIN
BRANCH BRANCH BRANCH BRANCH
DISTRIBUTION
PANEL PANEL PANEL PANEL
PANEL
“A” “B” “C” “D”
SUBSTATION
MAIN
BRANCH BRANCH BRANCH BRANCH
DISTRIBUTION
PANEL PANEL PANEL PANEL
PANEL
“A” “B” “C” “D”
INCOMING
HIGH VOLTAGE
POWER TO
SUBSTATION
OUTGOING
LOW VOLTAGE
POWER TO
RESTAURANT
Is a substation required?
Where can it be placed?
GENERATOR
G
MAIN
BRANCH BRANCH BRANCH BRANCH
DISTRIBUTION
PANEL PANEL PANEL PANEL
PANEL
“A” “B” “C” “D”
INCOMING
POWER FROM
UTILITY
SUBSTATION
MAIN
BRANCH BRANCH BRANCH BRANCH
DISTRIBUTION
PANEL PANEL PANEL PANEL
PANEL
“A” “B” “C” “D”
INCOMING
HIGH VOLTAGE
POWER TO
SUBSTATION
OUTGOING
LOW VOLTAGE
POWER TO
RESTAURANT
Electrical feeder cables on line and load sides of substation to line side of
main distribution panel may be aluminum if this is a locally acceptable,
standard practice - low cost. Copper conductors may also be used.
All restaurant wiring on the load side of the main distribution panel shall be
copper conductors with thermoplastic insulation. Aluminum wire shall not be
used.
ISOLATED GROUND
ELECTRICAL
CONVENIENCE
OUTLET - TYPICAL
ISOLATED GROUND
(EARTH) WIRE CONNECTED MAIN DISTRIBUTION BOARD
TO GROUND PIN OF EACH GROUND TERMINAL STRIP;
ISOLATED GROUND CONVENIENCE ELECTRICALLY BONDED TO
OUTLET DISTRIBUTION BOARD BODY
ISOLATED GROUND
ELECTRICAL
CONVENIENCE
OUTLET - TYPICAL
Easily
traceable
circuitry?
Future
Capacity?
Electrical receptacles installed in the following special areas shall meet the
following additional safety criteria:
8. Fixtures shall only use lamp types and wattages as specified for that fixture.
Overlamping shall not be allowed.
9. All fixtures shall be supported in final construction per the manufacturer’s
requirements.
10. No lighting fixtures shall be installed without lamps.
11. All fixtures shall be installed level, plumb, and square with ceilings and walls.
Operation:
Interior fixtures shall be controlled by an automatic controller (a timeclock or
lighting controller or EMS) or a local toggle type switch.
Emergency life-safety lighting shall not be switched.
In areas where high intensity discharge (HID) type fixtures are utilized (for
example, Playplaces), at least one fixture per area shall be provided with an
instant-on quartz restrike type lamp, so that an area is not left in total
darkness if power is disrupted and then reenergized.
Operation:
Select interior lighting can be controlled by either photocells or motion
sensors. The purpose and location of the lighting will determine
which of these control approaches is appropriate.
Lighting located in customer areas near exterior windows should be
controlled by photocells. The lights will be dimmed or extinguished
when adequate daylight is available.
Lighting located in non-customer rooms which are not continuously
occupied (janitors closet, storage, freezer/cooler) should be controlled
by motion sensors so that the lights only operate when the room is
occupied.
For toilet rooms, at least one light should not be controlled by a
motion sensor. This will ensure the toilet room is never completely
dark.
All restaurants shall have a complete exterior and parking lot lighting system
installed and operational prior to opening.
Parking lot lighting requirements:
Pole Height: 6 meters / 20 feet
Lamp: 400 Watt Metal Halide or LED equivalent.
Pole mounted on protective 1 meter / 3 foot high concrete base
Protective lens on all fixtures
A lot lighting study must be completed for each site prior to installation.
LED will have different light spread characteristics than Metal Halide, so
when comparing the two, different lighting designs may be required.
Installation:
Adjustment- exterior lighting fixtures shall be aimed to provide maximum
illumination of area, while preventing glare to pedestrians and vehicles.
Exterior lighting fixtures shall be aimed to prevent light trespass beyond
McDonald’s property line.
All exterior lighting shall be located so that it is inaccessible to customers.
Where ground exterior lighting is utilized, it shall be protected and insulated
to prevent burns if fixture is touched.
166 Building Systems Guide: Version 1.0 Nov 2012
Electrical - Exterior Lighting
Specifications:
All exterior lighting fixtures shall have a protective lens.
All exterior lighting fixtures shall be listed and labeled for use in wet/damp
locations.
All exterior lighting fixtures shall utilize high efficacy (lumens per watt) type
lighting sources. Recommend Metal Halide High Intensity Discharge (HID) type
lamps or quality LED to provide a high color rendering index (CRI).
All exterior signage shall be provided with a local disconnect/isolator.
Operation:
Lighting Control - All exterior signage, exterior area lighting and parking lot
lighting shall not be operated during daylight hours. These devices shall be
controlled by both a clock (or energy management system) which includes
algorithms to account for the local sunrise/sunset times, and a photocell to
provide control when severe weather darkens the sky.
Photocell adjustment – It is suggested to adjust the photocell so the lights are
energized when the outdoor ambient lighting falls below 85 lux (8.5 footcandles)
for signage and 75 lux (7.5 footcandles) for lot lights. Local conditions may
require a different adjustment.
On/Off Sequencing – Be sure not to turn on all exterior lighting simultaneously.
Doing so will result in a spike in electrical demand.
167 Building Systems Guide: Version 1.0 Nov 2012
Electrical - Exterior Lighting
The Ansul system is designed to meet the requirements of the latest versions of
NFPA 17a and NFPA 96 which are the fire protection standards that cover
ventilation control for cooking equipment and wet chemical fire protection agents
Three functions of Ansul Interlock System:
Cooking equipment can only operate if exhaust fan is functional
Exhaust fan operates as soon as first piece of equipment is turned on and
continues to operate until last piece of equipment is turned off
When Ansul discharges the interlock will disconnect power from equipment
via control circuit; the exhaust fan continues to operate.
The local Fire authority may require the Ansul system to de-energize the main
power to equipment under hoods
Not required by NFPA 17a or 96.
May require the installation of shunt-trip type circuit breakers. An additional
Ansul microswitch should be utilized to control circuit breakers.
Exhaust fan must continue to operate to allow the wet chemical agent to be
pulled up exhaust duct to extinguish latent fires.
170 Building Systems Guide: Version 1.0 Nov 2012
Electrical – ANSUL Interlock - Kitchen
Exhaust Fan (Individual System)
NORMAL
ANSUL SUPPRESSION SYSTEM IS ACTUATED.
ELECTRICAL ISOLATION SWITCH
LOCALLY PROVIDED
NC
CON.
JUNCTION BOX ON ELECTROSTATIC PRECIPITATOR (E.S.P.)
NO ELECTRONIC EXHAUST AIR CLEANER UNIT, TYPICAL ON
EACH GRILL AND FRYER EXHAUST HOOD ONLY IF E.S.P.
UNITS ARE USED - OPTIONAL EQUIPMENT
10 3-PHASE POWER
NC
CON.
OUTLETS
NO PROVIDED IN CHICKEN
FRYER STATION (1, 2, OR 3
ANSUL FIRE TERMINAL BLOCK QUANTITY REQUIRED)
SUPPRESSION SYSTEM PROVIDED IN
MICRO-SWITCH EQUIPMENT
PROVIDED
NEUTRAL
LOCALLY PROVIDED
CONTROL POWER TO GRILLS, FRYERS, AND CHICKEN FRYERS
IS ENERGIZED ONLY IF EXHAUST FAN IS OPERATING. KITCHEN EXHAUST FAN MOTOR STARTER (CONTRACTOR)
GRILL FRYER AND CHICKEN FRYER ON/OFF SWITCHES LOCALLY PROVIDED
NORMAL
WILL NOT CONTROL KITCHEN EXHAUST FAN.
GRILLS, FRYERS, AND CHICKEN COOKERS WILL AUTOMATICALLY KITCHEN EXHAUST FAN
NEUTRAL
SHUT OFF IF POWER TO KITCHEN EXHAUST FAN IS INTERRUPTED. LOCALLY PROVIDED
KITCHEN EXHAUST FAN REMAINS OF IF ANSUL FIRE SUPPRESSION
EXHAUST
SYSTEM IS ACTUATED. FAN
NC
To ensure the POS system operates properly, the following items shall be
completed by the Electrical Contractor.
YES NO
o o DO ALL EQUIPMENT GROUND CONDUCTORS TERMINATE ONLY TO THE EQUIPMENT GROUND BAR?
o DOES THE ISOLATED GROUND CONDUCTOR (GREEN W/ YELLOW STRIPE) TERMINATE ON THE
o EQUIPMENT GROUND BAR?
o IS THERE AN APPROPRIATE ELECTRICAL CONNECTION (BOND) BETWEEN THE NEUTRAL CAR AND THE
o EQUIPMENT GROUND BAR?
o DOES THE GROUNDING SYSTEM COMPLY WITH MCDONALD’S BUILDING ELECTRICAL GROUNDING
o DETAIL?
o IS A SURGE PROTECTOR INSTALLED THAT COMPLIES WITH MCDONALD’S “IVSS INSTALLATION GUIDE” OR
o DETAIL?
To ensure the POS system operates properly, the following items shall be
completed by the Electrical Contractor.
POS PANEL
VISUALLY INSPECT THE PANEL “CP” THAT POWERS POS
YES NO
o o IS AN ISOLATED GROUND BAR INSTALLED SUCH THAT IT IS ELECTRICALLY INSTALLED FROM THE PANEL?
o DO ALL EQUIPMENT GROUND CONDUCTORS TERMINATE ONLY TO THE EQUIPMENT GROUND BAR?
o
o DO ALL ISOLATED GROUND CONDUCTORS ( GREEN W/ YELLOW STRIPE) TERMINATE ONLY TO THE
ISOLATED GROUND BAR?
o
o ARE ALL ELECTRICAL CONNECTIONS (WIRING & BUSING) PROPERLY TIGHTENED?
o o ARE ALL POS AND COD CIRCUIT BREAKERS ON THE SAME PHASE?
o o DOES THE FEEDER FOR THE SUBPANEL CONTAIN PHASE NEUTRAL ONE EQUIPMENT GROUNDING AND
ONE ISOLATED GROUND CONDUCTORS THAT ARE PROPERLY TERMINATED (SEE POS AND COD ISO GND/
DED CKT DETAIL)?
To ensure the POS system operates properly, the following items shall be
completed by the Electrical Contractor.
POS SUB-PANELS
VISUALLY INSPECT ALL REMAINING ELECTRICAL SUBPANELS
YES NO
o o IS AN EQUIPMENT GROUND BAR INSTALLED SUCH THAT IT IS ELECTRICALLY CONNECTED TO THE PANEL?
To ensure the POS system operates properly, the following items shall be
completed by the Electrical Contractor.
YES NO
o o ARE THE POS BRANCH CIRCUITS ROUTED IN THEIR OWN CONDUIT BY THEMSELVES?
o o DOES EACH POS BRANCH CIRCUIT CONTAIN ONE PHASE (BLACK COLORED INSULATION)
ONE NEUTRAL (WHITE COLORED INSULATION) ONE EQUIPMENT GROUND ( GREEN COLORED
INSULATION) ONE ISOLATED GROUND (GREEN W/ YELLOW STRIPE COLORED INSULATION)?
o o DO ALL POS BRANCH CIRCUITS TERMINATE AT EITHER AN 1G4700, IG4710, IG5261, IG5262,
RECEPTACLES OR ANY COMBINATION OF THESE?
o o ARE ALL ELECTRICAL TERMINATIONS TO IG RECEPTACLES MADE WITH SOLID #12 AWG WIRE
CAPTURED AROUND THE SCREW BARREL AND SUITABLY TIGHTENED?
o o ARE THE CORRECT AMOUNT AND TYPE OF IG RECEPTACLES PROVIDED AS SHOWN IN THE
ELECTRICAL ROUGH-IN PLAN, NOTES, AND INFORMATION?
o o DO ALL POS BRANCH CIRCUITS COMPLY WITH THE POS & COD ISOLATED GROUND/
DEDICATED CIRCUIT DETAIL?
To ensure the POS system operates properly, the following items shall be
completed by the Electrical Contractor.
YES NO
o o ARE THE POS BRANCH CIRCUITS ROUTED IN THEIR OWN CONDUIT BY THEMSELVES?
o o DOES EACH POS BRANCH CIRCUIT CONTAIN ONE PHASE (BLACK COLORED INSULATION)
ONE NEUTRAL (WHITE COLORED INSULATION) ONE EQUIPMENT GROUND ( GREEN COLORED
INSULATION) ONE ISOLATED GROUND (GREEN W/ YELLOW STRIPE COLORED INSULATION)?
o o DO ALL POS BRANCH CIRCUITS TERMINATE AT EITHER AN 1G4700, IG4710, IG5261, IG5262,
RECEPTACLES OR ANY COMBINATION OF THESE?
o o ARE ALL ELECTRICAL TERMINATIONS TO IG RECEPTACLES MADE WITH SOLID #12 AWG WIRE
CAPTURED AROUND THE SCREW BARREL AND SUITABLY TIGHTENED?
o o ARE THE CORRECT AMOUNT AND TYPE OF IG RECEPTACLES PROVIDED AS SHOWN IN THE
ELECTRICAL ROUGH-IN PLAN, NOTES, AND INFORMATION?
o o DO ALL POS BRANCH CIRCUITS COMPLY WITH THE POS & COD ISOLATED GROUND/
DEDICATED CIRCUIT DETAIL?
The purpose of the energy management system is to provide precise control of the
restaurant’s lighting, signage and HVAC systems which in turn reduces energy
consumption.
Internal:
US MEP Prototype Drawings and Specifications
Korea HVAC Drawings (For Split System Designs)
McDonald’s Water Quality Manual