DESIGN SPECIFICATIONS

MATERIALS

CONCRETE
f’c = 20.70 MPa (3000 psi)
REINFORCING STEEL
fy = 414 MPa ; if db ≥ 16mm
fy = 275 MPa ; if db < 16mm

LOADINGS

A. DEAD LOADS

SLAB

One - Way Slab (100 mm thk. x 24 𝑘𝑁/𝑚3 ) 2.40 kPa


Two - Way Slab (110 mm thk. x 24 𝑘𝑁/𝑚3 ) 2.64 kPa
Electromechanical 0.10 kPa
Steel Railings (Steel Cold-Drawn) 0.77 kPa
Water Proofing 0.10 kPa

FLOOR

Porcelain Floor Tiles (10 mm thk.) 0.24 kPa


Indoor Mosaic Floor Tiles (Cement Tiles) 0.77 kPa
Ash Hardwood Flooring 0.19 kPa
20mm Concrete Fill Finish 0.46 kPa
Tile Grout 0.20 kPa
15 mm Mortar Bed 0.32 kPa
Water Proofing 0.10 kPa

CEILING

Fiber Cement Ceiling Board (4.5 mm thk.) 0.06 kPa


Suspended Steel Channel System 0.10 kPa
Paint 0.001 kPa
Electromechanical 0.10 kPa
Water Proofing 0.10 kPa

WALL

INTERIOR WALL 150 mm. THK. CHB,


16.50 kN/m3 density of unit, Grout Spacing 400
(BOTH FACES PLASTERED) 2.40 kPa
EXTERIOR WALL 200 mm. THK. CHB,
19.60 kN/m3 density of unit, Grout Spacing 400
(BOTH FACES PLASTERED) 2.82 kPa
Windows, Glass, Frame and Sash 0.77 kPa
Electromechanical 0.10 kPa
Water Proofing 0.10 kPa
Paint 0.001 kPa
Wall Tiles (Cement Tiles) 0.77 kPa
Interior Partition Load 1.00 kPa
Steel Cladding 0.77 kPa

BEAM

Beam (250mm x 400mm) 2.4 kN/m

B. LIVE LOADS

Residential (Basic Floor Area) 1.900 kPa


Restroom 2.400 kPa
Hallway 4.800 kPa
Exit Facilities 4.800 kPa
Roof Deck 1.900 kPa

C. ROOF LIVE LOAD

Roof Live Load = 1.000 kPa

D. WIND LOADS

Location Danao, Panglao Island, Bohol


Building Category Standard Occupancy Structures, IV
Basic Wind Speed, V 260 kph or 72.222 m/s
Importance Factor, Iw 1.0
Topographic Factor, Kzt 1.0
Wind Directionality Factor, Kd 0.85
Exposure B
Enclosure Classification Enclosed

E. EARTHQUAKE LOADS

Nearest Fault Line East Bohol Fault Line


Distance from Nearest Fault Line 27.5 km
Importance Factor, I 1.0
Zone 4, Z 0.40
SMRF, R 5.5
Type of Soil Stiff Soil Profile, SD

REFERENCES

National Structural Code of the Philippines 2015


American Concrete Institute
Design of Reinforced Concrete 9th Edition (McCormac J.C. and Brown, R.H.)
CALCULATIONS

SLABS

A. ONE-WAY SLAB THK.


𝐿
𝑆
>2
4150
2000
>2
2. 075 > 2 ; 1 way slab

𝑃𝑒𝑟𝑖𝑚𝑒𝑡𝑒𝑟 (4150+2000)(2)
THK =
1800
= 1800
= 68.83mm ; use 100mm THK

FOR DEAD LOAD OF ONE WAY SLAB


3
Unit Weight of Concrete = 24.4 kN/𝑚
Slab Thk. = 0.100 m
𝑆𝑙𝑎𝑏𝐷𝐿 = 24.4 x 0.100
𝑆𝑙𝑎𝑏𝐷𝐿 = 2.4 kPa

B. TWO-WAY SLAB THK.


𝐿
𝑆
<2
5150
4150
<2
1. 24 < 2 ; 2 way slab

𝑃𝑒𝑟𝑖𝑚𝑒𝑡𝑒𝑟 (4150+5150)(2)
` THK =
1800
= 1800
= 103mm ; use 110mm THK

FOR DEAD LOAD OF TWO WAY SLAB


3
Unit Weight of Concrete = 24.4 kN/𝑚
Slab Thk. = 0.110 m
𝑆𝑙𝑎𝑏𝐷𝐿 = 24.4 x 0.110
𝑆𝑙𝑎𝑏𝐷𝐿 = 2.7 kPa

BEAM

Beam (250mm x 400mm) = 𝑈𝑛𝑖𝑡 𝑊𝑒𝑖𝑔ℎ𝑡 𝑜𝑓 𝐶𝑜𝑛𝑐𝑟𝑒𝑡𝑒 𝑥 𝑊𝑖𝑑𝑡ℎ 𝑥 Depth


= 24 𝑘𝑁/𝑚3 𝑥 0.250𝑚 𝑥 0.400𝑚
= 𝟐.𝟒𝟎𝟎 𝒌𝑵/m