PLC based basic

commissioning solution
for SINAMICS G120X
Siemens
SINAMICS / G120(X) / TIA Portal ADDin Industry
Online
https://support.industry.siemens.com/cs/ww/en/view/109792547 Support
Legal information

Legal information
Use of application examples
Application examples illustrate the solution of automation tasks through an interaction of several
components in the form of text, graphics and/or software modules. The application examples are
a free service by Siemens AG and/or a subsidiary of Siemens AG ("Siemens"). They are
non-binding and make no claim to completeness or functionality regarding configuration and
equipment. The application examples merely offer help with typical tasks; they do not constitute
customer-specific solutions. You yourself are responsible for the proper and safe operation of the
products in accordance with applicable regulations and must also check the function of the
respective application example and customize it for your system.
Siemens grants you the non-exclusive, non-sublicensable and non-transferable right to have the
application examples used by technically trained personnel. Any change to the application
examples is your responsibility. Sharing the application examples with third parties or copying the
application examples or excerpts thereof is permitted only in combination with your own products.
The application examples are not required to undergo the customary tests and quality inspections
of a chargeable product; they may have functional and performance defects as well as errors. It is
your responsibility to use them in such a manner that any malfunctions that may occur do not
result in property damage or injury to persons.

Disclaimer of liability
Siemens shall not assume any liability, for any legal reason whatsoever, including, without
limitation, liability for the usability, availability, completeness and freedom from defects of the
application examples as well as for related information, configuration and performance data and
any damage caused thereby. This shall not apply in cases of mandatory liability, for example
under the German Product Liability Act, or in cases of intent, gross negligence, or culpable loss of
life, bodily injury or damage to health, non-compliance with a guarantee, fraudulent
non-disclosure of a defect, or culpable breach of material contractual obligations. Claims for
damages arising from a breach of material contractual obligations shall however be limited to the
© Siemens 2021 All rights reserved

foreseeable damage typical of the type of agreement, unless liability arises from intent or gross
negligence or is based on loss of life, bodily injury or damage to health. The foregoing provisions
do not imply any change in the burden of proof to your detriment. You shall indemnify Siemens
against existing or future claims of third parties in this connection except where Siemens is
mandatorily liable.
By using the application examples you acknowledge that Siemens cannot be held liable for any
damage beyond the liability provisions described.

Other information
Siemens reserves the right to make changes to the application examples at any time without
notice. In case of discrepancies between the suggestions in the application examples and other
Siemens publications such as catalogs, the content of the other documentation shall have
precedence.
The Siemens terms of use (https://support.industry.siemens.com) shall also apply.

Security information
Siemens provides products and solutions with Industrial Security functions that support the secure
operation of plants, systems, machines and networks.
In order to protect plants, systems, machines and networks against cyber threats, it is necessary
to implement – and continuously maintain – a holistic, state-of-the-art industrial security concept.
Siemens’ products and solutions constitute one element of such a concept.
Customers are responsible for preventing unauthorized access to their plants, systems, machines
and networks. Such systems, machines and components should only be connected to an
enterprise network or the Internet if and to the extent such a connection is necessary and only
when appropriate security measures (e.g. firewalls and/or network segmentation) are in place.
For additional information on industrial security measures that may be implemented, please visit
https://www.siemens.com/industrialsecurity.
Siemens’ products and solutions undergo continuous development to make them more secure.
Siemens strongly recommends that product updates are applied as soon as they are available
and that the latest product versions are used. Use of product versions that are no longer
supported, and failure to apply the latest updates may increase customer’s exposure to cyber
threats.
To stay informed about product updates, subscribe to the Siemens Industrial Security RSS Feed
at: https://www.siemens.com/industrialsecurity.

SINAMICS G120X: Basic Setup Add-in


Entry-ID: 109792547, V1.2, 04/2021 2
Table of contents

Table of contents
Legal information ......................................................................................................... 2
1 Introduction ........................................................................................................ 4
1.1 Overview............................................................................................... 4
1.2 Components used ................................................................................ 5
2 HW preparation .................................................................................................. 6
2.1 Hardware setup .................................................................................... 6
2.2 Hardware configuration in TIA Portal ................................................... 6
3 Software description ......................................................................................... 7
3.1 Add-ins installation ............................................................................... 7
3.2 Description of SINAMICS G120X Basic Setup add-in ......................... 9
3.2.1 Entry window ........................................................................................ 9
3.2.2 Motor setup ........................................................................................ 10
3.2.3 Operation limits .................................................................................. 11
3.2.4 I/O configuration ................................................................................. 11
3.2.5 Summary ............................................................................................ 12
3.3 Function block structure ..................................................................... 13
3.4 Error handling ..................................................................................... 15
© Siemens AG 2021 All rights reserved

3.4.1 LAcycCom_ReadDriveParams diagnostics messages ...................... 15


3.4.2 LAcycCom_WriteDriveParams diagnostics messages ...................... 16
3.4.3 FB_AcycJobs Error Codes ................................................................. 17
4 Application example ........................................................................................ 18
4.1 Using “SINAMICS G120X Basic Setup” add-in .................................. 18
4.2 Execution of commissioning in TIA Portal .......................................... 20
5 Appendix .......................................................................................................... 23
5.1 Service and support ........................................................................... 23
5.2 Industry Mall ....................................................................................... 24
5.3 Links and literature ............................................................................. 24
5.4 Change documentation ...................................................................... 24

SINAMICS G120X: Basic Setup Add-in


Entry-ID: 109792547, V1.2, 04/2021 3
1 Introduction

1 Introduction
1.1 Overview
In this application example it is shown how to use a TIA Portal add-in for
commissioning of two SINAMICS G120X demo-cases at once. This is achieved
with PLC having also the function of local storage center (i.e. commissioning data
are stored in a PLC for future use like for example in case of inverter replacement).
Add-in: SINAMICS G120X Basic Setup – simplified version for quick and easy
basic drive commissioning (no inverter parameters knowledge required)
Our example is worked out on using two SINAMICS G120X demo-cases and one
SIMATIC S7-1200 PLC.
The workflow with add-in in TIA Portal comprises following steps:
• Preparation of commissioning data offline and its backup (optional) on
PC/PG in .xml format.
• Assignment of commissioning data to a single or more identical inverters
and storing the data in the PLC (as a local backup).
• Execution of commissioning of one or more inverters (mass
commissioning) from PLC on demand using acyclic communication.
© Siemens AG 2021 All rights reserved

Figure 1 – Graphical overview of commissioning workflow

SINAMICS G120X: Basic Setup Add-in


Entry-ID: 109792547, V1.2, 04/2021 4
1 Introduction

1.2 Components used


This application example has been created with the following hardware and
software components:
Table 1-1
Component Number Article number Note
SIMATIC S7-1200 1 6ES7 214-1AG40- Alternatively, other
CPU 1214C DC/DC/DC 0XB0 types of SIMATIC S7-
(Firmware V4.4) 1200 or S7-1500 can
be used.
SINAMICS G120X 2 6SL3200-0AE70-0AA0 Alternatively, any type
Starter Kit (FW1.0.1) of SINAMICS
G120(X) drives with
PROFINET interface
can be used.
SIMATIC STEP 7 1 6ES7822-1AA06-0YA5 TIA Portal V16
Professional V16 Update 1 and higher
can be used to do the
configuration as
described.

This application example consists of the following components:


Table 1-2
© Siemens AG 2021 All rights reserved

Component Note
TIA PORTAL It is automatically integrated in TIA Portal V16. There is no
OPENNESS V16 need to install it.
G120X GSDML File can be downloaded from:
PROFINET file https://support.industry.siemens.com/cs/ww/en/view/109763250
Used file: G120X_GSDML_PN_V1.01.ZIP
SINAMICS Startdrive Required due to Add-In activation but otherwise not used in
V16 this application example.
Program can be downloaded from:
https://support.industry.siemens.com/cs/ww/en/view/109771710
TIA Portal Add-In File can be downloaded from:
https://support.industry.siemens.com/cs/ww/en/view/109792547
Used file:
109792547_SINAMICS_G120X_Basic_Setup_v16.0.120.2.zip

SINAMICS G120X: Basic Setup Add-in


Entry-ID: 109792547, V1.2, 04/2021 5
2 HW preparation

2 HW preparation
2.1 Hardware setup
This application example shows the case of two G120X demo-cases on the PN
network.

Figure 2 – HW connection

2.2 Hardware configuration in TIA Portal


© Siemens AG 2021 All rights reserved

After creating a project in TIA Portal make following configuration:


• Add the PLC as a new device
• Add G120X PN V1.0 drives from HW catalog (installation of SINAMICS
GSD library required) and rename them to G120X_Demo1 and 2.
• Create the PN network and set IP addresses

Figure 3 – PN network configuration

• Finally move the added drives from Ungrouped devices folder to a project
root (drag-drop)

Figure 4 – Moving out from Ungrouped devices

SINAMICS G120X: Basic Setup Add-in


Entry-ID: 109792547, V1.2, 04/2021 6
3 Software description

3 Software description
3.1 Add-ins installation
Before you can start using the Openness add-in ensure it is installed and activated
as per following procedure (Close TIA Portal before installation).
1. Download and unpack the add-in file in your PC/PG

2. In the subfolder run the batch file (.bat) as an administrator


© Siemens AG 2021 All rights reserved

OR manually copy:

*.addin file into the location

*.zal16 compressed library file into the location

NOTE: Folder AppData is hidden by default. You might need to change


the Folder settings in your operating system to find it:

SINAMICS G120X: Basic Setup Add-in


Entry-ID: 109792547, V1.2, 04/2021 7
3 Software description

3. Start TIA Portal V16 and


click on Add-ins in right
hand tab

4. Show the list of all


installed Add-ins

5. Select the add-in


Sinamics G120X Basic
Setup.addin

6. Change status to
Activate

Note: Only one add-in


can be activated at a
time.

7. Confirm the activation


© Siemens AG 2021 All rights reserved

8. The status is now


Activated

9. The Sinamics G120X


Basic Setup add-in can
be now found and
launched by right-mouse
click on project root or
any G120X drive

SINAMICS G120X: Basic Setup Add-in


Entry-ID: 109792547, V1.2, 04/2021 8
3 Software description

3.2 Description of SINAMICS G120X Basic Setup add-in


This add-in can be launched by right-mouse click on a project root, any group of
devices or only a single device in the project. The project must contain at least one
G120X inverter. Note once the app is running the main TIA Portal window is
inhibited.
The entry window that appears after app launch lets you select whether you want
to work with a new- or already saved drive configuration. You are also supposed to
select which drive(s) you want the configuration to apply.

3.2.1 Entry window


© Siemens AG 2021 All rights reserved

Figure 5 – SINAMICS G120X Basic Setup: Entry window


1. Saved configurations – in this pane you have displayed all previously saved
or imported configurations that you can use for drive(s) commissioning either
unchanged or you can modify them in the next steps.
2. Import from file – if you migrate configuration file from another PG/PC you
can use „Import from file” button to import .xml file. Saved configurations are
stored under the path:

3. Select device(s) – in this pane you can select (tick) the inverters you want the
new or selected configuration to apply.
4. Next with selected configuration – moves you to the next window (Motor
Setup) with pre-filled setting according to selected Saved configuration. This
button is inhibited if no Saved configuration nor device is selected.
5. Next with new configuration – moves you to the next window (Motor Setup)
with zeroed setting. This button is inhibited if no device is selected.

SINAMICS G120X: Basic Setup Add-in


Entry-ID: 109792547, V1.2, 04/2021 9
3 Software description

3.2.2 Motor setup

Figure 6 – SINAMICS G120X Basic Setup: Motor setup

1. Back and Next buttons – moves you one step back or forward without
discarding values (applies to all following windows).
© Siemens AG 2021 All rights reserved

2. Converter supply voltage – enter nominal value of power supply grid here
3. Start with Parameter reset – this box is preselected if you start with a new
configuration. If ticked the parametrization starts with drive parameters reset so
all previous drive setting is cleared and set to factory default.
4. Select Motor Control Mode – if you commission asynchronous motors as a
rule select SDC for drives up to 15kW and DDC above this power rating. For
commissioning other types of motors (synchronous, reluctance) select always
DDC.
5. Select Motor Standard – depending on motor nameplate units select either
IEC or NEMA (SI units) if the rated power is expressed in „kW” or NEMA (US
units) if it’s in „HP”.
6. Select Motor Type – select type of motor. If using SIMOTICS motor then
preferably select the correct design type, f.e. 1LE1 induction motor (not a code
number). If you know the SIMOTICS motor code then better select the option
with code required, f.e. 1LE1 induction motor (code required).
7. Motor data – enter motor nameplate data in all displayed and enabled fields.
Select also right connection type Y or . If you selected  then you are allowed
to choose also 87Hz operation if suitable. Perform motor stationary ID test
option is by default ticked and it is strongly recommended to keep this setting
on.

SINAMICS G120X: Basic Setup Add-in


Entry-ID: 109792547, V1.2, 04/2021 10
3 Software description

3.2.3 Operation limits

Figure 7 – SINAMICS G120X Basic Setup: Operation limits

1. Max. and Min. speed – enter limits in RPM units. For conversion from Hz units
use formula RPM = 60 * Hz / number of motor pole pairs.
© Siemens AG 2021 All rights reserved

Min. speed value should not be less than 15% of motor nominal speed.
2. Ramp up and Ramp down – enter the acceleration and deceleration time.
Default value is 10s.

3.2.4 I/O configuration

Figure 8 – SINAMICS G120X Basic Setup: I/O configuration

1. Select Macro from the drop-down menu according to the required drive I/O
pre-configuration. The I/O function assignment is then displayed in the table
below.

SINAMICS G120X: Basic Setup Add-in


Entry-ID: 109792547, V1.2, 04/2021 11
3 Software description

3.2.5 Summary

Figure 9 – SINAMICS G120X Basic Setup: Summary

1. General – basic overview of your configuration. At this stage it is possible to


© Siemens AG 2021 All rights reserved

change setting for:


• Reset parameters
• Save RAM to ROM
• Identifying motor data (at standstill)
2. Motor – overview of motor data
3. Limits – overview of limit setting
4. Save configuration – this button allows you to save the configuration locally
on your PG/PC. Enter the name and optionally the description.

5. Finish – click on this button to generate program and data blocks for PLC that
are needed for drive(s) commissioning. If you already used the add-in in the
past you are asked to delete temporary data from previous use. Press Yes to
proceed.

SINAMICS G120X: Basic Setup Add-in


Entry-ID: 109792547, V1.2, 04/2021 12
3 Software description

Once the blocks are generated you will see the pop-up window:

Press Yes to exit the application or No to stay in it (for future exit you can use
the icon at right top corner).
6. Log – toggles between Log and Summary table.
© Siemens AG 2021 All rights reserved

3.3 Function block structure


DbAcycCtrl_xxxx - this control block contains AcycJobs data, i.e. Job Type,
Waiting time, Values and Comments as defined in the Add-in and it is generated
for each selected device. There are also some other inputs/outputs:

Figure 10 - DbAcycCtrl_xxxx control block structure

Execute (input) – change from 0 to 1 starts commissioning of the specific device


HwiD
Busy (output) – value 1 shows the commissioning being in progress
Done (output) – value 1 shows the commissioning was successfully done

SINAMICS G120X: Basic Setup Add-in


Entry-ID: 109792547, V1.2, 04/2021 13
3 Software description

Error (output) – value 1 shows error during commissioning, see Status code to find
the cause.

OB_AcycJobs_xxx – this is the block calling DbAcycInst_xxxx to update


DbAcycCtrl_xxxx inputs/outputs and Ayclic job data.

Figure 11 - OB_AcycJobs_xxx operating block structure


© Siemens AG 2021 All rights reserved

SINAMICS G120X: Basic Setup Add-in


Entry-ID: 109792547, V1.2, 04/2021 14
3 Software description

3.4 Error handling


In DbAcycCtrl_xxxx if during commissioning any error occurs the Error output is
set to 1 and Status output is showing the error code.

Figure 12 - Finding error value in DbAcycCtrl_xxxx


In case of the error during processing Read/Write Job the Error number is
displayed in ErrorValue variable of the Job.
To be able to track down which Job caused the error see variable CurrentJobIndx
in DbAcycInst_xxxx.
© Siemens AG 2021 All rights reserved

Figure 13 - Tracking down the error via CurrentJobIndx tag


Depending on Job type and its Error code you can find the cause of the error in
following tables.
• Read or Check Job: LAcycCom_ReadDriveParams diagnostics messages
• Write Job: LAcycCom_WriteDriveParams diagnostics messages

3.4.1 LAcycCom_ReadDriveParams diagnostics messages

Status Meaning Comment


16#0000 STATUS_EXECUTION_FINISH Execution finished without
ED errors
16#7000 STATUS_NO_CALL No call of FB
16#7001 STATUS_ALLOCATE FB is currently allocating a
request element
16#7002 STATUS_GET_RESOURCE FB is waiting until it has
“speaking rights”
16#7003 STATUS_BUSY FB is currently in processing
16#7004 STATUS_RELEASE FB is releasing the allocated
element
16#7100 WARN_EXECUTE Execute input set during silent
operation mode
16#7101 WARN_EXECUTE_SET_DURI Execute input set during
NG_PROCESSING processing
16#8001 ERR_NO_OF_PARAMETERS Invalid count of parameters
16#8002 ERR_INVALID_PRIORITY_CL FB is not called in OB1
ASS
16#8004 ERR_JOB_REJECTED Request rejected
16#8005 ERR_RESOURCE_RELEASED Request is already released
16#8006 ERR_AMBIGUOUS_FB_CALL Execute input set during
processing (possible

SINAMICS G120X: Basic Setup Add-in


Entry-ID: 109792547, V1.2, 04/2021 15
3 Software description

inconsistent data at output)


16#8200 ERR_INVALID_DATA_TYPE Invalid PLC data type at the
input “dataset”
16#8201 ERR_INVALID_BUF_INDEX Buffer index is invalid
16#8600 ERR_COMMAND_TIMEOUT The assigned buffer element is
no longer available for the
request
16#8601 ERR_RDREC_TEMP_COUNT Counter for temporary errors
ER reached the maximum during
RDREC command
16#8602 ERR_WRREC_TEMP_COUNT Counter for temporary errors
ER reached the maximum during
WRREC command
16#8603 ERR_WRREC Error occurred during WRREC
command
16#8604 ERR_RDREC Error occurred during RDREC
command
16#8605 ERR_REFERENCE_NO Reference number of the
request does not match the
response reference number
16#8606 ERR_RESPONSE_ID Invalid response from the drive
object
16#8607 ERR_PARAMETER_NO The number of parameters
received does not match the
requested number of
parameters
16#8608 ERR_DRIVE_OBJECT_NO The drive object does not match
the responded drive object
© Siemens AG 2021 All rights reserved

16#8609 ERR_ALLOCATION_TIME The allocation time exceeded


the configured value
16#8610 ERR_MOVE_BLK_VARIANT Error occurred during
MOVE_BLK_VARIANT
command
16#8611 ERR_UNDEFINED_STATE Error due to an undefined state
16#8612 ERR_UNDEFINED_SUBSTAT Error due to an undefined
E substate
16#8619 ERR_PARAMETER Error in at least one parameter
(see: errorValue in dataset)

3.4.2 LAcycCom_WriteDriveParams diagnostics messages

Status Meaning Comment


16#0000 STATUS_EXECUTION_FINISH Execution finished without
ED errors
16#7000 STATUS_NO_CALL No call of FB
16#7001 STATUS_ALLOCATE FB is currently allocating a
request element
16#7002 STATUS_GET_RESOURCE FB is waiting until it has
“speaking rights”
16#7003 STATUS_BUSY FB is currently in processing
16#7004 STATUS_RELEASE FB is releasing the allocated
element
16#7100 WARN_EXECUTE Execute input set during silent
operation mode
16#7101 WARN_EXECUTE_SET_DURI Execute input set during
NG_PROCESSING processing
16#8001 ERR_NO_OF_PARAMETERS Invalid count of parameters
16#8004 ERR_REQUEST_REJECTED Request rejected
16#8005 ERR_RESOURCE_RELEASED Request is already released
16#8006 ERR_AMBIGUOUS_FB_CALL Execute input set during
processing (possible

SINAMICS G120X: Basic Setup Add-in


Entry-ID: 109792547, V1.2, 04/2021 16
3 Software description

inconsistent data at output)


16#8200 ERR_INVALID_DATA_TYPE Invalid PLC data type at the
input “dataset”
16#8201 ERR_INVALID_BUF_INDEX Buffer index is invalid
16#8600 ERR_COMMAND_TIMEOUT The assigned buffer element is
no longer available for the
request
16#8601 ERR_RDREC_TEMP_COUNT Counter for temporary errors
ER reached the maximum during
RDREC command
16#8602 ERR_WRREC_TEMP_COUNT Counter for temporary errors
ER reached the maximum during
WRREC command
16#8603 ERR_WRREC Error occurred during WRREC
command
16#8604 ERR_RDREC Error occurred during RDREC
command
16#8605 ERR_REFERENCE_NO Reference number of the
request does not match the
response reference number
16#8606 ERR_RESPONSE_ID Invalid response from the drive
object
16#8607 ERR_PARAMETER_NO The number of parameters
received does not match the
requested number of
parameters
16#8608 ERR_DRIVE_OBJECT_NO The drive object does not match
the responded DO
© Siemens AG 2021 All rights reserved

16#8609 ERR_ALLOCATION_TIME The allocation time exceeded


the configured value
16#8610 ERR_MOVE_BLK_VARIANT Error occurred during
MOVE_BLK_VARIANT
command
16#8611 ERR_UNDEFINED_STATE Error due to an undefined state
16#8612 ERR_UNDEFINED_SUBSTAT Error due to an undefined
E substate
16#8619 ERR_PARAMETER Error in at least one parameter
(see: errorValue in dataset)

3.4.3 FB_AcycJobs Error Codes

Status Meaning Comment


16#9000 ERR_NEXT_JOB MOVE_BLK_VARIANT error
while copying next job
16#9001 ERR_UNKNOWN_JOB Unknown job type
16#9002 ERR_READ_COPY MOVE_BLK_VARIANT error
while copying read values
16#9003 ERR_WRITE_COPY MOVE_BLK_VARIANT error
while copying write values
16#9004 ERR_CHECK_TIMEOUT Timeout error in check job.
Time elapsed without reaching
the expected values
16#9005 ERR_CHECK_COPY MOVE_BLK_VARIANT error
while copying check values

SINAMICS G120X: Basic Setup Add-in


Entry-ID: 109792547, V1.2, 04/2021 17
4 Application example

4 Application example
Following example shows simple commissioning of two G120X PN Democases.
Chapter 2 HW Preparation describes details regarding HW configuration in TIA
portal.

4.1 Using “SINAMICS G120X Basic Setup” add-in

Run the application from project


root to ensure both drives are
shown in the add-in.

Select both inverters and click


on Next with new configuration.
© Siemens AG 2021 All rights reserved

Enter the supply voltage 430V


and motor type and data
according to the rating plate
values.
Proceed with Next.

Limits for drive operation can


stay at default.
Proceed with Next.

SINAMICS G120X: Basic Setup Add-in


Entry-ID: 109792547, V1.2, 04/2021 18
4 Application example

Depending on preferred way of


drive control select suitable
macro.
Proceed with Next.

To make the configuration


backup click on Save
Configuration button and enter
Name and Description. Then
click on Save.

Finally click on Finish button


and confirm the warning
© Siemens AG 2021 All rights reserved

message if it appears:

Exit the add-in and continue


according to the description in
the following chapter 4.2.

SINAMICS G120X: Basic Setup Add-in


Entry-ID: 109792547, V1.2, 04/2021 19
4 Application example

4.2 Execution of commissioning in TIA Portal

Generated blocks are now visible


under PLC device.

Create new Watch table in order to


control/monitor commissioning.
© Siemens AG 2021 All rights reserved

From each Control DB


select .execute, .busy, .done, .error
and .status variables.

Select the PLC device and compile


the project.

During compilation you might face


the warning message informing
about same numbering of some
blocks. It can be easily resolved by
a click on Yes button.

SINAMICS G120X: Basic Setup Add-in


Entry-ID: 109792547, V1.2, 04/2021 20
4 Application example

After the successful compilation


save the TIA Portal project.

Download the project to PLC.

Select the slot “1 X1” on PLC side.

Start search for target device and


© Siemens AG 2021 All rights reserved

select the PLC CPU.

Press the Load button.

Confirm loading…

… After loading select the action


Start module and Finish.

Since now the commissioning data


are stored locally on PLC and you
can perform commissioning both
Democases anytime when
needed…

SINAMICS G120X: Basic Setup Add-in


Entry-ID: 109792547, V1.2, 04/2021 21
4 Application example

In TIA Portal select PLC device


and Go online.

The statuses should signalize OK.

Select the Watch table_1 and click


on Monitor all.

Toggle the value of .execute


variable to 1 (TRUE) and wait until
the acyclic jobs perform the
parametrizing of the first drive.
© Siemens AG 2021 All rights reserved

Then repeat the same for the other


drive.

You should have both .done


variables now set to 1 (TRUE)
which indicates both drives are
parametrized.

Before you save the project in TIA


Portal, manually reset all .execute
variables to 0 (FALSE).

Congratulations, you are done!


Both drives are now parametrized.
On the next RUN command each
drive will perform Stationary ID
test. Then it will be ready for
operation.

SINAMICS G120X: Basic Setup Add-in


Entry-ID: 109792547, V1.2, 04/2021 22
5 Appendix

5 Appendix
5.1 Service and support
Industry Online Support
Do you have any questions or need assistance?
Siemens Industry Online Support offers round the clock access to our entire
service and support know-how and portfolio.
The Industry Online Support is the central address for information about our
products, solutions and services.
Product information, manuals, downloads, FAQs, application examples and videos
– all information is accessible with just a few mouse clicks:
support.industry.siemens.com

Technical Support
The Technical Support of Siemens Industry provides you fast and competent
support regarding all technical queries with numerous tailor-made offers
– ranging from basic support to individual support contracts.
Please send queries to Technical Support via Web form:
support.industry.siemens.com/cs/my/src
© Siemens AG 2021 All rights reserved

SITRAIN – Digital Industry Academy


We support you with our globally available training courses for industry with
practical experience, innovative learning methods and a concept that’s tailored to
the customer’s specific needs.
For more information on our offered trainings and courses, as well as their
locations and dates, refer to our web page:
siemens.com/sitrain

Service offer
Our range of services includes the following:
• Plant data services
• Spare parts services
• Repair services
• On-site and maintenance services
• Retrofitting and modernization services
• Service programs and contracts
You can find detailed information on our range of services in the service catalog
web page:
support.industry.siemens.com/cs/sc

Industry Online Support app


You will receive optimum support wherever you are with the "Siemens Industry
Online Support" app. The app is available for iOS and Android:
support.industry.siemens.com/cs/ww/en/sc/2067

SINAMICS G120X: Basic Setup Add-in


Entry-ID: 109792547, V1.2, 04/2021 23
5 Appendix

5.2 Industry Mall

The Siemens Industry Mall is the platform on which the entire siemens Industry
product portfolio is accessible. From the selection of products to the order and the
delivery tracking, the Industry Mall enables the complete purchasing processing –
directly and independently of time and location:
mall.industry.siemens.com

5.3 Links and literature


Table 5-1
No. Topic
\1\ Siemens Industry Online Support
https://support.industry.siemens.com
© Siemens AG 2021 All rights reserved

\2\ Link to this entry page of this application example


https://support.industry.siemens.com/cs/ww/en/view/109792547
\3\ Add-In "EditParametersinSeveralDrives"
https://support.industry.siemens.com/cs/ww/en/view/109777633

5.4 Change documentation


Table 5-2
Version Date Modifications
V1.0 01/2021 First version
V1.1 02/2021 Change in example description in chapter 4.2, page 22
V1.2 04/2021 Changed chapter 3.1 Add-ins installation

SINAMICS G120X: Basic Setup Add-in


Entry-ID: 109792547, V1.2, 04/2021 24