Blu 3000.1 4000.1 Pre 2017 en
Blu 3000.1 4000.1 Pre 2017 en
com
Technical data
Operating instructions
Electric diagrams
28-08-2017
EN
INDEX
Burner description 5
Electrical control panel 5
Gas train - Kit - Accessories: assembly to the burner 6
Technical data 7
Gas category by country 7
Working diagrams 8
Test boiler - Flame dimension 8
Overall dimensions 9
Gas operating mode - General safety functions 10
Installation 11
Fitting the burner to the boiler 11
Gas line 12
Kit and accessories connection - Head loss diagram 13
Pressure loss diagrams 14
Electrical connections 16
Start-up 19
Adjusting the max air flow rate 19
Firing head setting 19
Servomotor pre-setting 19
Adjusting the intermediate burner capacity 20
Pressure switch adjustment 20
Maintenance program 21
Troubleshooting instructions 23
Operating troubles 23
Appendix 23
Control box - Damper actuators 23
Electrical diagrams 24
Spare parts list 26
2 www.ecoflam-burners.com 420010829401
EN
!
BURNER SELECTION: Type of operation and configuration must be done by professional personnel in order to grant correct working of the
burner. Installation, start-up and maintenance must be carried out by authorised specialists and all applicable guidelines and regulations
(including local safety regulations and codes of practise) must be observed.
We accept no responsibility for Final delivery and instructions for use Notes for the operator
damage arising from:
The firing system installer must supply The system should be inspected by a
- inappropriate use; the operator of the system with operating specialist at least once a year.
- incorrect installation and/or repair on and maintenance instructions on or before Depending on the type of installation,
the part of the buyer or any third party, final delivery. These instructions should shorter maintenance intervals may be
including the fitting of non-original parts; be displayed in a prominent location at the necessary.
- non authorised modifications made point of installation of the heat generator, It is advisable to take out a maintenance
on the burner. They should include the address and contract to guarantee regular servicing.
telephone number of the nearest customer
service centre.
Ecoflam burners have been designed and built in compliance with all current regulations
and directives.
All burners comply to the safety and energy saving operation regulations within the standard
of their respective performance range. The quality is guaranteed by a quality and management
system certified in accordance with ISO 9001:2008.
420010829401 www.ecoflam-burners.com 3
EN
BURNER DESIGNATION
BLU 3000.1 PRE TC
MODEL SIZE
BLU 3000.1 3000 kW
EMISSIONS
Standard Class 2 - GAS EN676 (<120 mg/kWh)
LN Low NOx Class 3 - GAS EN676 (<80 mg/kWh)
OPERATION TYPE
PAB 2 stages soft start
PR 2 stages progressive mechanical
PRE 2 stages modulating electronic
HEAD TYPE
TC Short head
TL Long head
FUEL
Natural gas
LPG Liquid gas
BIOGAS Biogas
Gas burners
All gas burners are delivered in separate set/box, i.e. burner body including combustion
head and separate gas train with separate additional kit and accessories that shall
complete the gas train or the burner according to the applicable standard.
Kit and accessories are delivered separately.
All gas and dual fuel burners gas trains are delivered separately in different models and
configuration.
Export configuration gas train completion are available but it is mandatory for the local
installer in this case to comply to the local safety regulations.
For burners over 1700 kW gas train connection pipe must be ordered.
Kits and accessories are managed and delivered separately.
Component type
4 www.ecoflam-burners.com 420010829401
EN
BURNER DESCRIPTION
6 12
1
1
8
14
2
15
GTCP
LEGENDA 15. Air servomotor
1. Housing 19. Gas filter
2. Electrical control panel 20. Ball valve
3. Blower motor 23. Antivibration coupling
5. Hinge flange GTCP. Gas train connection pipe
19 6. Blast tube
7. Burner head
8. Burner fixing flange
9. Air flap regulation
23 12. Lifting eyebolts
14. Gas servomotor
20
Control panel
1 - Fuse
3
2 - Termal lock-out lamp
2
3 - Working lamp
1
I
4 - Main switch I / O
0 4 5 - Display
5
420010829401 www.ecoflam-burners.com 5
EN
BURNER DESCRIPTION
313 314
100
144
141
143 142 150
Gas
151 M
350
Ecoflam gas trains are delivered separately for all gas and dual fuel burners and are available in different configurations:
Double gas valves with actuators and regulator VGD Siemens and min pressure switch + ACS gas filter
VGD 20.503 Rp 2” / VGD 40.065 - 40.080 - 40.100 - 40.125 1. Main gas pipe
2. Ball valve ACS
3. Antivibration coupling ACS
7 6
5. Min gas pressure switch
EXPORT
6. Safety gas valve + 10. Actuator GAS TRAIN
EN676
7. Working gas valve + 11. Actuator
8. Gas leakage control KITTC *
9. Gas filter ACS
1 2 3 9 5 8 11 10
KIT - MAX Gas pressure switch KITPRES
ACS - Gas train connection pipe GTCP **
! GTCP-...* WARNING: in order to fit the gas train, the corresponding connection pipe must be ordered (GTCP size and fitting depend on the
burner and the gas train selected).
HOW TO INSTALL THE GAS TRAIN INTO THE BURNER AND CALCULATE THE OVERALL DIMENSIONS:
refer to the dimension page and thE gas train manual for all detailed information
! WARNING: EN676 compulsory kit and accessories in order to comply to the safety regulations. Additional accessories and kits
shall be installed by the installer in accordance to the local safety regulations and codes of practise.
Gas governor / Filter Modulation Kit Max Pressure switch Other accessories
6 www.ecoflam-burners.com 420010829401
EN
TECHNICAL DATA
kW 3.000 3.900
Thermal power max.
kcal/h 2.580.000 3.354.000
kW 630 875
Thermal power min.
kcal/h 541.800 752.500
Fuel Type G20 (L.C.V. 8.570 kcal/Nm3), G25 (L.C.V. 7.370 kcal/Nm3)
Gas connection GTCP Gas connection range RP50 to DN100 depending on the gas train selected
420010829401 www.ecoflam-burners.com 7
EN
WORKING DIAGRAMS
mbar 25
Calculation of
burner output
QF = Burner output (kW)
QN = Rated boiler output(kW)
20
η = Boiler efficiency (%)
QF = QN x 100
η
15
BLU 4000.1
Working diagrams
The working diagram shows
10 burner output as a function of
BLU 3000.1 combustion chamber pressure.
It corresponds to the maximum
values specified by EN 676
5 measured at the test fire tube.
Boiler efficiency should be
taken into consideration when
selecting the burner.
0
0 1000 2000 3000 4000 5000 6000 kW
0 1000 2000 3000 4000 5000 kcal/h*1000
FLAME LENGHT GAS BURNERS The burner/boiler matching does not pose
L (m) 11
any problems if the boiler is CE type-
10 approved.
9
If the burner must be combined with a
boiler that has not been CE type-approved
8
and/or its combustion chamber dimensions
7 are clearly smaller than those indicated in
6 diagram, consult the manufacturer.
5
The firing rates were set in relation to
special test boilers, according to EN676 -
4
EN267 regulations.
3
0
The sizes are indicative and dipend on
kcal/h
1000 2000 3000 4000 5000 6000 7000 8000 9000 10000 11000 12000 13000 14000 15000
x 1000 the configuration, to the combustion
1000 2000 3000 4000 5000 6000 7000 8000 9000 10000 11000 12000 13000 14000 15000 16000 17000 kW
chamber pressure and to the draught.
100 200 300 400 500 600 700 800 900 1000 1100 1200 1300 1400 1500 1600 1700 Nm3/h
The values have been taken out from
tests executed with flame tubes.
FLAME DIAMETER GAS BURNERS
Ø (m) 2 The dimensions of the flame are made
1,8
in test boiler in laboratory without
resistence therefore exists max and
1,6
min lenght that take into account the
1,4 difference in lenght that comes from the
1,2
boiler backpressure.
1
Example:
0,8
Burner thermal output = 8000 kW;
0,6 L flame (m) = 5 m (medium value)
0,4
D flame (m) = 1 m (medium value)
0,2
WARNING: Some flame modifications
0
1000 2000 3000 4000 5000 6000 7000 8000 9000 10000 11000 12000 13000 14000 15000
kcal/h can be done in our FLEXSHOP in the
x 1000
1000 2000 3000 4000 5000 6000 7000 8000 9000 10000 11000 12000 13000 14000 15000 16000 17000 kW
factory in order to shape the flame and
100 200 300 400 500 600 700 800 900 1000 1100 1200 1300 1400 1500 1600 1700 Nm3/h adapt it to some special boiler
or application.
8 www.ecoflam-burners.com 420010829401
EN
OVERALL DIMENSIONS
A
E D - D1 B C
I
M
L
F
G
O
N
H1
D = Short head
D1= Long head
Dimensions (mm)
Model A B C D D1 E F G H1 I L M N O
BLU 3000.1 PRE 941 448 493 330 530 780 290 471 746 315 315 M16 195 250
BLU 4000.1 PRE 941 448 493 365 565 780 320 471 746 315 315 M16 195 250
Model X Y Z kg
BLU 3000.1 1580 1630 1090 230(241,2) Z
BLU 4000.1 1580 1630 1090 249,5
X Y
420010829401 www.ecoflam-burners.com 9
EN
GENERAL SAFETY FUNCTIONS the pre-ventilation phase (external light A voltage failure will result in a regular
control) will result in a shut-off on trouble shut-off of the burner. Upon voltage
In case a flame does not develop when with the automatic furnace controller being recovery there may be an automatic
starting the burner (fuel release) the locked. restart unless another interlock is
burner will shut off at the end of the safety provided, e.g. by the safety system. In any
period (shut-off on trouble). The trouble is indicated by the trouble case of trouble the fuel oil supply will be
A shut-off on trouble will also occur in the signal lamp lighting up. shut off right away. The program unit will
case of flame failure during operation, air The automatic furnace controller can be stop at the same time causing also the
flow failure during the pre-ventilation unlocked immediately after a shut-off on trouble location indicator to stop.
phase and pressure failure during the trouble by pressing the unlocking key. The The symbols will indicate the kind of
whole period of burner operation. program unit will return to its starting trouble.
Any failure of the flame signal at the end of position and proceed with the restart of the
the safety period and a flame signal during burner.
10 www.ecoflam-burners.com 420010829401
EN
INSTALLATION
! WARNING: handling and moving operations must be carried out by specialised personnel.
Use the eyebolts to lift the burner in order that it will not overturn and fall down.
Exhaust system A1
To avoid unfavourable noise emissions,
right-angled connectors should not be
used on the flue gas side of the boiler.
procedure.
B Ignition Electrode
Elettrodo di accensione
SECTION B-B
3. Check that the head is preset at 50%.
420010829401 www.ecoflam-burners.com 11
EN
INSTALLATION
Gas line
100 Burner
CONNECTION DIAGRAM FOR BURNERS WITH 120 Air damper
141 Ball valve
GAS TRAIN SIEMENS VGD... 142 Gas filter
143 Antivibration coupling
144 Gas governor
To be supplied by the installer 150 Throttle valve
151 Gas train SiemensVGD....
313 Min.gas pressure switch
314 Max.gas pressure switch (optional)
349 Air damper motor
350 Gas damper motor
313 314
100
144
141
143 142 150
Gas
151 M
350
GAS CONNECTION PRESSURE Take care to observe the correct order of VENTING
A minimum connection pressure must be installation and direction of flow (arrow on Prior to taking the burner into operation or
available upstream of the burner gas valve housing). after any repair work make sure to vent the
to ensure the proper functioning of the Check the valves and instruments and complete gas feed line and the gas valves
burner. connection pieces for absence of dirt and instruments group into the open
WARNING: the total gas pressure loss particles and foreign matter before atmosphere (e.g. by means of a hose)
must always be smaller than the available installation and initial operation. To provide taking care to avoid any hazards.
gas flow pressure. effective conditions for start-up make sure In no case should the gas line be vented
For the installation of the valves and the distance between the burner and the into the heating or furnace chambers.
instruments group take care to observe the gas stop valve is as short as possible. Make use of a test burner to check the
mounting instructions supplied by their gas-carrying spaces are free from an
manufacturers (these are packed with the LEAK TEST inflammable gas mixture.
equipment). The gas line upstream of the burner gas
The gas line installed to the burner must valves and instruments group must be SUPPORT
be dimensioned in accordance with the installed in accordance with the applicable The valves and instruments group must be
throughput rate and the available regulations, checked for absence of leaks, supported with a telescopic jacking
pressure. vented and certified accordingly by the gas member or similar during and after
For selecting the nominal bore “DN” of the installation company. The screwed unions installation (e.g. on filter and valve).
gas valves and instruments group care and flanged joints must be checked for
should be taken to observe the flue proper tightness (by making a pressure JOINT
resistance of the boiler and the gas test). The leak test must be made under It is recommended to provide an easy to
pressure loss of the burner and valves and pressure using approved foaming agents disconnect joint (with planar sealing faces)
instruments group. which do not cause corrosion. For steam to facilitate repair work on the boiler
boiler furnaces the result of the leak test (furnace) and allow the boiler door to be
GAS VALVES AND INSTRUMENTS GROUP must be duly certified. swivelled out if required.
The gas valves and instruments group can
be connected directly to the gas feed line.
12 www.ecoflam-burners.com 420010829401
EN
INSTALLATION
KITPRES... Maximum pressure switch assembly
Modulation Kit Max Pressure switch
Maximum pressure switch is provided as a kit and
KITMD-RWF50 KITPRES50
shall be assembled into the main gas train
according to the instructions of the gas train Probe-... KITPRES150
separate manual.
diagrams. 13
12
BLU 3000.1
11
10
WARNING:
9
Note that the head loss diagram
8
is only indicative and does vary
7
depending on the setting of the head.
6
5
60 80 100 120 140 160 180 200 220 240 260 280 300 320 340 360 380 400
OUTPUT - Stm3/h
420010829401 www.ecoflam-burners.com 13
EN
INSTALLATION
! PRESSURE DROP includes: “COMBUSTION HEAD + GAS TRAIN + GAS GOVERNOR & FILTER” as per EN676 Standard.
Back pressure of boiler (or other applications) must be added/included in order to have the total min pressure drop.
60 180
150
50
140
pressure drop (gas train + firing head) mbar
120
40
110
90
VGD 40.080 + F- DN80
30
80 VGD 20.503
VGD 40.080
70
25
60
VGD 40.100 + F- DN100
20 50
VGD 40.100
40
15
30
20
10
10
5 0
100 150 200 250 300 350 100 150 200 250 300 350
1C 1C.2
flow m3/h flow m3/h
LEGENDA
Pf: Back pressure of furnace
Pb: Pressure of burner (combustion head + complete gas train)
Pin: Minimum inlet pressure
14 www.ecoflam-burners.com 420010829401
EN
INSTALLATION
! PRESSURE DROP includes: “COMBUSTION HEAD + GAS TRAIN + GAS GOVERNOR & FILTER” as per EN676 Standard.
Back pressure of boiler (or other applications) must be added/included in order to have the total min pressure drop.
170
150
140
120
110
100
90 VGD 40.065 + F- DN 65
80
VGD 40.065
70
60
50 VGD 40.080 + F- DN 80
40 VGD 40.080
10
0
200 250 300 350 400 450
2C
flow m3/h
LEGENDA
Pf: Back pressure of furnace
Pb: Pressure of burner (combustion head + complete gas train)
Pin: Minimum inlet pressure
420010829401 www.ecoflam-burners.com 15
EN
INSTALLATION
Electrical connections
! WARNING: Electrical wiring must be carried out with electrical supply disconnected and with burner switch in position OFF.
Electrical supply must correspond to the one shown on the burner label.
dimension the suitable input power and electric box of the motor, from star to delta QAE...
16 www.ecoflam-burners.com 420010829401
EN
CHECKS BEFORE COMMISSIONING: GAS START-UP Prior to the initial fuel feed start make
a functional test of the burner program
• That the burner is assembled in • Connect the measuring instruments for flow:
accordance with the instructions given the gas head pressure on the test
here. connection downstream of the gas damper Gas system:
• Setting the combustion components. and the air pressure on the burner test • Shortly open the gas shut-off valve
• All electrical connections must be correct. connection. before the gas train until pressure is
• Check the burner motor for correct • Open the gas shut-off valve before the available and close again.
direction of rotation. gas-armatures and test the gas pressure • Start burner and check program flow for
• The heat generator must be ready for on the pressure gauge correct start-up sequence:
operation, and the operating regulations • Set the “Manual-Automatic” selector 1. Fan.
for the heat generator must be observed. switch to “Manual”. 2. Pre-ventilation damper.
• The heat generator and heating system 3. Check air pressure.
must be filled with water and the If the gas valves are tested for absence of 4. Partial-load damper.
circulating pumps must be in operation. leaks, this should be continued until a 5. Ignition.
• The temperature regulator, pressure positive result is obtained. If a valve is 6. Valves open.
regulator, low water detectors and any found to leak, the program will not step 7. The burner will either stop as the gas
other safety or limiting devices that might forward to the control box. valves open (due to gas pressure
be fitted must be connected and The burner will start according to the decrease) or lock out at the end of the
operational. program flow of the control box. safety time.
• The exhaust gas duct must be • Unlock the control box.
unobstructed and the secondary air
system, if available, must be operational.
• An adequate supply of fresh air must be
guaranteed.
• Make a test of the all gas-carrying
elements for absence of leaks.
• With burner in starting position check that
air damper is in “CLOSED” position.
• Check that control box is unlocked and in
its original position.
• A standard-compliant measuring point
must be available, the exhaust gas duct up
to the measuring point must be free of
leaks to prevent anomalies in the
measurement results.
420010829401 www.ecoflam-burners.com 17
EN
Recommended Recommended WARNING: if the installation is above sea level the output of the burner
Fuel (%) CO2 (%) O2 vary base on the diagram.
Natural gas 10 ÷ 9 3,1 ÷ 4,8 The regulation of the burner in this case shall take into account the
reduced power of the burner due to the missing air.
Light oil 13 ÷ 11,5 3,3 ÷ 5,3
18 www.ecoflam-burners.com 420010829401
EN
START-UP
Select the gas operation in order to proceed with start up on the gas side. On the selector put the operation on minimum capacity.
MAIN SWITCH
SAL ! KMV contactor: check the air fan motor rotation.
If not correct invert the two phases on the power supply.
0 - OFF
0 1
1 - ON KMV
Air and Gas adjustment are accomplished through LAMTEC pa- The firing head is pre-adjusted at the 50% from the factory. The
rameters setting. Refer to LAMTEC manual attacched. setting fully open enables to reach the full power of the burner
and full close to reach the minimum power of the burner.
The optimal position depends on the output that we need to
reach but the default setting shall be modified only when you are
not able to reach the suggested combustion value by adjusting
the air flow in the maximum flame.
+
-- +
–
B
Air adjustment is accomplished through LAMTEC parameters setting. Refer to LAMTEC manual
attacched.
420010829401 www.ecoflam-burners.com 19
EN
START-UP
WARNING: the variable profile of the cam shall have a normal proportional
curvature in order to have good combustion values and reduce its mechanical stress breakdown.
on the low flame by slowly turning the relative knob clockwise until the burner locks out.
2,4
3,0
2,1
1,8
Read the value and then decrease it by 15%. D
1,5
Set the pressure switch to the minimum by turning knob D to position 1. C 0,4
1,2
0,6
0,9
Start the burner and keep in low flame running, while checking that combustion is
correct. Through a small cardboard, progressively obstruct the air intake until to obtain a A
CO2 increase of 0,5÷0,8% or else, if a pressure gauge is available, connected to
pressure port E, until reaching a pressure drop of 1 mbar (10 mm of W.G.). B
Slowly increase the adjustment value of the air pressure switch until to have the burner
lockout. Remove the obstruction from the air intake, screw on the cover C and start the Gas pressure switch
burner by pressing the control box rearm button.
WARNING: the air pressure switch shall prevent the air pressure to go below 80% from 45
40
50
35
the adjustment value in order to prevent the CO in the fumes to exceed 1% (10000 ppm).
30
N
25
Using the analyser try to close the air inlet and check that the burner locks out before M
2,5
5
20
10
15
20 www.ecoflam-burners.com 420010829401
EN
MAINTENANCE PROGRAM
!
Burner and boiler servicing must only be carried out by authorised and qualified personnel at least once a year.
Depending on the type of installation, shorter maintenance intervals may be necessary.
The system operator is advised to take out a maintenance contract to guarantee regular servicing.
WARNING: Use original spare parts.
SAFETY WARNINGS:
1. Turn off the power supply and protect the system from accidental start-up MAIN SWITCH
2. Cut gas supply SAL
3. Make sure there is no residual power in the system and that the actions in points 1 0 - OFF
and 2 have been completed. 0 1
4. Before opening the burner casing, ensure that the fan motor has stopped completely 1 - ON
Failure to observe any of these instructions will result in the risk of death or injury!
NOTES ON REASSEMBLING: Perform the described step in reverse order and make sure to refit components
as they were originally assembled and the system is free from leaks. Use only original spare parts.
qA = exhaust gas loss [%] The exhaust gas loss can be calculated The exhaust gas loss can be calculated
tA = exhaust gas temperature [°C] as follows: as follows:
tL = combustion air temperature [°C]
CO2 = volumetric content of carbon 0,37 0,49
dioxide [%] qAf = (195-22)( + 0,009) = 7,48% qAf = (195-22)( + 0,007) = 7,83%
10,8 12,8
420010829401 www.ecoflam-burners.com 21
EN
MAINTENANCE PROGRAM
REMOVING REMOVING
THE BLAST TUBE THE FIRING HEAD
ATTENTION:
Check the position of the electrodes after any intervention as wrong position could cause ignition troubles.
B
59 mm SECTION A-A
Elettrodo di rivelazione
Ionization Probe
14 mm
A A
20 mm
3 mm
B Ignition Electrode
Elettrodo di accensione
SECTION B-B
22 www.ecoflam-burners.com 420010829401
EN
TROUBLESHOOTING INSTRUCTIONS
For Setting and Error Lists refer to LAMTEC manual attacched.
OPERATING TROUBLE
In case of operating trouble it should be 3. Proper functional order and setting of all Proceed with searching for the cause of
checked whether the system is in proper control and safety instruments such as the trouble and eliminate it. Unlock the
working order. temperature controller, safety limiter, water control box by pressing the fault eliminate
failure cut-out, electrical limit switches, etc. key and start the burner.
Make a check for the following: If the trouble is not found to be due to any Do not press the fault eliminate key longer
1. Availability of fuel. of the above-mentioned points it will be than 10 seconds.
Availability of gas in the line at sufficiently necessary to test the burner functions very The start-up program will be initiated and
high pressure. carefully. should be carefully monitored.
Availability of fuel oil in the tank (for dual The possible cause of the fault may be
fuel burner). Prevailing conditions: quickly found by reference to the fault
Correct position of fuel selector switch. The burner will be found to be out of indicator of the control box and watching
2. Availability of electric power in the operation and in faulty and interlocked the start-up and operating program.
burner system. position.
APPENDIX
1 Display
2 Back key Jump to previous window.
1 2 3 4 3 Cursor keys
4 Enter key You navigate in the menu using
cursor keys. You use ’left’ and ’right’
Display keys to move step by step in a
The display shows in pictogram: selected row. At the end of the
• the menu structure selected row the cursor jumps
• operating status down to the next row, if possible.In
• parameters a multiline menu use ’up’ and
• error messages ’down’ keys to switch to other
rows.To display parameters, switch
between various fields.
!
in the menu window. Transfer
Always switch off the power supply before installing or removing the control unit. setting values by pressing ENTER
Do not attempt to open or carry out repairs on the control unit. key in a parameter window.Use a
flushing, red ENTER key to release
Refer to LAMTEC manual attacched.
a fault interlocker.If the ENTER key
is permanently lit red, a fault with
an automatic restart is displayed.
420010829401 www.ecoflam-burners.com 23
EN
24
1 2 3 4 5 6 7 8
A A
APPENDIX
Servomotore Aria
Electrical diagrams
Air Servomotor
STE
1 2 3 4 5 6 1 2 3
4 5 6
LAMTEC DISPLAY 7 8 9
B B
1 1 1 1 1 1 1 1 1 1 10 11 12
X10 X09 X08 X07 X06 X05 X04 X03 X02 X01
6
Maschio
www.ecoflam-burners.com
4
X30
1
X31
1 3 2 1
LAMTEC
6 6 5 4
X32
BurnerTronic BT 3XX 9 8 7
1
12 11 10
6
X33
HLBT
1 97 HLF Femmina L1 N T1 T2 S3
FMV
98
C ER C
X20 X21 X22 X23 X24 X25 X26 PE
1 1 1 1 1 1 1
L1 N T1 T2 S3
2 1 3 SPGmin/c.t
1 2 3 4 5 6
95
SPA YVGS
STE YVG
T T
P P
R S T NO FMV TV
KMV 96
LOAD
Z
FMV LINE
D Servomotore Gas D
Gas Servomotor
FU
BY TERM LAWS WE RESERVED THE PROPERTY OF THIS WIRING DIAGRAM WITH PROHIBITION OF USE AND REPRODUCTION
SAL
MV U V W
M
3
R S T N 1 2 3 4 5 6 7 8 9 10 11 12 13 25 26
Q
E E
HLF
50 Hz 400V HLB STAB STC STS
T T T
P P P
PE
R
S
T
N
420010829401
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
420010829401
FU FUSIBILE HLF LAMPADA DI FUNZIONAMENTO
FUSE WORKING LAMP
FUSIBLE LAMPE DE FONCTIONNEMENT
FUSIBLE ESPIA DE FUNCIONAMIENTO
MV MOTORE VENTILATORE
MOTOR FAN
MUTEUR VENTILATEUR
MOTOR VENTILADOR
B TV TRASFORMATORE B
IGNITION TRANSFORMER
TRANSFORMATEUR D'ALLUMAGE
TRANSFORMADOR
ER ELETTRODO DI RIVELAZIONE
IONISATION PROBE
ELECTRODE D'IONISATION
ELECTRODO DE IONIZACION
FMV RELE' TERMICO MOTORE VENTILATORE
MOTOR THERMAL RELAY (FAN MOTOR)
RELAIS THERMIQUE MOTEUR VENTILATEUR
RELE' TERMICO MOTOR VENTILADOR
HLB LAMPADA DI BLOCCO
LOCK-OUT LAMP
C LAMPE DE SECURITE C
ESPIA DE BLOQUEO
KMV CONTATTORE MOTORE VENTILATORE
REMOTE CONTROL SWITCH (FAN MOTOR)
CONTACTEUR MOTEUR VENTILATEUR
TELERRUPTOR MOTOR VENTILATOR
SAL INTERRUTTORE DI LINEA
WORKING SWITCH
INTERRUPTEUR DE LIGNE
INTERRUPTOR DE LINEA
SPA PRESSOSTATO ARIA
AIR PRESSURE SWITCH
PRESSOSTAT AIR
PRESOSTATO AIRE
D D
STC TERMOSTATO CALDAIA
BOILER THERMOSTAT
BY TERM LAWS WE RESERVED THE PROPERTY OF THIS WIRING DIAGRAM WITH PROHIBITION OF USE AND REPRODUCTION
THERMOSTAT CHAUDIERE
TERMOSTATO CALDERA
STS TERMOSTATO DI SICUREZZA
SAFETY THERMOSTAT
THERMOSTAT DE SECURITE
TERMOSTATO DE SEGURIDAD
HLBT LAMPADA DI BLOCCO TERMICO
THERMAL LOCK-OUT LAMP
LAMPE DE THERMAL DE SECURITE
ESPIA DE BLOQUEO RELE TERMICO
STAB TERMOSTATO DI ALTA-BASSA FIAMMA
E HIGH-LOW FLAME THERMOSTAT E
THERMOSTAT GRANDE-PETIRE ALLURE
TERMOSTATO DE ALTA-BAJA LLAMA
YVG ELETTROVALVOLA GAS DI PRIMA FIAMMA
FIRST STAGE GAS SOLENOID VALVE
ELECTROVANNE GAZ PETITE ALLURE
ELECTROVALVULA GAS DE 1^ LLAMA
www.ecoflam-burners.com
1 2 3 4 5 6 7 8
25
EN
EN
26
Blu 3000.1 PRE
Blu 4000.1 PRE 34
32
APPENDIX
33
4
27
26
www.ecoflam-burners.com
24
25 30
28
35 29
7
15
36 5
14 40
38
16 BT3xx
17
39 1
6 37
13
3 12
8
9
10
20 2 11
21
I
18 0
420010829401
37
EN
APPENDIX
420010829401 www.ecoflam-burners.com 27
Ecoflam Bruciatori S.p.A.
Via Roma, 64 - 31023 Resana (TV) - Italy
Tel. +39 0423 719500
Fax +39 0423 719580
http://www.ecoflam-burners.com
e-mail: [email protected]
Società soggetta alla direzione e al coordinamento di Ariston Thermo S.p.A.
Via A. Merloni, 45 - 60044 Fabriano (AN) - CF 01026940427
Ecoflam Bruciatori S.p.A. reserves the right to make any adjustments, without prior notice, which is considered necessary
or useful to its products, without affecting their main features
Ecoflam Bruciatori S.p.A. si riserva il diritto di apportare ai prodotti le modifiche che riterrà necessarie o utili, senza
pregiudicarne le caratteristiche principali.
La maison Ecoflam Bruciatori S.p.A. se réserve le droit d’apporter les modifications qu’elle jugera nécessaires ou utiles
à ses produits sans pour autant nuire à leurs caractéristiques principales
Ecoflam Bruciatori S.p.A. se reserva el derecho a introducir en sus productos todas las modificaciones que considere
necesarias o utiles, sin prejudicar sus caracteristicas
“Ecoflam Bruciatori S.p.A.” оставляет за собой право вносить в конструкцию оборудования любые необходимые
изменения без особого предупреждения