Exp 1
Exp 1
A Lab Report
submitted in partial fulfillment of the
requirements of the coursework for
Power Engineering Lab(ELP303)
Submitted by:
Shubham Kumar(2020EE30627)
Kushagr Goyal(2021EE10634)
Pramsu Shrivastava(2021EE10140)
Aniket Abhiraj(2021EE10676)
1 Objective
To determine experimentally the positive, negative and zero sequence reactance of a syn-
chronous machine.
2 Theory
2.1 Symmetrical Components
When a synchronous generator is carrying an unbalanced load its operation may be analyzed
by symmetrical components. In a synchronous machine, the sequence current produces an
armature reaction which is stationary with respect to reactance and is sta- tionary with respect
to field poles. The component currents therefore encounter exactly same as that by a balanced
load as discussed. The negative sequence is produced and armature reaction which rotates
around armature at synchronous speed in direction to that of field poles and therefore rotates
part the field poles at synchronous speed. Induc- ing current in the field damper winding
and rotor iron. The impedance encountered by the negative sequence is called the negative
sequence impedance of the generator. The zero sequence current produce flux in each phase
but their combined armature reaction at the air gap is zero. The impedance encountered by
their currents is therefore different from that encountered by positive and negative sequence
components and is called zero sequence impedance of generator.
E
The saturated value of synchronous impedance at an excitation current ie is given by ISC where
E is the rated value of induced emf at an excitation current of rated current and ISC is the three-
phase short circuit current at the same excitation current. If the positive-sequence resistance
is neglected the positive-sequence reactance is same as the positive-sequence impedance.
X d + Xq
X2 =
2
V2
Z2 =
I2
where,
V2 = Applied terminal voltage per phase
P2 = Power input per phase
I2 = Current flowing per phase
X2 = Z2 sinϕ where ϕ = arccos( VP2 2I2 )
The circuit diagram for this method is given below:
where,
V0 = Applied voltage across the three phase winding in series
I0 = Currents flowing in the three phase winding in series
If the zero sequence resistance is neglected then the zero-sequence reactance X0 equals the zero
sequence impedance Z0 .
The circuit implemented is shown below:
The synchronous machine is run at rated speed. A voltmeter is connected across the machine
terminals and an ammeter is attached to measure the field excitation current of the DC winding.
The exciting current is varied to gather different observation points.
The synchronous machine is run at rated speed. We connected a high resistance rheostat in
the field circuit with full field voltage applied. An ammeter is connected in the field circuit.
We apply three-phase short circuit at the synchronous machine terminals with the ammeter
connected in any phase and measure the short circuit current corresponding to the field current
given by the ammeter reading.
3.3.1 Method I
We short circuit the field winding and run the machine at rated speed. Low voltage is applied
from the three-phase variac to the armature terminals with the phase sequence of the machine
and supply reversed with respect to each other. It is noted that the armature current given by
the ammeter reading should not exceed the rated value.
V2 I2
24.9 1
35.35 1.5
44.4 2
53.2 2.5
61.5 3.0
69.7 3.5
78.2 4
3.3.2 Method II
We run the machine at rated speed and short circuit two phases of the alternator through an
ammeter. The voltage coil of the wattmeter is connected along with a volt- meter between the
open phase and any short circuited phase. We gradually increase the excitation such that the
short circuit current doesn’t exceed the full load value.
VOS ISC
11.61 1
17.21 1.5
23.1 2.0
27.95 2.5
32.3 3
37.74 3.5
42.05 4
We connect the armature winding in parallel with proper polarity. The field winding is short
circuited and the machine is run at rated speed. We apply a low voltage from the variac and
measure both voltage and current taken by the armature winding.
V0 I0
2.36 1.2
2.86 1.5
4.41 2.25
5.01 2.6
5.71 3.05
6.35 3.4
6.96 3.75
7.61 4.1
4 Graphs
4.1 Determining positive sequence reactance X1
4.1.1 Open Circuit test
Open Circuit Voltage vs Excitation Current
5 Calculations
5.1 Calculating positive sequence reactance X1
Ie E ISC X1 = E/ISC
0.1 100.8 1.35 74.66
0.2 206.6 2.45 84.32
0.3 283.2 3.65 77.59
0.4 326.9 4.15 78.77
The average of all the readings is taken. The positive sequence impedance X̂1 is 78.83 Ω.
V2 I2 Z2 = V2 /I2
24.9 1 24.9
35.35 1.5 23.56
44.4 2 22.2
53.2 2.5 21.28
61.5 3.0 20.5
69.7 3.5 19.91
78.2 4 19.55
5.2.2 Method II
VOS
VOS ISC Z2 = 3I SC
11.61 1 3.87
17.21 1.5 3.82
23.1 2.0 3.85
27.95 2.5 3.73
32.3 3 3.59
37.74 3.5 3.59
42.05 4 3.50
V0
V0 I0 Z0 = 3I 0
2.36 1.2 0.65
2.86 1.5 0.63
4.41 2.25 0.65
5.01 2.6 0.64
5.71 3.05 0.62
6.35 3.4 0.62
6.96 3.75 0.62
7.61 4.1 0.62
6 Conclusion
The different parts of the experiment are very helpful in determining the three se- quence
impedances of the synchronous machine as well as the graphs plotted show us the nature of the
device.
We determined from the open circuit test and short circuit test the value of positive sequence
impedance as 78.83 Ω. Also, the curves plotted for open circuit test has a increasing trend
which saturates at high field current. Also, the curve does not start at origin since there is
residual magnetism even at zero field current. The curve for short circuit test is linear with the
field current.
We employed two methods for determining the negative sequence impedance. The value of
negative sequence impedance obtained from first method is 21.7 Ω, while that obtained from
second method is 3.7 Ω. In both the methods, we observe that the trend-line of the V vs I
graph plotted from the data values observed are approximately linear.
Finally, from the last subpart of the experiment, we obtain the zero sequence impedance as
0.63 Ω. Here also, we obtain a linear graph of V vs I from the observed data values. The linear
graphs for V vs I show that the experimental values are closely matching with Ohm’s law. All
the graphs match with the theoretical expectations.
7 Quizzes
7.1 Pre-Experiment Quiz
1. What do you understand by the term phase sequence?
Phase sequence refers to the order in which the voltage waveforms of a multi-phase al-
ternating current (AC) system reach their peak values within each cycle. Phase sequence
is crucial in applications where the direction of rotation is important, such as in motors.
Incorrect phase sequence can lead to motors running in the wrong direction, potentially
causing equipment damage or safety hazards.
6. Explain how double frequency currents are produced in the rotor field when
negative-sequence currents are impressed on the armature. mpressing negative-
sequence currents on the armature of a three-phase AC induc- tion motor generates a
reverse-rotating magnetic field in the stator. This, in turn, induces double frequency
currents in the rotor due to the interaction between the rotor and stator fields, leading
to potential issues like increased losses, heating, and mechanical stress.
7. If rotor is at stand still, what will be the frequency of rotor field currents when
(a) positive-sequence currents are impressed (b) negative-sequence currents
are impressed?
When the rotor is at a standstill in a three-phase AC induction motor, the rotor field
currents will have specific frequencies depending on whether positive-sequence or negative-
sequence currents are impressed:
(a) If positive-sequence currents are impressed while the rotor is at a standstill, the
frequency of the rotor field currents will be the same as the frequency of the applied
11. Define positive, negative, and zero sequence components of a set of unbal-
anced three phasors?
Any unbalanced three phasors can be broken down into positive, negative and zero se-
quence components. The unbalanced phasors are replaced by the balanced, positive set
and a symmetrical balanced negative sequence set and a single phase zero sequence set.
This helps to simplify calculations.
(a) Positive sequence have 3 phasors with equal magnitude and phase shifted by ̸ 120◦ .
(b) Negative sequence have 3 phasors with equal magnitude and phase shifted by ̸ 120◦ .
(c) Zero sequence have 3 phasors with equal magnitude and parallel to each other.
2. Does the positive-sequence impedance determined from O.C.C and S.C.C ap-
ply to the steady state condition or transient condition?
The positive-sequence impedance determined from open-circuit (OCC) and short- circuit
(SCC) tests applies only to the steady-state condition. This is because both OCC and
SCC tests are performed under steady-state conditions. The voltage and current values
measured are steady-state values and subsequently the calculated impedance is also for
steady-state only.
4. For the zero-sequence reactance if the windings are connected in parallel, will
the results so obtained be correct?
No, the results obtained will not be correct as the zero-sequence reactance of a winding
cannot be determined by connecting the windings in parallel. This is be- cause the
zero-sequence current does not flow through the windings in parallel. The zero-sequence
current flows through each winding individually, and the reactance of each winding is
therefore different.
6. How would you connect the sequence network for a single line to ground fault
on the armature?
In case of an LG fault, sequence network is obtained by connecting positive, negative and
zero sequence networks in series.
7. If the three-phase generated emfs are balanced, will you obtain negative se-
quence voltage in the network under unsymmetrical fault condition?
Yes, under unsymmetrical fault conditions, even if the three-phase generated electro-
motive forces (emfs) are balanced, you can still obtain negative-sequence voltage in the
network. This is because negative-sequence voltage is a result of the phase shift between
the voltages of the three phases during unbalanced conditions, regardless of whether the
emfs are initially balanced or not.
8. What is the relationship between positive, negative, and zero sequence cur-
rents in case of a single line to ground fault for an unloaded alternator solidly
grounded?
In case of a single line to ground fault for an unloaded alternator solidly grounded, the
positive, negative, and zero sequence currents are all equal.
8 Precautions
1. One must always take a note of the rated machine values and never exceed them while
performing the experiment.
2. One must ensure that all the connections are tight and have been verified properly before
powering on the circuit.
3. One must wear proper clothes, shoes and handle the electrical outlets with care.