Annex 2 Control Building Lighting Calculation Report

Uploaded by

rs as
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
8 views

Annex 2 Control Building Lighting Calculation Report

Uploaded by

rs as
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 213

Date 26-06-2024

WAVE C1 CONTROL BUILDING

Created with DIALux


WAVE C1 CONTROL BUILDING

Table of Contents

Cover . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1. . . . . . . . . . . . . . . . . . . . . . . . . . . .
Table of Contents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2. . . . . . . . . . . . . . . . . . . . . . . . . . . .
Luminaire list . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7. . . . . . . . . . . . . . . . . . . . . . . . . . . .

WAVE C1 _CONTROL BUILDING - Ground Floor

Storey 1
Room list / 3. ESCAPE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8. . . . . . . . . . . . . . . . . . . . . . . . . . .

WAVE C1 _CONTROL BUILDING - Ground Floor - Storey 1

DCS SERVER ROOM


Summary / 1. NORMAL LIGHT SCENE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 .............................
Summary / 2. EMERGENCY LIGHT SCENE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15 .............................
Summary / 3. ESCAPE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17 .............................
Luminaire layout plan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19 .............................
Calculation objects / 1. NORMAL LIGHT SCENE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22.............................
Calculation objects / 2. EMERGENCY LIGHT SCENE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
24............................

WAVE C1 _CONTROL BUILDING - Ground Floor - Storey 1

DCS UPS ROOM


Summary / 1. NORMAL LIGHT SCENE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26 .............................
Summary / 2. EMERGENCY LIGHT SCENE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .............................
28
Summary / 3. ESCAPE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30. . . . . . . . . . . . . . . . . . . . . . . . . . . .
.
Luminaire layout plan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .............................
32
Calculation objects / 1. NORMAL LIGHT SCENE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .35.............................
Calculation objects / 2. EMERGENCY LIGHT SCENE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
37 ............................

WAVE C1 _CONTROL BUILDING - Ground Floor - Storey 1

KITCHEN
Summary / 1. NORMAL LIGHT SCENE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39 .............................
Summary / 2. EMERGENCY LIGHT SCENE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .............................
41
Summary / 3. ESCAPE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43. . . . . . . . . . . . . . . . . . . . . . . . . . . .
.
Luminaire layout plan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .............................
45
Calculation objects / 1. NORMAL LIGHT SCENE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .47.............................
Calculation objects / 2. EMERGENCY LIGHT SCENE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
49 ............................
WAVE C1 CONTROL BUILDING

Table of Contents

WAVE C1 _CONTROL BUILDING - Ground Floor - Storey 1

TOILET FEMALE
Summary / 1. NORMAL LIGHT SCENE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51 .............................
Summary / 2. EMERGENCY LIGHT SCENE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .............................
53
Summary / 3. ESCAPE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55. . . . . . . . . . . . . . . . . . . . . . . . . . . .
.
Luminaire layout plan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .............................
57
Calculation objects / 1. NORMAL LIGHT SCENE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .59.............................
Calculation objects / 2. EMERGENCY LIGHT SCENE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
61 ............................

WAVE C1 _CONTROL BUILDING - Ground Floor - Storey 1

BATTERY ROOM
Summary / 1. NORMAL LIGHT SCENE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63 .............................
Summary / 2. EMERGENCY LIGHT SCENE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .............................
65
Summary / 3. ESCAPE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67. . . . . . . . . . . . . . . . . . . . . . . . . . . .
.
Luminaire layout plan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .............................
69
Calculation objects / 1. NORMAL LIGHT SCENE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .72.............................
Calculation objects / 2. EMERGENCY LIGHT SCENE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
74 ............................

WAVE C1 _CONTROL BUILDING - Ground Floor - Storey 1

CLEAN AGENT CYLINDER ROOM


Summary / 1. NORMAL LIGHT SCENE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76 .............................
Summary / 2. EMERGENCY LIGHT SCENE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .............................
78
Summary / 3. ESCAPE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80. . . . . . . . . . . . . . . . . . . . . . . . . . . .
.
Luminaire layout plan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .............................
82
Calculation objects / 1. NORMAL LIGHT SCENE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .85 .............................
Calculation objects / 2. EMERGENCY LIGHT SCENE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87 .............................

WAVE C1 _CONTROL BUILDING - Ground Floor - Storey 1

CONTROL ROOM
Summary / 1. NORMAL LIGHT SCENE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89 .............................
Summary / 2. EMERGENCY LIGHT SCENE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .............................
91
Summary / 3. ESCAPE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93.............................
Luminaire layout plan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .95
.............................
Calculation objects / 1. NORMAL LIGHT SCENE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .99 .............................
Calculation objects / 2. EMERGENCY LIGHT SCENE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101 ..............................
WAVE C1 CONTROL BUILDING

Table of Contents

WAVE C1 _CONTROL BUILDING - Ground Floor - Storey 1

CORRIDOR
Summary / 1. NORMAL LIGHT SCENE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 103 ..............................
Summary / 2. EMERGENCY LIGHT SCENE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ..............................
105
Summary / 3. ESCAPE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
107 .............................
Luminaire layout plan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
109 .............................
Calculation objects / 1. NORMAL LIGHT SCENE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
112 .............................
Calculation objects / 2. EMERGENCY LIGHT SCENE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
114. ............................

WAVE C1 _CONTROL BUILDING - Ground Floor - Storey 1

DOCUMENTS ROOM
Summary / 1. NORMAL LIGHT SCENE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 116 ..............................
Summary / 2. EMERGENCY LIGHT SCENE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ..............................
118
Summary / 3. ESCAPE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
120 .............................
Luminaire layout plan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
122 .............................
Calculation objects / 1. NORMAL LIGHT SCENE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
124 .............................
Calculation objects / 2. EMERGENCY LIGHT SCENE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
126. ............................

WAVE C1 _CONTROL BUILDING - Ground Floor - Storey 1

ELECTRICAL ROOM
Summary / 1. NORMAL LIGHT SCENE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 128 ..............................
Summary / 2. EMERGENCY LIGHT SCENE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ..............................
130
Summary / 3. ESCAPE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
132.............................
Luminaire layout plan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
134.............................
Calculation objects / 1. NORMAL LIGHT SCENE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .137 ..............................
Calculation objects / 2. EMERGENCY LIGHT SCENE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 139 ..............................

WAVE C1 _CONTROL BUILDING - Ground Floor - Storey 1

ENGINEER'S ROOM
Summary / 1. NORMAL LIGHT SCENE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 141 ..............................
Summary / 2. EMERGENCY LIGHT SCENE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ..............................
143
Summary / 3. ESCAPE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .145..............................
Luminaire layout plan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .147
..............................
Calculation objects / 1. NORMAL LIGHT SCENE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .150 ..............................
Calculation objects / 2. EMERGENCY LIGHT SCENE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 152 ..............................
WAVE C1 CONTROL BUILDING

Table of Contents

WAVE C1 _CONTROL BUILDING - Ground Floor - Storey 1

MEETING ROOM
Summary / 1. NORMAL LIGHT SCENE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 154 ..............................
Summary / 2. EMERGENCY LIGHT SCENE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ..............................
156
Summary / 3. ESCAPE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
158 .............................
Luminaire layout plan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
160 .............................
Calculation objects / 1. NORMAL LIGHT SCENE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
163 .............................
Calculation objects / 2. EMERGENCY LIGHT SCENE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
165. ............................

WAVE C1 _CONTROL BUILDING - Ground Floor - Storey 1

OFFICE
Summary / 1. NORMAL LIGHT SCENE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 167 ..............................
Summary / 2. EMERGENCY LIGHT SCENE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ..............................
169
Summary / 3. ESCAPE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
171 .............................
Luminaire layout plan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
173 .............................
Calculation objects / 1. NORMAL LIGHT SCENE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
176 .............................
Calculation objects / 2. EMERGENCY LIGHT SCENE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
178. ............................

WAVE C1 _CONTROL BUILDING - Ground Floor - Storey 1

TELECOM ROOM
Summary / 1. NORMAL LIGHT SCENE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 180 ..............................
Summary / 2. EMERGENCY LIGHT SCENE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ..............................
182
Summary / 3. ESCAPE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
184.............................
Luminaire layout plan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
186.............................
Calculation objects / 1. NORMAL LIGHT SCENE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .189 ..............................
Calculation objects / 2. EMERGENCY LIGHT SCENE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 191 ..............................

WAVE C1 _CONTROL BUILDING - Ground Floor - Storey 1

TOILET MALE
Summary / 1. NORMAL LIGHT SCENE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 193 ..............................
Summary / 2. EMERGENCY LIGHT SCENE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ..............................
195
Summary / 3. ESCAPE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .197..............................
Luminaire layout plan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .199
..............................
Calculation objects / 1. NORMAL LIGHT SCENE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .201 ..............................
Calculation objects / 2. EMERGENCY LIGHT SCENE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 203 ..............................
WAVE C1 CONTROL BUILDING

Table of Contents

WAVE C1 _CONTROL BUILDING

ROOF
Summary / 1. NORMAL LIGHT SCENE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 205 ..............................
Summary / 3. ESCAPE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ..............................
207
Luminaire layout plan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ..............................
209
Calculation objects / 1. NORMAL LIGHT SCENE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ..............................
212
WAVE C1 CONTROL BUILDING

Luminaire list

Φtotal Ptotal Luminous efficacy ΦEmergency lighting PEmergency lighting


385757 lm 3169.1 W 121.7 lm/W 366876 lm 2971.2 W

pcs. Manufacturer Article No. Article name P Φ Luminous efficacy

6 Appleton FELED3CB FELED Zone 1 Linear, 3,000 Lumens, 30.9 W 3058 lm 99.0 lm/W
UxxD 5000K CCT, 120V-277Vac; 170-300VDC,
Diffused 30.9 W 3058 lm (100 %) –

6 Philips DN470B WR LED20S/- NO 18.3 W 1837 lm 100.4 lm/W

18.3 W 1837 lm (100 %) –

13 Philips DN470B WR LED20S/- NO 18.3 W 1837 lm 100.4 lm/W

23 Philips RC132V G5 PSD W60L60 OC 48S/840 40.0 W 4789 lm 119.7 lm/W


NO
40.0 W 4789 lm (100 %) –

10 Philips RC132V G5 WIA W60L60 ELB3 OC 34.0 W 3592 lm 105.6 lm/W


36S/840 NO
34.0 W 3592 lm (100 %) –

4 Philips RC133V G5 BN PSU W62L62 NOC 28.5 W 3600 lm 126.3 lm/W


36S/840 NO
28.5 W 3600 lm (100 %) –

14 Philips WT470X L1600 WB LED80S/- NO 58.0 W 8006 lm 138.0 lm/W

58.0 W 8006 lm (100 %) –

20 Philips 91240148 EM152C SM 2S CO NM3 ELP WH IP65 2.0 W 250 lm (100 %) –


3507

15 Philips SM350CI- SM350C 40S/840 PSD PCS L1200 30.0 W 3997 lm 133.2 lm/W
005dabf3-
c421- 30.0 W 3997 lm (100 %) –
4854-
b012-
9fb449cc2

7
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 (3. ESCAPE)


Room list

8
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 (3. ESCAPE)


Room list

DCS SERVER ROOM

Ptotal ARoom Lighting power density


4.0 W 35.87 m² 0.11 W/m² (Room)

pcs. Manufacturer Article No. Article name P Φ

2 Philips 91240148 EM152C SM 2S CO NM3 ELP WH IP65 2.0 W 250 lm (100 %)


3507

DCS UPS ROOM

Ptotal ARoom Lighting power density


4.0 W 22.58 m² 0.18 W/m² (Room)

pcs. Manufacturer Article No. Article name P Φ

2 Philips 91240148 EM152C SM 2S CO NM3 ELP WH IP65 2.0 W 250 lm (100 %)


3507

BATTERY ROOM

Ptotal ARoom Lighting power density


4.0 W 33.01 m² 0.12 W/m² (Room)

pcs. Manufacturer Article No. Article name P Φ

2 Philips 91240148 EM152C SM 2S CO NM3 ELP WH IP65 2.0 W 250 lm (100 %)


3507

9
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 (3. ESCAPE)


Room list

CLEAN AGENT CYLINDER ROOM

Ptotal ARoom Lighting power density


2.0 W 16.17 m² 0.12 W/m² (Room)

pcs. Manufacturer Article No. Article name P Φ

1 Philips 91240148 EM152C SM 2S CO NM3 ELP WH IP65 2.0 W 250 lm (100 %)


3507

CONTROL ROOM

Ptotal ARoom Lighting power density


6.0 W 105.86 m² 0.06 W/m² (Room)

pcs. Manufacturer Article No. Article name P Φ

3 Philips 91240148 EM152C SM 2S CO NM3 ELP WH IP65 2.0 W 250 lm (100 %)


3507

CORRIDOR

Ptotal ARoom Lighting power density


8.0 W 73.84 m² 0.11 W/m² (Room)

pcs. Manufacturer Article No. Article name P Φ

4 Philips 91240148 EM152C SM 2S CO NM3 ELP WH IP65 2.0 W 250 lm (100 %)


3507

10
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 (3. ESCAPE)


Room list

ELECTRICAL ROOM

Ptotal ARoom Lighting power density


2.0 W 14.35 m² 0.14 W/m² (Room)

pcs. Manufacturer Article No. Article name P Φ

1 Philips 91240148 EM152C SM 2S CO NM3 ELP WH IP65 2.0 W 250 lm (100 %)


3507

ENGINEER'S ROOM

Ptotal ARoom Lighting power density


2.0 W 15.87 m² 0.13 W/m² (Room)

pcs. Manufacturer Article No. Article name P Φ

1 Philips 91240148 EM152C SM 2S CO NM3 ELP WH IP65 2.0 W 250 lm (100 %)


3507

MEETING ROOM

Ptotal ARoom Lighting power density


4.0 W 24.05 m² 0.17 W/m² (Room)

pcs. Manufacturer Article No. Article name P Φ

2 Philips 91240148 EM152C SM 2S CO NM3 ELP WH IP65 2.0 W 250 lm (100 %)


3507

11
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 (3. ESCAPE)


Room list

OFFICE

Ptotal ARoom Lighting power density


2.0 W 15.76 m² 0.13 W/m² (Room)

pcs. Manufacturer Article No. Article name P Φ

1 Philips 91240148 EM152C SM 2S CO NM3 ELP WH IP65 2.0 W 250 lm (100 %)


3507

TELECOM ROOM

Ptotal ARoom Lighting power density


2.0 W 21.96 m² 0.09 W/m² (Room)

pcs. Manufacturer Article No. Article name P Φ

1 Philips 91240148 EM152C SM 2S CO NM3 ELP WH IP65 2.0 W 250 lm (100 %)


3507

12
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 · DCS SERVER ROOM ( 1. NORMAL LIGHT SCENE)


Summary

Ground area 35.87 m² Clearance height 4.800 m

Reflection factors Ceiling: 80.0 %, Mounting height 4.800 m


Walls: 50.0 %,
Floor: 20.0 % Height Working plane 0.800 m

Maintenance factor 0.80 (fixed) Wall zone Working plane 0.000 m

13
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 · DCS SERVER ROOM ( 1. NORMAL LIGHT SCENE)


Summary

Results

Symbol Calculated Index

Working plane Ēperpendicular 438 lx WP8

Uo (g1 ) 0.64 WP8

Glare valuation(1) RUG, max 18

Energy estimation(2) Consumption 608 kWh/a

Room Lighting power density 7.53 W/m²

1.72 W/m²/100 lx

(1) Based on a rectangular space of 5.885 m x 7.319 m and SHR of 0.25.


(2) Calculated using DIN:18599-4.

Utilisation profile: Industrial activities and crafts - Electrical and electronics industry (19.1 Cable and wire manufacture)

Luminaire list

pcs. Manufacturer Article No. Article name RUG P Φ Luminous efficacy

9 Philips SM350CI- SM350C 40S/840 PSD PCS 18 30.0 W 3997 lm 133.2 lm/W
005dabf3- L1200
c421- – 30.0 W 3997 lm (100 %) –
4854-
b012-
9fb449cc2

14
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 · DCS SERVER ROOM ( 2. EMERGENCY LIGHT SCENE)


Summary

Ground area 35.87 m² Clearance height 4.800 m

Reflection factors Ceiling: 80.0 %, Mounting height 4.800 m


Walls: 50.0 %,
Floor: 20.0 % Height Working plane 0.800 m

Maintenance factor 0.80 (fixed) Wall zone Working plane 0.000 m

15
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 · DCS SERVER ROOM ( 2. EMERGENCY LIGHT SCENE)


Summary

Results

Symbol Calculated Index

Working plane Ēperpendicular 145 lx WP8

Uo (g1 ) 0.35 WP8

Glare valuation(1) RUG, max 18

Energy estimation(2) Consumption 203 kWh/a

Room Lighting power density 2.51 W/m²

1.73 W/m²/100 lx

(1) Based on a rectangular space of 5.885 m x 7.319 m and SHR of 0.25.


(2) Calculated using DIN:18599-4.

Utilisation profile: Industrial activities and crafts - Electrical and electronics industry (19.1 Cable and wire manufacture)

Luminaire list

pcs. Manufacturer Article No. Article name RUG P Φ Luminous efficacy

3 Philips SM350CI- SM350C 40S/840 PSD PCS 18 30.0 W 3997 lm 133.2 lm/W
005dabf3- L1200
c421- – 30.0 W 3997 lm (100 %) –
4854-
b012-
9fb449cc2

16
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 · DCS SERVER ROOM (3. ESCAPE)


Summary

Ground area 35.87 m² Clearance height 4.800 m

Reflection factors Ceiling: 80.0 %, Mounting height 4.600 m


Walls: 50.0 %,
Floor: 20.0 % Height Working plane 0.800 m

Maintenance factor 0.80 (fixed) Wall zone Working plane 0.000 m

17
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 · DCS SERVER ROOM (3. ESCAPE)


Summary

Results

Symbol Calculated Target Check Index

Room Lighting power density 0.11 W/m² –

(2) Calculated using DIN:18599-4.

Notes on planning:
The emergency lighting scene was calculated without reflection and taking into account the placed furniture.

Luminaire list

pcs. Manufacturer Article No. Article name P Φ Luminous efficacy

2 Philips 91240148 EM152C SM 2S CO NM3 ELP WH IP65 2.0 W 250 lm (100 %) –


3507

18
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 · DCS SERVER ROOM


Luminaire layout plan

19
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 · DCS SERVER ROOM


Luminaire layout plan

Manufacturer Philips P 0.0 W

Article No. 912401483507 PEmergency lighting 2.0 W

Article name EM152C SM 2S CO ΦLuminaire 0 lm


NM3 ELP WH IP65
ΦEmergency lighting 250 lm
Fitting 1x LED/6500
ELF 100 %

Individual luminaires

X Y Mounting Luminaire
height

1.826 m 6.372 m 4.600 m 1

0.777 m 2.688 m 4.600 m 2

20
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 · DCS SERVER ROOM


Luminaire layout plan

Manufacturer Philips P 30.0 W

Article No. SM350CI-005dabf3- PEmergency lighting 30.0 W


c421-4854-b012-
9fb449cc2153 ΦLuminaire 3997 lm

Article name SM350C 40S/840 ΦEmergency lighting 3997 lm


PSD PCS L1200
ELF 100 %
Fitting 1x 40S/840

9 x Philips SM350C 40S/840 PSD PCS L1200

Type Field Arrangement X Y Mounting Luminaire


height
1st luminaire (X/Y/Z) 5.180 m / 1.483 m /
4.800 m 0.775 m 1.483 m 4.800 m 3

X-direction 3 pcs., Centre - 0.775 m 3.792 m 4.800 m 4


centre, Distances not
equal 0.775 m 6.102 m 4.800 m 5

Y-direction 3 pcs., Centre - 2.978 m 1.483 m 4.800 m 6


centre, Distances not
equal 2.978 m 3.792 m 4.800 m 7

Arrangement A1 2.978 m 6.102 m 4.800 m 8

5.180 m 1.483 m 4.800 m 9

5.180 m 3.792 m 4.800 m 10

5.180 m 6.102 m 4.800 m 11

21
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 · DCS SERVER ROOM ( 1. NORMAL LIGHT SCENE)


Calculation objects

22
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 · DCS SERVER ROOM ( 1. NORMAL LIGHT SCENE)


Calculation objects

Working planes

Properties Ē Emin Emax Uo (g1 ) g2 Index

Working plane ( DCS SERVER ROOM) 438 lx 280 lx 650 lx 0.64 0.43 WP8
Perpendicular illuminance
Height: 0.800 m, Wall zone: 0.000 m

Utilisation profile: Industrial activities and crafts - Electrical and electronics industry (19.1 Cable and wire manufacture)

23
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 · DCS SERVER ROOM ( 2. EMERGENCY LIGHT SCENE)


Calculation objects

24
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 · DCS SERVER ROOM ( 2. EMERGENCY LIGHT SCENE)


Calculation objects

Working planes

Properties Ē Emin Emax Uo (g1 ) g2 Index

Working plane ( DCS SERVER ROOM) 145 lx 50.2 lx 288 lx 0.35 0.17 WP8
Perpendicular illuminance
Height: 0.800 m, Wall zone: 0.000 m

Utilisation profile: Industrial activities and crafts - Electrical and electronics industry (19.1 Cable and wire manufacture)

25
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 · DCS UPS ROOM ( 1. NORMAL LIGHT SCENE)


Summary

Ground area 22.58 m² Clearance height 4.800 m

Reflection factors Ceiling: 80.0 %, Mounting height 4.500 m


Walls: 50.0 %,
Floor: 20.0 % Height Working plane 0.800 m

Maintenance factor 0.80 (fixed) Wall zone Working plane 0.300 m

26
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 · DCS UPS ROOM ( 1. NORMAL LIGHT SCENE)


Summary

Results

Symbol Calculated Index

Working plane Ēperpendicular 395 lx WP1

Uo (g1 ) 0.64 WP1

Lighting power density 10.93 W/m²

2.77 W/m²/100 lx

Glare valuation(1) RUG, max 18

Energy estimation(2) Consumption 405 kWh/a

Room Lighting power density 7.97 W/m²

2.02 W/m²/100 lx

(1) Based on a rectangular space of 6.064 m x 4.770 m and SHR of 0.25.


(2) Calculated using DIN:18599-4.

Utilisation profile: Industrial activities and crafts - Electrical and electronics industry (19.1 Cable and wire manufacture)

Luminaire list

pcs. Manufacturer Article No. Article name RUG P Φ Luminous efficacy

6 Philips SM350CI- SM350C 40S/840 PSD PCS 18 30.0 W 3997 lm 133.2 lm/W
005dabf3- L1200
c421- – 30.0 W 3997 lm (100 %) –
4854-
b012-
9fb449cc2

27
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 · DCS UPS ROOM ( 2. EMERGENCY LIGHT SCENE)


Summary

Ground area 22.58 m² Clearance height 4.800 m

Reflection factors Ceiling: 80.0 %, Mounting height 4.500 m


Walls: 50.0 %,
Floor: 20.0 % Height Working plane 0.800 m

Maintenance factor 0.80 (fixed) Wall zone Working plane 0.300 m

28
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 · DCS UPS ROOM ( 2. EMERGENCY LIGHT SCENE)


Summary

Results

Symbol Calculated Index

Working plane Ēperpendicular 196 lx WP1

Uo (g1 ) 0.32 WP1

Lighting power density 5.47 W/m²

2.78 W/m²/100 lx

Glare valuation(1) RUG, max 18

Energy estimation(2) Consumption 203 kWh/a

Room Lighting power density 3.99 W/m²

2.03 W/m²/100 lx

(1) Based on a rectangular space of 6.064 m x 4.770 m and SHR of 0.25.


(2) Calculated using DIN:18599-4.

Utilisation profile: Industrial activities and crafts - Electrical and electronics industry (19.1 Cable and wire manufacture)

Luminaire list

pcs. Manufacturer Article No. Article name RUG P Φ Luminous efficacy

3 Philips SM350CI- SM350C 40S/840 PSD PCS 18 30.0 W 3997 lm 133.2 lm/W
005dabf3- L1200
c421- – 30.0 W 3997 lm (100 %) –
4854-
b012-
9fb449cc2

29
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 · DCS UPS ROOM (3. ESCAPE)


Summary

Ground area 22.58 m² Clearance height 4.800 m

Reflection factors Ceiling: 80.0 %, Mounting height 4.600 m


Walls: 50.0 %,
Floor: 20.0 % Height Working plane 0.800 m

Maintenance factor 0.80 (fixed) Wall zone Working plane 0.300 m

30
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 · DCS UPS ROOM (3. ESCAPE)


Summary

Results

Symbol Calculated Target Check Index

Room Lighting power density 0.18 W/m² –

(2) Calculated using DIN:18599-4.

Notes on planning:
The emergency lighting scene was calculated without reflection and taking into account the placed furniture.

Luminaire list

pcs. Manufacturer Article No. Article name P Φ Luminous efficacy

2 Philips 91240148 EM152C SM 2S CO NM3 ELP WH IP65 2.0 W 250 lm (100 %) –


3507

31
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 · DCS UPS ROOM


Luminaire layout plan

32
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 · DCS UPS ROOM


Luminaire layout plan

Manufacturer Philips P 0.0 W

Article No. 912401483507 PEmergency lighting 2.0 W

Article name EM152C SM 2S CO ΦLuminaire 0 lm


NM3 ELP WH IP65
ΦEmergency lighting 250 lm
Fitting 1x LED/6500
ELF 100 %

Individual luminaires

X Y Mounting Luminaire
height

5.350 m 2.369 m 4.600 m 1

2.932 m 0.503 m 4.600 m 2

33
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 · DCS UPS ROOM


Luminaire layout plan

Manufacturer Philips P 30.0 W

Article No. SM350CI-005dabf3- PEmergency lighting 30.0 W


c421-4854-b012-
9fb449cc2153 ΦLuminaire 3997 lm

Article name SM350C 40S/840 ΦEmergency lighting 3997 lm


PSD PCS L1200
ELF 100 %
Fitting 1x 40S/840

6 x Philips SM350C 40S/840 PSD PCS L1200

Type Field Arrangement X Y Mounting Luminaire


height
1st luminaire (X/Y/Z) 1.448 m / 0.493 m /
4.500 m 1.447 m 4.252 m 4.500 m 3

X-direction 2 pcs., Centre - 4.411 m 4.254 m 4.500 m 4


centre, Distances not
equal 1.448 m 2.373 m 4.500 m 5

Y-direction 3 pcs., Centre - 4.412 m 2.374 m 4.500 m 6


centre, Distances not
equal 1.448 m 0.493 m 4.500 m 7

Arrangement A1 4.412 m 0.495 m 4.500 m 8

34
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 · DCS UPS ROOM ( 1. NORMAL LIGHT SCENE)


Calculation objects

35
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 · DCS UPS ROOM ( 1. NORMAL LIGHT SCENE)


Calculation objects

Working planes

Properties Ē Emin Emax Uo (g1 ) g2 Index

Working plane ( DCS UPS ROOM) 395 lx 252 lx 586 lx 0.64 0.43 WP1
Perpendicular illuminance
Height: 0.800 m, Wall zone: 0.300 m

Utilisation profile: Industrial activities and crafts - Electrical and electronics industry (19.1 Cable and wire manufacture)

36
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 · DCS UPS ROOM ( 2. EMERGENCY LIGHT SCENE)


Calculation objects

37
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 · DCS UPS ROOM ( 2. EMERGENCY LIGHT SCENE)


Calculation objects

Working planes

Properties Ē Emin Emax Uo (g1 ) g2 Index

Working plane ( DCS UPS ROOM) 196 lx 62.7 lx 296 lx 0.32 0.21 WP1
Perpendicular illuminance
Height: 0.800 m, Wall zone: 0.300 m

Utilisation profile: Industrial activities and crafts - Electrical and electronics industry (19.1 Cable and wire manufacture)

38
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 · KITCHEN ( 1. NORMAL LIGHT SCENE)


Summary

Ground area 16.27 m² Clearance height 4.800 m

Reflection factors Ceiling: 80.0 %, Mounting height 3.000 m


Walls: 50.0 %,
Floor: 20.0 % Height Working plane 0.800 m

Maintenance factor 0.80 (fixed) Wall zone Working plane 0.300 m

39
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 · KITCHEN ( 1. NORMAL LIGHT SCENE)


Summary

Results

Symbol Calculated Index

Working plane Ēperpendicular 512 lx WP14

Uo (g1 ) 0.65 WP14

Lighting power density 10.62 W/m²

2.08 W/m²/100 lx

Glare valuation(1) RUG, max 17

Energy estimation(2) Consumption 297 kWh/a

Room Lighting power density 7.38 W/m²

1.44 W/m²/100 lx

(1) Based on a rectangular space of 2.821 m x 5.878 m and SHR of 0.25.


(2) Calculated using DIN:18599-4.

Utilisation profile: DIALux presetting (34.2 Standard (office))

Luminaire list

pcs. Manufacturer Article No. Article name RUG P Φ Luminous efficacy

3 Philips RC132V G5 PSD W60L60 OC 17 40.0 W 4789 lm 119.7 lm/W


48S/840 NO
– 40.0 W 4789 lm (100 %) –

40
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 · KITCHEN ( 2. EMERGENCY LIGHT SCENE)


Summary

Ground area 16.27 m² Clearance height 4.800 m

Reflection factors Ceiling: 80.0 %, Mounting height 3.000 m


Walls: 50.0 %,
Floor: 20.0 % Height Working plane 0.800 m

Maintenance factor 0.80 (fixed) Wall zone Working plane 0.300 m

41
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 · KITCHEN ( 2. EMERGENCY LIGHT SCENE)


Summary

Results

Symbol Calculated Index

Working plane Ēperpendicular 198 lx WP14

Uo (g1 ) 0.27 WP14

Lighting power density 3.54 W/m²

1.79 W/m²/100 lx

Glare valuation(1) RUG, max 17

Energy estimation(2) Consumption 99.0 kWh/a

Room Lighting power density 2.46 W/m²

1.24 W/m²/100 lx

(1) Based on a rectangular space of 2.821 m x 5.878 m and SHR of 0.25.


(2) Calculated using DIN:18599-4.

Utilisation profile: DIALux presetting (34.2 Standard (office))

Luminaire list

pcs. Manufacturer Article No. Article name RUG P Φ Luminous efficacy

1 Philips RC132V G5 PSD W60L60 OC 17 40.0 W 4789 lm 119.7 lm/W


48S/840 NO
– 40.0 W 4789 lm (100 %) –

42
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 · KITCHEN (3. ESCAPE)


Summary

Ground area 16.27 m²

Reflection factors Ceiling: 80.0 %, Clearance height 4.800 m


Walls: 50.0 %,
Floor: 20.0 % Height Working plane 0.800 m

Maintenance factor 0.80 (fixed) Wall zone Working plane 0.300 m

43
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 · KITCHEN (3. ESCAPE)


Summary

Results

Symbol Calculated Target Check Index

Room Lighting power density 0.00 W/m² –

(2) Calculated using DIN:18599-4.

Notes on planning:
The emergency lighting scene was calculated without reflection and taking into account the placed furniture.

44
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 · KITCHEN


Luminaire layout plan

45
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 · KITCHEN


Luminaire layout plan

Manufacturer Philips P 40.0 W

Article name RC132V G5 PSD PEmergency lighting 40.0 W


W60L60 OC 48S/840
NO ΦLuminaire 4789 lm

Fitting 1x 48S/840 ΦEmergency lighting 4789 lm

ELF 100 %

3 x Philips RC132V G5 PSD W60L60 OC 48S/840 NO

Type Field Arrangement X Y Mounting Luminaire


height
1st luminaire (X/Y/Z) 4.935 m / 1.412 m /
3.000 m 1.155 m 1.352 m 3.000 m 1

X-direction 3 pcs., Centre - 3.045 m 1.382 m 3.000 m 2


centre, 1.890 m
4.935 m 1.412 m 3.000 m 3
Y-direction 1 pcs., Centre -
centre, 2.482 m

Arrangement A1

46
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 · KITCHEN ( 1. NORMAL LIGHT SCENE)


Calculation objects

47
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 · KITCHEN ( 1. NORMAL LIGHT SCENE)


Calculation objects

Working planes

Properties Ē Emin Emax Uo (g1 ) g2 Index

Working plane ( KITCHEN) 512 lx 333 lx 625 lx 0.65 0.53 WP14


Perpendicular illuminance
Height: 0.800 m, Wall zone: 0.300 m

Utilisation profile: DIALux presetting (34.2 Standard (office))

48
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 · KITCHEN ( 2. EMERGENCY LIGHT SCENE)


Calculation objects

49
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 · KITCHEN ( 2. EMERGENCY LIGHT SCENE)


Calculation objects

Working planes

Properties Ē Emin Emax Uo (g1 ) g2 Index

Working plane ( KITCHEN) 198 lx 52.9 lx 381 lx 0.27 0.14 WP14


Perpendicular illuminance
Height: 0.800 m, Wall zone: 0.300 m

Utilisation profile: DIALux presetting (34.2 Standard (office))

50
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 · TOILET FEMALE ( 1. NORMAL LIGHT SCENE)


Summary

Ground area 12.94 m² Clearance height 4.800 m

Reflection factors Ceiling: 80.0 %, Mounting height 4.800 m


Walls: 50.0 %,
Floor: 20.0 % Height Working plane 0.800 m

Maintenance factor 0.80 (fixed) Wall zone Working plane 0.000 m

51
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 · TOILET FEMALE ( 1. NORMAL LIGHT SCENE)


Summary

Results

Symbol Calculated Index

Working plane Ēperpendicular 86.9 lx WP5

Uo (g1 ) 0.73 WP5

Glare valuation(1) RUG, max 22

Energy estimation(2) Consumption 70.5 kWh/a

Room Lighting power density 2.83 W/m²

3.25 W/m²/100 lx

(1) Based on a rectangular space of 5.721 m x 2.280 m and SHR of 0.25.


(2) Calculated using DIN:18599-4.

Utilisation profile: Places of public assembly - General areas (36.1 Entrance halls)

Luminaire list

pcs. Manufacturer Article No. Article name RUG P Φ Luminous efficacy

2 Philips DN470B WR LED20S/- NO 22 18.3 W 1837 lm 100.4 lm/W

– 18.3 W 1837 lm (100 %) –

52
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 · TOILET FEMALE ( 2. EMERGENCY LIGHT SCENE)


Summary

Ground area 12.94 m² Clearance height 4.800 m

Reflection factors Ceiling: 80.0 %, Mounting height 4.800 m


Walls: 50.0 %,
Floor: 20.0 % Height Working plane 0.800 m

Maintenance factor 0.80 (fixed) Wall zone Working plane 0.000 m

53
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 · TOILET FEMALE ( 2. EMERGENCY LIGHT SCENE)


Summary

Results

Symbol Calculated Index

Working plane Ēperpendicular 43.7 lx WP5

Uo (g1 ) 0.41 WP5

Glare valuation(1) RUG, max 22

Energy estimation(2) Consumption 35.2 kWh/a

Room Lighting power density 1.41 W/m²

3.24 W/m²/100 lx

(1) Based on a rectangular space of 5.721 m x 2.280 m and SHR of 0.25.


(2) Calculated using DIN:18599-4.

Utilisation profile: Places of public assembly - General areas (36.1 Entrance halls)

Luminaire list

pcs. Manufacturer Article No. Article name RUG P Φ Luminous efficacy

1 Philips DN470B WR LED20S/- NO 22 18.3 W 1837 lm 100.4 lm/W

– 18.3 W 1837 lm (100 %) –

54
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 · TOILET FEMALE (3. ESCAPE)


Summary

Ground area 12.94 m²

Reflection factors Ceiling: 80.0 %, Clearance height 4.800 m


Walls: 50.0 %,
Floor: 20.0 % Height Working plane 0.800 m

Maintenance factor 0.80 (fixed) Wall zone Working plane 0.000 m

55
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 · TOILET FEMALE (3. ESCAPE)


Summary

Results

Symbol Calculated Target Check Index

Room Lighting power density 0.00 W/m² –

(2) Calculated using DIN:18599-4.

Notes on planning:
The emergency lighting scene was calculated without reflection and taking into account the placed furniture.

56
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 · TOILET FEMALE


Luminaire layout plan

57
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 · TOILET FEMALE


Luminaire layout plan

Manufacturer Philips P 18.3 W

Article name DN470B WR PEmergency lighting 18.3 W


LED20S/- NO
ΦLuminaire 1837 lm
Fitting 1x LED20S/840/-
ΦEmergency lighting 1837 lm

ELF 100 %

2 x Philips DN470B WR LED20S/- NO

Type Line arrangement X Y Mounting Luminaire


height
1st luminaire (X/Y/Z) 1.699 m / 1.203 m /
4.800 m 1.699 m 1.203 m 4.800 m 1

X-direction 2 pcs., Centre - 4.171 m 1.203 m 4.800 m 2


centre, 2.471 m

Arrangement A1

58
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 · TOILET FEMALE ( 1. NORMAL LIGHT SCENE)


Calculation objects

59
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 · TOILET FEMALE ( 1. NORMAL LIGHT SCENE)


Calculation objects

Working planes

Properties Ē Emin Emax Uo (g1 ) g2 Index

Working plane ( TOILET FEMALE) 86.9 lx 63.4 lx 103 lx 0.73 0.62 WP5
Perpendicular illuminance
Height: 0.800 m, Wall zone: 0.000 m

Utilisation profile: Places of public assembly - General areas (36.1 Entrance halls)

60
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 · TOILET FEMALE ( 2. EMERGENCY LIGHT SCENE)


Calculation objects

61
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 · TOILET FEMALE ( 2. EMERGENCY LIGHT SCENE)


Calculation objects

Working planes

Properties Ē Emin Emax Uo (g1 ) g2 Index

Working plane ( TOILET FEMALE) 43.7 lx 18.1 lx 63.5 lx 0.41 0.29 WP5
Perpendicular illuminance
Height: 0.800 m, Wall zone: 0.000 m

Utilisation profile: Places of public assembly - General areas (36.1 Entrance halls)

62
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 · BATTERY ROOM ( 1. NORMAL LIGHT SCENE)


Summary

Ground area 33.01 m² Clearance height 4.800 m

Reflection factors Ceiling: 80.0 %, Mounting height 4.600 m


Walls: 50.0 %,
Floor: 20.0 % Height Working plane 0.800 m

Maintenance factor 0.80 (fixed) Wall zone Working plane 0.000 m

63
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 · BATTERY ROOM ( 1. NORMAL LIGHT SCENE)


Summary

Results

Symbol Calculated Index

Working plane Ēperpendicular 169 lx WP11

Uo (g1 ) 0.79 WP11

Energy estimation(2) Consumption 417 kWh/a

Room Lighting power density 5.62 W/m²

3.33 W/m²/100 lx

(1) Based on a rectangular space of 5.860 m x 6.770 m and SHR of 0.25.


(2) Calculated using DIN:18599-4.

Utilisation profile: Industrial activities and crafts - Electrical and electronics industry (19.1 Cable and wire manufacture)

Luminaire list

pcs. Manufacturer Article No. Article name RUG P Φ Luminous efficacy

6 Appleton FELED3CB FELED Zone 1 Linear, 3,000 – 30.9 W 3058 lm 99.0 lm/W
UxxD Lumens, 5000K CCT, 120V-
277Vac; 170-300VDC, Diffused – 30.9 W 3058 lm (100 %) –

64
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 · BATTERY ROOM ( 2. EMERGENCY LIGHT SCENE)


Summary

Ground area 33.01 m² Clearance height 4.800 m

Reflection factors Ceiling: 80.0 %, Mounting height 4.600 m


Walls: 50.0 %,
Floor: 20.0 % Height Working plane 0.800 m

Maintenance factor 0.80 (fixed) Wall zone Working plane 0.000 m

65
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 · BATTERY ROOM ( 2. EMERGENCY LIGHT SCENE)


Summary

Results

Symbol Calculated Index

Working plane Ēperpendicular 84.8 lx WP11

Uo (g1 ) 0.45 WP11

Energy estimation(2) Consumption 208 kWh/a

Room Lighting power density 2.81 W/m²

3.31 W/m²/100 lx

(1) Based on a rectangular space of 5.860 m x 6.770 m and SHR of 0.25.


(2) Calculated using DIN:18599-4.

Utilisation profile: Industrial activities and crafts - Electrical and electronics industry (19.1 Cable and wire manufacture)

Luminaire list

pcs. Manufacturer Article No. Article name RUG P Φ Luminous efficacy

3 Appleton FELED3CB FELED Zone 1 Linear, 3,000 – 30.9 W 3058 lm 99.0 lm/W
UxxD Lumens, 5000K CCT, 120V-
277Vac; 170-300VDC, Diffused – 30.9 W 3058 lm (100 %) –

66
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 · BATTERY ROOM (3. ESCAPE)


Summary

Ground area 33.01 m² Clearance height 4.800 m

Reflection factors Ceiling: 80.0 %, Mounting height 4.600 m


Walls: 50.0 %,
Floor: 20.0 % Height Working plane 0.800 m

Maintenance factor 0.80 (fixed) Wall zone Working plane 0.000 m

67
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 · BATTERY ROOM (3. ESCAPE)


Summary

Results

Symbol Calculated Target Check Index

Room Lighting power density 0.12 W/m² –

(2) Calculated using DIN:18599-4.

Notes on planning:
The emergency lighting scene was calculated without reflection and taking into account the placed furniture.

Luminaire list

pcs. Manufacturer Article No. Article name P Φ Luminous efficacy

2 Philips 91240148 EM152C SM 2S CO NM3 ELP WH IP65 2.0 W 250 lm (100 %) –


3507

68
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 · BATTERY ROOM


Luminaire layout plan

69
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 · BATTERY ROOM


Luminaire layout plan

Manufacturer Appleton P 30.9 W

Article No. FELED3CBUxxD PEmergency lighting 30.9 W

Article name FELED Zone 1 Linear, ΦLuminaire 3058 lm


3,000 Lumens, 5000K
CCT, 120V-277Vac; ΦEmergency lighting 3058 lm
170-300VDC,
Diffused ELF 100 %

Fitting 1x LED

6 x Appleton FELED Zone 1 Linear, 3,000 Lumens, 5000K CCT, 120V-277Vac; 170-300VDC, Diffused

Type Field Arrangement X Y Mounting Luminaire


height
1st luminaire (X/Y/Z) 0.928 m / 0.664 m /
4.600 m 0.924 m 4.601 m 4.600 m 3

X-direction 3 pcs., Centre - 2.949 m 4.604 m 4.600 m 4


centre, Distances not
equal 4.974 m 4.606 m 4.600 m 5

Y-direction 2 pcs., Centre - 0.928 m 0.664 m 4.600 m 6


centre, Distances not
equal 2.953 m 0.666 m 4.600 m 7

Arrangement A1 4.978 m 0.669 m 4.600 m 8

70
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 · BATTERY ROOM


Luminaire layout plan

Manufacturer Philips P 0.0 W

Article No. 912401483507 PEmergency lighting 2.0 W

Article name EM152C SM 2S CO ΦLuminaire 0 lm


NM3 ELP WH IP65
ΦEmergency lighting 250 lm
Fitting 1x LED/6500
ELF 100 %

Individual luminaires

X Y Mounting Luminaire
height

2.953 m 5.252 m 4.600 m 1

0.877 m 2.588 m 4.600 m 2

71
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 · BATTERY ROOM ( 1. NORMAL LIGHT SCENE)


Calculation objects

72
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 · BATTERY ROOM ( 1. NORMAL LIGHT SCENE)


Calculation objects

Working planes

Properties Ē Emin Emax Uo (g1 ) g2 Index

Working plane (BATTERY ROOM) 169 lx 133 lx 204 lx 0.79 0.65 WP11
Perpendicular illuminance
Height: 0.800 m, Wall zone: 0.000 m

Utilisation profile: Industrial activities and crafts - Electrical and electronics industry (19.1 Cable and wire manufacture)

73
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 · BATTERY ROOM ( 2. EMERGENCY LIGHT SCENE)


Calculation objects

74
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 · BATTERY ROOM ( 2. EMERGENCY LIGHT SCENE)


Calculation objects

Working planes

Properties Ē Emin Emax Uo (g1 ) g2 Index

Working plane (BATTERY ROOM) 84.8 lx 38.5 lx 111 lx 0.45 0.35 WP11
Perpendicular illuminance
Height: 0.800 m, Wall zone: 0.000 m

Utilisation profile: Industrial activities and crafts - Electrical and electronics industry (19.1 Cable and wire manufacture)

75
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 · CLEAN AGENT CYLINDER ROOM ( 1. NORMAL LIGHT SCENE)
Summary

Ground area 16.17 m² Clearance height 4.800 m

Reflection factors Ceiling: 80.0 %, Mounting height 4.800 m


Walls: 50.0 %,
Floor: 20.0 % Height Working plane 0.800 m

Maintenance factor 0.80 (fixed) Wall zone Working plane 0.000 m

76
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 · CLEAN AGENT CYLINDER ROOM ( 1. NORMAL LIGHT SCENE)
Summary

Results

Symbol Calculated Index

Working plane Ēperpendicular 80.1 lx WP13

Uo (g1 ) 0.74 WP13

Glare valuation(1) RUG, max 22

Energy estimation(2) Consumption 192 kWh/a

Room Lighting power density 2.26 W/m²

2.82 W/m²/100 lx

(1) Based on a rectangular space of 2.770 m x 5.860 m and SHR of 0.25.


(2) Calculated using DIN:18599-4.

Utilisation profile: Logistics and warehouse (13.1 Unloading / loading area)

Luminaire list

pcs. Manufacturer Article No. Article name RUG P Φ Luminous efficacy

2 Philips DN470B WR LED20S/- NO 22 18.3 W 1837 lm 100.4 lm/W

– 18.3 W 1837 lm (100 %) –

77
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 · CLEAN AGENT CYLINDER ROOM ( 2. EMERGENCY LIGHT SCENE)
Summary

Ground area 16.17 m² Clearance height 4.800 m

Reflection factors Ceiling: 80.0 %, Mounting height 4.800 m


Walls: 50.0 %,
Floor: 20.0 % Height Working plane 0.800 m

Maintenance factor 0.80 (fixed) Wall zone Working plane 0.000 m

78
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 · CLEAN AGENT CYLINDER ROOM ( 2. EMERGENCY LIGHT SCENE)
Summary

Results

Symbol Calculated Index

Working plane Ēperpendicular 40.2 lx WP13

Uo (g1 ) 0.34 WP13

Glare valuation(1) RUG, max 22

Energy estimation(2) Consumption 96.2 kWh/a

Room Lighting power density 1.13 W/m²

2.82 W/m²/100 lx

(1) Based on a rectangular space of 2.770 m x 5.860 m and SHR of 0.25.


(2) Calculated using DIN:18599-4.

Utilisation profile: Logistics and warehouse (13.1 Unloading / loading area)

Luminaire list

pcs. Manufacturer Article No. Article name RUG P Φ Luminous efficacy

1 Philips DN470B WR LED20S/- NO 22 18.3 W 1837 lm 100.4 lm/W

– 18.3 W 1837 lm (100 %) –

79
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 · CLEAN AGENT CYLINDER ROOM (3. ESCAPE)


Summary

Ground area 16.17 m² Clearance height 4.800 m

Reflection factors Ceiling: 80.0 %, Mounting height 3.000 m


Walls: 50.0 %,
Floor: 20.0 % Height Working plane 0.800 m

Maintenance factor 0.80 (fixed) Wall zone Working plane 0.000 m

80
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 · CLEAN AGENT CYLINDER ROOM (3. ESCAPE)


Summary

Results

Symbol Calculated Target Check Index

Room Lighting power density 0.12 W/m² –

(2) Calculated using DIN:18599-4.

Notes on planning:
The emergency lighting scene was calculated without reflection and taking into account the placed furniture.

Luminaire list

pcs. Manufacturer Article No. Article name P Φ Luminous efficacy

1 Philips 91240148 EM152C SM 2S CO NM3 ELP WH IP65 2.0 W 250 lm (100 %) –


3507

81
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 · CLEAN AGENT CYLINDER ROOM


Luminaire layout plan

82
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 · CLEAN AGENT CYLINDER ROOM


Luminaire layout plan

Manufacturer Philips P 18.3 W

Article name DN470B WR PEmergency lighting 18.3 W


LED20S/- NO
ΦLuminaire 1837 lm
Fitting 1x LED20S/840/-
ΦEmergency lighting 1837 lm

ELF 100 %

2 x Philips DN470B WR LED20S/- NO

Type Field Arrangement X Y Mounting Luminaire


height
1st luminaire (X/Y/Z) 1.605 m / 1.385 m /
4.800 m 1.605 m 1.385 m 4.800 m 2

X-direction 2 pcs., Centre - 4.535 m 1.385 m 4.800 m 3


centre, 2.930 m

Y-direction 1 pcs., Centre -


centre, 2.770 m

Arrangement A1

83
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 · CLEAN AGENT CYLINDER ROOM


Luminaire layout plan

Manufacturer Philips P 0.0 W

Article No. 912401483507 PEmergency lighting 2.0 W

Article name EM152C SM 2S CO ΦLuminaire 0 lm


NM3 ELP WH IP65
ΦEmergency lighting 250 lm
Fitting 1x LED/6500
ELF 100 %

Individual luminaires

X Y Mounting Luminaire
height

3.181 m 2.156 m 3.000 m 1

84
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 · CLEAN AGENT CYLINDER ROOM ( 1. NORMAL LIGHT SCENE)
Calculation objects

85
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 · CLEAN AGENT CYLINDER ROOM ( 1. NORMAL LIGHT SCENE)
Calculation objects

Working planes

Properties Ē Emin Emax Uo (g1 ) g2 Index

Working plane (CLEAN AGENT CYLINDER ROOM) 80.1 lx 59.6 lx 95.1 lx 0.74 0.63 WP13
Perpendicular illuminance
Height: 0.800 m, Wall zone: 0.000 m

Utilisation profile: Logistics and warehouse (13.1 Unloading / loading area)

86
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 · CLEAN AGENT CYLINDER ROOM ( 2. EMERGENCY LIGHT SCENE)
Calculation objects

87
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 · CLEAN AGENT CYLINDER ROOM ( 2. EMERGENCY LIGHT SCENE)
Calculation objects

Working planes

Properties Ē Emin Emax Uo (g1 ) g2 Index

Working plane (CLEAN AGENT CYLINDER ROOM) 40.2 lx 13.6 lx 62.2 lx 0.34 0.22 WP13
Perpendicular illuminance
Height: 0.800 m, Wall zone: 0.000 m

Utilisation profile: Logistics and warehouse (13.1 Unloading / loading area)

88
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 · CONTROL ROOM ( 1. NORMAL LIGHT SCENE)


Summary

Ground area 105.86 m² Clearance height 4.800 m

Reflection factors Ceiling: 80.0 %, Mounting height 3.000 m


Walls: 50.0 %,
Floor: 20.0 % Height Working plane 0.800 m

Maintenance factor 0.80 (fixed) Wall zone Working plane 0.300 m

89
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 · CONTROL ROOM ( 1. NORMAL LIGHT SCENE)


Summary

Results

Symbol Calculated Index

Working plane Ēperpendicular 559 lx WP6

Uo (g1 ) 0.71 WP6

Lighting power density 6.84 W/m²

1.22 W/m²/100 lx

Glare valuation(1) RUG, max 19

Energy estimation(2) Consumption 106 kWh/a

Room Lighting power density 6.05 W/m²

1.08 W/m²/100 lx

(1) Based on a rectangular space of 12.900 m x 8.260 m and SHR of 0.25.


(2) Calculated using DIN:18599-4.

Utilisation profile: General areas inside buildings - Control rooms (11.1 Plant rooms, switchgear rooms)

Luminaire list

pcs. Manufacturer Article No. Article name RUG P Φ Luminous efficacy

16 Philips RC132V G5 PSD W60L60 OC 19 40.0 W 4789 lm 119.7 lm/W


48S/840 NO
– 40.0 W 4789 lm (100 %) –

90
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 · CONTROL ROOM ( 2. EMERGENCY LIGHT SCENE)


Summary

Ground area 105.86 m² Clearance height 4.800 m

Reflection factors Ceiling: 80.0 %, Mounting height 3.000 m


Walls: 50.0 %,
Floor: 20.0 % Height Working plane 0.800 m

Maintenance factor 0.80 (fixed) Wall zone Working plane 0.300 m

91
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 · CONTROL ROOM ( 2. EMERGENCY LIGHT SCENE)


Summary

Results

Symbol Calculated Index

Working plane Ēperpendicular 280 lx WP6

Uo (g1 ) 0.32 WP6

Lighting power density 3.42 W/m²

1.22 W/m²/100 lx

Glare valuation(1) RUG, max 19

Energy estimation(2) Consumption 52.8 kWh/a

Room Lighting power density 3.02 W/m²

1.08 W/m²/100 lx

(1) Based on a rectangular space of 12.900 m x 8.260 m and SHR of 0.25.


(2) Calculated using DIN:18599-4.

Utilisation profile: General areas inside buildings - Control rooms (11.1 Plant rooms, switchgear rooms)

Luminaire list

pcs. Manufacturer Article No. Article name RUG P Φ Luminous efficacy

8 Philips RC132V G5 PSD W60L60 OC 19 40.0 W 4789 lm 119.7 lm/W


48S/840 NO
– 40.0 W 4789 lm (100 %) –

92
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 · CONTROL ROOM (3. ESCAPE)


Summary

Ground area 105.86 m² Clearance height 4.800 m

Reflection factors Ceiling: 80.0 %, Mounting height 3.000 m


Walls: 50.0 %,
Floor: 20.0 % Height Working plane 0.800 m

Maintenance factor 0.80 (fixed) Wall zone Working plane 0.300 m

93
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 · CONTROL ROOM (3. ESCAPE)


Summary

Results

Symbol Calculated Target Check Index

Room Lighting power density 0.06 W/m² –

(2) Calculated using DIN:18599-4.

Notes on planning:
The emergency lighting scene was calculated without reflection and taking into account the placed furniture.

Luminaire list

pcs. Manufacturer Article No. Article name P Φ Luminous efficacy

3 Philips 91240148 EM152C SM 2S CO NM3 ELP WH IP65 2.0 W 250 lm (100 %) –


3507

94
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 · CONTROL ROOM


Luminaire layout plan

95
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 · CONTROL ROOM


Luminaire layout plan

Manufacturer Philips P 40.0 W

Article name RC132V G5 PSD PEmergency lighting 40.0 W


W60L60 OC 48S/840
NO ΦLuminaire 4789 lm

Fitting 1x 48S/840 ΦEmergency lighting 4789 lm

ELF 100 %

16 x Philips RC132V G5 PSD W60L60 OC 48S/840 NO

Type Field Arrangement X Y Mounting Luminaire


height
1st luminaire (X/Y/Z) 1.650 m / 1.116 m /
3.000 m 1.592 m 7.061 m 3.000 m 4

X-direction 4 pcs., Centre - 4.757 m 7.092 m 3.000 m 5


centre, 3.165 m
7.922 m 7.123 m 3.000 m 6
Y-direction 4 pcs., Centre -
centre, 1.982 m 11.086 m 7.154 m 3.000 m 7

Arrangement A1 1.612 m 5.079 m 3.000 m 8

4.776 m 5.110 m 3.000 m 9

7.941 m 5.141 m 3.000 m 10

11.105 m 5.172 m 3.000 m 11

1.631 m 3.098 m 3.000 m 12

4.796 m 3.129 m 3.000 m 13

7.960 m 3.160 m 3.000 m 14

11.125 m 3.190 m 3.000 m 15

1.650 m 1.116 m 3.000 m 16

96
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 · CONTROL ROOM


Luminaire layout plan

X Y Mounting Luminaire
height

4.815 m 1.147 m 3.000 m 17

7.980 m 1.178 m 3.000 m 18

11.144 m 1.209 m 3.000 m 19

97
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 · CONTROL ROOM


Luminaire layout plan

Manufacturer Philips P 0.0 W

Article No. 912401483507 PEmergency lighting 2.0 W

Article name EM152C SM 2S CO ΦLuminaire 0 lm


NM3 ELP WH IP65
ΦEmergency lighting 250 lm
Fitting 1x LED/6500
ELF 100 %

Individual luminaires

X Y Mounting Luminaire
height

4.797 m 3.984 m 3.000 m 1

1.626 m 3.983 m 3.000 m 2

7.977 m 2.188 m 3.000 m 3

98
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 · CONTROL ROOM ( 1. NORMAL LIGHT SCENE)


Calculation objects

99
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 · CONTROL ROOM ( 1. NORMAL LIGHT SCENE)


Calculation objects

Working planes

Properties Ē Emin Emax Uo (g1 ) g2 Index

Working plane (CONTROL ROOM) 559 lx 397 lx 677 lx 0.71 0.59 WP6
Perpendicular illuminance
Height: 0.800 m, Wall zone: 0.300 m

Utilisation profile: General areas inside buildings - Control rooms (11.1 Plant rooms, switchgear rooms)

100
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 · CONTROL ROOM ( 2. EMERGENCY LIGHT SCENE)


Calculation objects

101
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 · CONTROL ROOM ( 2. EMERGENCY LIGHT SCENE)


Calculation objects

Working planes

Properties Ē Emin Emax Uo (g1 ) g2 Index

Working plane (CONTROL ROOM) 280 lx 90.5 lx 424 lx 0.32 0.21 WP6
Perpendicular illuminance
Height: 0.800 m, Wall zone: 0.300 m

Utilisation profile: General areas inside buildings - Control rooms (11.1 Plant rooms, switchgear rooms)

102
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 · CORRIDOR ( 1. NORMAL LIGHT SCENE)


Summary

Ground area 73.84 m² Clearance height 4.800 m

Reflection factors Ceiling: 80.0 %, Mounting height 3.000 m


Walls: 50.0 %,
Floor: 20.0 % Height Working plane 0.000 m

Maintenance factor 0.80 (fixed) Wall zone Working plane 0.000 m

103
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 · CORRIDOR ( 1. NORMAL LIGHT SCENE)


Summary

Results

Symbol Calculated Index

Working plane Ēperpendicular 145 lx WP15

Uo (g1 ) 0.64 WP15

Lighting power density 3.22 W/m²

2.23 W/m²/100 lx

Glare valuation(1) RUG, max 23

Energy estimation(2) Consumption 458 kWh/a

Room Lighting power density 3.22 W/m²

2.23 W/m²/100 lx

(1) Based on a rectangular space of 30.254 m x 6.588 m and SHR of 0.25.


(2) Calculated using DIN:18599-4.

Utilisation profile: Places of public assembly - General areas (36.1 Entrance halls)

Luminaire list

pcs. Manufacturer Article No. Article name RUG P Φ Luminous efficacy

13 Philips DN470B WR LED20S/- NO 23 18.3 W 1837 lm 100.4 lm/W

104
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 · CORRIDOR ( 2. EMERGENCY LIGHT SCENE)


Summary

Ground area 73.84 m² Clearance height 4.800 m

Reflection factors Ceiling: 80.0 %, Mounting height 3.000 m


Walls: 50.0 %,
Floor: 20.0 % Height Working plane 0.000 m

Maintenance factor 0.80 (fixed) Wall zone Working plane 0.000 m

105
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 · CORRIDOR ( 2. EMERGENCY LIGHT SCENE)


Summary

Results

Symbol Calculated Index

Working plane Ēperpendicular 46.1 lx WP15

Uo (g1 ) 0.046 WP15

Lighting power density 0.99 W/m²

2.15 W/m²/100 lx

Glare valuation(1) RUG, max 23

Energy estimation(2) Consumption 141 kWh/a

Room Lighting power density 0.99 W/m²

2.15 W/m²/100 lx

(1) Based on a rectangular space of 30.254 m x 6.588 m and SHR of 0.25.


(2) Calculated using DIN:18599-4.

Utilisation profile: Places of public assembly - General areas (36.1 Entrance halls)

Luminaire list

pcs. Manufacturer Article No. Article name RUG P Φ Luminous efficacy

4 Philips DN470B WR LED20S/- NO 23 18.3 W 1837 lm 100.4 lm/W

106
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 · CORRIDOR (3. ESCAPE)


Summary

Ground area 73.84 m² Clearance height 4.800 m

Reflection factors Ceiling: 80.0 %, Mounting height 3.000 m


Walls: 50.0 %,
Floor: 20.0 % Height Working plane 0.000 m

Maintenance factor 0.80 (fixed) Wall zone Working plane 0.000 m

107
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 · CORRIDOR (3. ESCAPE)


Summary

Results

Symbol Calculated Target Check Index

Room Lighting power density 0.11 W/m² –

(2) Calculated using DIN:18599-4.

Notes on planning:
The emergency lighting scene was calculated without reflection and taking into account the placed furniture.

Luminaire list

pcs. Manufacturer Article No. Article name P Φ Luminous efficacy

4 Philips 91240148 EM152C SM 2S CO NM3 ELP WH IP65 2.0 W 250 lm (100 %) –


3507

108
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 · CORRIDOR


Luminaire layout plan

109
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 · CORRIDOR


Luminaire layout plan

Manufacturer Philips P 18.3 W

Article name DN470B WR ΦLuminaire 1837 lm


LED20S/- NO

Fitting 1x LED20S/840/-

13 x Philips DN470B WR LED20S/- NO

Type Field Arrangement X Y Mounting Luminaire


height
1st luminaire (X/Y/Z) 1.361 m / 1.367 m /
3.000 m 5.754 m 28.860 m 3.000 m 5

X-direction 3 pcs., Centre - 1.361 m 28.860 m 3.000 m 6


centre, 2.197 m
3.558 m 28.860 m 3.000 m 7
Y-direction 11 pcs., Centre -
centre, 2.749 m 1.361 m 26.111 m 3.000 m 8

Arrangement A1 1.361 m 23.361 m 3.000 m 9

1.361 m 20.612 m 3.000 m 10

1.361 m 17.863 m 3.000 m 11

1.361 m 15.114 m 3.000 m 12

1.361 m 12.364 m 3.000 m 13

1.361 m 9.615 m 3.000 m 14

1.361 m 6.866 m 3.000 m 15

1.361 m 4.116 m 3.000 m 16

1.361 m 1.367 m 3.000 m 17

110
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 · CORRIDOR


Luminaire layout plan

Manufacturer Philips P 0.0 W

Article No. 912401483507 PEmergency lighting 2.0 W

Article name EM152C SM 2S CO ΦLuminaire 0 lm


NM3 ELP WH IP65
ΦEmergency lighting 250 lm
Fitting 1x LED/6500
ELF 100 %

Individual luminaires

X Y Mounting Luminaire
height

4.613 m 28.844 m 3.000 m 1

1.366 m 21.970 m 3.000 m 2

1.366 m 13.758 m 3.000 m 3

1.366 m 5.564 m 3.000 m 4

111
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 · CORRIDOR ( 1. NORMAL LIGHT SCENE)


Calculation objects

112
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 · CORRIDOR ( 1. NORMAL LIGHT SCENE)


Calculation objects

Working planes

Properties Ē Emin Emax Uo (g1 ) g2 Index

Working plane (CORRIDOR) 145 lx 93.3 lx 186 lx 0.64 0.50 WP15


Perpendicular illuminance
Height: 0.000 m, Wall zone: 0.000 m

Utilisation profile: Places of public assembly - General areas (36.1 Entrance halls)

113
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 · CORRIDOR ( 2. EMERGENCY LIGHT SCENE)


Calculation objects

114
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 · CORRIDOR ( 2. EMERGENCY LIGHT SCENE)


Calculation objects

Working planes

Properties Ē Emin Emax Uo (g1 ) g2 Index

Working plane (CORRIDOR) 46.1 lx 2.12 lx 102 lx 0.046 0.021 WP15


Perpendicular illuminance
Height: 0.000 m, Wall zone: 0.000 m

Utilisation profile: Places of public assembly - General areas (36.1 Entrance halls)

115
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 · DOCUMENTS ROOM ( 1. NORMAL LIGHT SCENE)


Summary

Ground area 15.64 m² Clearance height 4.800 m

Reflection factors Ceiling: 80.0 %, Mounting height 3.000 m


Walls: 50.0 %,
Floor: 20.0 % Height Working plane 0.800 m

Maintenance factor 0.80 (fixed) Wall zone Working plane 0.000 m

116
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 · DOCUMENTS ROOM ( 1. NORMAL LIGHT SCENE)


Summary

Results

Symbol Calculated Index

Working plane Ēperpendicular 344 lx WP7

Uo (g1 ) 0.52 WP7

Glare valuation(1) RUG, max 17

Energy estimation(2) Consumption 154 kWh/a

Room Lighting power density 5.12 W/m²

1.49 W/m²/100 lx

(1) Based on a rectangular space of 4.205 m x 3.745 m and SHR of 0.25.


(2) Calculated using DIN:18599-4.

Utilisation profile: Places of public assembly - General areas (36.1 Entrance halls)

Luminaire list

pcs. Manufacturer Article No. Article name RUG P Φ Luminous efficacy

2 Philips RC132V G5 PSD W60L60 OC 17 40.0 W 4789 lm 119.7 lm/W


48S/840 NO
– 40.0 W 4789 lm (100 %) –

117
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 · DOCUMENTS ROOM ( 2. EMERGENCY LIGHT SCENE)


Summary

Ground area 15.64 m² Clearance height 4.800 m

Reflection factors Ceiling: 80.0 %, Mounting height 3.000 m


Walls: 50.0 %,
Floor: 20.0 % Height Working plane 0.800 m

Maintenance factor 0.80 (fixed) Wall zone Working plane 0.000 m

118
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 · DOCUMENTS ROOM ( 2. EMERGENCY LIGHT SCENE)


Summary

Results

Symbol Calculated Index

Working plane Ēperpendicular 172 lx WP7

Uo (g1 ) 0.21 WP7

Glare valuation(1) RUG, max 17

Energy estimation(2) Consumption 77.0 kWh/a

Room Lighting power density 2.56 W/m²

1.49 W/m²/100 lx

(1) Based on a rectangular space of 4.205 m x 3.745 m and SHR of 0.25.


(2) Calculated using DIN:18599-4.

Utilisation profile: Places of public assembly - General areas (36.1 Entrance halls)

Luminaire list

pcs. Manufacturer Article No. Article name RUG P Φ Luminous efficacy

1 Philips RC132V G5 PSD W60L60 OC 17 40.0 W 4789 lm 119.7 lm/W


48S/840 NO
– 40.0 W 4789 lm (100 %) –

119
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 · DOCUMENTS ROOM (3. ESCAPE)


Summary

Ground area 15.64 m²

Reflection factors Ceiling: 80.0 %, Clearance height 4.800 m


Walls: 50.0 %,
Floor: 20.0 % Height Working plane 0.800 m

Maintenance factor 0.80 (fixed) Wall zone Working plane 0.000 m

120
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 · DOCUMENTS ROOM (3. ESCAPE)


Summary

Results

Symbol Calculated Target Check Index

Room Lighting power density 0.00 W/m² –

(2) Calculated using DIN:18599-4.

Notes on planning:
The emergency lighting scene was calculated without reflection and taking into account the placed furniture.

121
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 · DOCUMENTS ROOM


Luminaire layout plan

122
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 · DOCUMENTS ROOM


Luminaire layout plan

Manufacturer Philips P 40.0 W

Article name RC132V G5 PSD PEmergency lighting 40.0 W


W60L60 OC 48S/840
NO ΦLuminaire 4789 lm

Fitting 1x 48S/840 ΦEmergency lighting 4789 lm

ELF 100 %

2 x Philips RC132V G5 PSD W60L60 OC 48S/840 NO

Type Line arrangement X Y Mounting Luminaire


height
1st luminaire (X/Y/Z) 1.054 m / 1.927 m /
3.000 m 1.054 m 1.927 m 3.000 m 1

X-direction 2 pcs., Centre - 3.139 m 1.927 m 3.000 m 2


centre, 2.085 m

Arrangement A1

123
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 · DOCUMENTS ROOM ( 1. NORMAL LIGHT SCENE)


Calculation objects

124
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 · DOCUMENTS ROOM ( 1. NORMAL LIGHT SCENE)


Calculation objects

Working planes

Properties Ē Emin Emax Uo (g1 ) g2 Index

Working plane (DOCUMENTS ROOM) 344 lx 178 lx 519 lx 0.52 0.34 WP7
Perpendicular illuminance
Height: 0.800 m, Wall zone: 0.000 m

Utilisation profile: Places of public assembly - General areas (36.1 Entrance halls)

125
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 · DOCUMENTS ROOM ( 2. EMERGENCY LIGHT SCENE)


Calculation objects

126
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 · DOCUMENTS ROOM ( 2. EMERGENCY LIGHT SCENE)


Calculation objects

Working planes

Properties Ē Emin Emax Uo (g1 ) g2 Index

Working plane (DOCUMENTS ROOM) 172 lx 35.6 lx 384 lx 0.21 0.093 WP7
Perpendicular illuminance
Height: 0.800 m, Wall zone: 0.000 m

Utilisation profile: Places of public assembly - General areas (36.1 Entrance halls)

127
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 · ELECTRICAL ROOM ( 1. NORMAL LIGHT SCENE)


Summary

Ground area 14.35 m² Clearance height 4.800 m

Reflection factors Ceiling: 80.0 %, Mounting height 4.500 m


Walls: 50.0 %,
Floor: 20.0 % Height Working plane 0.800 m

Maintenance factor 0.80 (fixed) Wall zone Working plane 0.000 m

128
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 · ELECTRICAL ROOM ( 1. NORMAL LIGHT SCENE)


Summary

Results

Symbol Calculated Index

Working plane Ēperpendicular 361 lx WP12

Uo (g1 ) 0.75 WP12

Glare valuation(1) RUG, max 21

Energy estimation(2) Consumption 261 kWh/a

Room Lighting power density 8.09 W/m²

2.24 W/m²/100 lx

(1) Based on a rectangular space of 4.190 m x 3.770 m and SHR of 0.25.


(2) Calculated using DIN:18599-4.

Utilisation profile: Industrial activities and crafts - Electrical and electronics industry (19.1 Cable and wire manufacture)

Luminaire list

pcs. Manufacturer Article No. Article name RUG P Φ Luminous efficacy

2 Philips WT470X L1600 WB LED80S/- NO 21 58.0 W 8006 lm 138.0 lm/W

– 58.0 W 8006 lm (100 %) –

129
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 · ELECTRICAL ROOM ( 2. EMERGENCY LIGHT SCENE)


Summary

Ground area 14.35 m² Clearance height 4.800 m

Reflection factors Ceiling: 80.0 %, Mounting height 4.500 m


Walls: 50.0 %,
Floor: 20.0 % Height Working plane 0.800 m

Maintenance factor 0.80 (fixed) Wall zone Working plane 0.000 m

130
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 · ELECTRICAL ROOM ( 2. EMERGENCY LIGHT SCENE)


Summary

Results

Symbol Calculated Index

Working plane Ēperpendicular 179 lx WP12

Uo (g1 ) 0.54 WP12

Glare valuation(1) RUG, max 21

Energy estimation(2) Consumption 131 kWh/a

Room Lighting power density 4.04 W/m²

2.26 W/m²/100 lx

(1) Based on a rectangular space of 4.190 m x 3.770 m and SHR of 0.25.


(2) Calculated using DIN:18599-4.

Utilisation profile: Industrial activities and crafts - Electrical and electronics industry (19.1 Cable and wire manufacture)

Luminaire list

pcs. Manufacturer Article No. Article name RUG P Φ Luminous efficacy

1 Philips WT470X L1600 WB LED80S/- NO 21 58.0 W 8006 lm 138.0 lm/W

– 58.0 W 8006 lm (100 %) –

131
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 · ELECTRICAL ROOM (3. ESCAPE)


Summary

Ground area 14.35 m² Clearance height 4.800 m

Reflection factors Ceiling: 80.0 %, Mounting height 4.600 m


Walls: 50.0 %,
Floor: 20.0 % Height Working plane 0.800 m

Maintenance factor 0.80 (fixed) Wall zone Working plane 0.000 m

132
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 · ELECTRICAL ROOM (3. ESCAPE)


Summary

Results

Symbol Calculated Target Check Index

Room Lighting power density 0.14 W/m² –

(2) Calculated using DIN:18599-4.

Notes on planning:
The emergency lighting scene was calculated without reflection and taking into account the placed furniture.

Luminaire list

pcs. Manufacturer Article No. Article name P Φ Luminous efficacy

1 Philips 91240148 EM152C SM 2S CO NM3 ELP WH IP65 2.0 W 250 lm (100 %) –


3507

133
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 · ELECTRICAL ROOM


Luminaire layout plan

134
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 · ELECTRICAL ROOM


Luminaire layout plan

Manufacturer Philips P 58.0 W

Article name WT470X L1600 WB PEmergency lighting 58.0 W


LED80S/- NO
ΦLuminaire 8006 lm
Fitting 1x LED80S/840/-
ΦEmergency lighting 8006 lm

ELF 100 %

2 x Philips WT470X L1600 WB LED80S/- NO

Type Field Arrangement X Y Mounting Luminaire


height
1st luminaire (X/Y/Z) 1.039 m / 1.910 m /
4.500 m 1.039 m 1.910 m 4.500 m 2

X-direction 2 pcs., Centre - 3.140 m 1.910 m 4.500 m 3


centre, 2.101 m

Y-direction 1 pcs., Centre -


centre, 3.200 m

Arrangement A1

135
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 · ELECTRICAL ROOM


Luminaire layout plan

Manufacturer Philips P 0.0 W

Article No. 912401483507 PEmergency lighting 2.0 W

Article name EM152C SM 2S CO ΦLuminaire 0 lm


NM3 ELP WH IP65
ΦEmergency lighting 250 lm
Fitting 1x LED/6500
ELF 100 %

Individual luminaires

X Y Mounting Luminaire
height

2.082 m 1.907 m 4.600 m 1

136
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 · ELECTRICAL ROOM ( 1. NORMAL LIGHT SCENE)


Calculation objects

137
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 · ELECTRICAL ROOM ( 1. NORMAL LIGHT SCENE)


Calculation objects

Working planes

Properties Ē Emin Emax Uo (g1 ) g2 Index

Working plane (ELECTRICAL ROOM) 361 lx 270 lx 407 lx 0.75 0.66 WP12
Perpendicular illuminance
Height: 0.800 m, Wall zone: 0.000 m

Utilisation profile: Industrial activities and crafts - Electrical and electronics industry (19.1 Cable and wire manufacture)

138
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 · ELECTRICAL ROOM ( 2. EMERGENCY LIGHT SCENE)


Calculation objects

139
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 · ELECTRICAL ROOM ( 2. EMERGENCY LIGHT SCENE)


Calculation objects

Working planes

Properties Ē Emin Emax Uo (g1 ) g2 Index

Working plane (ELECTRICAL ROOM) 179 lx 96.1 lx 213 lx 0.54 0.45 WP12
Perpendicular illuminance
Height: 0.800 m, Wall zone: 0.000 m

Utilisation profile: Industrial activities and crafts - Electrical and electronics industry (19.1 Cable and wire manufacture)

140
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 · ENGINEER'S ROOM ( 1. NORMAL LIGHT SCENE)


Summary

Ground area 15.87 m² Clearance height 4.800 m

Reflection factors Ceiling: 80.0 %, Mounting height 3.000 m


Walls: 50.0 %,
Floor: 20.0 % Height Working plane 0.800 m

Maintenance factor 0.80 (fixed) Wall zone Working plane 0.300 m

141
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 · ENGINEER'S ROOM ( 1. NORMAL LIGHT SCENE)


Summary

Results

Symbol Calculated Index

Working plane Ēperpendicular 381 lx WP9

Uo (g1 ) 0.66 WP9

Lighting power density 6.99 W/m²

1.84 W/m²/100 lx

Glare valuation(1) RUG, max 17

Energy estimation(2) Consumption 180 kWh/a

Room Lighting power density 5.04 W/m²

1.32 W/m²/100 lx

(1) Based on a rectangular space of 3.779 m x 4.221 m and SHR of 0.25.


(2) Calculated using DIN:18599-4.

Utilisation profile: Industrial activities and crafts - Electrical and electronics industry (19.1 Cable and wire manufacture)

Luminaire list

pcs. Manufacturer Article No. Article name RUG P Φ Luminous efficacy

2 Philips RC132V G5 PSD W60L60 OC 17 40.0 W 4789 lm 119.7 lm/W


48S/840 NO
– 40.0 W 4789 lm (100 %) –

142
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 · ENGINEER'S ROOM ( 2. EMERGENCY LIGHT SCENE)


Summary

Ground area 15.87 m² Clearance height 4.800 m

Reflection factors Ceiling: 80.0 %, Mounting height 3.000 m


Walls: 50.0 %,
Floor: 20.0 % Height Working plane 0.800 m

Maintenance factor 0.80 (fixed) Wall zone Working plane 0.300 m

143
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 · ENGINEER'S ROOM ( 2. EMERGENCY LIGHT SCENE)


Summary

Results

Symbol Calculated Index

Working plane Ēperpendicular 190 lx WP9

Uo (g1 ) 0.25 WP9

Lighting power density 3.49 W/m²

1.84 W/m²/100 lx

Glare valuation(1) RUG, max 17

Energy estimation(2) Consumption 90.0 kWh/a

Room Lighting power density 2.52 W/m²

1.33 W/m²/100 lx

(1) Based on a rectangular space of 3.779 m x 4.221 m and SHR of 0.25.


(2) Calculated using DIN:18599-4.

Utilisation profile: Industrial activities and crafts - Electrical and electronics industry (19.1 Cable and wire manufacture)

Luminaire list

pcs. Manufacturer Article No. Article name RUG P Φ Luminous efficacy

1 Philips RC132V G5 PSD W60L60 OC 17 40.0 W 4789 lm 119.7 lm/W


48S/840 NO
– 40.0 W 4789 lm (100 %) –

144
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 · ENGINEER'S ROOM (3. ESCAPE)


Summary

Ground area 15.87 m² Clearance height 4.800 m

Reflection factors Ceiling: 80.0 %, Mounting height 3.000 m


Walls: 50.0 %,
Floor: 20.0 % Height Working plane 0.800 m

Maintenance factor 0.80 (fixed) Wall zone Working plane 0.300 m

145
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 · ENGINEER'S ROOM (3. ESCAPE)


Summary

Results

Symbol Calculated Target Check Index

Room Lighting power density 0.13 W/m² –

(2) Calculated using DIN:18599-4.

Notes on planning:
The emergency lighting scene was calculated without reflection and taking into account the placed furniture.

Luminaire list

pcs. Manufacturer Article No. Article name P Φ Luminous efficacy

1 Philips 91240148 EM152C SM 2S CO NM3 ELP WH IP65 2.0 W 250 lm (100 %) –


3507

146
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 · ENGINEER'S ROOM


Luminaire layout plan

147
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 · ENGINEER'S ROOM


Luminaire layout plan

Manufacturer Philips P 40.0 W

Article name RC132V G5 PSD PEmergency lighting 40.0 W


W60L60 OC 48S/840
NO ΦLuminaire 4789 lm

Fitting 1x 48S/840 ΦEmergency lighting 4789 lm

ELF 100 %

2 x Philips RC132V G5 PSD W60L60 OC 48S/840 NO

Type Field Arrangement X Y Mounting Luminaire


height
1st luminaire (X/Y/Z) 1.054 m / 1.888 m /
3.000 m 1.054 m 1.888 m 3.000 m 2

X-direction 2 pcs., Centre - 3.149 m 1.888 m 3.000 m 3


centre, Distances not
equal

Y-direction 1 pcs., Centre -


centre, Distances not
equal

Arrangement A1

148
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 · ENGINEER'S ROOM


Luminaire layout plan

Manufacturer Philips P 0.0 W

Article No. 912401483507 PEmergency lighting 2.0 W

Article name EM152C SM 2S CO ΦLuminaire 0 lm


NM3 ELP WH IP65
ΦEmergency lighting 250 lm
Fitting 1x LED/6500
ELF 100 %

Individual luminaires

X Y Mounting Luminaire
height

3.169 m 0.947 m 3.000 m 1

149
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 · ENGINEER'S ROOM ( 1. NORMAL LIGHT SCENE)


Calculation objects

150
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 · ENGINEER'S ROOM ( 1. NORMAL LIGHT SCENE)


Calculation objects

Working planes

Properties Ē Emin Emax Uo (g1 ) g2 Index

Working plane (ENGINEER'S ROOM) 381 lx 250 lx 504 lx 0.66 0.50 WP9
Perpendicular illuminance
Height: 0.800 m, Wall zone: 0.300 m

Utilisation profile: Industrial activities and crafts - Electrical and electronics industry (19.1 Cable and wire manufacture)

151
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 · ENGINEER'S ROOM ( 2. EMERGENCY LIGHT SCENE)


Calculation objects

152
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 · ENGINEER'S ROOM ( 2. EMERGENCY LIGHT SCENE)


Calculation objects

Working planes

Properties Ē Emin Emax Uo (g1 ) g2 Index

Working plane (ENGINEER'S ROOM) 190 lx 47.0 lx 383 lx 0.25 0.12 WP9
Perpendicular illuminance
Height: 0.800 m, Wall zone: 0.300 m

Utilisation profile: Industrial activities and crafts - Electrical and electronics industry (19.1 Cable and wire manufacture)

153
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 · MEETING ROOM ( 1. NORMAL LIGHT SCENE)


Summary

Ground area 24.05 m² Clearance height 4.800 m

Reflection factors Ceiling: 80.0 %, Mounting height 3.000 m


Walls: 50.0 %,
Floor: 20.0 % Height Working plane 0.800 m

Maintenance factor 0.80 (fixed) Wall zone Working plane 0.000 m

154
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 · MEETING ROOM ( 1. NORMAL LIGHT SCENE)


Summary

Results

Symbol Calculated Index

Working plane Ēperpendicular 507 lx WP10

Uo (g1 ) 0.68 WP10

Glare valuation(1) RUG, max 16

Energy estimation(2) Consumption 393 kWh/a

Room Lighting power density 8.48 W/m²

1.67 W/m²/100 lx

(1) Based on a rectangular space of 5.770 m x 4.205 m and SHR of 0.25.


(2) Calculated using DIN:18599-4.

Utilisation profile: Health care premises - Rooms for general use (45.1 Waiting rooms)

Luminaire list

pcs. Manufacturer Article No. Article name RUG P Φ Luminous efficacy

6 Philips RC132V G5 WIA W60L60 ELB3 16 34.0 W 3592 lm 105.6 lm/W


OC 36S/840 NO
– 34.0 W 3592 lm (100 %) –

155
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 · MEETING ROOM ( 2. EMERGENCY LIGHT SCENE)


Summary

Ground area 24.05 m² Clearance height 4.800 m

Reflection factors Ceiling: 80.0 %, Mounting height 3.000 m


Walls: 50.0 %,
Floor: 20.0 % Height Working plane 0.800 m

Maintenance factor 0.80 (fixed) Wall zone Working plane 0.000 m

156
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 · MEETING ROOM ( 2. EMERGENCY LIGHT SCENE)


Summary

Results

Symbol Calculated Index

Working plane Ēperpendicular 253 lx WP10

Uo (g1 ) 0.33 WP10

Glare valuation(1) RUG, max 16

Energy estimation(2) Consumption 196 kWh/a

Room Lighting power density 4.24 W/m²

1.67 W/m²/100 lx

(1) Based on a rectangular space of 5.770 m x 4.205 m and SHR of 0.25.


(2) Calculated using DIN:18599-4.

Utilisation profile: Health care premises - Rooms for general use (45.1 Waiting rooms)

Luminaire list

pcs. Manufacturer Article No. Article name RUG P Φ Luminous efficacy

3 Philips RC132V G5 WIA W60L60 ELB3 16 34.0 W 3592 lm 105.6 lm/W


OC 36S/840 NO
– 34.0 W 3592 lm (100 %) –

157
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 · MEETING ROOM (3. ESCAPE)


Summary

Ground area 24.05 m² Clearance height 4.800 m

Reflection factors Ceiling: 80.0 %, Mounting height 3.000 m


Walls: 50.0 %,
Floor: 20.0 % Height Working plane 0.800 m

Maintenance factor 0.80 (fixed) Wall zone Working plane 0.000 m

158
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 · MEETING ROOM (3. ESCAPE)


Summary

Results

Symbol Calculated Target Check Index

Room Lighting power density 0.17 W/m² –

(2) Calculated using DIN:18599-4.

Notes on planning:
The emergency lighting scene was calculated without reflection and taking into account the placed furniture.

Luminaire list

pcs. Manufacturer Article No. Article name P Φ Luminous efficacy

2 Philips 91240148 EM152C SM 2S CO NM3 ELP WH IP65 2.0 W 250 lm (100 %) –


3507

159
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 · MEETING ROOM


Luminaire layout plan

160
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 · MEETING ROOM


Luminaire layout plan

Manufacturer Philips P 34.0 W

Article name RC132V G5 WIA PEmergency lighting 34.0 W


W60L60 ELB3 OC
36S/840 NO ΦLuminaire 3592 lm

Fitting 1x 36S/840 ΦEmergency lighting 3592 lm

ELF 100 %

6 x Philips RC132V G5 WIA W60L60 ELB3 OC 36S/840 NO

Type Field Arrangement X Y Mounting Luminaire


height
1st luminaire (X/Y/Z) 1.035 m / 0.977 m /
3.000 m 1.056 m 4.825 m 3.000 m 3

X-direction 2 pcs., Centre - 3.163 m 4.813 m 3.000 m 4


centre, 2.107 m
1.046 m 2.901 m 3.000 m 5
Y-direction 3 pcs., Centre -
centre, 1.924 m 3.152 m 2.889 m 3.000 m 6

Arrangement A1 1.035 m 0.977 m 3.000 m 7

3.142 m 0.965 m 3.000 m 8

161
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 · MEETING ROOM


Luminaire layout plan

Manufacturer Philips P 0.0 W

Article No. 912401483507 PEmergency lighting 2.0 W

Article name EM152C SM 2S CO ΦLuminaire 0 lm


NM3 ELP WH IP65
ΦEmergency lighting 250 lm
Fitting 1x LED/6500
ELF 100 %

Individual luminaires

X Y Mounting Luminaire
height

2.128 m 4.833 m 3.000 m 1

3.142 m 2.014 m 3.000 m 2

162
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 · MEETING ROOM ( 1. NORMAL LIGHT SCENE)


Calculation objects

163
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 · MEETING ROOM ( 1. NORMAL LIGHT SCENE)


Calculation objects

Working planes

Properties Ē Emin Emax Uo (g1 ) g2 Index

Working plane (MEETING ROOM) 507 lx 347 lx 621 lx 0.68 0.56 WP10
Perpendicular illuminance
Height: 0.800 m, Wall zone: 0.000 m

Utilisation profile: Health care premises - Rooms for general use (45.1 Waiting rooms)

164
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 · MEETING ROOM ( 2. EMERGENCY LIGHT SCENE)


Calculation objects

165
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 · MEETING ROOM ( 2. EMERGENCY LIGHT SCENE)


Calculation objects

Working planes

Properties Ē Emin Emax Uo (g1 ) g2 Index

Working plane (MEETING ROOM) 253 lx 83.4 lx 353 lx 0.33 0.24 WP10
Perpendicular illuminance
Height: 0.800 m, Wall zone: 0.000 m

Utilisation profile: Health care premises - Rooms for general use (45.1 Waiting rooms)

166
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 · OFFICE ( 1. NORMAL LIGHT SCENE)


Summary

Ground area 15.76 m² Clearance height 4.800 m

Reflection factors Ceiling: 80.0 %, Mounting height 3.000 m


Walls: 50.0 %,
Floor: 20.0 % Height Working plane 0.800 m

Maintenance factor 0.80 (fixed) Wall zone Working plane 0.300 m

167
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 · OFFICE ( 1. NORMAL LIGHT SCENE)


Summary

Results

Symbol Calculated Index

Working plane Ēperpendicular 579 lx WP3

Uo (g1 ) 0.62 WP3

Lighting power density 12.04 W/m²

2.08 W/m²/100 lx

Glare valuation(1) RUG, max 16

Energy estimation(2) Consumption 337 kWh/a

Room Lighting power density 8.63 W/m²

1.49 W/m²/100 lx

(1) Based on a rectangular space of 4.190 m x 3.770 m and SHR of 0.25.


(2) Calculated using DIN:18599-4.

Utilisation profile: DIALux presetting (34.2 Standard (office))

Luminaire list

pcs. Manufacturer Article No. Article name RUG P Φ Luminous efficacy

4 Philips RC132V G5 WIA W60L60 ELB3 16 34.0 W 3592 lm 105.6 lm/W


OC 36S/840 NO
– 34.0 W 3592 lm (100 %) –

168
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 · OFFICE ( 2. EMERGENCY LIGHT SCENE)


Summary

Ground area 15.76 m² Clearance height 4.800 m

Reflection factors Ceiling: 80.0 %, Mounting height 3.000 m


Walls: 50.0 %,
Floor: 20.0 % Height Working plane 0.800 m

Maintenance factor 0.80 (fixed) Wall zone Working plane 0.300 m

169
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 · OFFICE ( 2. EMERGENCY LIGHT SCENE)


Summary

Results

Symbol Calculated Index

Working plane Ēperpendicular 290 lx WP3

Uo (g1 ) 0.42 WP3

Lighting power density 6.02 W/m²

2.08 W/m²/100 lx

Glare valuation(1) RUG, max 16

Energy estimation(2) Consumption 168 kWh/a

Room Lighting power density 4.32 W/m²

1.49 W/m²/100 lx

(1) Based on a rectangular space of 4.190 m x 3.770 m and SHR of 0.25.


(2) Calculated using DIN:18599-4.

Utilisation profile: DIALux presetting (34.2 Standard (office))

Luminaire list

pcs. Manufacturer Article No. Article name RUG P Φ Luminous efficacy

2 Philips RC132V G5 WIA W60L60 ELB3 16 34.0 W 3592 lm 105.6 lm/W


OC 36S/840 NO
– 34.0 W 3592 lm (100 %) –

170
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 · OFFICE (3. ESCAPE)


Summary

Ground area 15.76 m² Clearance height 4.800 m

Reflection factors Ceiling: 80.0 %, Mounting height 3.000 m


Walls: 50.0 %,
Floor: 20.0 % Height Working plane 0.800 m

Maintenance factor 0.80 (fixed) Wall zone Working plane 0.300 m

171
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 · OFFICE (3. ESCAPE)


Summary

Results

Symbol Calculated Target Check Index

Room Lighting power density 0.13 W/m² –

(2) Calculated using DIN:18599-4.

Notes on planning:
The emergency lighting scene was calculated without reflection and taking into account the placed furniture.

Luminaire list

pcs. Manufacturer Article No. Article name P Φ Luminous efficacy

1 Philips 91240148 EM152C SM 2S CO NM3 ELP WH IP65 2.0 W 250 lm (100 %) –


3507

172
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 · OFFICE


Luminaire layout plan

173
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 · OFFICE


Luminaire layout plan

Manufacturer Philips P 34.0 W

Article name RC132V G5 WIA PEmergency lighting 34.0 W


W60L60 ELB3 OC
36S/840 NO ΦLuminaire 3592 lm

Fitting 1x 36S/840 ΦEmergency lighting 3592 lm

ELF 100 %

4 x Philips RC132V G5 WIA W60L60 ELB3 OC 36S/840 NO

Type Field Arrangement X Y Mounting Luminaire


height
1st luminaire (X/Y/Z) 1.400 m / 1.266 m /
3.000 m 1.390 m 2.608 m 3.000 m 2

X-direction 2 pcs., Centre - 2.775 m 2.619 m 3.000 m 3


centre, Distances not
equal 1.400 m 1.266 m 3.000 m 4

Y-direction 2 pcs., Centre - 2.786 m 1.277 m 3.000 m 5


centre, Distances not
equal

Arrangement A1

174
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 · OFFICE


Luminaire layout plan

Manufacturer Philips P 0.0 W

Article No. 912401483507 PEmergency lighting 2.0 W

Article name EM152C SM 2S CO ΦLuminaire 0 lm


NM3 ELP WH IP65
ΦEmergency lighting 250 lm
Fitting 1x LED/6500
ELF 100 %

Individual luminaires

X Y Mounting Luminaire
height

2.088 m 1.277 m 3.000 m 1

175
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 · OFFICE ( 1. NORMAL LIGHT SCENE)


Calculation objects

176
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 · OFFICE ( 1. NORMAL LIGHT SCENE)


Calculation objects

Working planes

Properties Ē Emin Emax Uo (g1 ) g2 Index

Working plane (OFFICE) 579 lx 358 lx 809 lx 0.62 0.44 WP3


Perpendicular illuminance
Height: 0.800 m, Wall zone: 0.300 m

Utilisation profile: DIALux presetting (34.2 Standard (office))

177
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 · OFFICE ( 2. EMERGENCY LIGHT SCENE)


Calculation objects

178
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 · OFFICE ( 2. EMERGENCY LIGHT SCENE)


Calculation objects

Working planes

Properties Ē Emin Emax Uo (g1 ) g2 Index

Working plane (OFFICE) 290 lx 122 lx 403 lx 0.42 0.30 WP3


Perpendicular illuminance
Height: 0.800 m, Wall zone: 0.300 m

Utilisation profile: DIALux presetting (34.2 Standard (office))

179
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 · TELECOM ROOM ( 1. NORMAL LIGHT SCENE)


Summary

Ground area 21.96 m² Clearance height 4.800 m

Reflection factors Ceiling: 80.0 %, Mounting height 3.000 m


Walls: 50.0 %,
Floor: 20.0 % Height Working plane 0.800 m

Maintenance factor 0.80 (fixed) Wall zone Working plane 0.000 m

180
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 · TELECOM ROOM ( 1. NORMAL LIGHT SCENE)


Summary

Results

Symbol Calculated Index

Working plane Ēperpendicular 347 lx WP2

Uo (g1 ) 0.63 WP2

Glare valuation(1) RUG, max 19

Energy estimation(2) Consumption 282 kWh/a

Room Lighting power density 5.19 W/m²

1.50 W/m²/100 lx

(1) Based on a rectangular space of 4.194 m x 5.256 m and SHR of 0.25.


(2) Calculated using DIN:18599-4.

Utilisation profile: General areas inside buildings - Store rooms, cold stores (12.1 Store and stockrooms)

Luminaire list

pcs. Manufacturer Article No. Article name RUG P Φ Luminous efficacy

4 Philips RC133V G5 BN PSU W62L62 19 28.5 W 3600 lm 126.3 lm/W


NOC 36S/840 NO
– 28.5 W 3600 lm (100 %) –

181
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 · TELECOM ROOM ( 2. EMERGENCY LIGHT SCENE)


Summary

Ground area 21.96 m² Clearance height 4.800 m

Reflection factors Ceiling: 80.0 %, Mounting height 3.000 m


Walls: 50.0 %,
Floor: 20.0 % Height Working plane 0.800 m

Maintenance factor 0.80 (fixed) Wall zone Working plane 0.000 m

182
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 · TELECOM ROOM ( 2. EMERGENCY LIGHT SCENE)


Summary

Results

Symbol Calculated Index

Working plane Ēperpendicular 174 lx WP2

Uo (g1 ) 0.40 WP2

Glare valuation(1) RUG, max 19

Energy estimation(2) Consumption 141 kWh/a

Room Lighting power density 2.60 W/m²

1.50 W/m²/100 lx

(1) Based on a rectangular space of 4.194 m x 5.256 m and SHR of 0.25.


(2) Calculated using DIN:18599-4.

Utilisation profile: General areas inside buildings - Store rooms, cold stores (12.1 Store and stockrooms)

Luminaire list

pcs. Manufacturer Article No. Article name RUG P Φ Luminous efficacy

2 Philips RC133V G5 BN PSU W62L62 19 28.5 W 3600 lm 126.3 lm/W


NOC 36S/840 NO
– 28.5 W 3600 lm (100 %) –

183
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 · TELECOM ROOM (3. ESCAPE)


Summary

Ground area 21.96 m² Clearance height 4.800 m

Reflection factors Ceiling: 80.0 %, Mounting height 3.000 m


Walls: 50.0 %,
Floor: 20.0 % Height Working plane 0.800 m

Maintenance factor 0.80 (fixed) Wall zone Working plane 0.000 m

184
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 · TELECOM ROOM (3. ESCAPE)


Summary

Results

Symbol Calculated Target Check Index

Room Lighting power density 0.09 W/m² –

(2) Calculated using DIN:18599-4.

Notes on planning:
The emergency lighting scene was calculated without reflection and taking into account the placed furniture.

Luminaire list

pcs. Manufacturer Article No. Article name P Φ Luminous efficacy

1 Philips 91240148 EM152C SM 2S CO NM3 ELP WH IP65 2.0 W 250 lm (100 %) –


3507

185
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 · TELECOM ROOM


Luminaire layout plan

186
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 · TELECOM ROOM


Luminaire layout plan

Manufacturer Philips P 28.5 W

Article name RC133V G5 BN PSU PEmergency lighting 28.5 W


W62L62 NOC
36S/840 NO ΦLuminaire 3600 lm

Fitting 1x 36S/840 ΦEmergency lighting 3600 lm

ELF 100 %

4 x Philips RC133V G5 BN PSU W62L62 NOC 36S/840 NO

Type Field Arrangement X Y Mounting Luminaire


height
1st luminaire (X/Y/Z) 1.298 m / 1.396 m /
3.000 m 1.298 m 3.946 m 3.000 m 2

X-direction 2 pcs., Centre - 2.892 m 3.946 m 3.000 m 3


centre, Distances not
equal 1.298 m 1.396 m 3.000 m 4

Y-direction 2 pcs., Centre - 2.892 m 1.396 m 3.000 m 5


centre, Distances not
equal

Arrangement A1

187
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 · TELECOM ROOM


Luminaire layout plan

Manufacturer Philips P 0.0 W

Article No. 912401483507 PEmergency lighting 2.0 W

Article name EM152C SM 2S CO ΦLuminaire 0 lm


NM3 ELP WH IP65
ΦEmergency lighting 250 lm
Fitting 1x LED/6500
ELF 100 %

Individual luminaires

X Y Mounting Luminaire
height

2.001 m 2.538 m 3.000 m 1

188
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 · TELECOM ROOM ( 1. NORMAL LIGHT SCENE)


Calculation objects

189
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 · TELECOM ROOM ( 1. NORMAL LIGHT SCENE)


Calculation objects

Working planes

Properties Ē Emin Emax Uo (g1 ) g2 Index

Working plane (TELECOM ROOM) 347 lx 220 lx 448 lx 0.63 0.49 WP2
Perpendicular illuminance
Height: 0.800 m, Wall zone: 0.000 m

Utilisation profile: General areas inside buildings - Store rooms, cold stores (12.1 Store and stockrooms)

190
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 · TELECOM ROOM ( 2. EMERGENCY LIGHT SCENE)


Calculation objects

191
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 · TELECOM ROOM ( 2. EMERGENCY LIGHT SCENE)


Calculation objects

Working planes

Properties Ē Emin Emax Uo (g1 ) g2 Index

Working plane (TELECOM ROOM) 174 lx 69.1 lx 257 lx 0.40 0.27 WP2
Perpendicular illuminance
Height: 0.800 m, Wall zone: 0.000 m

Utilisation profile: General areas inside buildings - Store rooms, cold stores (12.1 Store and stockrooms)

192
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 · TOILET MALE ( 1. NORMAL LIGHT SCENE)


Summary

Ground area 13.22 m² Clearance height 4.800 m

Reflection factors Ceiling: 80.0 %, Mounting height 4.800 m


Walls: 50.0 %,
Floor: 20.0 % Height Working plane 0.800 m

Maintenance factor 0.80 (fixed) Wall zone Working plane 0.000 m

193
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 · TOILET MALE ( 1. NORMAL LIGHT SCENE)


Summary

Results

Symbol Calculated Index

Working plane Ēperpendicular 85.3 lx WP4

Uo (g1 ) 0.71 WP4

Glare valuation(1) RUG, max 22

Energy estimation(2) Consumption 70.5 kWh/a

Room Lighting power density 2.77 W/m²

3.24 W/m²/100 lx

(1) Based on a rectangular space of 5.894 m x 2.261 m and SHR of 0.25.


(2) Calculated using DIN:18599-4.

Utilisation profile: Places of public assembly - General areas (36.1 Entrance halls)

Luminaire list

pcs. Manufacturer Article No. Article name RUG P Φ Luminous efficacy

2 Philips DN470B WR LED20S/- NO 22 18.3 W 1837 lm 100.4 lm/W

– 18.3 W 1837 lm (100 %) –

194
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 · TOILET MALE ( 2. EMERGENCY LIGHT SCENE)


Summary

Ground area 13.22 m² Clearance height 4.800 m

Reflection factors Ceiling: 80.0 %, Mounting height 4.800 m


Walls: 50.0 %,
Floor: 20.0 % Height Working plane 0.800 m

Maintenance factor 0.80 (fixed) Wall zone Working plane 0.000 m

195
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 · TOILET MALE ( 2. EMERGENCY LIGHT SCENE)


Summary

Results

Symbol Calculated Index

Working plane Ēperpendicular 43.2 lx WP4

Uo (g1 ) 0.38 WP4

Glare valuation(1) RUG, max 22

Energy estimation(2) Consumption 35.2 kWh/a

Room Lighting power density 1.38 W/m²

3.21 W/m²/100 lx

(1) Based on a rectangular space of 5.894 m x 2.261 m and SHR of 0.25.


(2) Calculated using DIN:18599-4.

Utilisation profile: Places of public assembly - General areas (36.1 Entrance halls)

Luminaire list

pcs. Manufacturer Article No. Article name RUG P Φ Luminous efficacy

1 Philips DN470B WR LED20S/- NO 22 18.3 W 1837 lm 100.4 lm/W

– 18.3 W 1837 lm (100 %) –

196
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 · TOILET MALE (3. ESCAPE)


Summary

Ground area 13.22 m²

Reflection factors Ceiling: 80.0 %, Clearance height 4.800 m


Walls: 50.0 %,
Floor: 20.0 % Height Working plane 0.800 m

Maintenance factor 0.80 (fixed) Wall zone Working plane 0.000 m

197
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 · TOILET MALE (3. ESCAPE)


Summary

Results

Symbol Calculated Target Check Index

Room Lighting power density 0.00 W/m² –

(2) Calculated using DIN:18599-4.

Notes on planning:
The emergency lighting scene was calculated without reflection and taking into account the placed furniture.

198
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 · TOILET MALE


Luminaire layout plan

199
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 · TOILET MALE


Luminaire layout plan

Manufacturer Philips P 18.3 W

Article name DN470B WR PEmergency lighting 18.3 W


LED20S/- NO
ΦLuminaire 1837 lm
Fitting 1x LED20S/840/-
ΦEmergency lighting 1837 lm

ELF 100 %

2 x Philips DN470B WR LED20S/- NO

Type Line arrangement X Y Mounting Luminaire


height
1st luminaire (X/Y/Z) 1.597 m / 1.174 m /
4.800 m 1.597 m 1.174 m 4.800 m 1

X-direction 2 pcs., Centre - 4.097 m 1.174 m 4.800 m 2


centre, Distances not
equal

Arrangement A1

200
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 · TOILET MALE ( 1. NORMAL LIGHT SCENE)


Calculation objects

201
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 · TOILET MALE ( 1. NORMAL LIGHT SCENE)


Calculation objects

Working planes

Properties Ē Emin Emax Uo (g1 ) g2 Index

Working plane (TOILET MALE) 85.3 lx 60.7 lx 102 lx 0.71 0.60 WP4
Perpendicular illuminance
Height: 0.800 m, Wall zone: 0.000 m

Utilisation profile: Places of public assembly - General areas (36.1 Entrance halls)

202
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 · TOILET MALE ( 2. EMERGENCY LIGHT SCENE)


Calculation objects

203
WAVE C1 CONTROL BUILDING

Ground Floor · Storey 1 · TOILET MALE ( 2. EMERGENCY LIGHT SCENE)


Calculation objects

Working planes

Properties Ē Emin Emax Uo (g1 ) g2 Index

Working plane (TOILET MALE) 43.2 lx 16.6 lx 64.4 lx 0.38 0.26 WP4
Perpendicular illuminance
Height: 0.800 m, Wall zone: 0.000 m

Utilisation profile: Places of public assembly - General areas (36.1 Entrance halls)

204
WAVE C1 CONTROL BUILDING

ROOF ( 1. NORMAL LIGHT SCENE)


Summary

Mounting height 2.600 m

Ground area 513.45 m² Height Working plane 0.000 m

Maintenance factor 0.60 (fixed) Wall zone Working plane 0.000 m

205
WAVE C1 CONTROL BUILDING

ROOF ( 1. NORMAL LIGHT SCENE)


Summary

Results

Symbol Calculated Index

Working plane Ēperpendicular 81.4 lx WP16

Uo (g1 ) 0.22 WP16

Energy estimation(2) Consumption 6097 kWh/a

Space Lighting power density 1.36 W/m²

1.67 W/m²/100 lx

(1) Based on a rectangular space of 39.161 m x 13.133 m and SHR of 0.25.


(2) Calculated using DIN:18599-4.

Utilisation profile: General circulation areas at outdoor workplaces (5.1.1 Walkways exclusively for pedestrians)

Luminaire list

pcs. Manufacturer Article No. Article name RUG P Φ Luminous efficacy

12 Philips WT470X L1600 WB LED80S/- NO 23 58.0 W 8006 lm 138.0 lm/W

– 58.0 W 8006 lm (100 %) –

206
WAVE C1 CONTROL BUILDING

ROOF (3. ESCAPE)


Summary

Ground area 513.45 m² Height Working plane 0.000 m

Maintenance factor 0.60 (fixed) Wall zone Working plane 0.000 m

207
WAVE C1 CONTROL BUILDING

ROOF (3. ESCAPE)


Summary

Results

Symbol Calculated Target Check Index

Space Lighting power density 0.00 W/m² –

(2) Calculated using DIN:18599-4.

Notes on planning:
The emergency lighting scene was calculated without reflection and taking into account the placed furniture.

208
WAVE C1 CONTROL BUILDING

ROOF
Luminaire layout plan

209
WAVE C1 CONTROL BUILDING

ROOF
Luminaire layout plan

Manufacturer Philips P 58.0 W

Article name WT470X L1600 WB PEmergency lighting 58.0 W


LED80S/- NO
ΦLuminaire 8006 lm
Fitting 1x LED80S/840/-
ΦEmergency lighting 8006 lm

ELF 100 %

4 x Philips WT470X L1600 WB LED80S/- NO

Type Line arrangement X Y Mounting Luminaire


height
1st luminaire (X/Y/Z) 0.827 m / 30.776 m /
2.600 m 0.827 m 30.776 m 2.600 m 5

X-direction 4 pcs., Centre - 0.823 m 23.603 m 2.600 m 6


centre, 7.174 m
0.819 m 16.429 m 2.600 m 7
Arrangement A1
0.815 m 9.256 m 2.600 m 8

4 x Philips WT470X L1600 WB LED80S/- NO

Type Line arrangement X Y Mounting Luminaire


height
1st luminaire (X/Y/Z) 12.498 m / 9.365 m /
2.600 m 12.498 m 9.365 m 2.600 m 1

X-direction 4 pcs., Centre - 12.498 m 16.502 m 2.600 m 2


centre, 7.137 m
12.498 m 23.639 m 2.600 m 3
Arrangement A2
12.498 m 30.775 m 2.600 m 4

210
WAVE C1 CONTROL BUILDING

ROOF
Luminaire layout plan

Individual luminaires

X Y Mounting Luminaire
height

0.786 m 38.735 m 2.600 m 9

12.609 m 38.638 m 2.600 m 10

0.820 m 0.818 m 2.600 m 11

12.731 m 0.741 m 2.600 m 12

211
WAVE C1 CONTROL BUILDING

ROOF ( 1. NORMAL LIGHT SCENE)


Calculation objects

212
WAVE C1 CONTROL BUILDING

ROOF ( 1. NORMAL LIGHT SCENE)


Calculation objects

Working planes

Properties Ē Emin Emax Uo (g1 ) g2 Index

Working plane (ROOF) 81.4 lx 17.7 lx 252 lx 0.22 0.070 WP16


Perpendicular illuminance
Height: 0.000 m, Wall zone: 0.000 m

Utilisation profile: General circulation areas at outdoor workplaces (5.1.1 Walkways exclusively for pedestrians)

213