Annex 2 Control Building Lighting Calculation Report
Annex 2 Control Building Lighting Calculation Report
Table of Contents
Cover . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1. . . . . . . . . . . . . . . . . . . . . . . . . . . .
Table of Contents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2. . . . . . . . . . . . . . . . . . . . . . . . . . . .
Luminaire list . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7. . . . . . . . . . . . . . . . . . . . . . . . . . . .
Storey 1
Room list / 3. ESCAPE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8. . . . . . . . . . . . . . . . . . . . . . . . . . .
KITCHEN
Summary / 1. NORMAL LIGHT SCENE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39 .............................
Summary / 2. EMERGENCY LIGHT SCENE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .............................
41
Summary / 3. ESCAPE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43. . . . . . . . . . . . . . . . . . . . . . . . . . . .
.
Luminaire layout plan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .............................
45
Calculation objects / 1. NORMAL LIGHT SCENE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .47.............................
Calculation objects / 2. EMERGENCY LIGHT SCENE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
49 ............................
WAVE C1 CONTROL BUILDING
Table of Contents
TOILET FEMALE
Summary / 1. NORMAL LIGHT SCENE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51 .............................
Summary / 2. EMERGENCY LIGHT SCENE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .............................
53
Summary / 3. ESCAPE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55. . . . . . . . . . . . . . . . . . . . . . . . . . . .
.
Luminaire layout plan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .............................
57
Calculation objects / 1. NORMAL LIGHT SCENE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .59.............................
Calculation objects / 2. EMERGENCY LIGHT SCENE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
61 ............................
BATTERY ROOM
Summary / 1. NORMAL LIGHT SCENE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63 .............................
Summary / 2. EMERGENCY LIGHT SCENE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .............................
65
Summary / 3. ESCAPE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67. . . . . . . . . . . . . . . . . . . . . . . . . . . .
.
Luminaire layout plan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .............................
69
Calculation objects / 1. NORMAL LIGHT SCENE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .72.............................
Calculation objects / 2. EMERGENCY LIGHT SCENE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
74 ............................
CONTROL ROOM
Summary / 1. NORMAL LIGHT SCENE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89 .............................
Summary / 2. EMERGENCY LIGHT SCENE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .............................
91
Summary / 3. ESCAPE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93.............................
Luminaire layout plan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .95
.............................
Calculation objects / 1. NORMAL LIGHT SCENE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .99 .............................
Calculation objects / 2. EMERGENCY LIGHT SCENE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101 ..............................
WAVE C1 CONTROL BUILDING
Table of Contents
CORRIDOR
Summary / 1. NORMAL LIGHT SCENE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 103 ..............................
Summary / 2. EMERGENCY LIGHT SCENE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ..............................
105
Summary / 3. ESCAPE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
107 .............................
Luminaire layout plan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
109 .............................
Calculation objects / 1. NORMAL LIGHT SCENE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
112 .............................
Calculation objects / 2. EMERGENCY LIGHT SCENE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
114. ............................
DOCUMENTS ROOM
Summary / 1. NORMAL LIGHT SCENE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 116 ..............................
Summary / 2. EMERGENCY LIGHT SCENE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ..............................
118
Summary / 3. ESCAPE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
120 .............................
Luminaire layout plan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
122 .............................
Calculation objects / 1. NORMAL LIGHT SCENE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
124 .............................
Calculation objects / 2. EMERGENCY LIGHT SCENE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
126. ............................
ELECTRICAL ROOM
Summary / 1. NORMAL LIGHT SCENE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 128 ..............................
Summary / 2. EMERGENCY LIGHT SCENE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ..............................
130
Summary / 3. ESCAPE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
132.............................
Luminaire layout plan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
134.............................
Calculation objects / 1. NORMAL LIGHT SCENE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .137 ..............................
Calculation objects / 2. EMERGENCY LIGHT SCENE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 139 ..............................
ENGINEER'S ROOM
Summary / 1. NORMAL LIGHT SCENE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 141 ..............................
Summary / 2. EMERGENCY LIGHT SCENE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ..............................
143
Summary / 3. ESCAPE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .145..............................
Luminaire layout plan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .147
..............................
Calculation objects / 1. NORMAL LIGHT SCENE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .150 ..............................
Calculation objects / 2. EMERGENCY LIGHT SCENE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 152 ..............................
WAVE C1 CONTROL BUILDING
Table of Contents
MEETING ROOM
Summary / 1. NORMAL LIGHT SCENE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 154 ..............................
Summary / 2. EMERGENCY LIGHT SCENE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ..............................
156
Summary / 3. ESCAPE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
158 .............................
Luminaire layout plan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
160 .............................
Calculation objects / 1. NORMAL LIGHT SCENE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
163 .............................
Calculation objects / 2. EMERGENCY LIGHT SCENE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
165. ............................
OFFICE
Summary / 1. NORMAL LIGHT SCENE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 167 ..............................
Summary / 2. EMERGENCY LIGHT SCENE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ..............................
169
Summary / 3. ESCAPE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
171 .............................
Luminaire layout plan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
173 .............................
Calculation objects / 1. NORMAL LIGHT SCENE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
176 .............................
Calculation objects / 2. EMERGENCY LIGHT SCENE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
178. ............................
TELECOM ROOM
Summary / 1. NORMAL LIGHT SCENE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 180 ..............................
Summary / 2. EMERGENCY LIGHT SCENE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ..............................
182
Summary / 3. ESCAPE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
184.............................
Luminaire layout plan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
186.............................
Calculation objects / 1. NORMAL LIGHT SCENE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .189 ..............................
Calculation objects / 2. EMERGENCY LIGHT SCENE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 191 ..............................
TOILET MALE
Summary / 1. NORMAL LIGHT SCENE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 193 ..............................
Summary / 2. EMERGENCY LIGHT SCENE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ..............................
195
Summary / 3. ESCAPE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .197..............................
Luminaire layout plan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .199
..............................
Calculation objects / 1. NORMAL LIGHT SCENE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .201 ..............................
Calculation objects / 2. EMERGENCY LIGHT SCENE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 203 ..............................
WAVE C1 CONTROL BUILDING
Table of Contents
ROOF
Summary / 1. NORMAL LIGHT SCENE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 205 ..............................
Summary / 3. ESCAPE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ..............................
207
Luminaire layout plan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ..............................
209
Calculation objects / 1. NORMAL LIGHT SCENE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ..............................
212
WAVE C1 CONTROL BUILDING
Luminaire list
6 Appleton FELED3CB FELED Zone 1 Linear, 3,000 Lumens, 30.9 W 3058 lm 99.0 lm/W
UxxD 5000K CCT, 120V-277Vac; 170-300VDC,
Diffused 30.9 W 3058 lm (100 %) –
15 Philips SM350CI- SM350C 40S/840 PSD PCS L1200 30.0 W 3997 lm 133.2 lm/W
005dabf3-
c421- 30.0 W 3997 lm (100 %) –
4854-
b012-
9fb449cc2
7
WAVE C1 CONTROL BUILDING
8
WAVE C1 CONTROL BUILDING
BATTERY ROOM
9
WAVE C1 CONTROL BUILDING
CONTROL ROOM
CORRIDOR
10
WAVE C1 CONTROL BUILDING
ELECTRICAL ROOM
ENGINEER'S ROOM
MEETING ROOM
11
WAVE C1 CONTROL BUILDING
OFFICE
TELECOM ROOM
12
WAVE C1 CONTROL BUILDING
13
WAVE C1 CONTROL BUILDING
Results
1.72 W/m²/100 lx
Utilisation profile: Industrial activities and crafts - Electrical and electronics industry (19.1 Cable and wire manufacture)
Luminaire list
9 Philips SM350CI- SM350C 40S/840 PSD PCS 18 30.0 W 3997 lm 133.2 lm/W
005dabf3- L1200
c421- – 30.0 W 3997 lm (100 %) –
4854-
b012-
9fb449cc2
14
WAVE C1 CONTROL BUILDING
15
WAVE C1 CONTROL BUILDING
Results
1.73 W/m²/100 lx
Utilisation profile: Industrial activities and crafts - Electrical and electronics industry (19.1 Cable and wire manufacture)
Luminaire list
3 Philips SM350CI- SM350C 40S/840 PSD PCS 18 30.0 W 3997 lm 133.2 lm/W
005dabf3- L1200
c421- – 30.0 W 3997 lm (100 %) –
4854-
b012-
9fb449cc2
16
WAVE C1 CONTROL BUILDING
17
WAVE C1 CONTROL BUILDING
Results
Notes on planning:
The emergency lighting scene was calculated without reflection and taking into account the placed furniture.
Luminaire list
18
WAVE C1 CONTROL BUILDING
19
WAVE C1 CONTROL BUILDING
Individual luminaires
X Y Mounting Luminaire
height
20
WAVE C1 CONTROL BUILDING
21
WAVE C1 CONTROL BUILDING
22
WAVE C1 CONTROL BUILDING
Working planes
Working plane ( DCS SERVER ROOM) 438 lx 280 lx 650 lx 0.64 0.43 WP8
Perpendicular illuminance
Height: 0.800 m, Wall zone: 0.000 m
Utilisation profile: Industrial activities and crafts - Electrical and electronics industry (19.1 Cable and wire manufacture)
23
WAVE C1 CONTROL BUILDING
24
WAVE C1 CONTROL BUILDING
Working planes
Working plane ( DCS SERVER ROOM) 145 lx 50.2 lx 288 lx 0.35 0.17 WP8
Perpendicular illuminance
Height: 0.800 m, Wall zone: 0.000 m
Utilisation profile: Industrial activities and crafts - Electrical and electronics industry (19.1 Cable and wire manufacture)
25
WAVE C1 CONTROL BUILDING
26
WAVE C1 CONTROL BUILDING
Results
2.77 W/m²/100 lx
2.02 W/m²/100 lx
Utilisation profile: Industrial activities and crafts - Electrical and electronics industry (19.1 Cable and wire manufacture)
Luminaire list
6 Philips SM350CI- SM350C 40S/840 PSD PCS 18 30.0 W 3997 lm 133.2 lm/W
005dabf3- L1200
c421- – 30.0 W 3997 lm (100 %) –
4854-
b012-
9fb449cc2
27
WAVE C1 CONTROL BUILDING
28
WAVE C1 CONTROL BUILDING
Results
2.78 W/m²/100 lx
2.03 W/m²/100 lx
Utilisation profile: Industrial activities and crafts - Electrical and electronics industry (19.1 Cable and wire manufacture)
Luminaire list
3 Philips SM350CI- SM350C 40S/840 PSD PCS 18 30.0 W 3997 lm 133.2 lm/W
005dabf3- L1200
c421- – 30.0 W 3997 lm (100 %) –
4854-
b012-
9fb449cc2
29
WAVE C1 CONTROL BUILDING
30
WAVE C1 CONTROL BUILDING
Results
Notes on planning:
The emergency lighting scene was calculated without reflection and taking into account the placed furniture.
Luminaire list
31
WAVE C1 CONTROL BUILDING
32
WAVE C1 CONTROL BUILDING
Individual luminaires
X Y Mounting Luminaire
height
33
WAVE C1 CONTROL BUILDING
34
WAVE C1 CONTROL BUILDING
35
WAVE C1 CONTROL BUILDING
Working planes
Working plane ( DCS UPS ROOM) 395 lx 252 lx 586 lx 0.64 0.43 WP1
Perpendicular illuminance
Height: 0.800 m, Wall zone: 0.300 m
Utilisation profile: Industrial activities and crafts - Electrical and electronics industry (19.1 Cable and wire manufacture)
36
WAVE C1 CONTROL BUILDING
37
WAVE C1 CONTROL BUILDING
Working planes
Working plane ( DCS UPS ROOM) 196 lx 62.7 lx 296 lx 0.32 0.21 WP1
Perpendicular illuminance
Height: 0.800 m, Wall zone: 0.300 m
Utilisation profile: Industrial activities and crafts - Electrical and electronics industry (19.1 Cable and wire manufacture)
38
WAVE C1 CONTROL BUILDING
39
WAVE C1 CONTROL BUILDING
Results
2.08 W/m²/100 lx
1.44 W/m²/100 lx
Luminaire list
40
WAVE C1 CONTROL BUILDING
41
WAVE C1 CONTROL BUILDING
Results
1.79 W/m²/100 lx
1.24 W/m²/100 lx
Luminaire list
42
WAVE C1 CONTROL BUILDING
43
WAVE C1 CONTROL BUILDING
Results
Notes on planning:
The emergency lighting scene was calculated without reflection and taking into account the placed furniture.
44
WAVE C1 CONTROL BUILDING
45
WAVE C1 CONTROL BUILDING
ELF 100 %
Arrangement A1
46
WAVE C1 CONTROL BUILDING
47
WAVE C1 CONTROL BUILDING
Working planes
48
WAVE C1 CONTROL BUILDING
49
WAVE C1 CONTROL BUILDING
Working planes
50
WAVE C1 CONTROL BUILDING
51
WAVE C1 CONTROL BUILDING
Results
3.25 W/m²/100 lx
Utilisation profile: Places of public assembly - General areas (36.1 Entrance halls)
Luminaire list
52
WAVE C1 CONTROL BUILDING
53
WAVE C1 CONTROL BUILDING
Results
3.24 W/m²/100 lx
Utilisation profile: Places of public assembly - General areas (36.1 Entrance halls)
Luminaire list
54
WAVE C1 CONTROL BUILDING
55
WAVE C1 CONTROL BUILDING
Results
Notes on planning:
The emergency lighting scene was calculated without reflection and taking into account the placed furniture.
56
WAVE C1 CONTROL BUILDING
57
WAVE C1 CONTROL BUILDING
ELF 100 %
Arrangement A1
58
WAVE C1 CONTROL BUILDING
59
WAVE C1 CONTROL BUILDING
Working planes
Working plane ( TOILET FEMALE) 86.9 lx 63.4 lx 103 lx 0.73 0.62 WP5
Perpendicular illuminance
Height: 0.800 m, Wall zone: 0.000 m
Utilisation profile: Places of public assembly - General areas (36.1 Entrance halls)
60
WAVE C1 CONTROL BUILDING
61
WAVE C1 CONTROL BUILDING
Working planes
Working plane ( TOILET FEMALE) 43.7 lx 18.1 lx 63.5 lx 0.41 0.29 WP5
Perpendicular illuminance
Height: 0.800 m, Wall zone: 0.000 m
Utilisation profile: Places of public assembly - General areas (36.1 Entrance halls)
62
WAVE C1 CONTROL BUILDING
63
WAVE C1 CONTROL BUILDING
Results
3.33 W/m²/100 lx
Utilisation profile: Industrial activities and crafts - Electrical and electronics industry (19.1 Cable and wire manufacture)
Luminaire list
6 Appleton FELED3CB FELED Zone 1 Linear, 3,000 – 30.9 W 3058 lm 99.0 lm/W
UxxD Lumens, 5000K CCT, 120V-
277Vac; 170-300VDC, Diffused – 30.9 W 3058 lm (100 %) –
64
WAVE C1 CONTROL BUILDING
65
WAVE C1 CONTROL BUILDING
Results
3.31 W/m²/100 lx
Utilisation profile: Industrial activities and crafts - Electrical and electronics industry (19.1 Cable and wire manufacture)
Luminaire list
3 Appleton FELED3CB FELED Zone 1 Linear, 3,000 – 30.9 W 3058 lm 99.0 lm/W
UxxD Lumens, 5000K CCT, 120V-
277Vac; 170-300VDC, Diffused – 30.9 W 3058 lm (100 %) –
66
WAVE C1 CONTROL BUILDING
67
WAVE C1 CONTROL BUILDING
Results
Notes on planning:
The emergency lighting scene was calculated without reflection and taking into account the placed furniture.
Luminaire list
68
WAVE C1 CONTROL BUILDING
69
WAVE C1 CONTROL BUILDING
Fitting 1x LED
6 x Appleton FELED Zone 1 Linear, 3,000 Lumens, 5000K CCT, 120V-277Vac; 170-300VDC, Diffused
70
WAVE C1 CONTROL BUILDING
Individual luminaires
X Y Mounting Luminaire
height
71
WAVE C1 CONTROL BUILDING
72
WAVE C1 CONTROL BUILDING
Working planes
Working plane (BATTERY ROOM) 169 lx 133 lx 204 lx 0.79 0.65 WP11
Perpendicular illuminance
Height: 0.800 m, Wall zone: 0.000 m
Utilisation profile: Industrial activities and crafts - Electrical and electronics industry (19.1 Cable and wire manufacture)
73
WAVE C1 CONTROL BUILDING
74
WAVE C1 CONTROL BUILDING
Working planes
Working plane (BATTERY ROOM) 84.8 lx 38.5 lx 111 lx 0.45 0.35 WP11
Perpendicular illuminance
Height: 0.800 m, Wall zone: 0.000 m
Utilisation profile: Industrial activities and crafts - Electrical and electronics industry (19.1 Cable and wire manufacture)
75
WAVE C1 CONTROL BUILDING
Ground Floor · Storey 1 · CLEAN AGENT CYLINDER ROOM ( 1. NORMAL LIGHT SCENE)
Summary
76
WAVE C1 CONTROL BUILDING
Ground Floor · Storey 1 · CLEAN AGENT CYLINDER ROOM ( 1. NORMAL LIGHT SCENE)
Summary
Results
2.82 W/m²/100 lx
Luminaire list
77
WAVE C1 CONTROL BUILDING
Ground Floor · Storey 1 · CLEAN AGENT CYLINDER ROOM ( 2. EMERGENCY LIGHT SCENE)
Summary
78
WAVE C1 CONTROL BUILDING
Ground Floor · Storey 1 · CLEAN AGENT CYLINDER ROOM ( 2. EMERGENCY LIGHT SCENE)
Summary
Results
2.82 W/m²/100 lx
Luminaire list
79
WAVE C1 CONTROL BUILDING
80
WAVE C1 CONTROL BUILDING
Results
Notes on planning:
The emergency lighting scene was calculated without reflection and taking into account the placed furniture.
Luminaire list
81
WAVE C1 CONTROL BUILDING
82
WAVE C1 CONTROL BUILDING
ELF 100 %
Arrangement A1
83
WAVE C1 CONTROL BUILDING
Individual luminaires
X Y Mounting Luminaire
height
84
WAVE C1 CONTROL BUILDING
Ground Floor · Storey 1 · CLEAN AGENT CYLINDER ROOM ( 1. NORMAL LIGHT SCENE)
Calculation objects
85
WAVE C1 CONTROL BUILDING
Ground Floor · Storey 1 · CLEAN AGENT CYLINDER ROOM ( 1. NORMAL LIGHT SCENE)
Calculation objects
Working planes
Working plane (CLEAN AGENT CYLINDER ROOM) 80.1 lx 59.6 lx 95.1 lx 0.74 0.63 WP13
Perpendicular illuminance
Height: 0.800 m, Wall zone: 0.000 m
86
WAVE C1 CONTROL BUILDING
Ground Floor · Storey 1 · CLEAN AGENT CYLINDER ROOM ( 2. EMERGENCY LIGHT SCENE)
Calculation objects
87
WAVE C1 CONTROL BUILDING
Ground Floor · Storey 1 · CLEAN AGENT CYLINDER ROOM ( 2. EMERGENCY LIGHT SCENE)
Calculation objects
Working planes
Working plane (CLEAN AGENT CYLINDER ROOM) 40.2 lx 13.6 lx 62.2 lx 0.34 0.22 WP13
Perpendicular illuminance
Height: 0.800 m, Wall zone: 0.000 m
88
WAVE C1 CONTROL BUILDING
89
WAVE C1 CONTROL BUILDING
Results
1.22 W/m²/100 lx
1.08 W/m²/100 lx
Utilisation profile: General areas inside buildings - Control rooms (11.1 Plant rooms, switchgear rooms)
Luminaire list
90
WAVE C1 CONTROL BUILDING
91
WAVE C1 CONTROL BUILDING
Results
1.22 W/m²/100 lx
1.08 W/m²/100 lx
Utilisation profile: General areas inside buildings - Control rooms (11.1 Plant rooms, switchgear rooms)
Luminaire list
92
WAVE C1 CONTROL BUILDING
93
WAVE C1 CONTROL BUILDING
Results
Notes on planning:
The emergency lighting scene was calculated without reflection and taking into account the placed furniture.
Luminaire list
94
WAVE C1 CONTROL BUILDING
95
WAVE C1 CONTROL BUILDING
ELF 100 %
96
WAVE C1 CONTROL BUILDING
X Y Mounting Luminaire
height
97
WAVE C1 CONTROL BUILDING
Individual luminaires
X Y Mounting Luminaire
height
98
WAVE C1 CONTROL BUILDING
99
WAVE C1 CONTROL BUILDING
Working planes
Working plane (CONTROL ROOM) 559 lx 397 lx 677 lx 0.71 0.59 WP6
Perpendicular illuminance
Height: 0.800 m, Wall zone: 0.300 m
Utilisation profile: General areas inside buildings - Control rooms (11.1 Plant rooms, switchgear rooms)
100
WAVE C1 CONTROL BUILDING
101
WAVE C1 CONTROL BUILDING
Working planes
Working plane (CONTROL ROOM) 280 lx 90.5 lx 424 lx 0.32 0.21 WP6
Perpendicular illuminance
Height: 0.800 m, Wall zone: 0.300 m
Utilisation profile: General areas inside buildings - Control rooms (11.1 Plant rooms, switchgear rooms)
102
WAVE C1 CONTROL BUILDING
103
WAVE C1 CONTROL BUILDING
Results
2.23 W/m²/100 lx
2.23 W/m²/100 lx
Utilisation profile: Places of public assembly - General areas (36.1 Entrance halls)
Luminaire list
104
WAVE C1 CONTROL BUILDING
105
WAVE C1 CONTROL BUILDING
Results
2.15 W/m²/100 lx
2.15 W/m²/100 lx
Utilisation profile: Places of public assembly - General areas (36.1 Entrance halls)
Luminaire list
106
WAVE C1 CONTROL BUILDING
107
WAVE C1 CONTROL BUILDING
Results
Notes on planning:
The emergency lighting scene was calculated without reflection and taking into account the placed furniture.
Luminaire list
108
WAVE C1 CONTROL BUILDING
109
WAVE C1 CONTROL BUILDING
Fitting 1x LED20S/840/-
110
WAVE C1 CONTROL BUILDING
Individual luminaires
X Y Mounting Luminaire
height
111
WAVE C1 CONTROL BUILDING
112
WAVE C1 CONTROL BUILDING
Working planes
Utilisation profile: Places of public assembly - General areas (36.1 Entrance halls)
113
WAVE C1 CONTROL BUILDING
114
WAVE C1 CONTROL BUILDING
Working planes
Utilisation profile: Places of public assembly - General areas (36.1 Entrance halls)
115
WAVE C1 CONTROL BUILDING
116
WAVE C1 CONTROL BUILDING
Results
1.49 W/m²/100 lx
Utilisation profile: Places of public assembly - General areas (36.1 Entrance halls)
Luminaire list
117
WAVE C1 CONTROL BUILDING
118
WAVE C1 CONTROL BUILDING
Results
1.49 W/m²/100 lx
Utilisation profile: Places of public assembly - General areas (36.1 Entrance halls)
Luminaire list
119
WAVE C1 CONTROL BUILDING
120
WAVE C1 CONTROL BUILDING
Results
Notes on planning:
The emergency lighting scene was calculated without reflection and taking into account the placed furniture.
121
WAVE C1 CONTROL BUILDING
122
WAVE C1 CONTROL BUILDING
ELF 100 %
Arrangement A1
123
WAVE C1 CONTROL BUILDING
124
WAVE C1 CONTROL BUILDING
Working planes
Working plane (DOCUMENTS ROOM) 344 lx 178 lx 519 lx 0.52 0.34 WP7
Perpendicular illuminance
Height: 0.800 m, Wall zone: 0.000 m
Utilisation profile: Places of public assembly - General areas (36.1 Entrance halls)
125
WAVE C1 CONTROL BUILDING
126
WAVE C1 CONTROL BUILDING
Working planes
Working plane (DOCUMENTS ROOM) 172 lx 35.6 lx 384 lx 0.21 0.093 WP7
Perpendicular illuminance
Height: 0.800 m, Wall zone: 0.000 m
Utilisation profile: Places of public assembly - General areas (36.1 Entrance halls)
127
WAVE C1 CONTROL BUILDING
128
WAVE C1 CONTROL BUILDING
Results
2.24 W/m²/100 lx
Utilisation profile: Industrial activities and crafts - Electrical and electronics industry (19.1 Cable and wire manufacture)
Luminaire list
129
WAVE C1 CONTROL BUILDING
130
WAVE C1 CONTROL BUILDING
Results
2.26 W/m²/100 lx
Utilisation profile: Industrial activities and crafts - Electrical and electronics industry (19.1 Cable and wire manufacture)
Luminaire list
131
WAVE C1 CONTROL BUILDING
132
WAVE C1 CONTROL BUILDING
Results
Notes on planning:
The emergency lighting scene was calculated without reflection and taking into account the placed furniture.
Luminaire list
133
WAVE C1 CONTROL BUILDING
134
WAVE C1 CONTROL BUILDING
ELF 100 %
Arrangement A1
135
WAVE C1 CONTROL BUILDING
Individual luminaires
X Y Mounting Luminaire
height
136
WAVE C1 CONTROL BUILDING
137
WAVE C1 CONTROL BUILDING
Working planes
Working plane (ELECTRICAL ROOM) 361 lx 270 lx 407 lx 0.75 0.66 WP12
Perpendicular illuminance
Height: 0.800 m, Wall zone: 0.000 m
Utilisation profile: Industrial activities and crafts - Electrical and electronics industry (19.1 Cable and wire manufacture)
138
WAVE C1 CONTROL BUILDING
139
WAVE C1 CONTROL BUILDING
Working planes
Working plane (ELECTRICAL ROOM) 179 lx 96.1 lx 213 lx 0.54 0.45 WP12
Perpendicular illuminance
Height: 0.800 m, Wall zone: 0.000 m
Utilisation profile: Industrial activities and crafts - Electrical and electronics industry (19.1 Cable and wire manufacture)
140
WAVE C1 CONTROL BUILDING
141
WAVE C1 CONTROL BUILDING
Results
1.84 W/m²/100 lx
1.32 W/m²/100 lx
Utilisation profile: Industrial activities and crafts - Electrical and electronics industry (19.1 Cable and wire manufacture)
Luminaire list
142
WAVE C1 CONTROL BUILDING
143
WAVE C1 CONTROL BUILDING
Results
1.84 W/m²/100 lx
1.33 W/m²/100 lx
Utilisation profile: Industrial activities and crafts - Electrical and electronics industry (19.1 Cable and wire manufacture)
Luminaire list
144
WAVE C1 CONTROL BUILDING
145
WAVE C1 CONTROL BUILDING
Results
Notes on planning:
The emergency lighting scene was calculated without reflection and taking into account the placed furniture.
Luminaire list
146
WAVE C1 CONTROL BUILDING
147
WAVE C1 CONTROL BUILDING
ELF 100 %
Arrangement A1
148
WAVE C1 CONTROL BUILDING
Individual luminaires
X Y Mounting Luminaire
height
149
WAVE C1 CONTROL BUILDING
150
WAVE C1 CONTROL BUILDING
Working planes
Working plane (ENGINEER'S ROOM) 381 lx 250 lx 504 lx 0.66 0.50 WP9
Perpendicular illuminance
Height: 0.800 m, Wall zone: 0.300 m
Utilisation profile: Industrial activities and crafts - Electrical and electronics industry (19.1 Cable and wire manufacture)
151
WAVE C1 CONTROL BUILDING
152
WAVE C1 CONTROL BUILDING
Working planes
Working plane (ENGINEER'S ROOM) 190 lx 47.0 lx 383 lx 0.25 0.12 WP9
Perpendicular illuminance
Height: 0.800 m, Wall zone: 0.300 m
Utilisation profile: Industrial activities and crafts - Electrical and electronics industry (19.1 Cable and wire manufacture)
153
WAVE C1 CONTROL BUILDING
154
WAVE C1 CONTROL BUILDING
Results
1.67 W/m²/100 lx
Utilisation profile: Health care premises - Rooms for general use (45.1 Waiting rooms)
Luminaire list
155
WAVE C1 CONTROL BUILDING
156
WAVE C1 CONTROL BUILDING
Results
1.67 W/m²/100 lx
Utilisation profile: Health care premises - Rooms for general use (45.1 Waiting rooms)
Luminaire list
157
WAVE C1 CONTROL BUILDING
158
WAVE C1 CONTROL BUILDING
Results
Notes on planning:
The emergency lighting scene was calculated without reflection and taking into account the placed furniture.
Luminaire list
159
WAVE C1 CONTROL BUILDING
160
WAVE C1 CONTROL BUILDING
ELF 100 %
161
WAVE C1 CONTROL BUILDING
Individual luminaires
X Y Mounting Luminaire
height
162
WAVE C1 CONTROL BUILDING
163
WAVE C1 CONTROL BUILDING
Working planes
Working plane (MEETING ROOM) 507 lx 347 lx 621 lx 0.68 0.56 WP10
Perpendicular illuminance
Height: 0.800 m, Wall zone: 0.000 m
Utilisation profile: Health care premises - Rooms for general use (45.1 Waiting rooms)
164
WAVE C1 CONTROL BUILDING
165
WAVE C1 CONTROL BUILDING
Working planes
Working plane (MEETING ROOM) 253 lx 83.4 lx 353 lx 0.33 0.24 WP10
Perpendicular illuminance
Height: 0.800 m, Wall zone: 0.000 m
Utilisation profile: Health care premises - Rooms for general use (45.1 Waiting rooms)
166
WAVE C1 CONTROL BUILDING
167
WAVE C1 CONTROL BUILDING
Results
2.08 W/m²/100 lx
1.49 W/m²/100 lx
Luminaire list
168
WAVE C1 CONTROL BUILDING
169
WAVE C1 CONTROL BUILDING
Results
2.08 W/m²/100 lx
1.49 W/m²/100 lx
Luminaire list
170
WAVE C1 CONTROL BUILDING
171
WAVE C1 CONTROL BUILDING
Results
Notes on planning:
The emergency lighting scene was calculated without reflection and taking into account the placed furniture.
Luminaire list
172
WAVE C1 CONTROL BUILDING
173
WAVE C1 CONTROL BUILDING
ELF 100 %
Arrangement A1
174
WAVE C1 CONTROL BUILDING
Individual luminaires
X Y Mounting Luminaire
height
175
WAVE C1 CONTROL BUILDING
176
WAVE C1 CONTROL BUILDING
Working planes
177
WAVE C1 CONTROL BUILDING
178
WAVE C1 CONTROL BUILDING
Working planes
179
WAVE C1 CONTROL BUILDING
180
WAVE C1 CONTROL BUILDING
Results
1.50 W/m²/100 lx
Utilisation profile: General areas inside buildings - Store rooms, cold stores (12.1 Store and stockrooms)
Luminaire list
181
WAVE C1 CONTROL BUILDING
182
WAVE C1 CONTROL BUILDING
Results
1.50 W/m²/100 lx
Utilisation profile: General areas inside buildings - Store rooms, cold stores (12.1 Store and stockrooms)
Luminaire list
183
WAVE C1 CONTROL BUILDING
184
WAVE C1 CONTROL BUILDING
Results
Notes on planning:
The emergency lighting scene was calculated without reflection and taking into account the placed furniture.
Luminaire list
185
WAVE C1 CONTROL BUILDING
186
WAVE C1 CONTROL BUILDING
ELF 100 %
Arrangement A1
187
WAVE C1 CONTROL BUILDING
Individual luminaires
X Y Mounting Luminaire
height
188
WAVE C1 CONTROL BUILDING
189
WAVE C1 CONTROL BUILDING
Working planes
Working plane (TELECOM ROOM) 347 lx 220 lx 448 lx 0.63 0.49 WP2
Perpendicular illuminance
Height: 0.800 m, Wall zone: 0.000 m
Utilisation profile: General areas inside buildings - Store rooms, cold stores (12.1 Store and stockrooms)
190
WAVE C1 CONTROL BUILDING
191
WAVE C1 CONTROL BUILDING
Working planes
Working plane (TELECOM ROOM) 174 lx 69.1 lx 257 lx 0.40 0.27 WP2
Perpendicular illuminance
Height: 0.800 m, Wall zone: 0.000 m
Utilisation profile: General areas inside buildings - Store rooms, cold stores (12.1 Store and stockrooms)
192
WAVE C1 CONTROL BUILDING
193
WAVE C1 CONTROL BUILDING
Results
3.24 W/m²/100 lx
Utilisation profile: Places of public assembly - General areas (36.1 Entrance halls)
Luminaire list
194
WAVE C1 CONTROL BUILDING
195
WAVE C1 CONTROL BUILDING
Results
3.21 W/m²/100 lx
Utilisation profile: Places of public assembly - General areas (36.1 Entrance halls)
Luminaire list
196
WAVE C1 CONTROL BUILDING
197
WAVE C1 CONTROL BUILDING
Results
Notes on planning:
The emergency lighting scene was calculated without reflection and taking into account the placed furniture.
198
WAVE C1 CONTROL BUILDING
199
WAVE C1 CONTROL BUILDING
ELF 100 %
Arrangement A1
200
WAVE C1 CONTROL BUILDING
201
WAVE C1 CONTROL BUILDING
Working planes
Working plane (TOILET MALE) 85.3 lx 60.7 lx 102 lx 0.71 0.60 WP4
Perpendicular illuminance
Height: 0.800 m, Wall zone: 0.000 m
Utilisation profile: Places of public assembly - General areas (36.1 Entrance halls)
202
WAVE C1 CONTROL BUILDING
203
WAVE C1 CONTROL BUILDING
Working planes
Working plane (TOILET MALE) 43.2 lx 16.6 lx 64.4 lx 0.38 0.26 WP4
Perpendicular illuminance
Height: 0.800 m, Wall zone: 0.000 m
Utilisation profile: Places of public assembly - General areas (36.1 Entrance halls)
204
WAVE C1 CONTROL BUILDING
205
WAVE C1 CONTROL BUILDING
Results
1.67 W/m²/100 lx
Utilisation profile: General circulation areas at outdoor workplaces (5.1.1 Walkways exclusively for pedestrians)
Luminaire list
206
WAVE C1 CONTROL BUILDING
207
WAVE C1 CONTROL BUILDING
Results
Notes on planning:
The emergency lighting scene was calculated without reflection and taking into account the placed furniture.
208
WAVE C1 CONTROL BUILDING
ROOF
Luminaire layout plan
209
WAVE C1 CONTROL BUILDING
ROOF
Luminaire layout plan
ELF 100 %
210
WAVE C1 CONTROL BUILDING
ROOF
Luminaire layout plan
Individual luminaires
X Y Mounting Luminaire
height
211
WAVE C1 CONTROL BUILDING
212
WAVE C1 CONTROL BUILDING
Working planes
Utilisation profile: General circulation areas at outdoor workplaces (5.1.1 Walkways exclusively for pedestrians)
213