Marechal PF Range en
Marechal PF Range en
PF
INDUSTRIAL PLUGS
MECHANICAL FEATURES
Pilot contacts : designed to connect after and disconnect before IK10 metal casing
the phase contacts. excellent resistance to shocks.
Off load engagement The male-female connection is Locking the plug in the socket
automatically watertight. closes the pilots and connects
the main circuit.
100
PRESENTATION OF HIGH POWER INDUSTRIAL
PLUG MOUNTING IS AVAILABLE ON OUR
YOUTUBE CHANNEL
ELECTRICAL INTERLOCKING
At this level of power, it is not possible to directly disconnect under load.
Electrical interlocking with a switch or a pilot controlled contactor is required.
Boxes with the following equipment are available upon request:
• circuit breaker or differential switch,
• contactor,
• fuses,
• loop-out enclosures,
• terminals for single pole cables...
COIL
PILOT CIRCUIT
COIL SUPPLY
FUSE
PILOT CONTACTS
PILOT
CONTACTS
PILOT CONTACTS
PFQ4 PFC6
Pilot contacts 2 2
Pilot Amperage 10 A/400 V AC 20 A/400 V AC
Interlocking Type Mechanical Mechanical
Terminal Type Solder/crimp Screw
Notes: The mechanical locking of the plug to the socket-outlet, via the rotation of a cam, closes the pilot contacts.
Failure to use a pilot/relay system can create an electrical shock hazard.
101
PFQ4
400ÌA 690 V
INDUSTRIAL PLUG
PFQ4
SOCKET-OUTLET
female INLET male
PFQ4 PFQ4
102
400ÌA PFQ4
On request: boxes for installation in ducts, boxes equipped with circuit breaker, earth-leakage switch, contactor,…
INFOS +
STRAIGHT CONNECTION RIGHT ANGLE CONNECTION
use (Ø 12) straight cable lugs and sleeves Right angle connection using straight (Ø 12) cable lugs
and insulation sleeves
it is recommended to fit
insulating sleeves to each
lug.
ACCESSORIES AND OPTIONS Reference
473A393
INLET LID
474A126
474A277
103
400ÌA PFQ4
DRAWINGS
AND DIMENSIONS
B C
E
A B C E
471 301 196 145
A C
E B
A B C E
605 246 204 148
104
400ÌA PFQ4
E1
E2
A
B C
A B C E1 E2
95-150 mm² 713 510 389 460 458
150-240 mm² 1013 510 483 460 400/800
105
PFC6
600ÌA 1 000 V
INDUSTRIAL PLUG
PFC6
SOCKET-OUTLET
female INLET male
PFC6 PFC6
왘 Other currents, voltages, frequencies and contact configurations are available (see page 14).
106
600ÌA PFC6
On request: boxes for installation in ducts, boxes equipped with circuit breaker, earth-leakage switch, contactor,…
INFOS +
STRAIGHT CONNECTION RIGHT ANGLE CONNECTION
A right angled cable lug (Ø 14) with insulated sleeve. Straight cable lug (Ø 14) with insulated sleeve.
it is recommended to fit
insulating sleeves to each
lug.
LOCKING KEY
496A393
INLET LID
496A126
107
600ÌA PFC6
DRAWINGS
AND DIMENSIONS
B C
E
A B C E
540 373 266 190
A C
E B
A B C E
683 273 266 190
108
600ÌA PFC6
E1
E2
A
B C
A B C E1 E2
95-150 mm² 713 510 390 460 458
150-240 mm² 1013 510 479 460 400/800
109